Installation, Start-Up and Service Instructions

Size: px
Start display at page:

Download "Installation, Start-Up and Service Instructions"

Transcription

1 39NC Curb-Mounted Central Station Air-Handling Units Installation, Start-Up and Service Instructions This air-handling equipment is designed to provide safe and reliable service when installed correctly and operated within design specifications. To avoid injury to personnel and damage to equipment or property when operating this equipment, use good judgment and follow safe practices as outlined below. NEVER enter an enclosed fan cabinet or reach into a unit while the fan is running. LOCK OPEN AND TAG the fan motor power disconnect switch before working on a fan. Take fuses with you and note removal on tag. CHECK the assembly and component weights to be sure that the rigging equipment can handle them safely. Note, also, the centers of gravity and any specific rigging instructions. CHECK for adequate ventilation so that fumes will not migrate through ductwork to occupied spaces when welding or cutting inside air-handling unit cabinet or plenum. WHEN STEAM CLEANING COILS be sure that the area is clear of personnel. DO NOT remove access panel fasteners until fan is completely stopped. Pressure developed by a moving fan can cause excessive force against the panel and toward personnel. DO NOT work on dampers until their operators are disconnected. BE SURE that fans are properly grounded before working on them. SAFETY CONSIDERATIONS SECURE drive sheaves with a rope or strap before working on a fan to ensure that rotor cannot free-wheel. DO NOT restore power to unit until all temporary walkways inside components have been removed. NEVER pressurize equipment in excess of specified test pressures. PROTECT adjacent flammable material when welding or flame cutting. Have a fire extinguisher at hand and ready for immediate use. If unit is installed on a curb open to the inside of the building, have a fire extinguisher ready for immediate use inside the building under the unit. PREVENT unauthorized entry into the unit; leave safety latches in place on access doors except during installation or service procedures. After accessing a section, replace and tighten the safety latch. FIELD supplied motors should be Underwriters Laboratories (UL) or Canadian Standards Association (CSA) approved. FIELD wiring must comply with National Electrical Code (NEC) and all local requirements. DO NOT destroy watertight integrity by fastening electrical conduit, disconnects, or other hardware to the unit with screws that pierce the exterior cabinet. Both exterior and bottom panels are watertight. Use conduit standpipes in fan section(s) to route wiring into the unit from the interior space below. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 3 PC 201 Catalog No Printed in U.S.A. Form 39NC-1SI 3-97 Pg 1 Replaces: New Tab 1b

2 CONTENTS Page SAFETY CONSIDERATIONS...1 INTRODUCTION...2 UNIT AND COMPONENT IDENTIFICATION PHYSICAL DATA PREINSTALLATION Inspection...10 Rigging...10 Long-Term Storage...10 Service Clearance...10 Internal Vibration Isolation...19 Roof Curb...19 Pier or Beam Mount...19 INSTALLATION Rigging...22 Sheet Metal Duct Connections...23 Doors...26 Intake Rain Hoods...26 Wiring...26 Fan Motors and Drives...26 Sheaves...28 V-Belts...29 Inlet Guide Vane Actuators, Forward-Curved Fans...30 Inlet Guide Vane Actuators, Airfoil Fans...31 Damper Actuators...32 Water and Steam Coil Piping Recommendations...34 Coil Freeze-Up Protection...35 Refrigerant Piping, Direct-Expansion Coils...35 Condensate Drain...52 START-UP Checklist...53 SERVICE General...55 Fan Motor Replacement...55 Cleaning Double-Wall Interiors...55 Coil Cleaning...55 Winter Shutdown...55 Coil Removal...55 Changing Coil Hand...58 Filters...58 Intake Hood Demisters...69 Fan Shaft Bearing Removal...70 Fan and Shaft Removal...70 Lubrication...70 Drive Package Data METRIC CONVERSION CHART...74 INTRODUCTION Carrier 39NC Series air-handling units are designed specifically for outdoor installation. The units have sloped tops, watertight cabinets, and specially designed base rails that ensure a tight seal with a curb. Each unit is factory assembled and shipped as a completely integrated package. The 39NC Series units are available for 2 basic duct arrangements. In the first arrangement, the fan discharge is directly attached to the supply duct, which is exposed for a distance before the duct penetrates the roof into the building. This arrangement can be installed either on a roof curb or on a pier. In the second type of duct arrangement, the fan discharges into a factory supplied plenum. The plenum (DPL1) has an opening at the bottom where supply air ductwork can be attached; the supply duct is confined within the curb. This arrangement must be curb mounted. UNIT AND COMPONENT IDENTIFICATION All 39NC component codes are listed and described in Table 1. Each component code has a 3-digit letter prefix that describes the basic component type; a fourth numerical digit indicates the variant for a given type of section. Components are assembled into an integrated unit at the factory. See Fig. 1 for an example of a unit label showing the model number and components in a typical assembled unit. The 39NC units are configured for blow-thru or drawthru operation. Return fan arrangements are also available. See Fig. 2-4 for unit component arrangements for each configuration. Fig. 1 Unit Identification Label 2

3 Table 1 39NC Component Code Definitions COMPONENT CODE ACC1 ACC2 AFS3 AFS5 AMX1 ANG1 BCC2 BCF1 BCF2 BCS7 BPH1 BPH2 CDC1 CDC2 CIC1 CIC2 CIC3 DIF2 DPL1 EMB1 FBP1 FCS3 FCS5 FLT1 DESCRIPTION Access Section (Upstream Location) Access Section (Downstream Location) Airfoil Fan Section, Horizontal Draw Thru Airfoil Fan Section, Blow-Thru Air Mixer Section Angle Filter Section Bypass Cooling Coil Section Bag/Cartridge Filter Section (Upstream Location, 2-in. Prefilters) Bag/Cartridge Filter Section (Downstream Location, 2-in. Prefilters) Blow-Thru Cooling Coil Section (Downstream Location) Bypass Heating Coil Section Bypass Heating Coil Section (Extended Length) Curb Discharge Component (Blank End Cap) Curb Discharge Component (Discharge Duct Connection) Curb Inlet Component (Blank End Cap) Curb Inlet Component (Horizontal Inlet Duct Connection) Curb Inlet Component (Outside Air Intake with Hood) Diffuser Section (Downstream Location) Downblast Plenum Section (Bottom Discharge) Exhaust and Mixing Box (Side Exhaust with Opposite-Side Outdoor-Air Intake) Face and Bypass Damper Section Forward-Curved Fan Section, Horizontal Draw-Thru (07-61 Sizes Only) Forward-Curved Fan Section, Blow-Thru (07-61 Sizes Only) Flat Filter Section COMPONENT CODE FMB4 HRS1 LCS1 LCS2 LCS3 MCS1 MCS2 MCS3 MHS1 MXB4 MXB7 PLN1 PLN2 PLN6 RAF1 RAF2 RFC1 RFC2 SHS1 DESCRIPTION Combination Filter Mixing Box (Bottom and Rear Inlet) Heat Reclaim Section Large Cooling Coil Section Large Cooling Coil Section With Extended Drain Pan (Upstream Humidifier Mount) (07-26 Sizes Only) Large Cooling Coil Section With Extended Drain Pan (Downstream Humidifier Mount) (07-26 Sizes Only) Medium Cooling Coil Section Medium Cooling Coil Section With Extended Drain Pan (Upstream Humidifier Mount) Medium Cooling Coil Section With Extended Drain Pan (Downstream Humidifier Mount) Medium Heating Coil Section (uses large face area coil in sizes, medium face area coil in sizes) Mixing Box (Bottom and Rear Inlet) Mixing Box (Rear Inlet Only) Short Plenum Section (Upstream Location) Long Plenum Section (Upstream Location) Short Plenum Section (Downstream Location) Return-Air Airfoil Fan Section (Bottom Inlet) Return-Air Airfoil Fan Section (Rear Inlet) Return-Air Forward-Curved Fan Section (Bottom Inlet) (07-61 Sizes Only) Return-Air Forward-Curved Fan Section (Rear Inlet) (07-61 Sizes Only) Small Heating Coil Section (uses bypass face area coil in all unit sizes) NOTE: Components are not available for individual shipment. All components must be ordered for factory assembly into integrated units. 3

4 WITHOUT FACE AND BYPASS WITH FACE AND BYPASS NOTES: 1. If first component in airstream is a coil or filter section, PLN2 or ACC1 must be immediately upstream. 2. BCF1 accepts bag filters up to 12-in. long. When longer filters are used, one or more plenum sections (PLN1) must be ordered. Each PLN1 section provides 8 in. of additional clearance. 3. Two coils on 61 size and larger units. 4. Two coils on 92 size unit. 5. Two coils on sizes Not available on sizes ACC1 required before FBP1 for service access. 8. When DPL1 and CDC1 are added downstream, static pressure correction factor applies to fan performance. See Fan Performance section in Product Data catalog. Fig. 2 Unit Section Arrangements, Horizontal Draw-Thru Units 4

