FlexPoint AX: Residential and MDU UPS System for NID/NIU/ONTS. Installation Manual Effective: April 2016

Size: px
Start display at page:

Download "FlexPoint AX: Residential and MDU UPS System for NID/NIU/ONTS. Installation Manual Effective: April 2016"

Transcription

1 FlexPoint AX: Residential and MDU UPS System for NID/NIU/ONTS Installation Manual Effective: April 2016

2 Safety Notes Alpha considers customer safety and satisfaction its most important priority. To reduce the risk of injury or death and to ensure continual safe operation of this product, certain information is presented differently in this manual. Alpha tries to adhere to ANSI Z535 and encourages special attention and care to information presented in the following manner. WARNING! GENERAL HAZARD GENERAL HAZARD WARNING provides safety information to PREVENT INJURY OR DEATH to the technician or user. WARNING! ELECTRICAL HAZARD ELECTRICAL HAZARD WARNING provides electrical safety information to PREVENT INJURY OR DEATH to the technician or user. WARNING! FUMES HAZARD FUMES HAZARD WARNING provides fumes safety information to PREVENT INJURY OR DEATH to the technician or user. WARNING! FIRE HAZARD FIRE HAZARD WARNING provides flammability safety information to PREVENT INJURY OR DEATH to the technician or user. There may be multiple warnings associated with the call out. Example: WARNING! ELECTRICAL & FIRE HAZARD This WARNING provides safety information for both Electrical AND Fire Hazards CAUTION! CAUTION provides safety information intended to PREVENT DAMAGE to material or equipment. NOTE: NOTE provides additional information to help complete a specific task or procedure. ATTENTION: ATTENTION provides specific regulatory/code requirements that may affect the placement of equipment and /or installation procedures. The following sections contain important safety information that must be followed during the installation and maintenance of the equipment and batteries. Read all of the instructions before installing or operating the equipment, and save this manual for future reference.

3 FlexPoint TM AX Installation Manual C0-007, Rev. J Effective Date: April by Alpha Technologies, Inc. Disclaimer Images contained in this manual are for illustrative purposes only. These images may not match your installation. Operator is cautioned to review the drawings and illustrations contained in this manual before proceeding. If there are questions regarding the safe operation of this powering system, please contact Alpha Technologies or your nearest Alpha representative. Alpha shall not be held liable for any damage or injury involving its enclosures, power supplies, generators, batteries or other hardware if used or operated in any manner or subject to any condition not consistent with its intended purpose or is installed or operated in an unapproved manner or improperly maintained. Contact Information Sales information and customer service in USA (7AM to 5PM, Pacific Time): Complete technical support in USA (7AM to 5PM, Pacific Time or 24/7 emergency support): Sales information and technical support in Canada: Website:

4 Table of Contents FlexPoint AX Safety Notes Introduction Applications Outdoor Non-UPS Configuration Indoor to Outdoor Non-UPS Configuration Outdoor UPS Configuration Indoor to Outdoor UPS Configuration Specifications System Specifications, Power Supply and Battery Box Safety Fuse Power-Ring Converter Home Converter Ah and 17Ah Battery Modules Installation Installing the Power-Ring Installing the Safety Fuse Power-Ring Converter Installing the Home Converter Installing the Battery Module Installing the AX-12D-BBPS Installing the AX-12D-BBPS Battery Replacement / Maintenance Component Interconnection Cable Input Wiring Output Cable Wiring Alternate connection method for AX-12D BBPS Activation Activating the Safety Fuse Power-Ring Converter Activating the Home Converter System Runtime and Battery Charging Battery Management Frequently Asked Questions Glossary Figures & Tables Fig. 4-1, Interior view, AX-12D-BBPS Fig. 4-2, Front and Rear view, AX-12D-BBPS Fig. 4-3, Input/Output Connection Points...24 Fig. 4-4, Inner Label, AX-12D-BBPS Table 4-1, Pin Out, Battery Module 7-pin connector...24 Fig. 4-5, Rotating the Microboard...25 Fig. 5-1, Power-Ring and BBPS Installation Components...26 Table 5-1, LED Indications...27 Table 5-2, AX-12D-BBPS-7.2 UPS Runtimes as a function of Temperature and Load...28 Table 5-3, AX-12D-BBPS-17 UPS Runtimes as a function of Temperature and Load...28 Table 5-4, Battery Capacity Retention and Charging C0-007, Rev. J (04/2016)

5 FlexPoint AX Safety Notes Review the drawings and illustrations contained in this document before proceeding. If there are any questions regarding the safe installation or operation of the system, contact Alpha Technologies or the nearest Alpha representative. Save this document for future reference. To reduce the risk of injury or death and to ensure the continued safe operation of this product, the following symbols have been placed throughout this manual. Where these symbols appear, use extra care and attention. WARNING! ELECTRICAL HAZARD Electrical shock can kill or seriously injure. AC Meters contain lethal voltages. Only qualified service personnel should perform any installation dealing with meter boxes. CAUTION! Only qualified personnel may service the system. Verify the voltage requirements of the equipment to be protected (load), the AC input voltage to the power supply (line), and the output voltage of the system prior to installation. Verify the utility service panel is equipped with a properly rated circuit breaker for use with this system. When connecting the load, DO NOT exceed the output rating of the power supply. The battery pack, which provides backup power, contains dangerous voltages. Only qualified personnel should inspect or replace batteries. In the event of a short-circuit, batteries present a risk of electrical shock and burns from high current. Observe proper safety precautions. Always wear protective clothing, insulated gloves and eye protection (i.e. safety glasses or a face shield) whenever working with batteries. Always carry a supply of water, such as a water jug, to wash the eyes or skin in the event of exposure to battery electrolyte. ATTENTION: Local codes and ordinances may differ depending on location. If there is any question regarding product installation consult with local codes officers before proceeding C0-007, Rev. J (04/2016) 5

