LE MODELS: SHIPPING, RIGGING, LIFTING, ASSEMBLY MANUAL

Size: px
Start display at page:

Download "LE MODELS: SHIPPING, RIGGING, LIFTING, ASSEMBLY MANUAL"

Transcription

1 4510 Helgesen Drive, Madison, WI (608) , (800) , Fax: (608) LE MODELS: SHIPPING, RIGGING, LIFTING, ASSEMBLY MANUAL This manual provides an overview of shipping, rigging, lifting and assembly information of the LE Series energy recovery ventilators. Carefully read all instructions before proceeding with any work. These instructions outline the suggested method of placing a RenewAire LE ERV in position. See also the Installation and Operation Manual supplied with the unit. Following these instructions does not necessarily assure compliance with local codes and standards, which must always be observed. All local codes and regulations must be adhered by the Installing Contractor. Any additional holes made by the installing Contractor must be well sealed to prevent air or water infiltration. Any questions please contact your RenewAire representative. LE8X shown Table of Contents SHIPPING...2 RIGGING...2 LIFTING...2 ASSEMBLY (UNITS SHIPPED IN 2 MODULES)...4 Indoor Units...4 Rooftop Units...7 ADDITIONAL INSTALLATION...7 MODULE AND DIMENSIONS....8 IMPROPER INSTALLATION, ADJUSTMENT, ALTETION, SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. INSTALLATION AND SERVICE MUST BE PERFORMED BY A TINED, QUALIFIED INSTALLER. A COPY OF THIS MANUAL SHOULD BE KEPT WITH THE UNIT. LE Rigging _ This shipping, rigging, joining and installation manual shows the suggested installation method. Additional measures may be required by local codes and standards. 2. Installation work and electrical wiring must be done by qualified professional(s) in accordance with all applicable codes, standards and licensing requirements. 3. Any structural alterations necessary for installation must comply with all applicable building, health, and safety code requirements. 4. This unit must be grounded. 5. Danger of severe injury to bystanders and damage to unit or property if high winds move this unit. Secure this unit to the building! 6. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment that might be installed in the area affected by this equipment. If this unit is exhausting air from a space in which chimney-vented fuel burning equipment is located, take steps to assure that combustion air supply is not affected. Follow the heating equipment manufacturer s requirements and the combustion air supply requirements of applicable codes and standards. 7. Use the unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer. 8. This unit is intended for general ventilating only. Do not use to exhaust hazardous or explosive materials and vapors. Do not connect this unit to range hoods, fume hoods or collection systems for toxics. 9. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities. Due to continuing product development, specifications are subject to change without notice RenewAire LLC LERiggingMan_Dec15.indd Revised 12/2015 Page 1

2 SHIPPING LIFTING INDOOR/ROOFTOP LE models can be delivered in two modules for on-site assembly or as a complete unit (additional charges apply). In all cases, units or individual modules are shipped on pallets. In all cases, extra protective pallet materials may have been added; this material was added at the factory to protect the unit or modules during shipping. In all cases, when shipped in modules, assembly materials ship loose and can be found inside the modules. Note: Assembly materials must be removed and installed prior to unit operation. For rooftop models, the outdoor air weather hoods ship loose and can be found inside the modules. Note: Weather hoods and assembly materials must be removed and installed prior to unit operation. STOGE If installation will not occur immediately following delivery, store equipment in a dry protected area away from construction traffic and in the proper orientation as marked on the packaging with all internal packaging in place. RIGGING EQUIPMENT AND TOOLS All rigging equipment is to be provided by the installing Contractor. Rigging procedures may differ depending on the physical dimensions of the unit or modules, it s location, the job site, or Installing Contractor preferences. Tools needed (Suggested): Crane to lift proper capacity Adjustable spreader bars Cables 1.5 Dia. steel pipe schedule 40. Tools requited to pull modules together, chains, bar clamps, come alongs etc. UNIT AND MSURES See LE6X/8X/10X corner weights for individual modules and completed units starting on page 16. All lifting lugs provided must be used. Never lift the unit or modules from the top of the unit. Do not lift joined unit by the 4 corner lifting lugs only. Secure lifting cables to the center lifting lugs also. Incorrect lifting can cause damage to the unit. The units are designed to be lifted from lifting lugs attached to the unit base structure. Spreader bars must be used to hoist sections to avoid damaging the enclosure. The unit comes equipped with base rail lifting lugs at the lower 4 corners and in the middle of the unit. Each lifting lugs come equipped with a 2 diameter hole which will accommodate a 1.5 dia. schedule 40 steel pipe (not provided). Unit or module sections shall be lifted by cables attached to all of the lifting lugs. If cables or chains are used to lift the unit they must be the same length. Care should be taken not to damage the cabinet, dampers, or electrical box. Adjustable spreader bars should be used to properly support the unit in order to properly distribute the load thus applying an even vertical lifting force to all of the lifting lugs. This will prevent structural damage to the unit. Also adjustable spreader bars should be used to maintain the required 10 clearance between the cables and the cabinet or any of the equipment attached to the unit or modules. Provide additional blocking or covering as required. Secure hooks and cables at all lifting points. Take up slack in cables gradually as to avoid sudden movements as this may cause the unit or modules to shift. Suspending the unit or modules for an extended period of time is not recommended and it is advised to place the unit as soon as possible after lifting. Do not lift in high winds. RenewAire will not be responsible for any damage during the rigging, lifting or installing of the unit or modules. Refer to Corner Weight Charts for exact center of gravity _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 2

3 LIFTING LE8X shown FORKLIFT REQUIREMENTS When lifting individual modules, forklift extensions must be used and a minimum length of 72 (96 preferred). When lifting modules off the pallets: If entering from the door side or the open side of the module insure forks extend in far enough as to catch the furthest away stringer with fork extensions. If entering from the side of the module, insure forks extend all the way through the module. Do not attempt to lift a rooftop module off the pallet from the door side or open side as there are no stringers under the unit to carry the load. Assembled modules should never be lifted using a forklift. enewaire.comle Rigging _002 Due to continuing product development, specifications are subject to change without notice RenewAire LLC LERiggingMan_Dec15.indd Revised 12/2015 Page 3

4 ASSEMBLY CONFIGUTION LABEL RenewAire LE series Energy Recovery Ventilators can either be built and shipped factory assembled or be ordered unassembled for applications where modules must be manipulated separately. If the unit was ordered unassembled, then you will need to assemble the modules in the field. Each module is labeled with a configuration and serial number label. Locate these labels and insure each module assembled together have the same configuration and serial number. If for any reason you are unable to identify a module or it s position in the final assembly, then consult the Installation Contractor or RenewAire Customer Service. INDOOR MODULES Extra protective pallet material has to be removed prior to assembly. This additional pallet material was added at the factory to protect the unit during shipping. Also, plywood protective packaging material has to be removed from modules before assembly. It is desirable to situate all required modules in the installation location as near as possible to the order in which they will be connected. Be sure to leave enough space to work between modules before connection. Gasket tape will be applied before assembling the modules. Shipping straps on open end. Apply gasket tape Apply 1/4" X 1" gasket tape (provided), as shown on next page. Gasket tape creates an airtight seal between modules. The adhesive backing on the gasket tape is easily repositioned during assembly if needed. However, if gasket tape is allowed to set more than 48 hours, it will be difficult to reposition. All materials for assembling the modules are supplied by RenewAire. Remove shipping straps Remove shipping straps from opening/mating ends before joining modules and operating the unit. Shipping straps are attached to the modules at the factory. These straps insure proper rigidity when shipping and lifting. Once the straps are removed they may be disposed of along with the screws that held them in place. LE Rigging _002 Due to continuing product development, specifications are subject to change without notice RenewAire LLC LERiggingMan_Dec15.indd Revised 12/2015 Page 4

5 ASSEMBLY Failure to apply gasket tape in these locations will compromise water and airtight seal of the unit. Additionally, for added unit strength and gasket clamping force, insert four 3/8" - 16 x 1-1/4 plated hex head bolts through holes in base rails of joining ends in LE indoor units or through holes in base centering angles of joining ends in LE rooftop units as shown below. Hand holes are provided in base rails to reach these locations when joined. Assemble Align modules and push together using forklift or other means compressing the gasket tape. The lower lifting lugs are equipped with 2" diameter holes that 1.5" dia. (2" OD) steel pipe could be used to assist in alignment. Joining lift lugs also have a spacing bolt at the tip of one lug that will fit into the empty lug hole of the other module for alignment and lug tip spacing. Clamping Together at Lifting Lugs After positioning the modules together, compressing the gasket tape, insert four 3/8-16 x 1-1/4 plated hex head bolts through the holes on the base rail lifting lugs of the two adjacent modules. Secure the nuts to secure the bases of the two modules together tightly. Bolt Together Mating Roof Beams Use bar clamps, or other non-destructive winching device to pull the top of the modules together tightly compressing the gasket. After aligning the 4 roof bolt locations, insert 1/4-20 x 1.00 Grade 5 zinc plated hex head bolts through the holes in the roof beam. Secure the nuts to secure the roof section. Failure to install bolts in these locations will compromise the structural integrity of the unit and damage will occur during lifting. Also a water and airtight seal of the unit will be compromised. LE Rigging _002 Due to continuing product development, specifications are subject to change without notice RenewAire LLC LERiggingMan_Dec15.indd Revised 12/2015 Page 5