5 Typical draw-thru components as shown in Fig. 2 may be used upstream of fan section NOTES: 1. Two cooling coils on 61 and larger units. 2. BCF2 accepts bag filters up to 12-in. long. When longer filters are used, one or more plenum sections (PLN6) must be ordered. Each PLN6 section provides 8 in. of additional clearance. Fig. 3 Unit Section Arrangements, Blow-Thru Units Fig. 4 Unit Section Arrangements, Return Fan 5

6 PHYSICAL DATA Data describing the physical properties of 39NC coils and fans is provided in Tables Table 2 Coil Physical Data 39NC UNIT SIZE CHILLED WATER/ DIRECT EXPANSION Large Face Area Nominal Capacity (cfm) at 550 fpm ,894 11,440 14,214 Size (Length x Width) (in.) x x x x x x x Total Face Area (sq ft) Medium Face Area Nominal Capacity (cfm) at 550 fpm ,989 9,421 11,970 Size (Length x Width) (in.) x x x x x x x40 Total Face Area (sq ft) Bypass (Chilled Water Only) Nominal Capacity (cfm) at 550 fpm ,989 9,421 11,970 Size (Length x Width) (in.) x x x x x x x40 Total Face Area (sq ft) HOT WATER HEATING Large Face Area Nominal Capacity (cfm) at 700 fpm ,320 14,559 18,090 Size (Length x Width) (in.) x x x x x x x Total Face Area (sq ft) Bypass Nominal Capacity (cfm) at 700 fpm ,894 11,990 15,234 Size (Length x Width) (in.) x x x x x x x40 Total Face Area (sq ft) STEAM HEATING COIL Large Face Area Nominal Capacity (cfm) at 700 fpm ,673 14,388 17,138 Size (Length x Width) (in.) x x x x x x x45 Total Face Area (sq ft) Bypass Nominal Capacity (cfm) at 700 fpm ,762 11,305 14,853 Size (Length x Width) (in.) x x x x x x x39 Total Face Area (sq ft)

7 Table 2 Coil Physical Data (cont) 39NC UNIT SIZE CHILLED WATER/ DIRECT EXPANSION Large Face Area Nominal Capacity (cfm) at 550 fpm 17,898 21,334 27,052 33,446 40,567 50,401 Size (Length x Width) (in.) x27 1 2(U) x 30 (U) x35(u) 113x37 1 2(U) x 40 (U) x 50 (U) x 30 (L) x32 1 2(L) x35(l) 113x40 (L) x42 1 2(L) x52 1 2(L) Total Face Area (sq ft) Medium Face Area Nominal Capacity (cfm) at 550 fpm 14,785 17,067 21,255 26,973 33,191 40,567 Size (Length x Width) (in.) x x x55 113x30 (U) 113x32 1 2(L) x32 1 2(U) x 35 (L) x 40 (U) x42 1 2(L) Total Face Area (sq ft) Bypass (Chilled Water Only) Nominal Capacity (cfm) at 550 fpm 14,785 17,067 21,255 26,973 31,962 40,567 Size (Length x Width) (in.) x22 1 2(U) x 25 (L) x25(u) x25(l) x27 1 2(U) x27 1 2(L) 113x30 (U) 113x32 1 2(L) x x x 40 (U) x42 1 2(L) Total Face Area (sq ft) HOT WATER HEATING Medium Face Area Nominal Capacity (cfm) at 700 fpm 18,818 21,722 27,052 34,329 42,243 51,630 Size (Length x Width) (in.) x x x55 113x30 (U) 113x32 1 2(L) x32 1 2(U) x 35 (L) x 40 (U) x42 1 2(L) Total Face Area (sq ft) Bypass Nominal Capacity (cfm) at 700 fpm 13,866 16,291 20,904 27,463 32,856 39,114 Size (Length x Width) (in.) x x x x x x 30 (U) x32 1 2(L) Total Face Area (sq ft) STEAM HEATING COIL Medium Face Area Nominal Capacity (cfm) at 700 fpm 17,640 20,650 26,530 31,010 39,130 50,260 Size (Length x Width) (in.) x x x54 112x27(U) 112x30(L) x30(u) x39(u) x33(l) x42(l) Total Face Area (sq ft) Bypass Nominal Capacity (cfm) at 700 fpm 12,950 15,470 20,650 26,110 31,640 35,420 Size (Length x Width) (in.) x x x42 112x x x27(u) x30(l) Total Face Area (sq ft) LEGEND U Upper Coil L Lower Coil 7

8 Table 3 Coil Volume (gal. water) 39NC UNIT SIZE CHILLED WATER Large Face Area 4-Row Row Row Row Medium Face Area 4-Row Row Row Row Bypass Face Area 4-Row Row Row Row HOT WATER Large Face Area 1-Row Row Medium Face Area 1-Row Row Bypass Face Area 1-Row Row NOTE: One gallon of water weighs 8.33 lbs. CIRCUIT TYPE FACE AREA Table 4 Chilled Water Coil Connection Sizes 39NC UNIT SIZE Nozzle Size (in. MPT) HALF LARGE, MEDIUM, FULL BYPASS LARGE DOUBLE MEDIUM BYPASS NOTE: The following sizes have two coils: Large and bypass face area sizes 32-92, medium face area sizes FACE AREA Table 5 Hot Water Coil Connection Sizes 39NC UNIT SIZE Nozzle Size (in. MPT) LARGE MEDIUM BYPASS NOTE: The following sizes have two coils: medium face area sizes 61-92, bypass face area size 92. 8

9 FACE AREA LARGE MEDIUM BYPASS Table 6 Steam Coil Connection Sizes 39NC UNIT SIZE CONNECTION Nozzle Size (in. MPT) Inlet Outlet Inlet Outlet Inlet Outlet NOTE: The following sizes have two coils: medium face area sizes 61-92; bypass face area size 92. Table 7 Operating Charge (Approximate) Direct Expansion Coil NUMBER OF ROWS FACE AREA 39NC UNIT SIZE Refrigerant R-22 (lb) Large Medium Large Medium Large Medium Table 8 Coil Moisture Blowoff Limits (Fpm) FINS ALUMINUM COPPER PER INCH FINS FINS NOTE: See ACAPS (applied coil and air handler performance and selection) computer program for specific limitations. Data shown is for general use in worst case conditions. Table 9 Airfoil Fan Physical Data 39NC UNIT SIZE Wheel Diameter (in.) Max Speed (rpm) Fan Sheave Bore (in.) Fan Shaft Wt (lb) Fan Wheel Wt (lb) No. of Fan Blades MOTOR FRAME SIZE Maximum ODP 215T 215T 254T 256T 256T 286T 286T 326T 364T 365T 404T 405T 405T TEFC 213T 213T 215T 256T 256T 284T 284T 324T 324T 364T 364T 404T 404T Minimum 143T 143T 145T 145T 182T 182T 182T 182T 182T 182T 184T 213T 213T MOTOR HP Maximum Minimum LEGEND ODP Open Drip Proof TEFC Totally-Enclosed, Fan Cooled NOTES: 1. Motor data applies to units with or without inlet guide vanes. 2. Data shown is for 60 Hz motors. Contact Application Engineering for 50 Hz applications. 9

