FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS

Size: px
Start display at page:

Download "FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS"

Transcription

1 FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS API/IP SPECIFICATION 1584 Third edition April 2001

2

3 FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS API/IP SPECIFICATION 1584 Third edition April 2001 Published jointly by American Petroleum Institute and The Institute of Petroleum, London A charitable company limited by guarantee

4 Copyright 2001 by American Petroleum Institute, and The Institute of Petroleum, London: A charitable company limited by guarantee. Registered No , England All rights reserved No part of this book may be reproduced by any means, or transmitted or translated into a machine language without the written permission of the publisher. ISBN Published by The Institute of Petroleum Further copies can be obtained from Portland Press Ltd. Commerce Way, Whitehall Industrial Estate, Colchester CO2 8HP, UK. Tel: 44 (0) sales@portlandpress.com

5 CONTENTS Foreword... vii Page Acknowledgements... ix 1 Introduction, scope and referenced publications Introduction Scope Referenced publications Terms, definitions and abbreviations Terms and definitions Abbreviations Units used General arrangements and features Typical arrangement of hydrant pit equipment and controls Mandatory requirements Optional items Performance criteria and testing procedures Mechanical strength Test fluid Dimensional checks Proof and burst pressure Pressure loss Opening and closing times and overshoot Vacuum test Pilot device override test External load resistance and failure mode Catastrophic excess flow Decoupling spillage Pressure, surge and flow control Type approval testing and quality assurance Quality assurance Approval testing Documentation and instruction v

6 Contents Cont.. Page Annex A - Catastrophic excess flow Annex B - Hydrant pit valve assemblies in small pit boxes Annex C - Hydrant riser stress during impact of the hydrant pit valve/hydrant coupler assembly Annex D - Air-operated pilot devices Annex E - The inspection and testing of airport hydrant pit valves vi

7 FOREWORD This joint Institute of Petroleum and American Petroleum Institute publication provides recommended minimum performance and mechanical specifications for the design of aviation fuel hydrant system pit valves and associated couplers. This publication also specifies requirements that need to be met to achieve full interchangeability between components of various manufacturers and requirements for optional features which component manufacturers may be requested by users to provide. This publication has been produced jointly by the API Aviation Technical Services Subcommittee and the IP Aviation Committee. It replaces API Standard 1584 second edition, December 1994, IP Aviation hydrant pit systems recommended arrangements, August 1990 and IP The inspection and testing of airport hydrant pit valves, July It is possible that this joint publication will have a wider scope of usage and will encompass differing operating practices and safety and environmental legislation. Therefore, this publication should be read in conjunction with appropriate national and local statutory operating requirements. It is recommended that, if procedures defined in this publication are more stringent than those at the point of use are they should be followed. Whilst the use of hydrant pit valve assemblies designed for use with 150 mm (6 in.) hydrant riser flanges is preferred, requirements for valves that are able to mate with other flanges are also included. The requirements of this publication are not retroactive. Users of existing equipment should decide what action to take if equipment in current use does not conform to the requirements of this edition. Due consideration should be taken of the safety implications of non-conformance. Within six months of the publication of this edition, manufacturers will be expected to be able to supply modification kits, where necessary, for any existing equipment that does not conform to the requirements of this edition. The Institute of Petroleum and American Petroleum Institute are not undertaking to meet duties of employers, manufacturers or suppliers to warn and properly train and equip their employees, and others exposed, concerning health and safety risks and precautions, nor undertaking their obligations under local and regional laws and regulations. vii

8 Nothing contained in any Institute of Petroleum or American Petroleum Institute joint publication is to be construed as granting any right, by implication or otherwise, for the manufacture, sale, or use of any method, apparatus, or product covered by letters patent. Neither should anything contained in the publication be construed as insuring anyone against liability for infringement of letters patent. Although it is hoped and anticipated that this publication will assist both the manufacturers and purchasers of aviation fuel hydrant system pit valves and couplers, the Institute of Petroleum and the American Petroleum Institute cannot accept any responsibility, of whatever kind, for damage or loss, or alleged damage or loss, arising or otherwise occurring as a result of the application of the specifications or qualification procedures contained herein. Suggested revisions are invited and should be submitted to the Manager of Standardization, American Petroleum Institute, 1220 L Street, N.W., Washington, D.C , USA or to the Technical Department, Institute of Petroleum, 61 New Cavendish Street, London W1G 7AR, UK. Note for users of equipment covered by this publication. This publication includes a requirement for couplers to break away cleanly from the pit valve adapter if struck with a force as defined herein. It is recommended that, if a pit valve/coupler assembly is struck with sufficient force to remove the coupler during refuelling operations, the pit valve should be removed from service for inspection and tested to prove its suitability for further use. Users are referred to the recommended post-impact action in Annex C. viii

9 ACKNOWLEDGEMENTS This edition of API/IP 1584 has been prepared by the IP Equipment Sub-Committee on behalf of the Institute of Petroleum and the American Petroleum Institute Aviation Technical Services Sub-Committee. Much of the redrafting was undertaken by Bob Simpson (Consultant) and Adrian Hamra (ExxonMobil). Draft versions of this third edition were reviewed by representatives of the following companies: AgipPetroli Air BP Limited Air TOTAL Avery Hardoll SBU, BAE Systems Power & Control Ltd. Caltex Corporation Carter Ground Fueling Co. Chevron Products Co. Conoco Limited Elf Aviation International Equilon Enterprises ExxonMobil Aviation International Ltd. Intertechnique Zenith Aviation Kuwait Petroleum International Aviation Company Ltd. Phillips 66 Company Shell Aviation Ltd. Texaco Global Aviation Marketing Ltd. Whittaker Controls Inc. ix

10 x

11 1 INTRODUCTION, SCOPE AND REFERENCED PUBLICATIONS 1.1 INTRODUCTION The performance requirements and optional recommendations included in this publication are intended to achieve the following: (a) Establish the acceptable structural and operating integrity of the components involved. (b) Provide a compatible coupling configuration and arrangement at the hydrant pit that will permit interchangeability between the components of different manufacturers. (c) Assist component manufacturers in their design efforts by detailing operational, maintenance and ergonomic features of components that are considered desirable based upon experience in aircraft fuelling. (d) Describe the alternative arrangements of hydrant pit components that are typical for API and IP 4 inch hydrant systems and thereby assist component manufacturers and aircraft fuelling system designers and operators in their efforts. (e) Provide mechanical strength criteria for normal handling loads and failure modes for excess mechanical loadings and impact damage General 1.2 SCOPE This publication specifies dimensions, coupling action, activation, and other requirements to achieve the necessary operational requirements and full interchangeability between components from manufacturers of hydrant pit valve assemblies and couplers. It also includes requirements for other optional features which component manufacturers may be requested to provide by purchasers. The performance specifications are for equipment intended for systems in aviation turbine fuel service. They do not apply to aviation gasoline (Avgas) Organization If complete interchangeability is to be attained, certain features of the mating components shall be standardised. Other features, although desirable, are not so critical, but are pointed out to assist manufacturers in the design of these components. The pit valve and coupler, along with any other features attached, are considered to be as a whole for the purposes of this publication. Section 3 covers general arrangement and features, specifying those features of the hydrant components that are mandatory, as well as those that are optional. 1

12 FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS They are listed as "Mandatory" and "Optional" respectively. Section 4 describes performance criteria and test requirements for the hydrant pit valve assembly and hydrant coupler. Section 5 contains the quality assurance and information requirements. Five annexes are included for information only. 1.3 REFERENCED PUBLICATIONS The following publications are cited in this publication. The latest available edition of each referenced publication applies. API RP 1004 Bottom loading and vapour recovery for MC-306 tank motor vehicles. Specification Q1 Specification for quality programs for the petroleum and natural gas industry. IP 2 Fuel hydrant riser pipe stress analysis due to accidental impact loads. The closure behaviour of aviation hydrant pit valves (Delft Hydraulics). Sanderson, T.A., and Simpson, R.A. 1990, Excess flow testing of hydrant pit valves, Petroleum Review, May ISO :2000 Quality management systems Quality assurance requirements for measuring equipment: Metrological confirmation system for measuring equipment. SAE 4 ARP 868A Method pressure drop test for fuel system components. ASME 1 B.16.5 Pipe flanges and flanged fittings. 1. American Society of Mechanical Engineers, 3 Park Avenue, New York, NY , USA Available from the Institute of Petroleum library, 61 New Cavendish Street, London W1G 7AR, UK 3. International Organization for Standardization, Case Postale 56, CH-1211 Geneva, Switzerland Society of Automotive Engineers, 400 Commonwealth Drive, Warrendale, PA , USA. 2

13 2 TERMS, DEFINITIONS AND ABBREVIATIONS 2.1 TERMS AND DEFINITIONS For the purposes of this publication the following terms and definitions apply: clean breakaway: when used in describing the breakaway of the hydrant coupler from the hydrant pit valve adapter, means that the coupler breaks away completely to allow the pit valve outlet adapter poppet to close. In practice, complete seating of the poppet cannot be guaranteed as coupler debris that may be left could prevent full poppet closing. hydrant coupler: a unit that is attached to the inlet end of the hydrant dispenser inlet hose or boom assembly to provide for quick coupling to the outlet adapter of the hydrant pit valve assembly. The coupler may be one of four types, any of which can be equipped for product selectivity: standard coupler: a quick coupling device that allows for manually opening and closing the poppet on the hydrant pit valve assembly and provides a flow path from the hydrant pit valve assembly to the dispenser. direct acting digital control coupler: a coupler that incorporates the same features as a standard coupler, but uses a digital module to control pressure and flow for each hose combination. A timer deadman may be included with this system as an option. direct acting pressure control coupler: a coupler that incorporates the same features as the standard unit, but also includes air-operated deadman and spring biased pressure regulation at a remote sensing point. This coupler also has optional excess flow control. pilot-operated pressure control coupler: a coupler that has the same features as the standard unit, plus the air deadman feature, but controls pressure by means of a pilot mechanism. This coupler also has optional excess flow control (with either single or dual flow rate settings). hydrant coupler carriage assembly: a device fitted to the hydrant coupler to assist in moving the coupler to and from the pit valve whilst keeping the coupler from dragging on the ground. Note: It generally takes the form of two small wheels on a structure that may be folded up beneath the inlet hose when not in use. hydrant dispenser: (also known as 'hydrant servicer', 'aircraft fuel servicer' or 'hydrant cart') a fuelling unit used to receive fuel from a hydrant fuel supply system and deliver it to aircraft. It may be self-propelled, trailer mounted or skid mounted. 3