6 ASSEMBLY Caulk the Seams Install Assembly Strap Attention should be taken to assure the modules are forming an air and water tight seal. Two (2) galvanized metal assembly straps are used to secure the module seams to assist in maintaining a water and airtight seal and provide structural rigidity during lifting. One (1) used on each side of the unit. These straps are provided with pre-drilled holes. #12 X.75 hex head tek screw w/washers are provided to attach the joining straps to the unit. For additional protection, caulk sides of straps after attachment. Apply a continuous ½ bead of Tremsil 600 Silicone Sealant caulk (provided) at the seam along the entire roof and sides of the unit. For best results, use a lower torque setting on the power drill. Be careful not to over tighten the screw. Failure to apply caulk in these locations will compromise the water and airtight seal of the unit. Install Joining Roof Cap A galvanized cap roof flange is provided to seal the roof seam and to maintain an water and airtight seal. The cap roof flange is provided with pre-drilled holes. #12 X.75 hex head tek screw w/ washers are provided to attach the cap roof flange. For best results, use a lower torque setting on the power drill. Be careful not to over tighten the screw. Failure to install the roof cap will compromise the water and airtight integrity of the unit. LE Rigging _002 Failure to install the assembly straps will compromise the structural integrity of the unit and cause unit damage during lifting. Also compromise the water and airtight integrity of the unit. Install Joining Roof End Caps Two (2) galvanized roof cap ends are provided to seal the top end of each module and maintain a water and airtight seal. The roof cap joining ends are provided with pre-drilled holes. #12 X.75 hex head tek screw w/washers are provided to attach these roof cap joining ends to the unit. Failure to install roof cap ends will compromise the structural integrity of the unit and cause unit damage during lifting. Also compromise the water and airtight integrity of the unit. Due to continuing product development, specifications are subject to change without notice RenewAire LLC LERiggingMan_Dec15.indd Revised 12/2015 Page 6

7 ROOFTOP MODULES Assembly Before Lifting (See Indoor Module Assembly) FOLLOW STEPS FOR INDOOR UNIT. LVE HOODS INSIDE. The RenewAire roofcurb is shipped knocked-down with assembly hardware and instructions provided. The roof curb must then be assembled on the job site and set in place. Curb must be installed first. In all cases curb must be properly installed on roof before placing the unit on it. Dimensions accompany the curb but can also be found in this manual. See below. Cross members must be positioned per the drawing in order for properly support the unit. Align modules and push together compressing the gasket tape. The lower lifting lugs are equipped with 2 diameter holes that 1.5 dia. Schedule 40 steel pipe could be used to assist in alignment. Joining lift lugs also have a spacing bolt at the tip of one lug that will fit into the empty lug hole of hte other module for unit alignment and lug tip spacing. Follow assembly instructions above per indoor models to insure structural, water and airtight integrity. ROOFTOP MODELS ADDITIONAL INSTALLATION Weather hoods are located inside the unit and must be installed after the unit is in place (See IOM Manual accompanying the unit) Before operating the unit, insure all materials have been removed from the unit. The building structure must provide adequate structural support under vertical roofcurb members. Ensure that the roofcurb is square and level before installing the ERV. The installing contractor is responsible for proper connection to the roof along with insuring the curb to be watertight by caulking all curb joints. UNITS ASSEMBLED ON THE GROUND Apply curb clips as per RenewAire Curb Clip Manual Insure ducts are in place. Insure the curb is properly gasketed and the orientation of the unit is correct to line up with the curb openings. Hoist unit directly over duct openings. Carefully lower and align the unit with duct openings. Make sure the unit is properly seated and level. UNITS ASSEMBLED ON THE CURB When placing the unit on the curb in two modules, ensure the first module that is lifted and set in place has equal amount of gap between the frame rail of the unit and the curb approx. ½ all around. A shim should be used to properly align the module to the curb. This insures proper alignment of the second module to the first when pulling the modules together. NOTE For modular units, make certain to always install the module with bottom duct connection/s first. These shims also act to hold the first module in place as the second module is slid along the curb to be joined to the first. Set the second module on the curb as close as possible to the first module to minimize curb gasket tape damage when modules are slid together _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 7

8 LE6XRT Curb ROOFTOP CURB DIMENSIONS LE6XRT CURB 6X CURB CROSS-SECTION A-A (TYP.) 1 1/2" X 1/4" Neoprene Gasket 3/4" X 3 1/2" Wooden Nailer 1 7/8" 14" 9 1/2" 111 1/2" I.D. 25" 3" 3" A A 60 1/2" I.D. 64 1/4" O.D. SECTION A-A SCALE 1 : 30 20" 33" 17 1/4" 115 1/4" O.D. LE8XRT Curb CURB CROSS-SECTION A-A (TYP.) LE8XRT CURB 8X 9 1/2" 151 1/2" I.D. 25" 4 7/8" 1 1/2" X 1/4" Neoprene Gasket 3/4" X 3 1/2" Wooden Nailer 14" 1 7/8" 3" A A 60 1/2" I.D. 64 1/4" O.D. SECTION A-A SCALE 1 : 30 20" 155 1/4" O.D. 49" 21 1/8" _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 8

9 LE10XRT Curb ROOFTOP CURB DIMENSIONS _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 9

10 LE6XRT 71 1/8" Overall 65 5/8" Case 4" 115 1/4" O.D. Outlet 17 1/4" 33" A Location (Optional) CURB LE6X A 64 1/4" O.D. 9 1/2" 20" 25" 60 1/2" I.D. 25 1/4" 44 5/8" C L 11 3/8" (5) 7/8" 3" 15 1/2" X 13 3/8" Electrical Connection Cover 9" 53 1/2" E-Box Disconnect Switch C L 5 1/4" (2) 7/8" ROOFTOP UNIT DIMENSIONS 36" E-Box 44" (RTV, RTF) Opening 19 1/2" X 16 1/8" 38 7/8" 22 1/4" 18 3/8" RTH, RTR ONLY 69 3/4" 49 5/8" 111" 111 1/8" Overall 69 1/4" Case 2" Typ. 73 3/8" Lifting Lugs RTV, RTF ONLY RTV, RTR ONLY 60 1/4" Blower Service Area Typ. 19 5/8" Typ. Pressure Ports (4) Typ. RTH, RTF ONLY 2" Typ. (RTV, RTR) Opening 33 1/2" X 24" CURB CROSS-SECTION A-A (TYP.) 1 1/2" X 1/4" Neoprene Gasket 3/4" X 3 1/2" Wooden Nailer 8 3/4" ABBREVIATIONS : Exhaust Air to outside : Outside Air intake : Room Air to be exhausted : Fresh Air to inside RTV: Rooftop Vertical & RTF: Rooftop Vertical Only RTR: Rooftop Vertical Only RTH: Rooftop Horizontal & INSTALLATION ORIENTATION Unit must be installed in orientation shown. NOTE: 1. UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NREST EIGHTH OF AN INCH. 2. SPECIFICATIONS MAY BE SUBJECT 3" 125 3/8" Overall 122 5/8" Case 25 3/8" Inlets, Locations (Optional) 1 7/8" 14" SECTION A-A Duct Flange 24" X 32" Typ. LEFT VIEW FRONT VIEW RIGHT VIEW LE8XRT CURB LE8X 64 1/4" O.D. 69 3/4" ABBREVIATIONS : Exhaust Air to outside : Outside Air intake : Room Air to be exhausted : Fresh Air to inside RTV: Rooftop Vertical & RTF: Rooftop Vertical Only RTR: Rooftop Vertical Only RTH: Rooftop Horizontal & 155 1/4" O.D. 21 1/4" 49" A A 9 1/2" 20" 25" 3" 60 1/2" I.D /2" I.D. 36" E-Box 52 1/8" Typ. (RTV, RTF) Opening 19" X 48" 49 3/8" 17 3/8" 78 1/2" Blower Service Area Typ. (RTV, RTR) Opening 24" X 48" CURB CROSS-SECTION A-A (TYP.) 1 1/2" X 1/4" Neoprene Gasket 3/4" X 3 1/2" Wooden Nailer INSTALLATION ORIENTATION Unit must be installed in orientation shown. NOTE: 1. UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NREST EIGHTH OF AN INCH. 2. SPECIFICATIONS MAY BE SUBJECT 3" 1 7/8" 14" Location (Optional) 71 1/8" Overall 65 5/8" Case Outlet 15 1/2" X 13 3/8" Electrical Connection Cover 64 5/8" 9" 53 1/2" E-Box Disconnect Switch 111 1/4" Overall 22 1/2" 69 1/8" Case 19 3/4" RTH, RTR ONLY 111" RTH, RTF ONLY 8 3/4" SECTION A-A 165 3/8" Overall 162 5/8" Case 4" 16 1/8" X 16 3/8" Typ. C L 11 3/8" (5) 7/8" LEFT VIEW 58 5/8" 28 1/2" C L 5 1/4" (2) 7/8" 73 3/8" Lifting Lugs RTV, RTF ONLY RTV, RTR ONLY FRONT VIEW 2" Typ. 27 3/8" Inlets, Locations (Optional) RIGHT VIEW Opening 24" X 48" _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 10