10 Table 10 Forward-Curved Fan Physical Data 39NC UNIT SIZE* Wheel Diameter (in.) Max Speed (rpm) Fan Sheave Bore (in.) Fan Shaft Wt (lb) Fan Width (in.) Fan Wheel Wt (lb) No. of Fan Blades MOTOR FRAME SIZE Maximum ODP 213T 215T 254T 254T 256T 284T 284T 326T 364T 365T 365T TEFC 184T 213T 215T 254T 256T 284T 284T 324T 324T 364T 364T Minimum 143T 143T 145T 145T 182T 182T 182T 182T 182T 182T 184T MOTOR HP Maximum Minimum LEGEND ODP Open Drip Proof TEFC Totally-Enclosed, Fan Cooled *Forward-curved fans available on sizes only. NOTES: 1. Motor data applies to units with or without inlet guide vanes. 2. Data shown is for 60 Hz motors. Contact Application Engineering for 50 Hz applications. PREINSTALLATION Inspection Inspect the unit. If unit is damaged, file a claim with the shipping company. Check the packing list to ensure that the correct items have been received and notify your Carrier representative of any discrepancy. Rigging Units can be rigged into place on top of the building using a crane or helicopter. Check the unit weight to make sure the rigging equipment is capable of handling the load. Refer to shipping company s bill of lading for the measured shipping weight of the unit. For unit weight estimation, component, coil, and motor weights are listed in Tables Component dimensions are listed in Fig. 5 and 6. Add the airway lengths of all components in the unit to obtain the overall unit length. To maintain watertight integrity, do not disassemble the unit before rigging. See Installation, Rigging section, for further rigging information. Long-Term Storage If long term storage is required, observe the following precautions: The storage site should be level, rigid, and clean of construction debris. If the site is in a heavy rain area, set the unit off the ground. Do not store the unit in heavy construction traffic area. Ensure that all coil connections have shipping caps in place. Cover the unit with a waterproof tarpaulin or plastic material. If the unit is stored on the ground, place plastic ground cover under the unit. Secure the cover with tie-downs if the unit is stored outdoors. Do not remove the cover or coil connection caps until the unit is installed. Do not stack units or store equipment on top of unit. Monthly: Using the doors for entry into the fan section, slowly rotate the fan and motor manually for a number of turns. This will redistribute the bearing grease and help prevent bearing corrosion. Service Clearance When planning the placement of the unit, ensure adequate space for service access. Typical service operations can require removing the coils and filters and accessing the motor and damper linkages. See Fig. 7 for required service clearances. Also ensure clearances conform to local codes. 10

11 Table 11 Nominal Component Weights (lb) DRAW-THRU COMPONENTS COMPONENT 39NC UNIT SIZE ACC AFS AMX ANG BCC BCF BPH BPH CDC CIC CIC CIC EMB FBP FCS FLT FMB HRS LCS LCS LCS MCS MCS MCS MHS MXB4, PLN PLN RAF1, RFC1, SHS BLOW-THRU COMPONENTS COMPONENT 39NC UNIT SIZE ACC AFS BCF BCS CDC DIF DPL FCS PLN NOTES: 1. Coil section weights are without coil. See Table 13 for dry coil weights. 2. Fan section weights are without motors or drives. See Table 12 for motor weights. Multiply motor weight by 0.10 to estimate drive weight. 3. Filter section weights are without filters. Filters are not shipped with the unit. 4. For complete component definition, see Table 1. 11

12 MOTOR TYPE Table 12 Motor Weights (Lb) OPEN DRIP-PROOF (ODP) MOTOR HP Standard High Efficiency MOTOR TYPE TOTALLY ENCLOSED FAN COOLED (TEFC) MOTOR HP Standard High Efficiency NOTES: 1. Weight of sheaves and belts not included. 2. Motor weights vary by vendor. 3. Multiply motor weight by 0.10 to estimate drive weight. 12

13 COIL TYPE CHILLED WATER OR DIRECT EXPANSION HOT WATER STEAM FACE AREA LARGE MEDIUM BYPASS* LARGE MEDIUM BYPASS LARGE MEDIUM BYPASS ROWS * * Table 13 Dry Coil Weights (Lb) FINS 39NC UNIT SIZE PER IN *Chilled water only. NOTES: 1. Weights shown include headers and are the sum of two coils where applicable. 2. Coils are full-length. 3. Weights shown are for aluminum-fin coils; for copper fins, multiply by To obtain approximate wet (filled) weight, multiply by

14 SIZE HORIZONTAL DRAW-THRU WITH OR WITHOUT BYPASS BLOW-THRU COMPONENTS DIMENSIONS (ft-in.) 39NC UNIT SIZE W H* *Height to high side of sloped top. Slope is 1 4 in. per foot minimum. Low-side height is in. less on sizes and 3 in. less on 26 size unit. Height includes in. vertical flange on roof panels. Fig. 5 Dimensions, Unit Sizes

15 HORIZONTAL DRAW-THRU COMPONENT AIRWAY LENGTHS (ft-in.) COMPONENT CIC CIC CIC3* RAF1, RFC1, EMB MXB4, FMB ANG BCF FLT AMX ACC PLN PLN HRS MHS SHS LCS LCS2, MCS MCS2, FBP BCC BPH BPH AFS FCS CDC BLOW-THRU COMPONENT AIRWAY LENGTHS (ft-in.) COMPONENT AFS FCS ACC PLN DIF BCF BCS DPL CDC *See Service Area Requirements, Fig. 7 for intake hood length. Length shown is for base of component. NOTE: See Table 1 for component description. Fig. 5 Dimensions, Unit Sizes (cont) 15

16 SIZE HORIZONTAL DRAW-THRU WITH OR WITHOUT BYPASS BLOW-THRU COMPONENTS DIMENSIONS (ft-in.) 39NC UNIT SIZE W H** *Unit sizes 61 and larger have 2 coils. Unit size 92 has 2 coils. **Height to high side of sloped top. Slope is 1 4 in. per foot minimum. Low-side height is 3 in. less on size units. Height includes in. vertical flange on roof panels. Fig. 6 Dimensions, Unit Sizes

17 HORIZONTAL DRAW-THRU COMPONENT AIRWAY LENGTHS (ft-in.) COMPONENT CIC CIC CIC3* RAF1, RFC1, EMB MXB4, FMB ANG BCF FLT AMX ACC PLN PLN HRS MHS SHS LCS MCS MCS MCS FBP BCC BPH BPH AFS FCS CDC BLOW-THRU COMPONENT AIRWAY LENGTHS (ft-in.) COMPONENT AFS FCS ACC PLN DIF BCF BCS DPL CDC *See Service Area Requirements, Fig. 7 for intake hood length. Length shown is for component base. NOTE: See Table 1 for component description. Fig. 6 Dimensions, Unit Sizes (cont) 17

18 HOOD CLEARANCE (EMB1 EXHAUST MIXING BOX) E (SHOWN SEPARATELY FOR CLARITY) HOOD CLEARANCE (CIC3 INLET) D BASE UNIT (ALL AREAS OF UNIT EXCEPT COILS AND FANS) 2'-2" [660] COIL FAN L* W 2'-0" ** [610] L* L* B A DIMENSIONS (ft-in.) 39NC UNIT SIZE A B D (CIC3) E (EMB1) *Airway length. See Fig. 5 and 6 for length of this area. Unit width. See Fig. 5 and 6 for width of this area. **Service area required for access door on side of fan opposite motor. Fig. 7 Service Area Requirements 18

19 Internal Vibration Isolation Units have internal vibration isolation and must be prepared as described in this section before they are installed. When adjusting fan isolation components, DO NOT enter or reach into the fan cabinet while fan is running. Serious injury can result. Be sure to disconnect power and tag controls before making adjustments. REMOVING HOLDDOWN BRACKET SCREWS Remove the holddown bracket screws (Fig. 8) as follows: 1. Open the fan access door. The yellow holddown brackets are on both sides of the fan. 2. Remove screws from top of each holding bracket so fan sled floats freely on isolator springs. 3. Discard screws. Holding bracket can remain attached to bottom of fan sled. 4. Remove and discard wood shipping blocks inserted between fan and side walls, if supplied. 5. Adjust isolators if required and close fan access door. NOTE: Drives, isolators, and sheaves are prealigned at factory and should not require adjustment. See following section. ADJUSTING ISOLATOR SPRINGS Units with factorysupplied motors and drives are preset to ± 1 8-in. clearance between the base frame assembly and the bottom panels; field adjustment of the isolator springs is not normally required. Units that receive field-supplied motors require isolator spring adjustment to in. nominal clearance after the fan motor, sheaves, and belts have been installed. When field-supplied motors and drives have been installed, adjust the isolator springs as shown in Fig. 8 and described as follows: 1. Loosen the locknut. 2. Turn the adjusting stem until the specified clearance of ± 1 8-in. is obtained. (Turn clockwise to decrease clearance or counterclockwise to increase clearance.) 3. Tighten the locknut. 4. Repeat for each of the isolator springs and ensure that the fan sled is floating on the springs. Roof Curb Roof curbs must be field-supplied for 39NC units and should be installed according to the manufacturer s instructions. Before installing roof curb, check overall unit length as described in the Preinstallation section. Figure 9 shows recommended curb dimensions and typical construction. IMPORTANT: Verify installed curb dimensions before attempting to rig the unit and install it on the curb. After curb is installed, fabricate inlet and discharge according to the unit configuration. Dimensions for inlet and discharge locations are shown in Fig. 10. Before the unit is installed, gasketing must be installed between the curb and unit as shown in Fig. 11. This gasket material is often supplied by the curb manufacturer. If gasket is not supplied with the curb, recommended fieldsupplied gasket material is 1 2-in. thick by 2-in. wide closedcell neoprene. When curb is installed, place gasket on curb without stretching or overlapping the material, which can cause gaps or leaks. Butt all joints evenly and avoid creating gaps where water can leak into the curb. Make sure seams in gasket material overlap seams in the curb rail. See Fig. 11 for installation details. After gasket is in place, rig unit into position with overhead crane or helicopter as described in Installation, Rigging section. Locate unit on curb so it is correctly oriented with respect to curb inlet and discharge locations. Pier or Beam Mount As an alternative to curb mounting, units can also be mounted on I-beams or piers. For units mounted on I-beams, the beams must run the continuous length of the unit. If seismic criteria apply, cross-pieces must be added between the beams according to seismic calculations. See Fig. 12 for a typical installation. For pier-mounted units, one pier must be installed in each corner of the unit at the junction of the baserail corners. A minimum of 4 piers can be used for size units up to 15 ft long and size units up to 10 ft long. For each additional 15 ft of length for size units or 10 ft of length for size units, install one additional pier on each side of the unit underneath the baserails. See Fig. 12 for a typical installation. FAN REMOVE TOP SCREWS ONLY HOLDDOWN BRACKET (2 SIDES) Fig. 8 Removing Holddown Bracket Screws and Adjusting Isolator Spring 19