14 FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS Note: It is normally fitted with filtration, pressure control, deadman control and metering equipment and is connected to the hydrant pit valve by a hydrant coupler and an inlet hose or metal boom assembly. The hydrant dispenser is used to deliver fuel into aircraft via a delivery hose and nozzle. hydrant pit valve assembly: a valve that is vertically mounted on the flanged riser of an airport fuel piping system. Note: The valve is composed of three components: the flanged inlet pilot-operated valve, the pilot device and the outlet adapter that mates with the hydrant coupler. Optional features may be included. intermediate strainer: an optional fine mesh screen that is mounted internal to the hydrant pit valve assembly, normally between the pilot-operated valve and the outlet adapter. Note: The use of such a strainer is not recommended. outlet adapter: the outlet portion of the hydrant pit valve assembly to which the hydrant coupler mates. The outlet adapter has a poppet that is opened and closed by the coupler poppet. The outlet adapter provides a seating for the poppet and for optional product selectivity. pilot device: a mechanism which diverts pressure to and from the actuating element of the pilotoperated valve to enable it to either open or close in a controlled manner. Note: The required methods for operating the pilot device are defined in pilot device override: (also known as a 'servicing valve') a manually operated valve or device that overrides the action of the pilot valve thus preventing opening of the pilot-operated valve. pilot-operated valve: located at the inlet, it forms an integral part of the hydrant pit valve assembly and isolates downstream components from the fuel hydrant supply pressure. It is operated by the pilot device and controls the flow of fuel out of the hydrant pit valve assembly. pressure equalisation valve: a small valve located in the centre of the outlet adapter poppet that is actuated by the hydrant coupler poppet. This valve allows equalisation of the pressure contained within the hydrant pit valve assembly with the pressure within the hydrant coupler. stoneguard: a mandatory coarse mesh screen (e.g. 5 mm or ¼ in. or equivalent) perforated metal strainer that is mounted upstream of the hydrant pit valve assembly to impede the flow of large debris normally foreign to fuel systems. flow: automatic excess flow control: a device installed on or within the hydrant pit valve assembly and/or coupler to prevent excess flow. Note: Upon the flow rate increasing to a predetermined level, the device will actuate the hydrant pit valve assembly and/or coupler to close and remain closed until the excess flow control device is reset. catastrophic excess flow: the maximum flow rate required to be stopped by the hydrant pit valve. excess flow: a flow rate in excess of rated flow. rated flow: the maximum flow rate for which the components of the pit valve assembly and coupler are designed. in-line pressure control (or regulating) valve: a valve installed on board the hydrant dispenser forming a part of the fuel pressure control (or regulating) system. It may also provide a deadman operation, being opened and closed remotely by the fuelling operator. This valve is outside of the scope of this publication and may be fitted at the discretion of the user. opening and closing times: closing time: the time required, after the operating device is actuated to close, for flow to cease from rated flow. deadman control: a hand-held control to actuate the opening and closing of the hydrant pit valve assembly and/or hydrant coupler. opening time: the time taken to achieve 90 % of rated flow measured from the time that the operating device is actuated. overshoot: the volume of liquid passing through the valve during the closing time period. 4

15 TERMS, DEFINITIONS AND ABBREVIATIONS pressure: burst pressure: the pressure causing structural failure of the external casing of the hydrant pit components covered by this publication. Note: For the purposes of this publication, the pressure defined in is the minimum pressure above which structural failure may occur. design pressure: the maximum pressure to which the hydrant pit components will be subjected in service. Note: This pressure equates to operating pressure plus surge pressure to which the equipment may be exposed. The performance criteria of this document do not apply at design pressure. operating pressure: the maximum steady state pump pressure that can be experienced in the system. At this maximum pressure, the hydrant pit valve assembly and coupler are required to conform to the performance criteria of this publication. pressure loss: the difference in static pressures measured in the test set-up defined in Figure 6 from point A to point B. proof pressure: the maximum pressure required of the hydrant pit components without external leakage or damage after which the components will meet all other performance requirements. pressure control valve: a control valve that may be located either in the hydrant pit valve assembly or in the hydrant coupler assembly. This valve forms part of the pressure and flow control system delivering fuel to the aircraft. May also be known as a pressure-regulating valve. vacuum test: a negative pressure applied to the hydrant pit valve assembly under which the poppet shall remain closed and not allow leakage of air in the reverse direction. 2.2 ABBREVIATIONS The following abbreviations are used within this publication: ft in. kg kpa kph lbs lbf lpm m mm mph N psi USG USGPM o F o C o feet inch kilogram kilopascal kilometres per hour pounds mass pounds force litres per minute metre millimetre miles per hour Newton pounds per square in. US gallon US gallons per minute degrees Fahrenheit degrees Celsius degree of angle 2.3 UNITS USED This publication uses the Système International d Unités (International System of Units or SI). In this system, the decimal point is a comma (,). In writing numbers of greater than 3 digits, e.g. thousands, tens of thousands etc. a comma may not be used to demarcate the thousands. Thousands are demarcated by the use of a space. Within this publication SI Units are used with US Customary Units following in parentheses. Internationally agreed conversions have been applied to these values. 5

16 FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS 6

17 3 GENERAL ARRANGEMENTS AND FEATURES 3.1 TYPICAL ARRANGEMENT OF HYDRANT PIT EQUIPMENT AND CONTROLS A number of alternative component arrangements are offered, essentially determined by the location of one or more of the controls. The two extremes are shown in Figures 1 and 2. In Figure 1, the controls are in a regulating valve installed inside the coupler. In Figure 2, the controls are in the pit valve assembly. The purchaser shall specify the final component arrangement. The fitting of a separate hydrant riser shut-off valve is not a requirement of this publication. 3.2 MANDATORY REQUIREMENTS Dimensions and hydrant coupler/hydrant pit valve assembly mating The interface dimensions of the outlet adapter of the hydrant pit valve assembly and the hydrant coupler shall be in accordance with Figures 3A and 4A and 3B and 4B (US Customary Units). The sealing surface as indicated on Figures 3A and 3B shall be 1,6 micrometre (63 micro-inches) circular finish maximum. The outlet adapter poppet, including activation of the pressure relief equalising valve, shall allow a coupler poppet travel of 50,8 +1,588/-0,000 mm (2 +0,0625/-0,000 in.) measured from the sealing surface as identified on Figures 3A and 3B. A static seal shall be achieved automatically between the coupler and outlet adapter during the coupling and locking operations and before the adapter is actuated to open. The static seal shall be designed so that it cannot be broken until the outlet adapter and coupler are closed. Leakage in excess of 30 ml (1 fluid ounce) through the static seal shall not occur at any time during the coupling, fuelling, and uncoupling operation, regardless of system pressure. See 4.11 for test details Outlet adapter actuation The opening of the hydrant coupler poppet shall cause the outlet adapter poppet to open. The outlet adapter poppet shall close automatically whenever the coupler is closed or removed. In manual operation, the outlet adapter and hydrant coupler when coupled together shall be capable of being opened and closed by one operator applying a maximum force of 110 N (25 lbf). To function properly, the force shall be applied for a maximum of 5 seconds to hold the equalisation valve open and allow the pressure to equalise on both sides of the outlet adapter poppet. 7

18 FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS Fuel sense Coupler poppet operator Deadman air Hydrant coupler with deadman and pressure control Air to pilot device (if air-operated) Outlet adapter Lanyard attachment point Pilot device and override Hydrant pit valve assembly Hydrant pit box Stoneguard Pit box seal Hydrant riser Figure 1 - Typical arrangement of hydrant pit equipment (deadman and pressure regulating valve in coupler) Coupler poppet operator Standard hydrant coupler Deadman air Fuel sense Outlet adapter Lanyard attachment point Pilot device and override Hydrant pit valve assembly Hydrant pit box Stoneguard Pit box seal Hydrant riser Figure 2 - Typical arrangement of hydrant pit equipment (deadman and pressure regulation in pit valve) 8

19 40,5 BSC 212,725 dia. BSC 6 5 Fixed product selection posts located as shown unnumbered 2 places 4 ±0,127 1, Sealing surface ±0,127 38,100 ±0,127 9,525 ±0,127 6, ,800 +1,588-0,000 Poppet travel from sealing surface Valve head ±0, ,400 ±0, ,350 ±0, ,400 ±1, ,150 9 Fuel/air reference adapter Outer surface of mating fuel/air socket 54 BSC C B G F A Refer to Figure 5A for detail 1 40,5 BSC places BSC Movable product selection posts located as shown; 4,763 mm index numerals shall be permanently located A minimum clearance of 134,62 mm between hydrant pit valve center and fuel sense/air reference adapter coupled with mating socket. (Refer to Figure 5A for more details). 3 6,3 C ±0, ,100 ±0, ,050 ±0, ,600 Sealing surface Pressure equalizing valve Outlet adapter poppet ±1,524 45,974 Product selectivity set bolt (1/2" min. tall, 5/8" max. hex. or dia.) Notes: BSC = basic dimension; min. = minimum; max. = maximum; hex. = hexagonal; dia. = diameter. 1. All dimensions are in millimetres. 2. The breaking of all corners is required, not to exceed 3,175 millimetre radius. 3. The details of adapter body valve head and internals shown in dashed lines are to be determined by manufacturer. 4. Pressure equalizing valve stem on valve head is not to extend beyond sealing surface. 5. Sealing surface must be machined to 1,6 micrometre circular finish. 6. Couplers must be capable of mating with maximum dimensions shown. ±0, ,100 GENERAL ARRANGEMENTS AND FEATURES Figure 3A - API standard hydrant pit outlet adapter, SI measurements

20 40,5 BSC 8,375 dia. BSC 6 5 Fixed product selection posts located as shown unnumbered 2 places 4 ±0,005 0, Sealing surface ±0,005 1,500 ±0,005 0,375 ±0,005 0, ,000 +0, ,000 0 Poppet travel from sealing surface 10 Fuel / air reference adapter Outer surface of mating fuel/air socket 54 BSC C B G F A Refer to Figure 5A for detail 1 40,5 BSC 2 Movable product selection posts located as shown; 3/16 inch index numerals shall be permanently located A minimum clearance of 5,30 in. between hydrant pit valve center and fuel sense/air reference adapter coupled with mating socket. (Refer to Figure 5B for more details) places BSC Notes: 6,3 C ±0,005 6, All dimensions are in inches. ±0,005 6,000 ±0,005 5,750 ±0,005 5,250 ±0,005 4,000 Sealing surface BSC = basic dimension; min. = minimum; max. = maximum; hex. = hexagonal; dia. = diameter. Valve head Pressure equalizing valve Outlet adapter poppet ±0,060 1,81 Product selectivity set bolt (1/2" min. tall, 5/8" max. hex. or dia.) 2. The breaking of all corners is required, not to exceed 0,125 inch radius. 3. The details of adapter body valve head and internals shown in dashed lines are to be determined by manufacturer. 4. Pressure equalizing valve stem on valve head is not to extend beyond sealing surface. 5. Sealing surface must be machined to 63 microinches circular finish. 6. Couplers must be capable of mating with maximum dimensions shown. ±0,005 6,000 ±0,005 6,500 ±0, ,250 FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS Figure 3B - API standard hydrant pit outlet adapter, customary measurements