11 LE10XRT 71 1/8" Overall Outlet Location (Optional) 69 5/8" Case 37 7/8" 44 5/8" 195 1/4" O.D. 20" 9" A 41 1/8" 49" CURB LE10X 64 1/4" O.D. A 15 1/2" X 13 3/8" Electrical Connection Cover 24" X 48" Outlet RTH, RTR 60 1/2" I.D. 47 1/4" LEFT VIEW 9 1/2" 25" 3" 191 1/2" I.D. E-Box Disconnect Switch 84 5/8" C L 11 3/8" (5) 1 1/8" ROOFTOP UNIT DIMENSIONS 29 5/8" 36" E-Box 53 1/2" C L 5 1/4" (2) 7/8" 69 3/4" 72 1/8" Typ. (RTV, RTF) 19" X 48" 2" Typ. RTH, RTR ONLY RTH, RTR ONLY C L 2 1/4" Wiring 111" 4" 49 3/8" 17 3/8" 111 1/8" Overall 69 1/8" Case RTV, RTF ONLY 73 3/8" Lift Lugs RTV, RTR ONLY FRONT VIEW 79 7/8" Blower Service Area Typ. 2" (RTV, RTR) 24" X 48" Pressure Ports (4) Typ. RTH, RTF ONLY 4 1/2" 93 5/8" 8 3/4" CURB CROSS-SECTION A-A (TYP.) 1 1/2" X 1/4" Neoprene Gasket 3/4" X 3 1/2" Wooden Nailer 47 1/4" ABBREVIATIONS : Exhaust Air to outside : Outside Air intake : Room Air to be exhausted : Fresh Air to inside RTV: Rooftop Vertical & RTF: Rooftop Vertical Only RTR: Rooftop Vertical Only RTH: Rooftop Horizontal & INSTALLATION ORIENTATION Unit must be installed in orientation shown. NOTE: 1. UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NREST EIGHTH OF AN INCH. 2. SPECIFICATIONS MAY BE SUBJECT 205 3/8" Overall 202 5/8" Case Inlets Locations (Optional) 1 7/8" 3" 14" SECTION A-A RIGHT VIEW 24" X 48" Inlet (RTH, RTF) _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 11

12 LE6XINH INDOOR UNIT DIMENSIONS 69 3/4" ABBREVIATIONS : Exhaust Air to outside : Outside Air intake : Room Air to be exhausted : Fresh Air to inside INSTALLATION ORIENTATION Unit must be installed in orientation shown. NOTE 1.UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NREST EIGHTH OF AN INCH. 2.SPECIFICATIONS MAY BE SUBJECT 36" E-Box 60 1/4" Blower Service Area Typ. 22" X 24" Duct Flange Typ. Optional Motorized 71 1/8" Overall 69 5/8" Case 38 3/4" 15 1/2" X 13 3/8" Electrical Connection Cover 44 5/8" 33 5/8" E-Box Disconnect Switch 53 1/2" 4 1/4" Flanges 18 5/8" 111" 80 1/4" Overall Pressure Ports (4) Typ. 8 3/4" 125 3/8" Overall 122 5/8" Case 41 1/2" 27" Optional Motorized 6 1/4" C L 11 3/8" (5) 1 1/8" LEFT VIEW 29 5/8" C L 5 1/4" (2) 7/8" 4" C L 2 1/4" Wiring 69 1/8" Case C L 73 3/8" Lift Lugs FRONT VIEW 2" 2" Typ. 25 1/4" RIGHT VIEW 25 1/4" 24" X 32" Duct Flange Typ. LE8XINH 69 3/4" ABBREVIATIONS : Exhaust Air to outside : Outside Air intake : Room Air to be exhausted : Fresh Air to inside INSTALLATION ORIENTATION Unit must be installed in orientation shown. NOTE 1.UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NREST EIGHTH OF AN INCH. 2.SPECIFICATIONS MAY BE SUBJECT 22" X 24" Duct Flange Typ. Optional Motorized 71 1/8" Overall 69 5/8" Case 27 1/4" 38 1/4" 6" Optional Motorized 15 1/2" X 13 3/8" Electrical Connection Cover 27 1/4" 64 5/8" C L 11 3/8" (5) 1 1/8" LEFT VIEW Disconnect Switch 29 5/8" E-Box 53 1/2" C L 5 1/4" (2) 7/8" 36" E-Box 4 1/4" Flanges 18 5/8" 4" C L 2 1/4" Wiring 111" 80 1/4" Overall 69 1/8" Case C L 73 3/8" Lift Lugs FRONT VIEW 78 1/2" Blower Service Area Typ. Pressure Ports (4) Typ. 2" 2" Typ. 8 3/4" 165 3/8" Overall 162 5/8" Case 27 3/8" 27 3/8" 24" X 32" Duct Flange Typ. RIGHT VIEW 41 1/2" _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 12

13 LE10XINH INDOOR UNIT DIMENSIONS 69 3/4" ABBREVIATIONS : Exhaust Air to outside : Outside Air intake : Room Air to be exhausted : Fresh Air to inside INSTALLATION ORIENTATION Unit must be installed in orientation shown. NOTE: 1. UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NREST EIGHTH OF AN INCH. 2. SPECIFICATIONS MAY BE SUBJECT 36" E-Box 15 1/2" X 13 3/8" Electrical Connection 22" X 50" Cover Duct Flange Typ. 71 1/8" Overall 69 5/8" Case Optional Motorized 47 1/4" 6" E-Box Disconnect Switch 47 1/8" 84 5/8" 53 1/2" 4 1/4" Flanges 18 5/8" 111" 80 1/4" Overall 79 7/8" Blower Service Area Typ. Pressure 205 3/8" Overall Ports (4) Typ /8" Case 41 1/2" 38 1/4" Optional Motorized LEFT VIEW C L 11 3/8" (5) 1 1/8" 29 5/8" C L 5 1/4" (2) 7/8" 4" C L 2 1/4" Wiring 69 1/8" Case 73 3/8" Lift Lugs FRONT VIEW 2" 2" Typ. 8 3/4" 47 1/4" 24" X 48" Duct Flange Typ. RIGHT VIEW 47 1/4" _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 13

14 LE6XINV INDOOR UNIT DIMENSIONS 69 3/4" 34" ABBREVIATIONS : Exhaust Air to outside : Outside Air intake : Room Air to be exhausted : Fresh Air to inside INSTALLATION ORIENTATION Unit must be installed in orientation shown. NOTE 1.UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NREST EIGHTH OF AN INCH. 2.SPECIFICATIONS MAY BE SUBJECT 15 1/2" X 13 3/8" Electrical Optional Connection Motorized Cover 24" X 32" Duct Flange Typ. 71 1/8" Overall 69 5/8" Case 44 5/8" 33 5/8" E-Box 36" E-Box Disconnect Switch 53 1/2" 4 1/4" Flanges 111" 80 1/4" Overall 60 1/4" Blower Service Area Pressure Ports (4) Typ. 2" Optional Motorized 6 1/4" Typ /8" Overall 122 5/8" Case 41 1/2" Typ. 25 1/4" 22" X 24" Duct Flange Typ. C L 11 3/8" (5) 1 1/8" LEFT VIEW 29 5/8" C L 5 1/4" (2) 7/8" 4" C L 2 1/4" Wiring 69 1/8" Case C L 73 3/8" Lift Lugs FRONT VIEW 2" Typ. 18 5/8" Typ. 33 5/8" RIGHT VIEW 25 1/4" LE8XINV 69 3/4" 34" ABBREVIATIONS : Exhaust Air to outside : Outside Air intake : Room Air to be exhausted : Fresh Air to inside INSTALLATION ORIENTATION Unit must be installed in orientation shown. NOTE 1.UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NREST EIGHTH OF AN INCH. 2.SPECIFICATIONS MAY BE SUBJECT 36" E-Box 78 1/2" Blower Optional Motorized 24" X 48" Duct Flange Typ. 71 1/8" Overall 69 5/8" Case 27 3/8" 22" X 50" Duct FlangeTyp. 15 1/2" X 13 3/8" Electrical Connection Cover 27 1/4" 64 5/8" C L 11 3/8" (5) 1 1/8" LEFT VIEW E-Box Disconnect Switch 29 5/8" 53 1/2" C L 5 1/4" (2) 7/8" 4 1/4" Flanges 4" C L 2 1/4" Wiring 111" 80 1/4" Overall 69 1/8" Case C L 73 3/8" Lift Lugs FRONT VIEW Pressure Ports (4) Typ. 2" 18 5/8" Typ. 2" Typ. Optional Motorized 6" Typ /8" Overall 162 5/8" Case 27 1/4" 27 3/8" RIGHT VIEW 41 1/2" Typ _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 14