20 UNIT MOUNTING DETAIL 5 7/16 in. 1 7/8 in. TYPICAL UNIT BOTTOM 3 in. 2 7/8 in. 7/8 in. 5 in. CURB 2 3/4 in. 1 7/8 in. TYPICAL CURB DIMENSIONS (BASED ON 1 7/8 in. CURB RAIL WIDTH)* A AIRFLOW B *Adjust A and B dimensions accordingly if rail width is different from inches. CURB DIMENSIONS (ft-in.) 39NC UNIT SIZE A (Width) B (Airway Length) Varies By Unit Component NOTES: 1. The A dimension equals unit width minus inches. 2. The B dimension equals the unit airway length (sum of all components, including CIC and CDC) minus inches. 3. See Table 1 for component description and Fig. 5 and 6 for component airway lengths. Fig. 9 Determining Roof Curb Dimensions 20

21 MIXING BOX (MXB4, FMB4) MXB4 AND FMB4 INLET DIMENSIONS (ft-in.) 39NC UNIT SIZE A B C D RETURN FAN (RAF1, RFC1) DISCHARGE PLENUM (DPL1) RAF1 AND RFC1 INLET DIMENSIONS (ft-in.) 39NC UNIT SIZE A B C D * * *RAF1 only. DPL1 DISCHARGE DIMENSIONS (ft-in.) 39NC UNIT SIZE E F G H Fig. 10 Curb Inlet and Discharge Locations 21

22 GASKET SEAM BUTT JOINTS, DO NOT OVERLAP WRONG METHOD INSTALLATION This section describes how to install 39NC units. The base unit is shipped fully assembled (except for intake hoods on larger units) on a single skid up to 40 ft in length. To maintain watertight integrity, DO NOT attempt to disassemble the unit to install it. Rigging Units are shipped fully assembled and are designed to be lifted into final location by crane or helicopter using the lifting lugs on the base of the unit. Rigging details are shown in Fig. 13. Spreader bars must be used when rigging unit to avoid crushing or damaging unit top edges. Damage can result in air or water leaks. On curb installations, lower unit directly into place, ensuring that roof curb gasket does not shift or curl. When unit is in its final location, do not remove the caps from the coil connections until the coil is ready for piping. RAIL SEAM GASKET SEAM RIGHT METHOD RAIL SEAM Fig. 11 Installation of Curb Gasket BEAM MOUNT PIER MOUNT* L *Minimum number of piers shown for pier mounted unit. See tables below for number of equally-spaced piers required. QUANTITY OF PIERS REQUIRED 39NC UNIT LENGTH L, FT UNIT SIZE Fig. 12 Pier or Beam Mounting 22 39NC UNIT LENGTH L, FT UNIT SIZE

23 VERTICAL LIFT SPREADER BARS 15 MAXIMUM ASSEMBLED UNIT UNIT LENGTH NOTES: 1. Rig unit using all lifting lugs on the unit s base frame. 2. Use spreader bars to prevent damaging top panels and to ensure a vertical lift at all lifting points. Lifting angles greater than 15 from vertical will damage the unit. 3. Lift unit by crane or helicopter. Ensure rigging device can lift unit weight safely. 4. Ensure gasket on roof curb does not shift or curl when placing unit. Fig. 13 Rigging Sheet Metal Duct Connections For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install 90 degree turns in the supply and return ductwork between the unit and the conditioned space. If a 90 degree elbow cannot be installed, then grilles of sufficient strength and density should be installed to prevent objects from falling into the conditioned space. Attach the return and/or supply ductwork to the air inlet and outlet connection collars (provided at the bottom or ends of the unit) using sheet metal screws. No provisions have been made for attaching the ductwork to the curb. The ductwork must be sealed against the unit with caulk or other suitable material to avoid air or water leaks. See Fig. 14. The return and supply ducts must be supported independently from the unit. Do not exert weight or downward force on the unit other than minimal force required for duct attachment. IMPORTANT: When the air handler arrangement includes a return fan, MXB7 mixing box, filter mixing box, or discharge plenum, and the return and/or supply ducts are confined within the curb, then extra caution is necessary when attaching the ductwork. After the unit is installed, it is difficult to repair air or water leaks at these connections. Inlet and discharge locations and dimensions for withinthe-curb connections are shown in Fig. 10. Duct connections for CIC2 inlet and CDC2 outlet with connections outside the curb are shown in Fig. 15 and 16. UNIT BOTTOM PANEL GASKET OR CAULK FIELD SUPPLIED DUCTWORK Fig. 14 Connecting Duct to Unit (MXB4, FMB4, or DPL1) 23

24 CIC2 INLET DIMENSIONS END VIEW 10 1/4" F 7 7/8" E G DIMENSIONS (ft-in.) 39NC UNIT SIZE E F G [387] [533] [900] [1000] [1200] [1400] [1500] 5-3 [1600] [1800] [1900] [679] [2100] [2400] [825] [2700] [971] [3100] [1263] [271] [375] [371] [469] [565] [622] [725] [569] [672] [724] [933] [885] [984] Fig. 15 CIC2 Duct Connections 24

25 CDC2 DISCHARGE DIMENSIONS END VIEW F E H G RIGHT-HAND UNIT DIMENSIONS (ft-in.) CDC2 USED WITH 39NC UNIT SIZE Forward-Curved (FCS Fans) Airfoil (AFS Fans) E F G H E F G H Fig. 16 CDC2 Duct Connections 25