21 GENERAL ARRANGEMENTS AND FEATURES 264,160 C Coupler max. 259,080 Groove depth ^ G 0,508 D Coupler min. 250,088 Coupler poppet max. diameter 100,5 M 2,032 min. Under pressure P L 2,032 max. ^ Under pressure 1,651 min. At no pressure Seal surface - ref. Product selectivity set bolt (12,700 min. tall, 15,875 max. hex. or dia.) ± 1,524 57,150 min. 45,974 Pressure equalizing valve top surface must not extend beyond sealing surface H Coupler Max. 68,580 H Valve Min. 69,850 D Valve max. 245,008 Outside of coupler including bump ring 264,160 C Valve min. 269,240 Notes: Dimensions are in millimetres; max. = maximum; min. = minimum; ref. = reference; hex. = hexagonal; dia. = diameter. Figure 4A - Outlet adapter and coupler interface dimensions, SI measurements 10,40 C Coupler max. 10,20 Groove depth ^ G 0,020 D Coupler min. 9,846 Coupler poppet max. diameter 3,956 M 0,080 min. Under pressure P L 0,080 max. ^ Under pressure 0,065min. At no pressure Seal surface - ref. Product selectivity set bolt (1/2" min. tall, 5/8" max. hex. or dia.) 2,25 min. ± 0,060 1,81 Pressure equalizing valve top surface must not extend beyond sealing surface H Coupler Max. 2,700 H Valve Min. 2,750 D Valve max. 9,646 Outside of coupler including bump ring 10,40 C Valve min. 10,60 Notes: Dimensions are in inches; max. = maximum; min. = minimum; ref. = reference; hex. = hexagonal; dia. = diameter. Figure 4B - Outlet adapter and coupler interface dimensions, customary measurements 11

22 FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS Coupling action The coupling action shall be of the push type with provision for locking without rotating the coupler body. On systems requiring product selection, rotation of the coupler collar to mate with the appropriate hydrant pit valve assembly product selection device is permitted. The coupling range shall permit coupling to the outlet adapter in any position around the hydrant pit valve assembly, without interference with the hydrant pit walls, apron surface, or components. The hydrant coupler shall incorporate an interlock system to prevent opening of the coupler s poppet (and thus the hydrant pit valve assembly poppet) before being locked in position, and to prevent unlocking and disconnecting before the coupler poppet is closed. The hydrant coupler design shall prevent its ejection in the event of outlet adapter sealing failure or non-closure of the poppet with the pilot device in the open position Hydrant pit arrangement and mounting Hydrant pit components should normally be designed so that they can be installed and maintained in a pit that has a minimum internal diameter of 460 mm (18 in.). However, manufacturers should be aware that some old pit boxes have a diameter as small as mm (12-13 in.) with 100 mm (4 in.), 75 mm (3 in.) or other special riser flanges and may wish to design their valves to be accommodated in these small pit boxes (see Annex B). Hydrant pit components may be installed in a central or offset position within the pit; however, the overall pit box size and component spacing shall permit easy access for operation and maintenance. In the design, allowance shall be made for the operation of levers and switches within the pit using industrial type gloves and without the need for special tools. The arrangement of the pit equipment shall also allow for unobstructed (non-fouling) lanyard operation. Hydrant system riser pipe flanges shall be in accordance with the latest edition of ASME B.16.5, Class 300 pattern for 150 mm (6 in.) flanges and Class 150 for 100 mm (4 in.) flanges. All hydrant pit equipment flanges shall also be in accordance with ASME B.16.5 for assembly compatibility. This applies for stoneguards, pilot-operated valves and the inlet side of the hydrant pit valve assembly. All components shall be as compact as practicable. The overall height of the hydrant pit valve assembly, measured from the face of the inlet flange to the top of the outlet adapter, not including the dust cap, shall be: (a) For valves with either a 100 mm (4 in.) or 150 mm (6 in.) ASME Class 150 inlet flange: 290 mm to 415 mm (11,5 in. to 16,34 in.) (b) For valves with a 150 mm (6 in.) ASME Class 300 pattern inlet flange: 406 mm to 415 mm (16 in. to 16,34 in.) Manufacturers who offer a valve with dimensions shorter than those above should be able to provide spool pieces or adapters to accommodate any difference in the dimensions of the riser flange and the inlet flange of the valve and to bring their valve within the dimensional range in (b) if requested. Note: The dimensions quoted in (b) and the provision for spools and adapters will ensure that valves offered by different manufacturers are freely interchangeable. The pit valve assembly shall be installed within the pit box so that there is a clearance of not more than 100 mm (4 in.) and not less than 75 mm (3 in.) between the hydrant pit valve assembly outlet adapter sealing surface and the top of the hydrant pit box. This setting is necessary to ensure that when a coupler is attached to the pit valve, the underside of the elbow does not touch the top of the pit box. When a hydrant coupler fitted with a carriage assembly is attached to the hydrant pit valve outlet adapter, the carriage assembly shall be clear of the ground when in the folded up position Fuel sense and air reference lines The pressure/flow control and/or excess flow control, if fitted, shall be included either on the hydrant coupler or on the hydrant pit valve assembly. However, as a minimum, there shall be a deadman function installed either on the hydrant pit valve or the hydrant coupler upstream of the inlet hose or boom assembly. Where fitted, these controls shall be provided with air reference, and in the case of pressure/flow control and/or excess flow control, fuel reference pressures, to enable them to function. The connection of the lines to provide such pressures may be permanent (in the case of the hydrant coupler) or may be fitted to either the hydrant pit valve assembly or hydrant coupler by means of a quick coupling. Figures 3A and 3B, 4A and 4B, and 5A and 5B provide the interface dimensions, including product selectivity to ensure complete interchangeability, where both fuel and air lines are required. If used, this accommodation or any other such device shall be located so that it will not interfere with the operation of the other components. 12

23 GENERAL ARRANGEMENTS AND FEATURES An interlock feature capable of prohibiting accidental un-coupling that is compatible with the design shown in Figures 5A and 5B is desirable. On air-operated pilot devices, an air reference pressure line from the hydrant dispenser is required to control the opening and closing of the hydrant pit valve. This connection should be a "quick disconnect" type connection. Any standard, through-flow connection may be used. The self-sealing quick disconnect fitted to the pilot device shall be of the leaky type to ensure that no air is trapped within the pilot after disconnecting the mating half from the hydrant dispenser air system Flow rate Hydrant pit valve assembly The hydrant pit valve assembly shall be designed in accordance with the following rates: (a) rated flow: lpm (1 200 USGPM) (b) catastrophic excess flow: lpm (2 900 USGPM) Hydrant couplers Hydrant couplers shall be designed in accordance with the following rates: (a) for 4 in. inlet by 4 in. outlet (either pressure controlled or standard coupler): lpm (1 200 USGPM) (b) for 4 in. inlet by 3 in. outlet (either pressure controlled or standard coupler): lpm (800 USGPM) Pressure rating Hydrant pit valve assembly The hydrant pit valve assembly shall be designed in accordance with the following pressure ratings, all at 70 EC (158 EF): (a) design pressure: kpa (275 psi) (b) operating pressure: -10 to kpa (-1,5 to 200 psi) (c) proof pressure: kpa (415 psi) minimum (d) burst pressure: kpa (825 psi) minimum Hydrant couplers As the coupler shall be capable of being handled, coupled and uncoupled by one operator, the recommended weight of a coupler in all configurations should be not more than 17 kg (37 lbs). Hydrant couplers, either connected to a hydrant pit valve assembly or disconnected and closed, shall be designed in accordance with the following pressure ratings, all at 70 ºC (158 ºF): (a) design pressure: kpa (275 psi) (b) operating pressure: -10 to kpa (-1,5 to 200 psi) minimum (c) proof pressure: (i) uncoupled, closed: kpa (265 psi) minimum (ii) coupled, open: kpa (415 psi) minimum (d) burst pressure: (i) uncoupled, closed: kpa (400 psi) minimum (ii) coupled, open: kpa (825 psi) minimum Pilot device actuation Manual operation The pilot device shall have two separate actions for opening and closing. The open or close force at maximum operating pressure shall not exceed 110 N (25 lbf). The close actuator shall have a fitting to allow the attachment of a lanyard to achieve the closing function from a remote distance. The fitting and the lanyard shall not be able to foul on any hydrant pit equipment and shall be effective at any angle or direction of pull Air operation The pilot device is operated by the application of an externally supplied air pressure. Control air supply shall be a minimum of 240 kpa (35 psi) to the pilot device to control opening. The application of the air supply shall be via a deadman type valve system on the hydrant dispenser Lanyard connection It shall be possible to connect a lanyard to an airoperated pilot device to enable remote closing of the pilot valve. Note 1: The requirement in applies to those areas where legislation and/or safe practices require a dual operation, for example, if it is envisaged that air may fail to exhaust due to a system failure or restriction resulting from a vehicle collision. It does not apply to those areas where a lanyard has, traditionally, not been used. Note 2: See Annex D for a list of advantages in using air-operated pilot devices. 13

24 6,350 min 43,053 46,101 2,286 3,302 radius 1,524 radius 8,331 basic 11,786 basic 11,278 basic 14 9,525 11,049 23,876 25, Fuel pressure sense ports 1,905-2,108 dia. hole, 6 places equally spaced. All sharp edges to be removed. Radial location optional. Air reference pressure port 1,905-2,108 dia. hole. All sharp edges to be removed. Radial location optional. A 12,598 12,548 dia. 55,626 dia. max. 20,828 basic 14,046 basic 4,674-4,826 dia. 8,89 deep F C B A G 11,684 basic When used, product selector pin 3,150-3,277 dia. extending 6,350 above this surface and identified as shown. Location with respect to any other pin hole optional as long as radial location is maintained. A 0,254 dia. 19,558 basic 22,911 basic FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS Notes: Dimensions are in millimetres; min. = minimum; dia. = diameter; max. = maximum. Figure 5A - API standard fuel sense and air reference lines accommodation for regulating type hydrant valves (valve installation), SI measurements