15 41 1/2" LE10XINV INDOOR UNIT DIMENSIONS 69 3/4" 34" ABBREVIATIONS : Exhaust Air to outside : Outside Air intake : Room Air to be exhausted : Fresh Air to inside INSTALLATION ORIENTATION Unit must be installed in orientation shown. NOTE: 1. UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NREST EIGHTH OF AN INCH. 2. SPECIFICATIONS MAY BE SUBJECT 36" E-Box 71 1/8" Overall 69 5/8" Case 15 1/2" X 13 3/8" Electrical Connection Cover Optional Motorized 41 1/2" 47 1/4" 6" 47 1/8" LEFT VIEW E-Box Disconnect Switch 84 5/8" 29 5/8" 53 1/2" C L 11 3/8" (5) 1 1/8" C L 5 1/4" (2) 7/8" 4 1/4" Flanges 18 5/8" 2" Typ. 4" C L 2 1/4" Wiring 111" 80 1/4" Overall 69 1/8" Case 73 3/8" Lift Lugs FRONT VIEW 79 7/8" Blower Pressure Ports (4) Typ. 2" 6" Optional Motorized 47 1/4" 205 3/8" Overall 202 5/8" Case 22" X 50" Duct Flange Typ. RIGHT VIEW 24" X 48" Duct Flange Typ. 47 1/4" _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 15

16 LE6X CORNER 73.5" Lifting Lug Use all lifting lugs provided when lifting, including central lugs on assembled units. LE6XRT Models LR RR Basic Unit Weights (lbs.) "A" 119.5" Lifting Lug Adder Weights for Installed Options (lbs.) Options Double Wall (2) VFDs "B" LF RF Center of Gravity A = 33 B = 59-1/2 (+/- 2 ) LE6XRT Models LR LF "A" SPECIFICATIONS SUBJECT 73.5" Lifting Lug End "B" Back Module 73.5" Lifting Lug Front Module "B" End "A" RR 1/30/2014 MF RF 59.3" Lifting Lug 59.3" Lifting Lug 3 BASIC MODULE (lbs.) Motors 5 UNIT 1024 LF 257 LR RR 205 RF HP HP Basic Back Module Weights (lbs.) Adder 714 Module 207Weights 158for Installed 151 Options 198 (lbs.) 7.5 Options HP Double ADDITIONAL Wall 208 FOR 64 OPTIONS 40(lbs.) (2) Options VFDs UNIT 0 LF 0 LR RR 0 RF 0 0 Double Wall VFDs BASIC MODULE (lbs.) Motors UNIT LF LR RR RF Total Center Selected of Weights Gravity: A = 42 B = 25 (+/- 2 ) 3 HP Add the additional weights for options to the Basic Unit weights determined by motor size 5 to HP determine Unit and 1283Corner 345 weights for 306 a specific 297 unit. 335 LE6XRT Models 7.5 HP Basic Front Module Weights (lbs.) ADDITIONAL FOR OPTIONS (lbs.) Options Unit UNIT LF LF LR LR RR RF RR RF Double Wall RR VFDs MODULE AT LIFTING 3 LUGS Options Total Selected Weights Do not scale Double drawingwall Add the additional weights for options to the Basic Unit weights determined by motor size to determine Unit and Corner weights for a specific unit. RenewAire (2) LLCVFDs 15 LE-6X-INV_CORNER JAN14.2.dwg Center FRONT of Gravity: MODULE A = 37-1/4 B = AT 27 LIFTING (+/- 2 ) LUGS _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 16 SPECIFICATIONS SUBJECT 1/30/2014 MF Do not scale drawing

17 LE6X CORNER LE6XINV Models Basic Unit Weights (lbs.) Adder Weights for Installed Options (lbs.) Options Double Wall (2) VFDs LE6XINH Models Basic Unit Weights (lbs.) Adder Weights for Installed Options (lbs.) Options Double Wall #VALUE! (2) VFDs Center of Gravity A = 36 B = 51 (+/- 2 ) Center of Gravity A = 31-3/4 B = 59-1/2 (+/- 2 ) LE6XINV Models Basic Back Module Weights (lbs.) Options Double Wall (2) VFDs LE6XINH Models Basic Back Module Weights (lbs.) Options Double Wall (2) VFDs Center of Gravity: A = 36 B = 23 (+/- 2 ) Center of Gravity: A = 42 B = 25 (+/- 2 ) LE6XINV Models Basic Front Module Weights (lbs.) Options Double Wall (2) VFDs LE6XINH Models Basic Front Module Weights (lbs.) Options Double Wall (2) VFDs Center of Gravity: A = 36 B = 27 (+/- 2 ) Center of Gravity: A = 32-3/4 B = 27 (+/- 2 ) _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 17

18 LE8X CORNER LR 73.5" Lifting Lug RR Use all lifting lugs provided when lifting, including central lugs on assembled units. LE8XRT Models Basic Unit Weights (lbs.) "A" 159.5" Lifting Lug Adder Weights for Installed Options (lbs.) Options Double Wall (2) VFDs "B" LF RF Center of Gravity A = 32-1/2 B = 76-1/2 (+/- 2 ) LE8XRT Models RF RR LR SPECIFICATIONS SUBJECT LF "A" SPECIFICATIONS SUBJECT 73.5" Lifting Lug End "B" Back Module 73.5" Lifting Lug "A" LF LR RR Front Module 1/ MF "B" End RF 1/ MF 79.5" Lifting Lug 79.5" Lifting Lug Basic Back Module Weights (lbs.) BASIC UNIT (lbs.) Motors 3 UNIT 1320 LF LR 332 RR 266 RF HP HP HP ADDITIONAL FOR OPTIONS (lbs.) Options Options Double Wall UNIT 262 LF 78 LR RR 53 RF Double Wall (2) VFDs VFDs BASIC MODULE 21 0 (lbs.) Motors UNIT LF LR RR RF HP Total Selected Weights 5 HP Add the additional weights for options to the Basic Module weights determined by motor size to determine Module and Corner weights for a specific unit. Center 7.5 HP of Gravity: A 1709 = 42 B 516 = 35 (+/ ) ADDITIONAL FOR OPTIONS (lbs.) Options UNIT LF LE8XRT LR Models RR RF Double Wall Basic 53 Front Module 53 Weights 78 (lbs.) VFDs Unit LF 2 LR 0 1 RR RF BACK MODULE 3 CORNER AT LIFTING LUGS Total Selected 7.5Weights Add the additional weights for options to the Basic Module weights determined Do not scale drawing by motor size to determine Module and Corner weights for a specific unit. Options RenewAire LLC Unit LF LR RR LE-8X-INV_CORNER JAN14.1.dwg RF Double Wall (2) VFDs FRONT MODULE CORNER AT LIFTING LUGS Center of Gravity: A = 33 B = 32-3/4 (+/- 2 ) Do not scale drawing RenewAire LLC LE-8X-INV_CORNER JAN14.1.dwg _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 18

19 LE8X CORNER LE8XINV Models Basic Unit Weights (lbs.) Adder Weights for Installed Options (lbs.) Options Double Wall (2) VFDs LE8XINH Models Basic Unit Weights (lbs.) Adder Weights for Installed Options (lbs.) Options Double Wall (2) VFDs Center of Gravity A = 36-1/2 B = 66-1/2 (+/- 2 ) Center of Gravity A = 32-1/2 B = 76-1/2 (+/- 2 ) LE8XINV Models Basic Back Module Weights (lbs.) Options Double Wall (2) VFDs LE8XINH Models Basic Back Module Weights (lbs.) Options Double Wall (2) VFDs Center of Gravity: A = 36-3/4 B = 35 (+/- 2 ) Center of Gravity: A = 42 B = 35 (+/- 2 ) LE8XINV Models Basic Front Module Weights (lbs.) Options Double Wall (2) VFDs LE8XINH Models Basic Front Module Weights (lbs.) Options Double Wall (2) VFDs Center of Gravity: A = 36-1/2 B = 32-3/4 (+/- 2 ) Center of Gravity: A = 33 B = 32-3/4 (+/- 2 ) _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 19