26 Doors All unit access doors are designed for outside use. Each door has 2 seals: The outer seal is a water seal and the inner seal is an air seal. It may appear that a portion of the outer seal at the bottom of the door is missing, but this gap provides an atmospheric break between the inner and outer seal. The gap is required to relieve positive or negative pressure from building between the door seals. Intake Rain Hoods Two types of rain hoods are supplied on 39NC units. One type is used on the CIC3 intake section, and a second type is supplied for the EMB1 (exhaust mixing box). The 2 types of hoods are similar except for height and the slope of the hood angle. See Fig. 17 for a typical hood. Both types of intake rain hoods keep rain and snow out of the air intake; both also have integral demisters. The demisters remove atomized water from the air before it enters the unit and also prevent the entry of birds and debris. The demisters are factory supplied and installed in the hoods on the CIC3 and EMB1 sections. For smaller units that have a CIC3 intake section, the rain hood is factory assembled to the unit. Larger units that use the CIC3 section and all units that have EMB1 sections have the rain hoods shipped detached from the unit for field installation, due to shipping restrictions. On these units, use the supplied gasket material and fasteners to attach the intake rain hood to the intake section once the unit is in its final location. Wiring Install all wiring in accordance with National Electrical Code (NEC) and applicable local codes. To maintain watertight integrity, avoid drilling holes in (or attaching hardware to) unit outer panels. DO NOT drill holes in bottom panels for wiring or tubing; holes in the panels can be paths for water leakage into the building. Use wiring access conduits in bottom panels of fan sections for control and power wiring. Access conduit sizes are in. ID for unit sizes and in. ID for unit sizes After power and control lines have been routed through the conduit to connection points, seal the wires in the conduit with a non-conductive sealant to prevent air infiltration. Use a non-conductive, non-hardening sealant. Permagum (manufactured by Schnee Morehead) or sealing compound, thumb grade (manufactured by Calgon), are acceptable materials. For detailed standpipe location dimensions, see Fig. 18 or consult certified drawings. INTAKE HOOD DEMISTERS (4 ROWS SHOWN) GASKET Select motor branch circuit wire sizing according to the amp values shown in Table 14. Size overload protection or fuses according to the recommendation on the motor nameplate. Locate unit disconnect in accordance with NEC or local codes. Table 14 Motor Full-Load Current Values for Sizing Electrical Branch Circuits INDUCTION TYPE MOTOR SQUIRREL-CAGE AND HP WOUND-ROTOR AMPERES 200V 208V 230V 460V 575V NOTE: Branch circuit wire sizing can be selected using this table. Overload protection or fuse sizing must be selected according to information on motor nameplate. Fan Motors and Drives Field-supplied motors should be listed or approved by UL (Underwriter s Laboratories) or ETL (Engineering Testing Laboratories) and CSA (Canadian Standards Association) or ETL, Canada. When installing motors in the field, locate the electrical junction box toward the center of the unit. This arrangement is required for correct belt tension. Use the smallest mounting holes in the mounting base that will accommodate the motor and provide minimum overhang (see Fig. 19). Tighten the motor holddown bolts. JUNCTION BOX CONDENSATE PREVENTION When air handlers are installed outdoors, precautions must be taken to prevent condensation from forming inside the junction box of the internally mounted motor. Standard installation practice is to mount the motor starter or fused disconnect box adjacent to the air handler and enclose the power wiring to the motor in flexible conduit. The sheet metal housing of the disconnect switch or motor starter is not airtight (even when a box meeting NEMA [National Electrical Manufacturers Association] IV standards is used). Thus, warm moist air can migrate through the flexible conduit to the junction box on the motor. With the motor located inside the unit, the motor temperature is that of the cool supply air; thus, condensate can form inside the junction box and, possibly, on the live terminal lugs. To prevent the moist air from migrating through the conduit to the motor, seal the power wires inside the flexible conduit at the motor starter or fused disconnect (Fig. 20). Use a non-conductive, non-hardening sealant. Permagum (manufactured by Schnee Morehead) or sealing compound, thumb grade (manufactured by Calgon), are acceptable materials. Fig. 17 Intake Hood 26

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 39M Central Station Air-Handling Units Sizes 03-30 Installation, Start-Up and Service Instructions CONTENTS Page INTRODUCTION.................................. 1 SAFETY CONSIDERATIONS......................

More information

Product Data. 39T Central Station Air-Handling Units. Features/Benefits. Nominal 3,500 to 46,000 Cfm

Product Data. 39T Central Station Air-Handling Units. Features/Benefits. Nominal 3,500 to 46,000 Cfm Product Data 39T Central Station Air-Handling Units Nominal 3,500 to 46,000 Cfm Features/Benefits Flanged and gasketed modular components units are available as a single assembly up to 40 ft long, or shipped

More information

Product Data. Features/Benefits. 39NX Central Station Air-Handling Units. Nominal 2,000 to 55,000 Cfm

Product Data. Features/Benefits. 39NX Central Station Air-Handling Units. Nominal 2,000 to 55,000 Cfm Product Data 39NX Central Station Air-Handling Units Nominal 2,000 to 55,000 Cfm Features/Benefits Sloped, double-wall coil condensate drain pan complies with ASHRAE Standard 62 Double-wall casings solid,

More information

Complete HVAC Capability

Complete HVAC Capability Air Handling Units Brochure 1110 January 2006 Complete HVAC Capability MEA Horizontal Draw-Thru to Size 65 Vertical Draw-Thru to Size 50 1000 to 60,000 CFM Forward Curved or Airfoil Wheels Inlet Vane Option

More information

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS INSTALLATION OPERATION & MAINTENANCE New Release Form 130.13-NOM4 (908) In conjunction with the use of these instructions, obtain and refer to the construction,

More information

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS BY JOHNSON CONTROLS INSTALLATION OPERATION & MAINTENANCE MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS New Release Form ET130.13-NOM4 (908) In conjunction with the use of these instructions, obtain

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS.....................1,2 INSTALLATION................................ 2-31 Step 1 Complete Pre-Installation Checks.........................................

More information

INSTALLATION MANUAL TBH/TBV BELT DRIVE BLOWER-COIL UNITS HORIZONTAL. Redefine your comfort zone.

INSTALLATION MANUAL TBH/TBV BELT DRIVE BLOWER-COIL UNITS HORIZONTAL. Redefine your comfort zone. INSTALLATION MANUAL TBH/TBV BELT DRIVE BLOWER-COIL UNITS HORIZONTAL BELT DRIVE BLOWER-COIL UNITS TBH/TBV, HORIZONTAL Table of Contents Safety Symbols & Considerations...3 Return / Exhaust Casing Extension...4

More information

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL SO TOUGH, WE GUARANTEE IT. SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL SBH SBV www.superiorrex.com SO TOUGH, WE GUARANTEE IT! www.superiorrex.com SBH / SBV Series: CONSTRUCTION FEATURES

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS Part #469003 Model Vektor -H Installation Operation and Maintenance Manual for Vektor-H Laboratory Exhaust System Receiving Greenheck model Vektor-H fans are thoroughly

More information

Installation Instructions

Installation Instructions CAHZCOIL8A00 CAHZCOIL412A00 CAHZCOIL208A00 CAHZCOIL212A00 CAVTCOIL8A00 CAVTCOIL412A00 CAVTCOIL208A00 CAVTCOIL212A00 Installation Instructions DIRECT --- EXPANSION HORIZONTAL AND VERTICAL EVAPORATOR COILS

More information

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499]

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499] BC--1.0 03-01-1 Belt Drive Blower Coil Unit, Basic Unit Discharge ARGT. 1 4. See page 1 for filter rack details. 5. Base rail is optional on he base unit. See page 13. Base rails must be used with mixing

More information

Issue 4 (Record Only) Job #: Innovent Submittal Date: October 30, 2012 Project: Location: Columbus, OH Innovent Job #: Submittal Issue: 4 (Record Only) Engineer: Contractor: Tag Innovent Model # AHU-BG-01

More information

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System V-Series (rev. 08/17/10) Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System Note: Optional items and/or items requiring a choice, are shown between brackets and/or parentheses

More information

SECTION AXIAL HVAC FANS

SECTION AXIAL HVAC FANS SECTION 233413 - AXIAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,

More information

Filtered Kitchen Supply Packaged Ventilator

Filtered Kitchen Supply Packaged Ventilator Filtered Kitchen Supply Packaged Ventilator Page Introduction........................................... 2 Information............................................ 3 Specifications and Dimension Data KD................................................

More information

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS COMMERCIAL KITCHEN APPLICATIONS Belt Driven Model VRBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS The Carnes Company

More information

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw Small Packaged Products 2 to 5 Tons Accessory Electric Heaters Cancels: IIK 564A-24-2 IIK 564A-24- -02 Installation Instructions Electric Heaters 5 20 kw NOTE: Read the entire instruction manual before

More information

Tubular Centrifugal Fans

Tubular Centrifugal Fans Tubular Centrifugal Fans Model TCB Inline - Horizontal or Vertical Roof Upblast and Roof Supply March 2007 Tubular Centrifugal Fans The TCB series of inline centrifugal fans is designed for ducted inline,

More information

Tube Axial Fan Page Specifications & Dimension Data Performance Data

Tube Axial Fan Page Specifications & Dimension Data Performance Data Tube Axial Fan Page Introduction........................................... 2 Construction Features................................... 3 Information........................................... 4 Specifications

More information

Climas y Proyectos Leyco, S.A. de C.V.