25 15 0,25 min 0,375 0,435 0,940 1,000 1,695 1,815 0,090 0,13 radius 15 0,06 radius 16 Fuel pressure sense ports 0,075-0,083 dia. hole, 6 places equally spaced. All sharp edges to be removed. Radial location optional. Air reference pressure port 0,075-0,083 dia. hole. All sharp edges to be removed. Radial location optional. A 0,496 0,494 dia. 2,190 dia. max. 0,820 basic 0,328 basic 0,553 basic 0,184-0,190 dia deep F C B G A 0,464 basic 0,444 basic 0,460 basic When used, product selector pin 0,124-0,129 dia. extending 0,25 above this surface and identified as shown. Location with respect to any other pin hole optional as long as radial location is maintained. A 0,010 dia. 0,770 basic 0,902 basic GENERAL ARRANGEMENTS AND FEATURES Notes: Dimensions are in inches; min. = minimum; dia. = diameter; max. = maximum. Figure 5B - API standard fuel sense and air reference lines accommodation for regulating type hydrant valves (valve installation), customary measurements

26 FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS Operating temperature range The hydrant components covered by this publication shall meet all the design requirements within the temperature range of!40 EC to +70 EC (!40 EF to +158 EF) Pilot-operated valve closing and opening times The requirements for opening and closing times are those for carrying out acceptance and approval testing on a test rig. Opening and closing of the pilot-operated valve shall be even and progressive. The method of testing is defined in 4.6. Note: As the design of the hydrant dispenser control system may influence opening and closing times, users should ensure that their systems will achieve these opening and closing times in the field Closing time Pilot-operated valve closure shall be caused by actuation of the lanyard or air-operated pilot device. The valve shall fully close from rated flow within 2 to 5 seconds measured from the time that the closing mechanism is operated until flow ceases Opening time The pilot-operated valve assembly shall open from the fully closed position in normal operation such that the following flow conditions are satisfied. These conditions shall apply for both manual or air pilotoperated control: (a) 90 % of rated flow shall be achieved in not less than 5 seconds and no more than 20 seconds from the time of activation of the opening mechanism. (b) Full (100 %) of rated flow shall be achieved in not more than 30 seconds measured as in (a) Deadman control There is a major difference in the practices observed in some countries, such as the United States of America (USA), and other locations, particularly in European operations. For example, in the USA it is common practice to have the deadman function provided by the air-operated pilot device with an additional, in-line control valve installed in the vehicle pipework. This valve is outside the scope of this publication. Mainly, European practice is to have the deadman control fitted in the hydrant pit coupler with a lanyard operated pit valve pilot device, although air-operated pilots are not excluded. Upon actuation, the deadman control shall open or close a valve, either as a part of the hydrant pit valve assembly or hydrant coupler, or both. The deadman valve performance characteristics shall comply with and If the deadman valve is in the hydrant pit, the deadman valve shall be the pilotoperated valve. A deadman fitted in the hydrant coupler shall open to full flow in not less than 5 seconds and close to no flow in not less than 2 seconds nor more than 5 seconds. Overshoot shall not exceed 200 litres (53 USG) or 5 % of flow in areas where this limit applies. Air supply shall meet the following requirements: (a) For an air-operated deadman valve provided in the hydrant coupler and hydrant pit valve assembly, with the hydrant pit valve assembly equipped also with a lanyard, a common air supply may be provided. (b) For a hydrant pit valve provided with an airoperated deadman but no lanyard and with an airoperated deadman provided in the hydrant coupler, independent air supplies with no common components shall be provided. (c) For an air-operated deadman provided in the hydrant pit valve, with no lanyard attachment and no deadman in the hydrant coupler, a single air supply is satisfactory Overshoot Overshoot during closing of the pilot-operated valve shall not exceed 200 litres (53 USG) at all flow rates up to rated flow. Under catastrophic excess flow conditions, as defined in , overshoot shall not exceed 300 litres (80 USG). Note: In areas where a more stringent overrun limit is imposed, that condition shall apply Pressure loss Hydrant pit valve assembly The pressure loss at rated flow, unless otherwise stated, across a non-regulating hydrant pit valve assembly without an intermediate strainer but with a stoneguard in place, and assembled with a 4 in. straight hose unit in accordance with API RP 1004, shall be as follows from point A to B in Figure 6: 16

27 GENERAL ARRANGEMENTS AND FEATURES (a) for 150 mm (6 in.) inlet valve, with 100 mm (4 in.) inlet by 100 mm (4 in.) outlet coupler kpa (19,6 psi) maximum. (b) for 100 mm (4 in.) inlet valve, with 100 mm (4 in.) inlet by 100 mm (4 in.) outlet coupler kpa (24 psi) maximum. (c) for 150 mm (6 in.) inlet valve, with 100 mm (4 in.) inlet by 75 mm (3 in.) outlet coupler kpa (20 psi) maximum at lpm (800 USGPM) flow. (d) for 100 mm (4 in.) inlet valve, with 100 mm (4 in.) inlet by 75 mm (3 in.) outlet coupler kpa (22 psi) maximum at lpm (800 USGPM) flow Hydrant pit valve assembly with a standard regulating 90E coupler The pressure loss at rated flow across the hydrant pit valve assembly without an intermediate strainer but with a stoneguard in place and assembled with a regulating 90E hydrant coupler (fully open) shall be as follows from point A to B as defined in Figure 6: (a) for 150 mm (6 in.) inlet valve, with 100 mm (4 in.) inlet by 100 mm (4 in.) outlet coupler kpa (28 psi) maximum. (b) for 100 mm (4 in.) inlet valve, with 100 mm (4 in.) inlet by 100 mm (4 in.) outlet coupler kpa (35,5 psi) maximum. (c) for 150 mm (6 in.) inlet valve, with 100 mm (4 in.) inlet by 75 mm (3 in.) outlet coupler kpa (21 psi) maximum at lpm (800 USGPM). (d) for 100 mm (4 in.) inlet valve, with 100 mm (4 in.) inlet by 75 mm (3 in.) outlet coupler kpa (23,5 psi) maximum at lpm (800 USGPM) Pilot-operated valve leakage The allowed leakage downstream of a closed pilotoperated valve, under maximum operating pressure, shall be such that the 'well' (see Figures 4A and 4B, dimension M) formed on the top of the outlet adapter poppet and the upper sealing surface shall not fill in less than one minute with the pressure equalizing valve depressed. Pressure test point A 100 mm (4 in.) or 150 mm (6 in.) pipe Meter Y Pit valve & coupler under test Pump Z 1 m (3 ft) min. 1 m (3 ft) Straight pipe 1 m (3 ft) 100 mm (4 in.) pipe Pressure test point B X Test fluid tank Alternate meter position Note: m = metres; in. = inch; min. = minimum Figure 6 - Schematic of test rig to be used for pressure loss, opening and closing times and overshoot 17

28 FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS Vacuum testing During operation and/or maintenance of a hydrant system, vacuum conditions may occur. The hydrant pit valve assembly, with and without a hydrant coupler attached, shall be designed to withstand a -10 kpa (-1,5 psi) vacuum without admitting air or water into the system. See 4.7 for test details Catastrophic excess flow The lanyard or deadman control shall be designed to cause the pilot-operated valve to close under all normal and abnormal system excess flow rates up to and including lpm (2 900 USGPM). See 4.10 for test details Materials of construction All materials shall be chemically compatible with all aviation turbine fuels. All metal parts in contact with the fuel shall be free of zinc, cadmium, copper, and their alloys; however, an aggregate amount of 3 % maximum may be present as alloying elements. All non-metal gaskets, O-rings, or other seals or elastomers in contact with the fuel are to be made of materials suitable for use with aviation turbine fuels containing up to 30 % volume aromatics, 5 % volume olefins, and 3 % volume naphthalenes. All external surfaces shall be resistant to corrosion caused by atmospheric exposure and water immersion. Note: this could be achieved by using a corrosion resistant material or by applying a suitable coating. Care should be taken in the design of the equipment to reduce failures caused by wear from the equipment being dragged across the apron surface. Anticipated vulnerable points should be protected by wear pads, brackets or guards Serviceability Maintenance requirements of the hydrant pit valve assembly shall be minimal, but the hydrant pit valve shall be designed such that all parts of the assembly, except the pilot-operated valve portion, are removable from the pit for maintenance or replacement of seals. This should be possible without depressurising the hydrant line. In addition, seals and sealing surfaces should be protected from mechanical damage Decoupling spillage Spillage shall be minimal when the coupler is disconnected from the outlet adapter after aircraft fuelling. The limit for spillage into the pit box is no more than 30 ml (1 fluid ounce). See 4.11 for test details Stoneguard A stoneguard of robust construction and with an opening equivalent to 6 mm (¼ in.) mesh, shall be located upstream of the hydrant pit valve assembly. The stoneguard may be a part of, or furnished as a separate item to, the hydrant pit valve assembly. It shall be designed and proved to withstand a flow rate of lpm (2 900 USGPM) without becoming dislodged or deforming to a point where it would become ineffective or would interfere with the closing of the pilot-operated valve. The stoneguard will not receive maintenance or cleaning under normal operating conditions and should be designed accordingly Wear gauges Manufacturers shall provide, for their own hydrant coupler and hydrant pit valve assembly equipment, a simple wear gauge or gauges. The wear gauge(s) shall be suitable for accurate wear measurement on operationally critical faces. It shall be possible to routinely assess wear using the gauge(s) without requiring equipment disassembly. The wear gauges shall be permanently and legibly marked to show to which piece of equipment they apply. Manufacturers should define which parts and accessories require to be checked with these gauges. The results of the wear measurements shall indicate whether closer inspection of individual components is required. Manufacturers shall provide limits of wear beyond which repair is required Pilot device override The hydrant pit valve assembly shall include a manually operated mechanism which, when actuated to the closed position, will cause the pilot-operated valve to close and remain closed until the pilot device override is opened. The actuation of the pilot device override shall be easily 18