20 LE10X CORNER LR 73.5" Lifting Lug RR Use all lifting lugs provided when lifting, including central lugs on assembled units. LF "A" "B" RF 194.5" Lifting Lug LE10XRT Models Basic Unit Weights (lbs.) Adder Weights for Installed Options (lbs.) Options Double Wall VFDs Center of Gravity A = 32" B = 99-1/2" (+/- 2") 73.5" Lifting Lug End RF LF "B" "A" RR LR Back Module 99.5" Lifting Lug LE10XRT Models Basic Back Module Weights (lbs.) Options Double Wall VFDs Center of Gravity: A = 41" B = 48-1/2" (+/- 2") 73.5" Lifting Lug LR RR Front Module "A" "B" LF RF End 99.5" Lifting Lug LE10XRT Models Basic Front Module Weights (lbs.) Options Double Wall (2) VFDs Center of Gravity: A = 31-1/2" B = 46-1/2" (+/- 2") _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 20

21 LE10X CORNER LE10XINV Models Basic Unit Weights (lbs.) Adder Weights for Installed Options (lbs.) Options Double Wall (2) VFDs Center of Gravity A = 35-1/2" B = 86-1/2" (+/- 2") LE10XINH Models Basic Unit Weights (lbs.) Adder Weights for Installed Options (lbs.) Options Double Wall (2) VFDs Center of Gravity A = 30-1/2" B = 99" (+/- 2") LE10XINV Models Basic Back Module Weights (lbs.) Options Double Wall (2) VFDs Center of Gravity A = 37-1/2" B = 37" (+/- 2") LE10XINH Models Basic Back Module Weights (lbs.) Options Double Wall (2) VFDs Center of Gravity A = 43" B = 43" (+/- 2") LE10XINV Models Basic Front Module Weights (lbs.) Options Double Wall (2) VFDs Center of Gravity A = 35" B = 47" (+/- 2") LE10XINH Models Basic Front Module Weights (lbs.) Options Double Wall (2) VFDs Center of Gravity A = 30-1/2" B = 46-1/2" (+/- 2") _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 21

22 This page intentionally left blank _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 22

23 This page intentionally left blank _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 23

24 See more specific Installation and Operation Manual for additional Assembly, Start-Up, Commissioning and Maintenance supplied with the unit and Manuals at _002 LERiggingMan_Dec15.indd Revised 12/2015 Page 24

The newest addition to RenewAire s broad line of Energy Recovery Ventilators.

The newest addition to RenewAire s broad line of Energy Recovery Ventilators. INTRODUCING HE 1.5X The newest addition to RenewAire s broad line of Energy Recovery Ventilators. The perfect size for the largest number of ventilation applications in the industry: 375-1,400 CFM Advanced

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR

INSTALLATION, OPERATION & MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR INSTALLATION, OPERATION & MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR MODEL: WWW.RENEWAIRE.COM ERV TABLE OF CONTENTS HE1XIN info... 2-5 Installation... 6-14 Start-up...15-17 Maintenance...18-19 ABOUT

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR

INSTALLATION, OPERATION & MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR INSTALLATION, OPETION & MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR HE2XRT MODEL: HE2XRT RENEWAIRE.COM HE2XRT ABOUT RENEWAIRE For over 30 years, RenewAire has been a pioneer in enhancing indoor air quality

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR

INSTALLATION, OPERATION & MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR INSTALLATION, OPERATION & MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR HE6X MODEL: HE6XIN RENEWAIRE.COM ERV HE6X HE6X INFO TABLE OF CONTENTS HE6X info... 2-6 Installation...7-14 Start-up & Operation...15-18

More information

XeteX, Inc. All Rights Reserved.

XeteX, Inc. All Rights Reserved. Model XC Indoor or outdoor mounted, simple, in-case aluminum flat plate exchanger with options for frost control. Ideal for inline installations: in duct-work systems, in built-up units, or in modular

More information

INSTALLATION INSTRUCTIONS WALL MOUNT RANGE HOOD WITH M600 OR M1200 BLOWER

INSTALLATION INSTRUCTIONS WALL MOUNT RANGE HOOD WITH M600 OR M1200 BLOWER WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT RANGE HOOD

More information

GE Monogram. Installation. Instructions. Professional Vent Hoods. 48" Models ZV881WSS, ZV891YSS ZV880WSS, ZV890YSS. 36" Models ZV671WSS, ZV681YSS

GE Monogram. Installation. Instructions. Professional Vent Hoods. 48 Models ZV881WSS, ZV891YSS ZV880WSS, ZV890YSS. 36 Models ZV671WSS, ZV681YSS GE Monogram Installation Instructions Professional Vent Hoods 48" Models ZV881WSS, ZV891YSS ZV880WSS, ZV890YSS 36" Models ZV671WSS, ZV681YSS ZV670WSS, ZV680YSS 30" Models ZV370YSS, ZV371YSS CAUTION WARNING

More information

2520- EC Motor Speed Controller

2520- EC Motor Speed Controller 2520- EC Motor Speed Controller T1 AC Line Voltage From Contactor T2 or Neutral 760-ECM ECM Motor BLACK ORANGE BLACK RED (+) Signal 24VAC (-) GND Features Motor Types: ECM (dc brushless) Motors Motor Speed:

More information

SAFETY INSTRUCTIONS Before installation and operation, read these instructions carefully and use this product only in the manner described by the manu

SAFETY INSTRUCTIONS Before installation and operation, read these instructions carefully and use this product only in the manner described by the manu Installation Manual RANGE HOOD MODEL: BUF-07W BUF-07P BUF-07W/P TABLE OF CONTENTS Safety Instructions... 2, 3 Name of Parts... 4 Circuit Diagram... 4 Dimensions/Accessories... 5, 6 Range Hood Location...

More information

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System V-Series (rev. 08/17/10) Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System Note: Optional items and/or items requiring a choice, are shown between brackets and/or parentheses

More information

INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD

INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

INSTALLATION INSTRUCTIONS WALL MOUNT RANGE HOOD WITH M600 OR M1200 BLOWER

INSTALLATION INSTRUCTIONS WALL MOUNT RANGE HOOD WITH M600 OR M1200 BLOWER WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT RANGE HOOD

More information

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO ISLAND RANGE HOOD

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO ISLAND RANGE HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO ISLAND RANGE HOOD Read All Instructions Thoroughly Before Beginning

More information

INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD

INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Automatic Roof Door Vents

Automatic Roof Door Vents DATA SHEET Automatic Roof Door Vents Features n UL Listed for use as an automatic smoke vent n FM Approved as an automatic door vent for use in high expansion foam systems n Available in multiple sizes

More information

INSTALLATION INSTRUCTIONS ISLAND LINER INSERT

INSTALLATION INSTRUCTIONS ISLAND LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS ISLAND LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

MICRO-AIR DUST COLLECTOR Installation and Operation Manual MODEL RP6-2, RP-3, RP8-2 & RP-3

MICRO-AIR DUST COLLECTOR Installation and Operation Manual MODEL RP6-2, RP-3, RP8-2 & RP-3 MICRO-AIR DUST COLLECTOR Installation and Operation Manual MODEL RP6-2, RP-3, RP8-2 & RP-3 Important: This manual contains specific cautionary statements relative to worker safety. Read this manual thoroughly

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS Part #469003 Model Vektor -H Installation Operation and Maintenance Manual for Vektor-H Laboratory Exhaust System Receiving Greenheck model Vektor-H fans are thoroughly

More information

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO ISLAND RANGE HOOD

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO ISLAND RANGE HOOD WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO

More information

WALL MOUNTING KIT ASSEMBLY INSTRUCTIONS MODELS: TXBW & TXDW

WALL MOUNTING KIT ASSEMBLY INSTRUCTIONS MODELS: TXBW & TXDW Wall Opening Wall Mounting Adaptor (Optional) Support Strap E WALL MOUNTING KIT ASSEMBLY INSTRUTIONS MODELS: TXBW & TXDW The centrifugal power roof ventilators model TXB (belt drive) and TXD (direct drive)

More information

INSTALLATION INSTRUCTIONS JDH/C2 DESIGNER SERIES WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS JDH/C2 DESIGNER SERIES WALL MOUNT HOOD WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS JDH/C2 DESIGNER SERIES

More information

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO

More information

2-row and All-row systems included.