Climas y Proyectos Leyco, S.A. de C.V. GENERAL DESCRIPTION : FURNISH AND INSTALL MULTI COMPONENT ROOF MOUNTED LEYCO, MODEL CAH CUSTOM AIR HANDLER MADE SELF-CONTAINED, WEATHER RESISTANT, AIR HANDLING UNITS PER MODEL NUMBER, AND PERFORMANCE DATA

More information

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume PennBarry Fan Guide Specification Laboratory Exhaust System: Model vplume This document 2018 PennBarry vplume is a commercial lab exhaust fan that ensures a greater margin of safety by effectively dispersing

More information

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410. PART 1 - GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Product Data. Features/Benefits. 42BH System Fan Coil. 800 to 4000 Cfm

Product Data. Features/Benefits. 42BH System Fan Coil. 800 to 4000 Cfm Product Data 42BH System Fan Coil 800 to 4000 Cfm Satisfy All Your Design Requirements with Carrier s Versatile 42BH Fan Coil Unit A selection of 6 sizes covers capacities from 800 to 4000 cfm Choice of

More information

Fixed Pitch Vane Axial Fan

Fixed Pitch Vane Axial Fan Fixed Pitch Vane Axial Fan Page Introduction...........................................2 Construction Features...................................3 Mounting Options.......................................3

More information

Installation Instructions

Installation Instructions GEMINI SELECT 38APS025-065, 38APD025-130 Air-Cooled Condensing Units with PURON Refrigerant (R-410A) 50/60 Hz Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

MODELS STXD & STXDe DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS

MODELS STXD & STXDe DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS MODELS & e DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS MODEL DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER MODEL FEATURES Exhaust air up to 4,780 CFM in high static pressure applications up to 1-1/2 w.g. Attractive

More information

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw Small Packaged Products to 5 Tons Accessory Electric Heaters Cancels: IIK 564A--1 IIK 564A-- 11-01 Installation Instructions Electric Heaters 5 0 kw NOTE: Read the entire instruction manual before starting

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions Installation, Start-Up and Service Instructions 48AJ,AK,AW,AY020-060 with Reciprocating Compressor 48EJ,EK,EW,EY024-068 Single Package Rooftop Units Electric Cooling/Gas Heating CONTENTS Page SAFETY CONSIDERATIONS......................

More information

XeteX, Inc. All Rights Reserved.

XeteX, Inc. All Rights Reserved. Model XC Indoor or outdoor mounted, simple, in-case aluminum flat plate exchanger with options for frost control. Ideal for inline installations: in duct-work systems, in built-up units, or in modular

More information

forward curved inline duct blowers

forward curved inline duct blowers Defining Innovation. forward curved inline duct blowers TYPE DBS (Single) DBT (Twin) BULLETIN 4220 January 2011 Duct Blowers General Information Twin City Fan s belt driven DBS (single) and DBT (twin)

More information

SECTION CENTRIFUGAL HVAC FANS

SECTION CENTRIFUGAL HVAC FANS SECTION 233416 - CENTRIFUGAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS

Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS TABLE OF CONTENTS H & V Features and Benefits...4 Coil and Filter Data, Static Pressure Data...7 Electric Resistance Heat Section...8 Coil Information

More information

CPC Commercial. 15- & 20-Ton, Three-Phase Packaged Air Conditioner. 20-Ton Cooling Capacity: 240,000 BTU/h

CPC Commercial. 15- & 20-Ton, Three-Phase Packaged Air Conditioner. 20-Ton Cooling Capacity: 240,000 BTU/h CPC Commercial 15- & 20-Ton, Three-Phase Packaged Air Conditioner 15-Ton Cooling Capacity: 180,000 BTU/h 20-Ton Cooling Capacity: 240,000 BTU/h Contents Nomenclature...2 Product Features...3 Product Specifications...4

More information

Installation Instructions

Installation Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment

More information

Eclipse Hermetic Gas Boosters

Eclipse Hermetic Gas Boosters Information Guide 620 12/1/2008 Eclipse Hermetic Gas Boosters Series HB & HBLC Version 1 Applications Eclipse Inc., produces a line of single stage, centrifugal type, hermetically sealed gas boosters for

More information

Industrial Generator Set Accessories

Industrial Generator Set Accessories Industrial Generator Set Accessories Aluminum Sound Enclosure and Subbase Fuel Tank Package Applicable to the following models: KD800 - KD2500 Level 1 Sound Enclosure with Lift Base Sound Level 1 Enclosure

More information

University of Delaware

University of Delaware SECTION 23 36 00 _ SUMMARY PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Constant/Variable volume supply terminal units. 2. Fan powered terminal units. 3. Exhaust valves B. Related Sections: Section

More information

Installation Instructions

Installation Instructions GEMINI SELECT 38APS025-050,38APD025-100 Air-Cooled Condensing Units with PURON Refrigerant (R-410A) 50/60 Hz Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators Version: Dec. 01, 2004 RERV & RERVX Rotary Energy Recovery Ventilators Indoor and Outdoor Installations 250 20,000 CFM Capacities RERVLP Low Profile Indoor Rotary Energy Recovery Ventilators Ideal for

More information

Industrial Generator Set Accessories

Industrial Generator Set Accessories Industrial Generator Set Accessories Sound Enclosure and Subbase Fuel Tank Package Applicable to the following models: KD800 - KD2500 (includes KD1250-A) Level 1 Sound Enclosure with Lift Base Sound Level

More information

Industry best 5 year fan housing warranty, 1 year motor warranty

Industry best 5 year fan housing warranty, 1 year motor warranty MODELS & e DIRECT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTERS MODEL - DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER MODEL FEATURES Exhaust air up to 4,980 CFM in high static pressure applications up to 1-1/2

More information

DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS

DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS These completely assembled units include a well-insulated cabinet, a DX cooling coil

More information

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Direct and Belt Driven Models VUDK and VUBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS The Carnes Company

More information

Air Handling Unit Construction Checklist

Air Handling Unit Construction Checklist Air Handling Unit Construction Checklist Project: Date: AHU Tag: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

READ AND SAVE THESE INSTRUCTIONS. Air Boss MP600M Vertical Air Flow Mist Precipitator Industrial Applications. TRION

READ AND SAVE THESE INSTRUCTIONS. Air Boss MP600M Vertical Air Flow Mist Precipitator Industrial Applications. TRION READ AND SAVE THESE INSTRUCTIONS Vertical Air Flow Mist Precipitator Industrial Applications TRION Vertical Air Flow Mist Precipitator for Industrial Applications Table of Contents Design...2 Installation...2

More information

Roof Upblast and Sidewall Exhaust

Roof Upblast and Sidewall Exhaust XRUB, XRUD, XSEB, XSED, and XRUBS models are listed for electrical (UL/C-UL US 705) File no. E40001 and for grease removal (UL/C-UL US 762) File no. MH11745. Accurex, LLC certifies model XRUB, XRUD, XSEB,

More information

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS 50FN-1SB 50FNX,FNY078,088,104 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE AIR VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE WITH INTEGRAL ECONOMIZER AND HIGH-CAPACITY MODULATING

More information

Roof Upblast and Sidewall Exhaust

Roof Upblast and Sidewall Exhaust XRUB, XRUD, XSEB, XSED, and XRUBS models are listed for electrical (UL/C-UL US 0) File no. E000 and for grease removal (UL/C-UL US ) File no. MH. Accurex, LLC certifies model XRUB, XRUD, XSEB, XSED, and

More information

TUBULAR CENTRIFUGAL INLINE FANS

TUBULAR CENTRIFUGAL INLINE FANS Twin City Fan INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS TUBULAR CENTRIFUGAL INLINE FANS MODEL TSL CATALOG 1001 APRIL 2014 CENTRIFUGAL INLINE FANS Model TSL The TSL is an inline centrifugal

More information

CENTRIFUGAL WALL EXHAUSTERS Models VWDK and VWBK

CENTRIFUGAL WALL EXHAUSTERS Models VWDK and VWBK CENTRIFUGAL WALL EXHAUSTERS Models VWDK and VWBK CENTRIFUGAL WALL EXHAUSTERS Direct and Belt Driven Models VWDK and VWBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS The Carnes Company centrifugal wall

More information

Centrifugal Spun Aluminum Products

Centrifugal Spun Aluminum Products Centrifugal Spun Aluminum Products SDB SDBD STXB STXD Downblast & Upblast Centrifugal Roof Wall Exhausters Designed with Efficiency in Mind CSAP_0415 April 2015 Centrifugal Spun Aluminum Line Overview

More information

UTILITY BLOWERS. Models: BIUB / BIUBR / BIUBSH BAUB / DFC / FCUB. The Industrial Choice.