29 GENERAL ARRANGEMENTS AND FEATURES operable. Whilst the removal of the adapter and/or pilot device when the hydrant is still under pressure is not recommended, manufacturers shall demonstrate that removal of these components is possible with hydrant inlet pressure up to kpa (200 psi). See 4.8 for test details. Note: The purpose of the pilot device override is to allow limited servicing of the outlet adapter and pilot device sections of the hydrant pit valve assembly, without the removal of the hydrant pit valve assembly from the system or the depressurizing of the upstream hydrant system Dust covers Dust covers shall be provided to protect the outlet of the hydrant pit valve assembly and the inlet of the hydrant coupler from dust, rain, snow, or ice. In the case of the hydrant coupler, the dust cover may be made a permanent part of the hydrant dispenser Reverse flow 3.3 OPTIONAL ITEMS Reverse flow through a hydrant pit valve assembly and hydrant coupler assembly is not recommended. If a manufacturer offers an option for reverse flow capability, the maximum pressure drop from Point B to Point A in Figure 6, for a reverse flow of 750 lpm (200 USGPM) shall be 105 kpa (15 psi) Intermediate strainer It is recommended that an intermediate strainer should not be included in the hydrant pit valve, as debris trapped by the strainer may, on termination of flow, fall into the pilot-operated valve impairing its performance. If a manufacturer offers this option, it should be made of 10 or 20 mesh (2,5 or 1,25 mm) material and shall be mounted such that it is easily removed for cleaning. The strainer shall provide coverage of 100 % of the flow path in which it is mounted Automatic excess flow control If specified by the purchaser, the hydrant pit valve assembly or hydrant coupler shall have a device, or devices, that provides automatic excess flow control at predetermined flow rates. The single position unit should be adjustable over a flow range of from to lpm (845 to USGPM). The dual position unit should be adjustable within two flow ranges. When set in low flow position, it shall cover a flow range from to lpm (580 to 765 USGPM). When set in the high flow position, the flow range shall be from to lpm (845 to USGPM) Secondary breakaway features A secondary means to prevent damage to the pilotoperated valve housing, such as a frangible adapter or a shear section, is permitted. This feature shall not interfere with the ability of the pilot-operated valve assembly to withstand the steady load force of N (9 000 lbf) as required in Product selectivity Product selectivity may be achieved either using the pilot device (if pneumatic), or the hydrant coupler (or both). Outlet adapters and hydrant couplers may have capability of up to six-product selectivity, via either a pilot selectivity device of the type, or equivalent, shown in Figures 3A and 3B and 5A and 5B, or by using coupler selectivity. Coupler selectivity would involve designing the hydrant coupler and outlet adapter to mate uniquely for a particular grade of product only, physically preventing connection of a hydrant coupler which services a different grade of product Pressure control (regulation) If a pressure control (regulating) valve is located within the hydrant coupler or hydrant pit valve assembly, it shall be capable of being adjusted. For all hydrant supply pressures up to the system design pressure, the pressure-regulating valve shall, at any flowrate or inlet pressure, maintain the corresponding control pressure stable and repeatable within +/- 14 kpa (2 psi) Other mechanical means of closing the pilot-operated valve Other mechanical means of causing the closure of the pilot-operated valve, such as detecting the upward movement of the outlet adapter poppet valve, may be offered. Such a device is considered to be an additional safety measure if the coupler is separated from the hydrant pit valve assembly due to impact. Any such device shall not interfere with the normal operation of the hydrant pit valve assembly. 19

EI Specification Four-inch hydrant system components and arrangements. 4th edition

EI Specification Four-inch hydrant system components and arrangements. 4th edition EI Specification 1584 Four-inch hydrant system components and arrangements 4th edition EI SPECIFICATION 1584 FOUR-INCH HYDRANT SYSTEM COMPONENTS AND ARRANGEMENTS 4th edition May 2017 Published by Energy

More information

PART XV Metering Systems SECTION 2 GUIDE TO GAS METERING SYSTEMS

PART XV Metering Systems SECTION 2 GUIDE TO GAS METERING SYSTEMS THE INSTITUTE OF PETROLEUM PETROLEUM MEASUREMENT MANUAL PART XV Metering Systems SECTION 2 GUIDE TO GAS METERING SYSTEMS THE INSTITUTE OF PETROLEUM PETROLEUM MEASUREMENT MANUAL PART XV Metering Systems

More information

INSTITUTE OF PETROLEUM TESTING OF VAPOUR CONTAINMENT ON PETROLEUM ROAD TANKERS

INSTITUTE OF PETROLEUM TESTING OF VAPOUR CONTAINMENT ON PETROLEUM ROAD TANKERS INSTITUTE OF PETROLEUM TESTING OF VAPOUR CONTAINMENT ON PETROLEUM ROAD TANKERS INSTITUTE OF PETROLEUM TESTING OF VAPOUR CONTAINMENT ON PETROLEUM ROAD TANKERS April 2001 Published by The Institute of Petroleum,

More information

A MODEL SYLLABUS FOR THE TRAINING OF TECHNICIANS INVOLVED IN THE EXAMINATION, TESTING, MAINTENANCE AND REPAIR OF PETROLEUM ROAD TANKERS

A MODEL SYLLABUS FOR THE TRAINING OF TECHNICIANS INVOLVED IN THE EXAMINATION, TESTING, MAINTENANCE AND REPAIR OF PETROLEUM ROAD TANKERS A MODEL SYLLABUS FOR THE TRAINING OF TECHNICIANS INVOLVED IN THE EXAMINATION, TESTING, MAINTENANCE AND REPAIR OF PETROLEUM ROAD TANKERS A MODEL SYLLABUS FOR THE TRAINING OF TECHNICIANS INVOLVED IN THE

More information

THE INSTITUTE OF PETROLEUM GUIDELINES FOR THE DESIGN AND PROTECTION OF PRESSURE SYSTEMS TO WITHSTAND SEVERE FIRES

THE INSTITUTE OF PETROLEUM GUIDELINES FOR THE DESIGN AND PROTECTION OF PRESSURE SYSTEMS TO WITHSTAND SEVERE FIRES THE INSTITUTE OF PETROLEUM GUIDELINES FOR THE DESIGN AND PROTECTION OF PRESSURE SYSTEMS TO WITHSTAND SEVERE FIRES THE INSTITUTE OF PETROLEUM GUIDELINES FOR THE DESIGN AND PROTECTION OF PRESSURE SYSTEMS

More information

PETROLEUM MEASUREMENT MANUAL THE PERFORMANCE OF TURBINE METERS IN LOADING GANTRIES - A REVIEW OF PROVING AND TEST DATA

PETROLEUM MEASUREMENT MANUAL THE PERFORMANCE OF TURBINE METERS IN LOADING GANTRIES - A REVIEW OF PROVING AND TEST DATA THE INSTITUTE OF PETROLEUM PETROLEUM MEASUREMENT MANUAL THE PERFORMANCE OF TURBINE METERS IN LOADING GANTRIES - A REVIEW OF PROVING AND TEST DATA Petroleum Measurement Paper No. 9 THE INSTITUTE OF PETROLEUM

More information

Lubricant Service Designations for Automotive Manual Transmissions, Manual Transaxles, and Axles

Lubricant Service Designations for Automotive Manual Transmissions, Manual Transaxles, and Axles Lubricant Service Designations for Automotive Manual Transmissions, Manual Transaxles, and Axles API PUBLICATION 1560 EIGHTH EDITION, 2012 SPECIAL NOTES 1. API PUBLICATIONS NECESSARILY ADDRESS PROBLEMS

More information

*** DRAFT *** Lubricant Service Designations for Automotive Manual Transmissions, Manual Transaxles, and Axles

*** DRAFT *** Lubricant Service Designations for Automotive Manual Transmissions, Manual Transaxles, and Axles *** DRAFT *** Lubricant Service Designations for Automotive Manual Transmissions, Manual Transaxles, and Axles API PUBLICATION 1560 EIGHTH EDITION, 2011 American Petroleum Institute 1220 L Street, Northwest

More information

Hydraulic fluid power Dimensions and requirements of quick-action couplings

Hydraulic fluid power Dimensions and requirements of quick-action couplings INTERNATIONAL STANDARD ISO 7241 First edition 2014-07-15 Hydraulic fluid power Dimensions and requirements of quick-action couplings Transmissions hydrauliques Dimensions et exigences des raccords rapides

More information

Code of practice for petroleum road tanker vapour collection systems and equipment used in unloading operations

Code of practice for petroleum road tanker vapour collection systems and equipment used in unloading operations Code of practice for petroleum road tanker vapour collection systems and equipment used in unloading operations CODE OF PRACTICE FOR PETROLEUM ROAD TANKER VAPOUR COLLECTION SYSTEMS AND EQUIPMENT USED IN

More information

1. All aircraft fueling equipment shall have a Filter/Separator or a Full-Flow Fuel Monitor.

1. All aircraft fueling equipment shall have a Filter/Separator or a Full-Flow Fuel Monitor. No. 401 STANDARD SAFETY PROCEDURES STANDARD EQUIPMENT LIST FOR FUELING VEHICLES OBJECTIVE: To ensure the safety of property and personnel, the following minimum operational/equipment list, for each fueling

More information

Lubricant Service Designations for Automotive Manual Transmissions, Manual Transaxles, and Axles

Lubricant Service Designations for Automotive Manual Transmissions, Manual Transaxles, and Axles Lubricant Service Designations for Automotive Manual Transmissions, Manual Transaxles, and Axles API PUBLICATION 1560 SEVENTH EDITION, JULY 1995 American Petroleum Institute 1220 L Street, Northwest Washington,

More information

Carter Hydrant Pit Valve 4th Edition EI 1584 Model 60554

Carter Hydrant Pit Valve 4th Edition EI 1584 Model 60554 Carter Hydrant Pit Valve 4th Edition EI 1584 Model 60554 Eaton s Carter Model 60554 Hydrant Pit Valve is a family of valves that includes lanyard, air or dual air/lanyard operated pilot valves, with available

More information

INSTITUTE OF PETROLEUM RESEARCH REPORT INVESTIGATION INTO THE EFFECTS OF LUBRICITY ADDITIVES ON THE PERFORMANCE OF FILTER/WATER SEPARATORS

INSTITUTE OF PETROLEUM RESEARCH REPORT INVESTIGATION INTO THE EFFECTS OF LUBRICITY ADDITIVES ON THE PERFORMANCE OF FILTER/WATER SEPARATORS INSTITUTE OF PETROLEUM RESEARCH REPORT INVESTIGATION INTO THE EFFECTS OF LUBRICITY ADDITIVES ON THE PERFORMANCE OF FILTER/WATER SEPARATORS Daniel E. Kadlecek 1 March 2003 1 ExxonMobil Research & Engineering

More information

Hydraulic fluid power Dimensions and requirements for screw-toconnect quick-action couplings for general purpose

Hydraulic fluid power Dimensions and requirements for screw-toconnect quick-action couplings for general purpose INTERNATIONAL STANDARD ISO 14541 First edition 2013-03-15 Hydraulic fluid power Dimensions and requirements for screw-toconnect quick-action couplings for general purpose Transmissions hydrauliques Dimensions

More information

These regulations are created pursuant to and of the Colorado Revised Statutes.