2-row and All-row systems included. Ag Leader Technology Cotton Picker Installation Installation Instructions for John Deere cotton picker models: 2-row and All-row systems included. IMPORTANT: Ensure the model numbers shown above correspond

More information

WARNING: FIRE OR EXPLOSION HAZARD

WARNING: FIRE OR EXPLOSION HAZARD D300530D (10-18) I-Y Supersedes D300530C (06-18) I-Y Installation/Operation Applies to: Models YDHA, YDMA, and YDSA Packaged Rooftop Equipment CUSTOMER AGENCY PROCESS CQS CONVERGENT QUALITY SYSTEM PRODUCT

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Intelligent Flow Measurement Your Sole Source for Badger Differential Producers Worldwide 6 Blackstone Valley Place, Lincoln RI 02865-1162 Ph: 401 334 1170 Fx: 401 334 1173 Em: solutions@wyattflow. Installation,

More information

READ THIS FIRST. Read and Save These Instructions AIR CURTAINS INSTALLATION INSTRUCTIONS S-XHD SERIES. TMI, LLC Managing Environments

READ THIS FIRST. Read and Save These Instructions AIR CURTAINS INSTALLATION INSTRUCTIONS S-XHD SERIES. TMI, LLC Managing Environments READ THIS FIRST Carefully examine the crate(s) for damage before opening. If the carton is damaged, immediately notify shipping company. If the unit(s) were shipped on wooden skids, remove protective wood

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 62MB,MC,MD,ME040-950 Energy Recovery Ventilators Installation, Start-Up and Service Instructions CONTENTS Page SFETY CONSIDERTIONS...1 INTRODUCTION...1 INSTLLTION... 1-58 Step 1 Inspection...1 Step 2 Install

More information

INSTALLATION INSTRUCTIONS CWSH3 WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWSH3 WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS CWSH3 WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

ERV ENERGY RECOVERY VENTILATOR 60 HZ. Indoor / Outdoor 500 to 10,000 cfm Capacity ERV I - D - D - P - 1 MODEL NUMBER IDENTIFICATION

ERV ENERGY RECOVERY VENTILATOR 60 HZ. Indoor / Outdoor 500 to 10,000 cfm Capacity ERV I - D - D - P - 1 MODEL NUMBER IDENTIFICATION P R O D U C T S P E C I F I C AT I O N S I N D O O R A I R Q U A L I T Y ERV ENERGY RECOVERY VENTILATOR 60 HZ Bulletin No. 20245 March 200 Supersedes April 2009 Indoor / Outdoor 500 to 0,000 cfm Capacity

More information

Viking Installation Guide

Viking Installation Guide Viking Installation Guide Professional Series Built-In Chimney-Style Hoods Viking Range Corporation 111 Front Street Greenwood, MIssissippi 38930 USA NOTE: IF INSTALLING HOOD WITH WARMING SHELF PANEL,

More information

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS BY JOHNSON CONTROLS INSTALLATION OPERATION & MAINTENANCE MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS New Release Form ET130.13-NOM4 (908) In conjunction with the use of these instructions, obtain

More information

! WARNING: CQS. Installation / Operation FIRE OR EXPLOSION HAZARD. R-410A Refrigerant

! WARNING: CQS. Installation / Operation FIRE OR EXPLOSION HAZARD. R-410A Refrigerant Form I-Y (3-16-16) Obsoletes Form I-Y (3-16) Installation / Operation Applies to: Models YDHA, YDMA, and YDSA Packaged Rooftop Equipment CUSTOMER AGENCY PROCESS CQS CONVERGENT QUALITY SYSTEM PRODUCT WARRANTY

More information

INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL 4510 Helgesen Drive, Madison, WI 53718 (608) 221-4499, (800) 627-4499, Fax: (608) 221-2824 support@renewaire.com www.renewaire.com INSTALLATION AND OPERATION MANUAL EV450IN RISK OF FIRE, ELECTRIC SHOCK,

More information

MODELS CSF & LSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS

MODELS CSF & LSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS S CSF & LSF Model CSF Hooded Design FEATURES Supply air to over 13,000 CFM in static pressure capabilities to 2 w.g. Heavy-galvanized construction Belt drives permit easy performance adjustments when needed

More information

P RO W ALL V ENTILATION H OODS INSTALLATION INSTRUCTIONS

P RO W ALL V ENTILATION H OODS INSTALLATION INSTRUCTIONS P RO W ALL V ENTILATION H OODS INSTALLATION INSTRUCTIONS CONTACT INFORMATION Wolf Customer Service: 800-332-9513 Website: wolfappliance.com As you follow these instructions, you will notice WARNING and

More information

Gravity Ventilators. Models FGI and FGR. Fabra Hood Intake and Relief

Gravity Ventilators. Models FGI and FGR. Fabra Hood Intake and Relief Gravity Ventilators Models FGI and FGR Fabra Hood Intake and Relief July 008 Page Fabra Header Hood Greenheck Fabra Hoods are designed for intake (Model FGI) or relief (Model FGR) applications with either

More information

INSTALLATION INSTRUCTIONS CWUH9 WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWUH9 WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS CWUH9 WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

INSTALLATION INSTRUCTIONS K SERIES LINER INSERT

INSTALLATION INSTRUCTIONS K SERIES LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS K SERIES LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Installation Instructions

Installation Instructions FILCAB Filter Cabinet Sizes 6 --- in., 0 --- in., 4 --- in. For Non---Condensing and Condensing Gas Furnaces and FILCAB Accessory Kits Installation Instructions NOTE: Read the entire instruction manual

More information

INSTALLATION INSTRUCTIONS UNDER CABINET HOOD

INSTALLATION INSTRUCTIONS UNDER CABINET HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS UNDER CABINET HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Inline and Roof Mounted Fans

Inline and Roof Mounted Fans CV Inline and Roof Mounted Fans Page Introduction........................................... 2 Construction Features................................. 3-4 Specifications and Dimension Data CVD (Direct Drive

More information

PowerFlex 7000 AC Drive with Direct-to-Drive Technology. Re-installing a Common Mode Choke Bulletin 7000 Installation Instructions

PowerFlex 7000 AC Drive with Direct-to-Drive Technology. Re-installing a Common Mode Choke Bulletin 7000 Installation Instructions PowerFlex 7000 AC Drive with Direct-to-Drive Technology Re-installing a Common Mode Choke Bulletin 7000 Installation Instructions Important User Information Solid-state equipment has operational characteristics

More information

VL-100U5-E (pull cord type) VL-100EU5-E (wall switch type)

VL-100U5-E (pull cord type) VL-100EU5-E (wall switch type) 1301875HF7701 Mitsubishi Lossnay Ventilator MODEL: VL-100U5-E (pull cord type) VL-100EU5-E (wall switch type) Installation Manual For Dealer and Contractor Please ensure that the separate Operating Instructions

More information

Safety & Installation Instructions

Safety & Installation Instructions Model 8120A & 8126A Digital Ventilation Controller Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Safety Instructions... 3 Specifications... 4 Overview... 4 Mounting

More information

INSTALLATION INSTRUCTIONS JCH/C2 DESIGNER SERIES WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS JCH/C2 DESIGNER SERIES WALL MOUNT HOOD WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS JCH/C2 DESIGNER SERIES

More information

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS MiniCOREVentilator ENERGY RECOVERY CORE INSTALLATION INSTRUCTIONS MC500-1ERV JANUARY 10, 2018 SUPERSEDES: NONE INSTALLATION INSTRUCTIONS FOR MINICORE VENTILATOR (MCV) WITH FACTORY INSTALLED OPTIONS USED

More information

INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL 0 Helgesen Drive, Madison, WI 78 (608) -99, (800) 67-99, Fax: (608) -8 support@renewaire.com www.renewaire.com INSTALLATION AND OPETION MANUAL HEXRT RISK OF FIRE, ELETRI SHOK, OR INJURY. OBSERVE ALL ODES

More information

CPC Commercial. 15- & 20-Ton, Three-Phase Packaged Air Conditioner. 20-Ton Cooling Capacity: 240,000 BTU/h

CPC Commercial. 15- & 20-Ton, Three-Phase Packaged Air Conditioner. 20-Ton Cooling Capacity: 240,000 BTU/h CPC Commercial 15- & 20-Ton, Three-Phase Packaged Air Conditioner 15-Ton Cooling Capacity: 180,000 BTU/h 20-Ton Cooling Capacity: 240,000 BTU/h Contents Nomenclature...2 Product Features...3 Product Specifications...4