UTILITY BLOWERS. Models: BIUB / BIUBR / BIUBSH BAUB / DFC / FCUB. The Industrial Choice. UTILITY BLOWERS Models: BIUB / BIUBR / BIUBSH BAUB / DFC / FCUB The Industrial Choice. CATALOG 760 April 2017 Utility Blowers Overview Utility Blowers Aerovent s line of utility blowers is one of the most

More information

McQuay. Central Station Air Handler. LHD, LML, LSL, LWL, LYF, MMM, MSL, MWL Vintage D. LML, LSB, MMM, MSB Vintage E

McQuay. Central Station Air Handler. LHD, LML, LSL, LWL, LYF, MMM, MSL, MWL Vintage D. LML, LSB, MMM, MSB Vintage E Replacement Parts List No. 046902100 Revision D 01/2015 McQuay Central Station Air Handler LHD, LML, LSL, LWL, LYF, MMM, MSL, MWL 137-172 Vintage D LML, LSB, MMM, MSB 137-172 Vintage E Last Manufactured:

More information

Modified Downdraft Paint Booth Nut and Bolt Assembly Pre-Punched Panel Flanges

Modified Downdraft Paint Booth Nut and Bolt Assembly Pre-Punched Panel Flanges Phone: 800-348-1097 www.aeipaintbooths.com Modified Downdraft Paint Booth Nut and Bolt Assembly Pre-Punched Panel Flanges Thank you for the opportunity to work with you on your paint booth project. Below

More information

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile Centrifugal Cabinet s BCF Belt Drive Low-Profile November 204 BCF Centrifugal Cabinet Contents Standard Construction Features... 3 Options and Accessories... 4 Filter and Mixing Box Data... 5 Typical Installations...

More information

belt drive utility sets vent-pak series models vp-bi & fc january 2007 vp 1.07

belt drive utility sets vent-pak series models vp-bi & fc january 2007 vp 1.07 belt drive utility sets vent-pak series models vp-bi & fc january 2007 vp 1.07 model vp - belt drive utility set Application VENT-PAK fan wheels are the versatile, quiet, energy efficiency backward inclined

More information

TURNING AIR INTO SOLUTIONS. LOW PROFILE HOODED PROPELLER ROOF VENTILATORS. LHD/LHB (Exhaust/Supply) LHDF/LHBF (Filtered Supply)

TURNING AIR INTO SOLUTIONS. LOW PROFILE HOODED PROPELLER ROOF VENTILATORS. LHD/LHB (Exhaust/Supply) LHDF/LHBF (Filtered Supply) TURNING AIR INTO SOLUTIONS. LOW PROFILE HOODED ROOF VENTILATORS LHD/LHB (Exhaust/Supply) LHDF/LHBF (Filtered Supply) CATALOG 4860 April 17 ROOF VENTILATORS Overview Propeller Roof Ventilators LHB with

More information

SPUN ALUMINUM POWER ROOF AND WALL VENTILATORS

SPUN ALUMINUM POWER ROOF AND WALL VENTILATORS BULLETIN 0 January 007 SPUN ALUMINUM POWER ROOF AND WALL VENTILATORS TYPE ACX / ACXD TYPE ATD / ATDR / ATDW / ATDWR TYPE ATB / ATBR / AWX / AWXR Model ACX Model ATB Model ACXD Model ATDR Model AWX Centrifugal

More information

Square Inline Fans with Multi-Directional Discharge

Square Inline Fans with Multi-Directional Discharge SQN Square Inline Fans with Multi-Directional Discharge Page Introduction............................................2 Standard Construction Features............................ 3 Specifications and Dimension

More information

SECTION DUCTWORK ACCESSORIES

SECTION DUCTWORK ACCESSORIES SECTION 15910 DUCTWORK ACCESSORIES PART 1- GENERAL SCOPE This sections includes accessories used in the installation of duct systems. Included are the following topics: PART 1- GENERAL Related Work Reference

More information

TURNING AIR INTO SOLUTIONS. LOW PROFILE UPBLAST PROPELLER ROOF VENTILATORS. LUD/LUB (Standard) LUBMO (Motor Out of Airstream) LUBSH (UL Smoke & Heat)

TURNING AIR INTO SOLUTIONS. LOW PROFILE UPBLAST PROPELLER ROOF VENTILATORS. LUD/LUB (Standard) LUBMO (Motor Out of Airstream) LUBSH (UL Smoke & Heat) TURNING AIR INTO SOLUTIONS. LOW PROFILE UPBLAST ROOF VENTILATORS LUD/LUB (Standard) LUBMO (Motor Out of Airstream) LUBSH (UL Smoke & Heat) CATALOG 4870 April 17 ROOF VENTILATORS Overview Propeller Roof

More information

INDUSTRIES AMERICAN COOLAIR CORPORATION. Centrifugal Filtered Supply Roof Ventilators TYPE CFS - TYPE SIS

INDUSTRIES AMERICAN COOLAIR CORPORATION. Centrifugal Filtered Supply Roof Ventilators TYPE CFS - TYPE SIS INDUSTRIES AMERICAN COOLAIR CORPORATION Centrifugal Filtered Supply Roof Ventilators TYPE CFS - TYPE SIS CFS Centrifugal Filtered Supply Fans Applications The CFS Centrifugal Filtered supply fans with

More information

TYPICAL SPECIFICATION: Critical Process Roof Top Unit 7/14/15

TYPICAL SPECIFICATION: Critical Process Roof Top Unit 7/14/15 UNIT CONSTRUCTION: Casing: A. 2.5 NTM (No Thru Metal Casing) 1. Base frame fabrication utilizes a single frame construction for supporting the casing and internal component. 2. The casing walls and roof

More information

Twin City Fan & Blower

Twin City Fan & Blower BULLETIN 600 Twin City Fan & Blower September 2009 VENTILATING SETS TYPE BCV (Backward Inclined) TYPE BCVU5 (UL 705 Listed) TYPE BCVU2 (UL 762 Listed) TYPE BCVSH (UL Smoke & Heat) TYPE BAV (Airfoil) TYPE

More information

INSTALLATION, START-UP AND SERVICE INSTRUCTIONS

INSTALLATION, START-UP AND SERVICE INSTRUCTIONS INSTALLATION, START-UP AND SERVICE INSTRUCTIONS P705 Refrigeration Condensing Units CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INTRODUCTION.................................. 1 HANDLING.......................................

More information

RECORD SUBMITTAL COVER SHEET

RECORD SUBMITTAL COVER SHEET RECORD SUBMITTAL COVER SHEET PROJECT TITLE: AXCELLERATE PHARMA EQUIPMENT DESCRIPTION: CARRIER AERO AIR-HANDLING UNIT AHU-1 OWNER: AXCELLERATE PHARMA MECHANICAL ENGINEER: ARDEN DATE: JUNE 27, 2014 SUBMITTED

More information

WAC Air Curtains Technical Guide

WAC Air Curtains Technical Guide TGWAC-2 WAC Air Curtains Technical Guide FOR WIND STOPPING, INSECT CONTROL, AND ENVIRONMENTAL SEPARATION IN COMMERCIAL AND INDUSTRIAL APPLICATIONS TABLE OF CONTENTS Introduction......................................................................2

More information

AIR ZONE INTERNATIONAL MIXED-FLOW AIR COLUMN UNIT

AIR ZONE INTERNATIONAL MIXED-FLOW AIR COLUMN UNIT ZONE INTERNATIONAL MIXED- COLUMN UNIT 5220 TED ST. HOUSTON, TEXAS 77040 (713) 460-4040 FAX (713) 460-4050 WWW.ZONEINC.COM ZONE INTERNATIONAL MIXED- COLUMN UNIT T DUCT COLLAR INLET (A x B) PRIMARY RETURN

More information

Tube Axial Inline Fans

Tube Axial Inline Fans Tube Axial Inline Fans Models TDI & TBI-CA Level 3 with Cast Aluminum Propeller Direct & Belt Drive Clean Air or Fume Exhaust July 2011 Features Tube Axial Inline Fans Greenheck s tube axial fans are the

More information

Energy Recovery Laboratory Exhaust

Energy Recovery Laboratory Exhaust Energy Recovery Laboratory Exhaust Model Vektor ERS-M For Vektor-M Fan Systems September 2012 Model Page Header Vektor ERS-M Greenheck s Vektor -ERS is a pre-engineered laboratory exhaust energy recovery

More information

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: 036-21323-001-B-0202 GENERAL SPECIFICATIONS OUTDOOR UNIT: Two independent refrigerant circuits Inherently protected fan motors Two independent scroll compressors V-Coil Design Exterior service port connections

More information

ENVIRO UNIT CES SERIES

ENVIRO UNIT CES SERIES ENVIRO UNIT CES SERIES ENVIRO UNIT FILTER BOX Commercial Kitchen Exhaust CES-ISH 1,000 to 40,000 CFM Operation The grease laden air rises from the cooking equipment into the NFPA- 96 commercial kitchen

More information

Installation Instructions

Installation Instructions 010A00 011A00 014A00 SMALL ROOFTOP UNITS TWO POSITION OUTDOOR AIR DAMPER 2to15TONS (50/60 Hz) Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 PACKAGE USAGE... 1 SAFETY CONSIDERATIONS...