These regulations are created pursuant to and of the Colorado Revised Statutes. DEPARTMENT OF LABOR AND EMPLOYMENT Division of Oil and Public Safety RETAIL NATURAL GAS (CNG/LNG) REGULATIONS 7 CCR 1101-16 [Editor s Notes follow the text of the rules at the end of this CCR Document.]

More information

Large Diameter Steel Flanges

Large Diameter Steel Flanges ASME B16.47-2011 (Revision of ASME B16.47-2006) Large Diameter Steel Flanges NPS 26 Through NPS 60 Metric/Inch Standard AN AMERICAN NATIONAL STANDARD ASME B16.47-2011 (Revision of ASME B16.47-2006) Large

More information

TODO-GAS COUPLINGS TODO-GAS DRY-BREAK COUPLINGS

TODO-GAS COUPLINGS TODO-GAS DRY-BREAK COUPLINGS TODO-GAS COUPLINGS TODO-GAS couplings are specifically designed for the safe transfer of LPG (typically Propane / Butane) in both liquid and vapour phases. The materials of construction and component design

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL SPECIFICATION ISO/TS 19880-1 First edition 2016-07-01 Gaseous hydrogen Fuelling stations Part 1: General requirements Carburant d hydrogène gazeux Stations-service Partie 1: Exigences générales

More information

Metallic Gaskets for Pipe Flanges

Metallic Gaskets for Pipe Flanges ASME B16.20-2012 (Revision of ASME B16.20-2007) Metallic Gaskets for Pipe Flanges Ring-Joint, Spiral-Wound, and Jacketed AN AMERICAN NATIONAL STANDARD ASME B16.20-2012 (Revision of ASME B16.20-2007) Metallic

More information

THE INSTITUTE OF PETROLEUM PROCEDURES FOR THE RECLAIM OF DUTY ON RECOVERED VAPOUR AT DUTY SUSPENDED INSTALLATIONS

THE INSTITUTE OF PETROLEUM PROCEDURES FOR THE RECLAIM OF DUTY ON RECOVERED VAPOUR AT DUTY SUSPENDED INSTALLATIONS THE INSTITUTE OF PETROLEUM PROCEDURES FOR THE RECLAIM OF DUTY ON RECOVERED VAPOUR AT DUTY SUSPENDED INSTALLATIONS THE INSTITUTE OF PETROLEUM PROCEDURES FOR THE RECLAIM OF DUTY ON RECOVERED VAPOUR AT DUTY

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 1179-3 First edition 2007-08-15 Connections for general use and fluid power Ports and stud ends with ISO 228-1 threads with elastomeric or metal-to-metal sealing Part 3: Light-duty

More information

Gas Turbine Aircraft Engines

Gas Turbine Aircraft Engines ASME PTC 55-2013 Gas Turbine Aircraft Engines Performance Test Codes AN AMERICAN NATIONAL STANDARD ASME PTC 55-2013 Gas Turbine Aircraft Engines Performance Test Codes AN AMERICAN NATIONAL STANDARD Two

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 18752 First edition 2006-07-15 Rubber hoses and hose assemblies Wire- or textile-reinforced single-pressure types for hydraulic applications Specification Tuyaux et flexibles

More information

SURFACE VEHICLE RECOMMENDED PRACTICE

SURFACE VEHICLE RECOMMENDED PRACTICE SURFACE VEHICLE RECOMMENDED PRACTICE J1095 Issued 1982-06 Revised 2003-03 REV. MAR2003 Superseding J1095 MAR1995 Spoke Wheels and Hub Fatigue Test Procedures 1. Scope This SAE Recommended Practice provides

More information

ISO INTERNATIONAL STANDARD. Liquid hydrogen Land vehicle fuel tanks. Hydrogène liquide Réservoirs de carburant pour véhicules terrestres

ISO INTERNATIONAL STANDARD. Liquid hydrogen Land vehicle fuel tanks. Hydrogène liquide Réservoirs de carburant pour véhicules terrestres INTERNATIONAL STANDARD ISO 13985 First edition 2006-11-01 Liquid hydrogen Land vehicle fuel tanks Hydrogène liquide Réservoirs de carburant pour véhicules terrestres Reference number ISO 13985:2006(E)

More information

Nic Mason Technical Services Manager Kuwait Petroleum International Aviation Company

Nic Mason Technical Services Manager Kuwait Petroleum International Aviation Company Nic Mason Technical Services Manager Kuwait Petroleum International Aviation Company EI 1584 Hydrant pit valves and couplers EI 1529 Aircraft Fuelling Hoses EI 1584 Third Edition EI 1584 Third Edition

More information

Australian Standard. Uninterruptible power systems (UPS) Part 1.1: General and safety requirements for UPS used in operator access areas

Australian Standard. Uninterruptible power systems (UPS) Part 1.1: General and safety requirements for UPS used in operator access areas AS 62040.1.1 2003 IEC 62040-1-1:2002 IEC 62040-1-1:2002/Corr.1:2002 Reconfirmed 2013 AS 62040.1.1 Australian Standard Uninterruptible power systems (UPS) Part 1.1: General and safety requirements for UPS

More information

Mechanical Trainstop Systems

Mechanical Trainstop Systems Mechanical Trainstop Systems Synopsis This document defines the functional requirements for mechanical trainstop systems and the requirements relating to their use on both track and trains. Signatures

More information

Digital III Fueling Vehicle Control System

Digital III Fueling Vehicle Control System SM64335-2 April 2005 Aerospace Group Conveyance Systems Division Carter Brand Ground Fueling Equipment Applicable additional manuals: SM64335-1 Setup & Calibration User s Manual Digital III Fueling Vehicle

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 1179-2 First edition 2007-08-15 Connections for general use and fluid power Ports and stud ends with ISO 228-1 threads with elastomeric or metal-to-metal sealing Part 2: Heavy-duty

More information

ISO INTERNATIONAL STANDARD. Seal-less rotodynamic pumps Class II Specification

ISO INTERNATIONAL STANDARD. Seal-less rotodynamic pumps Class II Specification INTERNATIONAL STANDARD ISO 15783 First edition 2002-02-01 Seal-less rotodynamic pumps Class II Specification Pompes rotodynamiques sans dispositif d'étanchéité d'arbre Classe II Spécifications Reference

More information

JIG Inspectors Workshop. Teddington September

JIG Inspectors Workshop. Teddington September JIG Inspectors Workshop Teddington September 28 2012 Title of Presentation Here Nic Mason Technical Services Manager Q8 Aviation 2 Equipment Qualification Aircraft fuelling nozzles and hose end regulators

More information

Connections for fluid power and general use Hydraulic couplings for diagnostic purposes. Part 2: Coupling for connection under pressure

Connections for fluid power and general use Hydraulic couplings for diagnostic purposes. Part 2: Coupling for connection under pressure FINAL DRAFT INTERNATIONAL STANDARD ISO/FDIS 15171-2 ISO/TC 131/SC 4 Secretariat: ANSI Voting begins on: 2015-10-20 Voting terminates on: 2015-12-20 Connections for fluid power and general use Hydraulic

More information

ISO INTERNATIONAL STANDARD. Road vehicles Roof load carriers Part 4: Magnetic fixing devices

ISO INTERNATIONAL STANDARD. Road vehicles Roof load carriers Part 4: Magnetic fixing devices INTERNATIONAL STANDARD ISO 11154-4 First edition 2004-10-15 Road vehicles Roof load carriers Part 4: Magnetic fixing devices Véhicules routiers Dispositifs porte-charges de toit Partie 4: Dispositifs à

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD ISO 16924 First edition 2016-12-01 Natural gas fuelling stations LNG stations for fuelling vehicles Stations-service de gaz naturel Stations GNL pour le ravitaillement de véhicules

More information

Australian Standard. Caravan and light trailer towing components. Part 1: Towbars and towing brackets AS

Australian Standard. Caravan and light trailer towing components. Part 1: Towbars and towing brackets AS AS 4177.1 2004 (Incorporating Amendment Nos 1 and 2) AS 4177.1 2004 Australian Standard Caravan and light trailer towing components Part 1: Towbars and towing brackets This Australian Standard was prepared

More information

ISO 2941 INTERNATIONAL STANDARD. Hydraulic fluid power Filter elements Verification of collapse/burst pressure rating

ISO 2941 INTERNATIONAL STANDARD. Hydraulic fluid power Filter elements Verification of collapse/burst pressure rating INTERNATIONAL STANDARD ISO 2941 Second edition 2009-04-01 Hydraulic fluid power Filter elements Verification of collapse/burst pressure rating Transmissions hydrauliques Éléments filtrants Vérification

More information

http://www.sis.se http://www.sis.se http://www.sis.se http://www.sis.se http://www.sis.se Provläsningsexemplar / Preview SVENSK STANDARD SS-ISO 14469-3:2006 Fastställd 2006-08-09 Utgåva 1 Vägfordon Koppling

More information

ISO INTERNATIONAL STANDARD. Road vehicles Brake lining friction materials Product definition and quality assurance

ISO INTERNATIONAL STANDARD. Road vehicles Brake lining friction materials Product definition and quality assurance INTERNATIONAL STANDARD ISO 15484 First edition 2008-08-01 Road vehicles Brake lining friction materials Product definition and quality assurance Véhicules routiers Matériaux de friction pour garnitures

More information

68-253/Issue 1 (DERD 2491) 1 August 1997

68-253/Issue 1 (DERD 2491) 1 August 1997 Ministry of Defence Defence Standard 68-25/Issue 1 (DERD 2491) 1 August 1997 FLUIDS, AVIATION, THRUST AUGMENTATION JOINT SERVICE DESIGNATION: AL-28 AND WTA This Defence Standard supersedes DERD 2491 Issue

More information

Specification for Sealless Horizontal End Suction Centrifugal Pumps for Chemical Process

Specification for Sealless Horizontal End Suction Centrifugal Pumps for Chemical Process ASME B73.3-2015 (Revision of ASME B73.3-2003) Specification for Sealless Horizontal End Suction Centrifugal Pumps for Chemical Process AN AMERICAN NATIONAL STANDARD ASME B73.3-2015 (Revision of ASME B73.3-2003)

More information

Taiwan Bicycle Industry Standard

Taiwan Bicycle Industry Standard TBIS 4210 5:2016 Taiwan Bicycle Industry Standard TBIS 4210-5 First edition 2016.01.01 Cycles Safety requirements for bicycles Part 5: Steering test methods Reference number: TBIS 4210-5:2015 (FDTS) TBIS

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61851-1 First edition 2001-01 Electric vehicle conductive charging system Part 1: General requirements Dispositif de charge conductive pour véhicules électriques Partie 1: Prescriptions