More information

INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

INSULATED CANTED ROOF CURB NON-PROPELLER PRODUCTS

INSULATED CANTED ROOF CURB NON-PROPELLER PRODUCTS INSULATED ANTED ROOF URB NON-PROPELLER PRODUTS Wood Nailer A 3" 3/4" 3" 1" Semi-Rigid Insulation Damper Shelf (Optional) (1) B OPTIONS: 1. Damper Shelf. 2. Metal Liner - solid or screen type. 3. Burglar

More information

ECONOMIZER FAN. Receiving and Inspection

ECONOMIZER FAN. Receiving and Inspection ECONOMIZER FAN Economizer Fans INSTALLATION, OPERATION AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance instructions for standard units of the Economizer Fan

More information

INSULATED CANTED ROOF CURB NON-PROPELLER PRODUCTS

INSULATED CANTED ROOF CURB NON-PROPELLER PRODUCTS INSULATED ANTED ROOF URB NON-PROPELLER PRODUTS Wood Nailer A OPTIONS: 1. Damper Shelf. 2. Metal Liner - solid or screen type. 3. Burglar bars - 1/2" dia. on 6" centers. 4. Finishes - baked or air-dried

More information

Roof Upblast and Sidewall Exhaust

Roof Upblast and Sidewall Exhaust XRUB, XRUD, XSEB, XSED, and XRUBS models are listed for electrical (UL/C-UL US 705) File no. E40001 and for grease removal (UL/C-UL US 762) File no. MH11745. Accurex, LLC certifies model XRUB, XRUD, XSEB,

More information

READ THIS FIRST. Read and Save These Instructions AIR CURTAINS INSTALLATION INSTRUCTIONS S-LP SERIES. TMI, LLC Managing Environments

READ THIS FIRST. Read and Save These Instructions AIR CURTAINS INSTALLATION INSTRUCTIONS S-LP SERIES. TMI, LLC Managing Environments READ THIS FIRST Carefully examine the crate(s) for damage before opening. If the carton is damaged, immediately notify shipping company. If the unit(s) were shipped on wooden skids, remove protective wood

More information

INSTALLATION AND OPERATION MANUAL HE4XRT RISK OF FIRE, ELECTRIC SHOCK, OR INJURY. OBSERVE ALL CODES AND THE FOLLOWING:

INSTALLATION AND OPERATION MANUAL HE4XRT RISK OF FIRE, ELECTRIC SHOCK, OR INJURY. OBSERVE ALL CODES AND THE FOLLOWING: 0 Helgesen Drive, Madison, WI 78 (608) -99, (800) 67-99, Fax: (608) -8 support@renewaire.com www.renewaire.com INSTALLATION AND OPETION MANUAL HEXRT RISK OF FIRE, ELETRI SHOK, OR INJURY. OBSERVE ALL ODES

More information

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS INSTALLATION OPERATION & MAINTENANCE New Release Form 130.13-NOM4 (908) In conjunction with the use of these instructions, obtain and refer to the construction,

More information

INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS. Twin City Fan GRAVITY VENTILATORS MGI & MGR GRV TEL & TIL LUG CATALOG 4720 MAY 2014

INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS. Twin City Fan GRAVITY VENTILATORS MGI & MGR GRV TEL & TIL LUG   CATALOG 4720 MAY 2014 Twin City Fan INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS GRAVITY VENTILATORS MGI & MGR GRV TEL & TIL LUG CATALOG 4720 MAY 2014 WWW.TCF.COM GRAVITY VENTILATORS Overview Gravity Ventilators Models

More information

WALL MOUNTING KIT ASSEMBLY INSTRUCTIONS MODELS: TXBW & TXDW

WALL MOUNTING KIT ASSEMBLY INSTRUCTIONS MODELS: TXBW & TXDW Wall Opening Wall Mounting Adaptor (Optional) Support Strap E WALL MOUNTING KIT ASSEMBLY INSTRUTIONS MODELS: TXBW & TXDW The centrifugal power roof ventilators model TXB (belt drive) and TXD (direct drive)

More information

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO

More information

Roof Upblast and Sidewall Exhaust

Roof Upblast and Sidewall Exhaust XRUB, XRUD, XSEB, XSED, and XRUBS models are listed for electrical (UL/C-UL US 0) File no. E000 and for grease removal (UL/C-UL US ) File no. MH. Accurex, LLC certifies model XRUB, XRUD, XSEB, XSED, and

More information

INSTALLATION INSTRUCTIONS WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING -

More information

ILL. 1. Horizontal. supply air cover panel shipped on HVAC unit. Access door/ panel

ILL. 1. Horizontal. supply air cover panel shipped on HVAC unit. Access door/ panel ICP INSTALLATION INSTRUCTIONS manual outside air hood / filter (NPMANDPR004A00) (NPMANDPR005A00) and (NPMANDPR006A00) The package includes the outside air hood, the filter access door and the filter. This

More information

Large Enclosure Safe Handling Requirements. Do not reposition until permanently installed.

Large Enclosure Safe Handling Requirements. Do not reposition until permanently installed. Large Enclosure Safe Handling Requirements Do not reposition until permanently installed. Tipover hazard. Enclosure can crush you resulting in serious injury or death. Read and follow precautions in the

More information

Installation Instructions

Installation Instructions Installation Instructions Speedcook Oven Read carefully. Keep these Instructions. INSTALLATION INSTRUCTIONS Electrical Requirements Product rating is 240/208 volts AC, 60 Hertz, 30 amps and 6.5 kilowatts.

More information

SUPERIOR PERFORMANCE

SUPERIOR PERFORMANCE REVERSE PULSE DUST COLLECTORS OPERATION & MAINTENANCE MANUAL M600-2C, M900-2C & M1200-2C SUPERIOR PERFORMANCE And Quality In Blast Cleaning Equipment! WARNING Read Manual Failure to read, understand &

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS FOR 3 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT General The instruction provides all the necessary information to properly field install this economizer on the above indicated equipment. Economizer Model

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS 8A000729 DuraLift 13.5 13,500 LB. CAPACITY Link Mfg. Ltd. 223 15th St. N.E. Sioux Center, IA USA 51250-2120 www.linkmfg.com QUESTIONS? CALL CUSTOMER SERVICE 1-800-222-6283 Refer

More information

CSA CERTIFIED Conforms to UL 507

CSA CERTIFIED Conforms to UL 507 Installation tion Instructions Please read and save these instructions! TURBO/MAXX12 Volt All Weather RV Ventilator Fans P/N 00-965001 Deluxe Model 1200T WITH THERMOSTAT P/N 00-965007 Standard Model 3550

More information

Installation and Operation Manual

Installation and Operation Manual Installation and Operation Manual Installation, Operation, and Service Information Unimaster Dust Collector Models UMA 40, 70, 100, 150, 250, 450, and 750 UMA-H 250 Hopper Base UMA-B 250 Bin Base UMA-D

More information

Installation Guidelines

Installation Guidelines STYLE No. EAXS32 EAXS33 EAXS34 EAXS35 STYLE No. EAHS32 - sold separately EAHS33 - sold separately EAHS34 - sold separately EAHS35 - sold separately 19 1 /4" 8" 9" 9" 3" In the State of Massachusetts, all

More information

ECONOMIZERS. 1/2012 Supersedes

ECONOMIZERS. 1/2012 Supersedes ECONOMIZERS Litho U.S.A. 2012 506948 01 1/2012 Supersedes 506394 01 K1ECON20C 1 ECONOMIZERS INSTALLATION INSTRUCTIONS FOR ECONOMIZER AND OUTDOOR AIR (604592 03; 54W77) USED WITH KG/KC/KH 180 300S UNITS

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL RBK FRP FAN

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL RBK FRP FAN Bulletin 62-January-20-09 ROOF UPBLAST & SIDEWALL CENTRIFUGAL FIBERGLASS EXHAUST FAN INSTALLATION, OPERATION, AND MAINTENANCE MANUAL RBK FRP FAN The M.K. Plastics catalog on the above corrosion resistant

More information

CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges. OUTDOOR AIR S Litho U.S.A. 507214-01 2014 12/2014 Supersedes 9/2013 OUTDOOR AIR S INSTALLATION INSTRUCTIONS FOR OUTDOOR AIR S AND OUTDOOR AIR USED WITH 156-300S UNITS Shipping and Packing List Package

More information

Installation Instructions

Installation Instructions Installation Instructions Models: SLP Venting System These venting system components have been tested for use with approved HHT Direct Vent appliances. Check with your local building code agency before

More information

New Holland Workmaster 25s

New Holland Workmaster 25s New Holland Workmaster 25s ROPS Cab ** Shown with optional equipment New Holland Workmaster 25s ROPS Cab This ROPS cab is designed and built to fit the New Holland Workmaster 25s tractor. Designed and

More information

Installation Instructions for John Deere cotton picker models: 9986 & 2-row and All-row systems included.