More information

DESIGN GUIDELINES FANS PAGE 1 of 7

DESIGN GUIDELINES FANS PAGE 1 of 7 DESIGN GUIDELINES FANS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the

More information

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved Centrifugal Roof Supply Fans Models and Forward Curved April 2008 Centrifugal Filtered Roof Supply Fan When you buy a Greenheck model or, you receive a fan with the industry s best performance and durability

More information

MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING

MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING SIZES FROM 600 TO 9,000 All Technical Specifications are Subject to Change without Notice.

More information

Installation Instructions

Installation Instructions Accessory Ultra-Violet Germicidal Lamps 40RM007-034, 40RMQ008-016 and 40RMS008-024 Air Handler Units Installation Instructions Part Numbers: CRDBLFIX001A00, CRDBLFIX002A00, CRDBLFIX003A00, CRDBLFIX004A00,

More information

McQuay. Central Station Air Handler. LHD, LML, LSL, LWL, LYF, MMM, MSL, MWL Vintage C. Last Manufactured: 1984

McQuay. Central Station Air Handler. LHD, LML, LSL, LWL, LYF, MMM, MSL, MWL Vintage C. Last Manufactured: 1984 Replacement Parts List No. 055222700 Revision D 0/205 McQuay Central Station Air Handler LHD, LML, LSL, LWL, LYF, MMM, MSL, MWL 37-72 Vintage C Last Manufactured: 984 To find your Daikin Applied parts

More information

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting READ AND SAVE THESE INSTRUCTIONS INSTALLATION, OPERATING INSTRUCTIONS & PARTS MANUAL Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting Electrical wiring and connections should be done

More information

Product Data. Features/Benefits. WEATHERMASTER 36S Water Control Induction Air Terminals to cfm (1770 to 8900 Btuh)

Product Data. Features/Benefits. WEATHERMASTER 36S Water Control Induction Air Terminals to cfm (1770 to 8900 Btuh) Product Data WEATHERMASTER 36S Water Control Induction Air Terminals 19.4 to 131.9 cfm (1770 to 8900 Btuh) Induction air terminals offer: Heating and cooling operation 2-pipe or 4-pipe system options Automatic

More information

The Industrial Choice. Vane Section For Model VTBD. Model TTABD TUBEAXIAL & VANEAXIAL FANS. Type "T" Belt Driven Model TTABD / VTBD

The Industrial Choice. Vane Section For Model VTBD. Model TTABD TUBEAXIAL & VANEAXIAL FANS. Type T Belt Driven Model TTABD / VTBD The Industrial Choice. Vane Section For Model VTBD Model TTABD TUBEAXIAL & VANEAXIAL S Type "T" Belt Driven Model TTABD / VTBD BULLETIN 424-A November 1998 Model TTABD/VTBD Tubeaxial/Vaneaxial Fans Aerovent

More information

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved Centrifugal Roof Supply Fans Models and Forward Curved B U I L D I N G V A L U E I N A I R. April 2008 Centrifugal Filtered Roof Supply Fan When you buy a Greenheck model or, you receive a fan with the

More information

FILTERED SUPPLY CENTRIFUGAL Belt Drive

FILTERED SUPPLY CENTRIFUGAL Belt Drive FILTERED SUPPLY CENTRIFUGAL Belt Drive FILTERED SUPPLY CENTRIFUGAL - BELT DRIVE SECTION 9 Carnes Models VSBB and VHBB centrifugal filtered roof supply fans are available in six sizes - 8 through 20 with

More information

MANUAL INSTALLATION. Active Chilled Beam Linear. ACBL Series. v101 Issue Date: 04/10/ Price Industries Limited. All rights reserved.

MANUAL INSTALLATION. Active Chilled Beam Linear. ACBL Series. v101 Issue Date: 04/10/ Price Industries Limited. All rights reserved. MANUAL INSTALLATION Active Chilled Beam Linear ACBL Series v11 Issue Date: 4/1/18 218 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview Before You Start...1 Maintenance...1

More information

MA-5200 Series MA-5300 Series

MA-5200 Series MA-5300 Series MA-5200 Series MA-5300 Series Two-Position Actuators General Instructions Application The MA-5200 series and MA-5300 series actuators are used for two-position control of valves and dampers which require

More information

Product Data. Features/Benefits 50JS SINGLE-PACKAGED HEAT PUMP 50 HZ UNITS 7 TO 18 KW (2 TO 5 NOMINAL TONS)

Product Data. Features/Benefits 50JS SINGLE-PACKAGED HEAT PUMP 50 HZ UNITS 7 TO 18 KW (2 TO 5 NOMINAL TONS) SINGLE-PACKAGED HEAT PUMP 50 HZ UNITS 7 TO 18 KW (2 TO 5 NOMINAL TONS) Product Data UNIT (50 Hz) Single-packaged Heat Pump for Residential and Light Commercial applications. Features/Benefits One-piece

More information

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm Product Data 35K Bypass Terminal 110 to 4400 cfm Carrier s 35K Series bypass terminals offer: 20-gage, galvanized steel casing construction 1/2-in. thick, dual density fiberglass insulation meeting NFPA

More information

AIR-AIR ENERGY CONSERVATION MODULE

AIR-AIR ENERGY CONSERVATION MODULE AIR-AIR ENERGY CONSERVATION MODULE BC-ECW SERIES INDOOR/OUTDOOR INSTALLATION MANUFACTURED BY TABLE OF CONTENTS BC-ECW - Description...3 Components and fabrication details...3-4 Frost prevention & selection

More information

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER MEL TXD Model Features Exhaust air up to 3,400 CFM in high static pressure applications up to 1-1/4 w.g. Attractive spun aluminum exterior Direct drive units have low sound levels and quiet operation Non-overloading

More information

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents. PART 1: GENERAL 1.01 This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is to apply the

More information

MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER

MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER MODEL MODEL FEATURES Exhaust air up to 60,116 CFM in static pressure applications up to 1 w.g. Straight-through air flow design results in maximum exhaust efficiency Motor and drives are located outside

More information

VAHU Vertical Air Handling Unit

VAHU Vertical Air Handling Unit 500 to 5,400 CFM @ up to 6.00" TSP 2" double wall construction, perforated or solid lined 18 gauge G90 galvanized steel cabinet 4 standard cabinet sizes available Internally isolated direct drive plug

More information

Centrifugal Utility Fans - SFD/SFB

Centrifugal Utility Fans - SFD/SFB C H F D B G E A Centrifugal Utility Fans - SFD/SFB SFB STANDARD CONSTRUCTION FEATURES HOUSING: Heavy gauge steel housing with Lock-seam construction Unit support angles with prepunched mounting holes Adjustable

More information

.3 Section Vibration Isolation and Seismic Control..2 ANSI/AMCA 210/ASHRAE 51 Laboratory Methods of Testing Fans for Rating.

.3 Section Vibration Isolation and Seismic Control..2 ANSI/AMCA 210/ASHRAE 51 Laboratory Methods of Testing Fans for Rating. Issued 2005/06/01 Section 15831 Commercial Fans Page 1 of 6 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01355 Waste Management and Disposal..2 Section 15053 Motors, Drives and Guards..3 Section 15072

More information

HORIZONTAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT

HORIZONTAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT HORIZONTAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT MADE IN USA SIZES FROM 600 TO 9,000 All Technical Specifications are Subject to Change

More information

First Inline fan in the industry to be UL/cUL Listed Power Ventilator for Smoke Control Systems

First Inline fan in the industry to be UL/cUL Listed Power Ventilator for Smoke Control Systems Medium Pressure Axial Fans Model TBI-FS Levels 3, 4 & 5 with Fabricated Steel Propeller Belt Drive Inline or Roof Mounted Upblast Clean Air or Fume Exhaust High Temperature Process Exhaust Emergency Smoke

More information

BULLETIN 456. July 1997 VANEAXIAL FANS. Type W Direct Drive/Belt Driven. Model VW Direct Drive. Model VWBD Belt Driven

BULLETIN 456. July 1997 VANEAXIAL FANS. Type W Direct Drive/Belt Driven. Model VW Direct Drive. Model VWBD Belt Driven BULLETIN 456 July 1997 VANEAXIAL FANS Type W Direct Drive/Belt Driven Model VW Direct Drive Model VWBD Belt Driven Aerovent certifies that the Type W Vaneaxial Fans shown herein are licensed to bear the

More information

Industry best 5 year fan housing warranty, 1 year motor warranty

Industry best 5 year fan housing warranty, 1 year motor warranty MEL FEATURES Exhaust air up to 28,000 CFM in high static pressure applications up to 1-1/4 w.g. Attractive spun aluminum exterior Belt drives permit easy performance adjustments when needed Non-overloading

More information