More information

ISO INTERNATIONAL STANDARD. Road vehicles Brake lining friction materials Friction behaviour assessment for automotive brake systems

ISO INTERNATIONAL STANDARD. Road vehicles Brake lining friction materials Friction behaviour assessment for automotive brake systems INTERNATIONAL STANDARD ISO 26867 First edition 2009-07-01 Road vehicles Brake lining friction materials Friction behaviour assessment for automotive brake systems Véhicules routiers Matériaux de friction

More information

NECO Pumping Systems

NECO Pumping Systems INSTALLATION OPERATION & MAINTENANCE INSTRUCTIONS For Your NECO Pumping Systems PACKAGED CIRCULATING SYSTEM THIS COMPLETELY ASSEMBLED, TESTED, PACKAGED CIRCULATING SYSTEM IS OF THE HIGHEST QUALITY AND

More information

ISO INTERNATIONAL STANDARD. Tyres Electrical resistance Test method for measuring electrical resistance of tyres on a test rig

ISO INTERNATIONAL STANDARD. Tyres Electrical resistance Test method for measuring electrical resistance of tyres on a test rig INTERNATIONAL STANDARD ISO 16392 First edition 2007-10-15 Tyres Electrical resistance Test method for measuring electrical resistance of tyres on a test rig Pneumatiques Résistance électrique Méthode d'essai

More information

Road vehicles Spark-plugs and their cylinder head housings Basic characteristics and dimensions

Road vehicles Spark-plugs and their cylinder head housings Basic characteristics and dimensions Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 28741 Second edition 2013-11-15 Road vehicles Spark-plugs and their cylinder head housings Basic characteristics and dimensions Véhicules routiers

More information

Pipe Flanges and Flanged Fittings

Pipe Flanges and Flanged Fittings ASME B16.5-2017 (Revision of ASME B16.5-2013) Pipe Flanges and Flanged Fittings NPS ½ Through NPS 24 Metric/Inch Standard AN AMERICAN NATIONAL STANDARD ASME B16.5-2017 (Revision of ASME B16.5-2013) Pipe

More information

This document is a preview generated by EVS

This document is a preview generated by EVS PUBLICLY AVAILABLE SPECIFICATION ISO/IEC PAS 16898 First edition 2012-12-01 Electrically propelled road vehicles Dimensions and designation of secondary lithium-ion cells Véhicules routiers à propulsion

More information

ISO Earth-moving machinery Wheeled or high-speed rubber-tracked machines Performance requirements and test procedures for brake systems

ISO Earth-moving machinery Wheeled or high-speed rubber-tracked machines Performance requirements and test procedures for brake systems INTERNATIONAL STANDARD ISO 3450 Fourth edition 2011-11-01 Earth-moving machinery Wheeled or high-speed rubber-tracked machines Performance requirements and test procedures for brake systems Engins de terrassement

More information

New Machinery Directive

New Machinery Directive New Machinery Directive Machinery Directive 2006/42/EC Member States to adopt and Publish 29 th June 2008 Directive applies in full 29 th December 2009 This Directive now looks at the lifecycle of the

More information

1004D2/1005E API Bottom Loading Coupler. 1005E Small handles used throughout Europe 1004D

1004D2/1005E API Bottom Loading Coupler. 1005E Small handles used throughout Europe 1004D PART #H32183PA February 2009 1004D2/1005E API Bottom Loading Coupler The 1004D2 is the standard in drip-less bottom loading couplers and a proven performer at major oil terminals worldwide. The 1004D2

More information

TERMINATOR User Manual

TERMINATOR User Manual TERMINATOR User Manual TERMINATOR User Manual Table of Contents Section Page 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Introduction Safety Precautions Features and Benefits Overview of the

More information

European Aviation Safety Agency. European Technical Standard Order. ED Decision 2016/013/R Annex II. Subject: FUEL DRAIN VALVES

European Aviation Safety Agency. European Technical Standard Order. ED Decision 2016/013/R Annex II. Subject: FUEL DRAIN VALVES European Aviation Safety Agency Date: 5.8.2016 European Technical Standard Order Subject: FUEL DRAIN VALVES 1 Applicability This ETSO provides the requirements which Fuel Drain Valves that are designed

More information

Mobile and Locomotive Cranes

Mobile and Locomotive Cranes ASME B30.5-2014 (Revision of ASME B30.5-2011) Mobile and Locomotive Cranes Safety Standard for Cableways, Cranes, Derricks, Hoists, Hooks, Jacks, and Slings AN AMERICAN NATIONAL STANDARD ASME B30.5-2014

More information

ISO 1728 INTERNATIONAL STANDARD. Road vehicles Pneumatic braking connections between motor vehicles and towed vehicles Interchangeability

ISO 1728 INTERNATIONAL STANDARD. Road vehicles Pneumatic braking connections between motor vehicles and towed vehicles Interchangeability INTERNATIONAL STANDARD ISO 1728 Third edition 2006-09-01 Road vehicles Pneumatic braking connections between motor vehicles and towed vehicles Interchangeability Véhicules routiers Liaisons de freinage

More information

Hydraulic fluid power Cylinders Dimensions and tolerances of housings for single-acting piston and rod seals in reciprocating applications

Hydraulic fluid power Cylinders Dimensions and tolerances of housings for single-acting piston and rod seals in reciprocating applications FINAL DRAFT INTERNATIONAL STANDARD ISO/FDIS 5597 ISO/TC 131/SC 7 Secretariat: JISC Voting begins on: 2018 01 29 Voting terminates on: 2018 03 26 Hydraulic fluid power Cylinders Dimensions and tolerances

More information

VAD Variable Area Desuperheaters

VAD Variable Area Desuperheaters Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

CETOP POSITION PAPER PP 07

CETOP POSITION PAPER PP 07 CETOP POSITION PAPER PP 07 MACHINERY DIRECTIVE 2006/42/EC Valid since 26 th May 2010 CETOP General Secretariat Lyoner Straße 18 D-60528 Frankfurt am Main Phone: +49 69 6603 1201 Fax: +49 69 6603 2201 E-mail:

More information

Identification markings for dedicated aviation fuel manufacturing and distribution facilities, airport storage and mobile fuelling equipment

Identification markings for dedicated aviation fuel manufacturing and distribution facilities, airport storage and mobile fuelling equipment API/IP Standard 1542 Identification markings for dedicated aviation fuel manufacturing and distribution facilities, airport storage and mobile fuelling equipment 8th edition An IP Publication Published

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 14635-3 First edition 2005-09-15 Gears FZG test procedures Part 3: FZG test method A/2,8/50 for relative scuffing load-carrying capacity and wear characteristics of semifluid

More information

GUIDELINES FOR UPLIFT OF PETROLEUM PRODUCTS FROM FILLING STATION AND CUSTOMER STORAGE TANKS

GUIDELINES FOR UPLIFT OF PETROLEUM PRODUCTS FROM FILLING STATION AND CUSTOMER STORAGE TANKS GUIDELINES FOR UPLIFT OF PETROLEUM PRODUCTS FROM FILLING STATION AND CUSTOMER STORAGE TANKS GUIDELINES FOR UPLIFT OF PETROLEUM PRODUCTS FROM FILLING STATION AND CUSTOMER STORAGE TANKS 2nd edition January

More information

Australian Standard. Pneumatic fluid power General requirements for systems (ISO 4414:1998, MOD) AS AS 2788

Australian Standard. Pneumatic fluid power General requirements for systems (ISO 4414:1998, MOD) AS AS 2788 AS 2788 2002 AS 2788 Australian Standard Pneumatic fluid power General requirements for systems (ISO 4414:1998, MOD) This Australian Standard was prepared by Committee ME-035, Fluid Power Systems and Components.

More information

ISO INTERNATIONAL STANDARD. Hoists for the transfer of disabled persons Requirements and test methods

ISO INTERNATIONAL STANDARD. Hoists for the transfer of disabled persons Requirements and test methods INTERNATIONAL STANDARD ISO 10535 Second edition 2006-12-15 Hoists for the transfer of disabled persons Requirements and test methods Lève-personnes pour transférer des personnes handicapées Exigences et

More information

ANSI/BIFMA X Desk/Table Products - Tests. American National Standard for Office and Institutional Furnishings

ANSI/BIFMA X Desk/Table Products - Tests. American National Standard for Office and Institutional Furnishings BSR/BIFMA X5.5-201X ANSI/BIFMA X5.5-2014 Desk/Table Products - Tests American National Standard for Office and Institutional Furnishings American National Standard Approval of an American National Standard

More information

PIP REEE003 Guidelines for General Purpose Non-Lubricated Flexible Couplings

PIP REEE003 Guidelines for General Purpose Non-Lubricated Flexible Couplings September 2016 Machinery PIP REEE003 Guidelines for General Purpose Non-Lubricated Flexible Couplings PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry

More information

Electric vehicle charging system

Electric vehicle charging system TECHNICAL REFERENCE (ICS 43.120) TECHNICAL REFERENCE FOR Electric vehicle charging system Published by SPRING Singapore 2 Bukit Merah Central Singapore 159835 SPRING Singapore Website: www.spring.gov.sg

More information

Safety Code for Existing Elevators and Escalators

Safety Code for Existing Elevators and Escalators ASME A17.3-2011 (Revision of ASME A17.3-2008) Safety Code for Existing Elevators and Escalators Includes Requirements for Electric and Hydraulic Elevators and Escalators A N A M E R I C A N N A T I O N

More information

AWRF Associated Wire Rope Fabricators

AWRF Associated Wire Rope Fabricators AWRF Associated Wire Rope Fabricators Recommended Practice and Guideline Disclaimer for version of AWRF Recommended Guideline for Proof Test Procedures for Slings Part I: Alloy Chain Slings Associated

More information

Intermodal Operations Committee

Intermodal Operations Committee for Privately Owned Dry Van and Temperature-Controlled Trailers Operating in Intermodal Service Adopted 2011 Association of American Railroads Safety and Operations 425 Third Street SW Washington, DC 20024

More information

ISO 5700 INTERNATIONAL STANDARD

ISO 5700 INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 5700 Fourth edition 2006-11-15 Tractors for agriculture and forestry Roll-over protective structures (ROPS) Static test method and acceptance conditions Tracteurs agricoles et

More information

ISO 4016 INTERNATIONAL STANDARD. Hexagon head bolts Product grade C. Vis à tête hexagonale partiellement filetées Grade C. Fourth edition