Installation Instructions for John Deere cotton picker models: 9986 & 2-row and All-row systems included. Ag Leader Technology Cotton Picker Installation Installation Instructions for John Deere cotton picker models: 9986 & 9996 2-row and All-row systems included. IMPORTANT: Ensure the model numbers shown

More information

Sub Base Fuel Tank With Walk-in Type Enclosure. Installation Instructions

Sub Base Fuel Tank With Walk-in Type Enclosure. Installation Instructions Sub Base Fuel Tank With Walk-in Type Enclosure Installation Instructions CONTRACTOR: INSTALLATION INSTRUCTIONS Phoenix Products, LLC 1727 Bennett St. Jacksonville, FL 32206-3197 Phone: (904) 354-1858 Fax:

More information

Albany RR1000. Mechanical Installation Manual. PN: 6410T0029 Version - Rev: 04/23/2014. ASSA ABLOY Entrance Systems

Albany RR1000. Mechanical Installation Manual. PN: 6410T0029 Version - Rev: 04/23/2014. ASSA ABLOY Entrance Systems PN: 6410T0029 Version - Rev: 04/23/2014 Mechanical Installation Manual Albany RR1000 ASSA ABLOY Entrance Systems High Performance Door Solutions Tel: (770) 338-5000 975A Old Norcross Road Fax: (770) 388-5024

More information

INDUSTRIES AMERICAN COOLAIR CORPORATION. Centrifugal Filtered Supply Roof Ventilators TYPE CFS - TYPE SIS

INDUSTRIES AMERICAN COOLAIR CORPORATION. Centrifugal Filtered Supply Roof Ventilators TYPE CFS - TYPE SIS INDUSTRIES AMERICAN COOLAIR CORPORATION Centrifugal Filtered Supply Roof Ventilators TYPE CFS - TYPE SIS CFS Centrifugal Filtered Supply Fans Applications The CFS Centrifugal Filtered supply fans with

More information

INSTALLATION INSTRUCTIONS ZTH WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS ZTH WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS ZTH WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

CV 1800 Assembly Manual

CV 1800 Assembly Manual CV 1800 Assembly Manual Clear Vue Cyclones - 2011 1 Disclaimer WARNING: All persons by purchasing a motorized dust collection system, motor, or individual parts from CLEAR VUE CYCLONES, or using these

More information

Square Inline Fans with Multi-Directional Discharge

Square Inline Fans with Multi-Directional Discharge SQN Square Inline Fans with Multi-Directional Discharge Page Introduction............................................2 Standard Construction Features............................ 3 Specifications and Dimension

More information

Installation Manual for Ecology

Installation Manual for Ecology Installation Manual for Ecology Manual provides Installation Instructions UL 1978 Standard for Grease Ducts, UL 710, Exhaust Hoods for Commercial Cooking Equipment, ULC-S647-05 and/or UL197 EcoloAir Unit

More information

INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD

INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD Read All Instructions Thoroughly Before Beginning Installation

More information

INSTALLATION INSTRUCTIONS UNDER CABINET HOOD

INSTALLATION INSTRUCTIONS UNDER CABINET HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS UNDER CABINET HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Tubular Centrifugal Fans

Tubular Centrifugal Fans Tubular Centrifugal Fans Model TCB Inline - Horizontal or Vertical Roof Upblast and Roof Supply March 2007 Tubular Centrifugal Fans The TCB series of inline centrifugal fans is designed for ducted inline,

More information

Riva Plus HEAT ONLY & COMBI BOILER. Please Read This Guide Carefully and Save for Future Reference

Riva Plus HEAT ONLY & COMBI BOILER. Please Read This Guide Carefully and Save for Future Reference Condensing Vent Component & Installation Guide Riva Plus HEAT ONLY & COMBI BOILER Please Read This Guide Carefully and Save for Future Reference - This guide is intended to provide detailed information

More information

Voltmaster Centrifugal Trash Pumps

Voltmaster Centrifugal Trash Pumps Voltmaster Centrifugal Trash Pumps Model TSP2, TSP3 and TSP4 Owner s Manual February 2011 Table of Contents 1 Introduction............................ 1 1.1 Read before using..................... 1 1.2

More information

Models eged/egsd. Installation, Operation, and Maintenance Manual. Direct Drive Sidewall Propeller Fans (Exhaust and Supply)

Models eged/egsd. Installation, Operation, and Maintenance Manual. Direct Drive Sidewall Propeller Fans (Exhaust and Supply) Models eged/egsd Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS The purpose of this manual is to aid in the proper installation and operation of fans manufactured by JencoFan.

More information

Industry best 5 year fan housing warranty, 1 year motor warranty

Industry best 5 year fan housing warranty, 1 year motor warranty MODELS & e DIRECT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTERS MODEL - DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER MODEL FEATURES Exhaust air up to 4,980 CFM in high static pressure applications up to 1-1/2

More information

RECEIVING AND INSPECTION EXAMINE ALL COMPONENTS FOR POSSIBLE SHIPPING DAMAGE PRIOR TO INSTALLATION.

RECEIVING AND INSPECTION EXAMINE ALL COMPONENTS FOR POSSIBLE SHIPPING DAMAGE PRIOR TO INSTALLATION. Non-Welded Grease Duct Systems Installation, Operation, and Maintenance Manual FOR YOUR SAFETY TWO MAJOR CAUSES OF GREASE DUCT RELATED FIRES: (1) FAILURE TO MAINTAIN REQUIRED CLEARANCE (AIR SPACE) TO COMBUSTIBLE

More information

CPC Series. Submittal Data Form. 15- & 20-Ton Self-Contained. Packaged Air Conditioner. with R-410A

CPC Series. Submittal Data Form. 15- & 20-Ton Self-Contained. Packaged Air Conditioner. with R-410A CPC Series 15- & 20-Ton Self-Contained Submittal Data Form Job Name Purchaser Order No. Engineer Unit No. Model No. Unit Designation Performance Data Certified By: Packaged Air Conditioner with R-410A

More information

ELECTRIC SHOCK HAZARD/FIRE AND/OR EXPLOSION HAZARD. ELECTRIC SHOCK HAZARD/FIRE AND/OR EXPLOSION HAZARD.

ELECTRIC SHOCK HAZARD/FIRE AND/OR EXPLOSION HAZARD. ELECTRIC SHOCK HAZARD/FIRE AND/OR EXPLOSION HAZARD. INSTALLATION INSTRUCTIONS FOR CONCENTRIC VENT KIT P/N AOPS7483 (for 4 flue roof jack) CONCENTRIC VENT KIT P/N AOPS7544 (for 5 flue roof jack) DUAL PIPE FLASHING KIT P/N AOPS7484 ELECTRIC SHOCK HAZARD/FIRE

More information

Centrifugal Spun Aluminum Products

Centrifugal Spun Aluminum Products Centrifugal Spun Aluminum Products SDB SDBD STXB STXD Downblast & Upblast Centrifugal Roof Wall Exhausters Designed with Efficiency in Mind CSAP_0415 April 2015 Centrifugal Spun Aluminum Line Overview

More information

KONGSKILDE Vertical Tillage - Assembly Guide ASSEMBLY INSTRUCTIONS Revision 18 Serial No current Series.

KONGSKILDE Vertical Tillage - Assembly Guide ASSEMBLY INSTRUCTIONS Revision 18 Serial No current Series. KONGSKILDE 9100 Vertical Tillage - Assembly Guide Kongskilde 9100 Series *Model may not be exactly as shown. Kongskilde reserves the right to make changes to product designs and specifications without

More information

The Industrial Choice. Model BSHD Direct Drive LOW PROFILE HOODED PROPELLER ROOF VENTILATORS. Models BSHD / BSHB

The Industrial Choice. Model BSHD Direct Drive LOW PROFILE HOODED PROPELLER ROOF VENTILATORS. Models BSHD / BSHB The Industrial Choice. Model BSHD Direct Drive LOW PROFILE HOODED ROOF VENTILATORS Models BSHD / BSHB CATALOG 632 November 12 Hooded Roof Ventilators Models BSHD BSHB Aerovent Low Profile Hooded Roof Ventilators

More information

Installation Instructions

Installation Instructions CAHZCOIL8A00 CAHZCOIL412A00 CAHZCOIL208A00 CAHZCOIL212A00 CAVTCOIL8A00 CAVTCOIL412A00 CAVTCOIL208A00 CAVTCOIL212A00 Installation Instructions DIRECT --- EXPANSION HORIZONTAL AND VERTICAL EVAPORATOR COILS

More information