ISO 4016 INTERNATIONAL STANDARD. Hexagon head bolts Product grade C. Vis à tête hexagonale partiellement filetées Grade C. Fourth edition INTERNATIONAL STANDARD ISO 4016 Fourth edition 2011-03-15 Hexagon head bolts Product grade C Vis à tête hexagonale partiellement filetées Grade C Reference number ISO 4016:2011(E) ISO 2011 PDF disclaimer

More information

TYPE-CERTIFICATE DATA SHEET

TYPE-CERTIFICATE DATA SHEET TYPE-CERTIFICATE DATA SHEET EASA.E.060 for RB211 Trent 500 Series Engines Type Certificate Holder 62 Buckingham Gate Westminster London SW1E 6AT United Kingdom For Models: RB211 Trent 553-61 RB211 Trent

More information

ISO INTERNATIONAL STANDARD. Lubricants, industrial oils and related products (Class L) Family X (Greases) Specification

ISO INTERNATIONAL STANDARD. Lubricants, industrial oils and related products (Class L) Family X (Greases) Specification INTERNATIONAL STANDARD ISO 12924 First edition 2010-05-01 Lubricants, industrial oils and related products (Class L) Family X (Greases) Specification Lubrifiants, huiles industrielles et produits connexes

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 1179-3 First edition 2007-08-15 Connections for general use and fluid power Ports and stud ends with ISO 228-1 threads with elastomeric or metal-to-metal sealing Part 3: Light-duty

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD ISO 1179-1 Second edition 2013-11-01 Connections for general use and fluid power Ports and stud ends with ISO 228-1 threads with elastomeric or metal-to-metal sealing Part 1: Threaded

More information

EI Specification Laboratory tests and minimum performance levels for aviation fuel dirt defence filters. 2nd edition

EI Specification Laboratory tests and minimum performance levels for aviation fuel dirt defence filters. 2nd edition EI Specification 1599 Laboratory tests and minimum performance levels for aviation fuel dirt defence filters 2nd edition EI SPECIFICATION 1599 LABORATORY TESTS AND MINIMUM PERFORMANCE LEVELS FOR AVIATION

More information

Part 11: Wheelchairs. Test dummies

Part 11: Wheelchairs. Test dummies INTERNATIONAL STANDARD ISO 7176-11 Second edition 2012-12-01 Wheelchairs Part 11: Test dummies Fauteuils roulants Partie 11: Mannequins d essai Reference number ISO 2012 COPYRIGHT PROTECTED DOCUMENT ISO

More information

SOUTH AFRICAN NATIONAL STANDARD

SOUTH AFRICAN NATIONAL STANDARD ISBN 978-0-626-23806-3 SOUTH AFRICAN NATIONAL STANDARD The handling, storage, distribution and maintenance of liquefied petroleum gas in domestic, commercial and industrial installations Part 4: The transportation

More information

ISO INTERNATIONAL STANDARD. Pneumatic fluid power Cylinders Final examination and acceptance criteria

ISO INTERNATIONAL STANDARD. Pneumatic fluid power Cylinders Final examination and acceptance criteria INTERNATIONAL STANDARD ISO 10099 Second edition 2001-05-01 Pneumatic fluid power Cylinders Final examination and acceptance criteria Transmissions pneumatiques Vérins Critères de réception et de vérification

More information

ISO/TC 131/SC

ISO/TC 131/SC DRAFT INTERNATIONAL STANDARD ISO/DIS 6164 ISO/TC 131/SC 4 Secretariat: ANSI Voting begins on: Voting terminates on: 2016-06-07 2016-08-29 Hydraulic fluid power Four-screw, one-piece square flange connections

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD ISO 13044-2 First edition 2013-08-15 Road vehicles Fully automatic coupling systems 24 V (FACS) for heavy commercial vehicle combinations Part 2: 50 mm fifth wheel couplings Electrical

More information

ISO INTERNATIONAL STANDARD. Mechanical vibration Rotor balancing Part 21: Description and evaluation of balancing machines

ISO INTERNATIONAL STANDARD. Mechanical vibration Rotor balancing Part 21: Description and evaluation of balancing machines INTERNATIONAL STANDARD ISO 21940-21 First edition 2012-07-15 Mechanical vibration Rotor balancing Part 21: Description and evaluation of balancing machines Vibrations mécaniques Équilibrage des rotors

More information

Temperature Life with or without Electrical Load Test Procedure for Electrical Connectors and Sockets

Temperature Life with or without Electrical Load Test Procedure for Electrical Connectors and Sockets ANSI/EIA-364-17B-1999 Approved: April 23, 1999 EIA STANDARD EIA-364-17B TP-17B Temperature Life with or without Electrical Load Test Procedure for Electrical Connectors and Sockets EIA-364-17B (Revision

More information

STANDARD FOR ROLLING SHEET DOORS

STANDARD FOR ROLLING SHEET DOORS DASMA 207-2008 DASMA STANDARD STANDARD FOR ROLLING SHEET DOORS Door & Access Systems Manufacturers Association, International Sponsor: 1300 Sumner Ave Cleveland, Ohio 44115-2851 DASMA 207-2008 DASMA STANDARD

More information

THIS BULLETIN MODIFIES THE A4A BULLETIN , DATED DECEMBER 11, 2017

THIS BULLETIN MODIFIES THE A4A BULLETIN , DATED DECEMBER 11, 2017 Bulletin 2018.1 Update on ATA103 Requirements June 5, 2018 THIS BULLETIN MODIFIES THE A4A BULLETIN 2017.2, DATED DECEMBER 11, 2017 Based on feedback from the industry, A4A is modifying the deadlines for

More information

Maintenance Manual. Hydrant Coupler. F250 Series

Maintenance Manual. Hydrant Coupler. F250 Series Hydrant Coupler F250 Series LIST OF EFFECTIVE PAGES On a revised page, the portion of text or illustrations affected by the change is indicated by a vertical line in the outer margin of the page. When

More information

Herpteraium SECTION VALVES GENERAL

Herpteraium SECTION VALVES GENERAL SECTION 22 05 23 VALVES GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

ISO 8847 INTERNATIONAL STANDARD. Small craft Steering gear Cable and pulley systems. Petits navires Appareils à gouverner Systèmes à drosses et réas

ISO 8847 INTERNATIONAL STANDARD. Small craft Steering gear Cable and pulley systems. Petits navires Appareils à gouverner Systèmes à drosses et réas INTERNATIONAL STANDARD ISO 8847 Second edition 2004-05-01 Small craft Steering gear Cable and pulley systems Petits navires Appareils à gouverner Systèmes à drosses et réas Reference number ISO 8847:2004(E)

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 20918 First edition 2007-10-15 Road vehicles Braking threshold pressures for heavy commercial vehicle combinations with fully pneumatic braking systems Test with roller brake

More information

ENGINEERING STANDARD FOR PROCESS DESIGN OF DOUBLE PIPE HEAT EXCHANGERS ORIGINAL EDITION JULY 1995

ENGINEERING STANDARD FOR PROCESS DESIGN OF DOUBLE PIPE HEAT EXCHANGERS ORIGINAL EDITION JULY 1995 ENGINEERING STANDARD FOR PROCESS DESIGN OF DOUBLE PIPE HEAT EXCHANGERS ORIGINAL EDITION JULY 1995 This standard specification is reviewed and updated by the relevant technical committee on June 2000. The

More information

ISO 1217 INTERNATIONAL STANDARD. Displacement compressors Acceptance tests. Compresseurs volumétriques Essais de réception. Fourth edition

ISO 1217 INTERNATIONAL STANDARD. Displacement compressors Acceptance tests. Compresseurs volumétriques Essais de réception. Fourth edition INTERNATIONAL STANDARD ISO 1217 Fourth edition 2009-07-01 Displacement compressors Acceptance tests Compresseurs volumétriques Essais de réception Reference number ISO 1217:2009(E) ISO 2009 PDF disclaimer

More information

6400 Series Horizontal Loading Valves

6400 Series Horizontal Loading Valves Leading The Way in Fluid Handling Solutions Worldwide 6400 Series Horizontal Loading Valves Document No. H32310PA, Rev. 0 Issue Date: February 19, 2015 Supersedes: September 9, 2013 The OPW Horizontal

More information

ISO/TC 131/SC Pneumatic fluid power Cylinders, kpa (10 bar) series Mounting dimensions of rod-end clevises

ISO/TC 131/SC Pneumatic fluid power Cylinders, kpa (10 bar) series Mounting dimensions of rod-end clevises DRAFT INTERNATIONAL STANDARD ISO/DIS 8140 ISO/TC 131/SC 3 Secretariat: DIN Voting begins on: Voting terminates on: 2017-06-07 2017-08-29 Pneumatic fluid power Cylinders, 1 000 kpa (10 bar) series Mounting

More information

GO Range. Gas-over-Oil Valve Actuators. Redefining Flow Control

GO Range. Gas-over-Oil Valve Actuators. Redefining Flow Control GO Range Gas-over-Oil Valve Actuators Redefining Flow Control Rotork Actuators Quality Controlled Rotork is a global leader in valve actuation technology. We provide a comprehensive range of valve actuators,

More information

Baumann Sanitary Diaphragm Angle and Inline Control Valve

Baumann Sanitary Diaphragm Angle and Inline Control Valve Instruction Manual 84000 Valve Baumann 84000 Sanitary Diaphragm Angle and Inline Control Valve Contents Introduction... 1 Scope of Manual... 1 Safety Precautions... 2 Maintenance... 2 Flow Direction...

More information

ISO INTERNATIONAL STANDARD. Metallic tube connections for fluid power and general use Part 2: 37 flared connectors

ISO INTERNATIONAL STANDARD. Metallic tube connections for fluid power and general use Part 2: 37 flared connectors INTERNATIONAL STANDARD ISO 8434-2 Second edition 2007-09-01 Metallic tube connections for fluid power and general use Part 2: 37 flared connectors Raccordements de tubes métalliques pour transmissions

More information

ENGINEERING STANDARD FOR MACHINERY PIPING

ENGINEERING STANDARD FOR MACHINERY PIPING ENGINEERING STANDARD FOR MACHINERY PIPING CONTENTS : PAGE No. 0. INTRODUCTION... 2 1. SCOPE... 3 2. REFERENCES... 3 3. UNITS... 4 4. PIPING DESIGN FOR MACHINERIES... 4 4.1 General... 4 4.2 Pumps... 5 4.3

More information

Standard Test Method for Pour Point of Petroleum Products (Automatic Air Pressure Method) 1

Standard Test Method for Pour Point of Petroleum Products (Automatic Air Pressure Method) 1 Designation: D 6749 02 An American National Standard Standard Test Method for Pour Point of Petroleum Products (Automatic Air Pressure Method) 1 This standard is issued under the fixed designation D 6749;

More information