6 FlexPoint AX Safety Information Battery Safety Information WARNING! ELECTRICAL HAZARD Electrical shock can kill or seriously injure. Lead-acid batteries contain dangerous voltages, currents and corrosive material. Battery installation, maintenance, service and replacement must be performed only by authorized personnel. Take the following precautions to help avoid injury: Never assume that an electrical connection or conductor is not energized. Check the circuit with a volt meter with respect to the grounded portion of the enclosure (both AC and DC) prior to any installation or removal procedure. Hazardous electrically live parts inside this unit are energized from batteries even when the AC input power is disconnected. Servicing and connection of batteries shall be performed by, or under the direct supervision of, personnel knowledgeable of batteries and the required safety precautions. Always wear eye protection, rubber gloves, and a protective vest when working near batteries. Remove all metallic objects from hands and neck. Use tools with insulated handles, do not rest any tools on top of batteries. Always replace batteries with those of an identical type and rating. Never install old or untested batteries. Prior to handling the batteries, touch a grounded metal object to dissipate any static charge that may have developed on your body. Use special caution when connecting or adjusting battery cabling. An improperly connected battery cable or an unconnected battery cable can make contact with an unintended surface that can result in arcing, fire, or possible explosion. A battery showing signs of cracking, leaking, or swelling should be replaced immediately by authorized personnel using a battery of identical type and rating. WARNING! CHEMICAL HAZARD Any gelled or liquid emissions from a valve-regulated lead-acid (VRLA) battery contain dilute sulfuric acid, which is harmful to the skin and eyes. Emissions are electrolytic, and are electrically conductive and corrosive. If any battery emission contacts the skin, wash immediately and thoroughly with water. Follow your company s approved chemical exposure procedures. Neutralize any spilled battery emission with the special solution contained in an approved spill kit or with a solution of one pound Bicarbonate of soda to one gallon of water. Report chemical spill using your company s spill reporting structure and seek medical attention if necessary C0-007, Rev. J (04/2016)

7 FlexPoint AX Safety Information Battery Safety Information WARNING! FIRE HAZARD Never charge batteries in a sealed container. All battery compartments must have adequate ventilation to prevent an accumulation of potentially dangerous/explosive gas. CAUTION! Always follow the battery manufacturer s instructions for transportation, installation, storage or maintenance take precedence over these instructions. The following scenarios may create an unsafe and potentially dangerous situation. Inspect batteries at least every 3 months for: Signs of battery cracking, leaking or swelling. The battery should be replaced immediately by authorized personnel using a battery of the identical type and rating. Signs of battery cable damage. Battery cable should be replaced immediately by authorized personnel using replacement parts specified by vendor. Loose battery connection hardware. Refer to battery manufacturer s documentation for the correct torque and connection hardware for the application. Adequate ventilation of the enclosure. Follow the battery manufacturer s approved transportation and storage instructions. Apply battery manufacturer s specified antioxidant compound on all exposed connections. Verify battery terminals and/or exposed connection hardware is not within 2 inches of a conductive surface. Reposition batteries as necessary to maintain adequate clearance. Clean up any electrolyte (battery emission) in accordance with all federal, state, and local regulations or codes. Always replace batteries with those of an identical type and rating. Never install old or untested batteries. Never charge batteries in a sealed container. Each individual battery should have at least 0.5 inches of space between it and all surrounding surfaces to allow for convection cooling. ATTENTION: Spent or damaged batteries are considered environmentally unsafe. Always recycle used batteries or dispose of the batteries in accordance with all federal, state and local regulations. Mechanical Safety Information CAUTION! Keep hands and tools clear of fans. Fans are thermostatically controlled and will turn on automatically. Power supplies can reach extreme temperatures under load. Use caution around sheet metal components and sharp edges. The following sections contain important safety information that must be followed during the installation and maintenance of the equipment and batteries. Read all of the instructions before installing or operating the equipment, and save this manual for future reference C0-007, Rev. J (04/2016) 7

8 1.0 Introduction The FlexPoint AX solution is a simple, modular, cost-effective way to provide local power to Fiber to the Home (FTTH), cable telephony, or other telecom services for Customer Premise Equipment (CPE). The FlexPoint AX system can be configured as a fully accessible outdoor powering solution, or as a partial outdoor system that keeps critical items, including the battery, outside and available to the service technician. ATTENTION: Compatibility Statement -Early Battery Modules with New Power Converters: Early FlexPoint AX 30Watt 17Ah battery modules and new power converters are not compatible and if installed together will result in continuous nuisance AC fail alarms and failed batteries due to an inability to properly charge deeply discharged batteries. New Power Converters must only be used with new 30Watt 17Ah battery modules. New power converters are compatible with early 18Watt 7.2Ah battery modules provided the cable length between the power converter and the battery module is less than 15- feet and the wire gauge is 18AWG or heavier. FlexPoint AX components (outdoor installations) Power-Ring: an electrical utility meter base extender. It fits between an outdoor, subscriber-located electrical utility power meter and the utility meter socket (or base). The Safety Fuse Power-Ring Converter can tap the utility power, either before or after the meter, and comes supplied with the Blanking Plate (see below). 175A Continuous, 240A Rated AX-Power-Ring-A (power tap after meter) AX-Power-Ring-B (power tap before meter) 175A Model Power-Ring Blanking Plate: covers the opening in the Power-Ring when the Safety Fuse Power-Ring Converter is not used. Cover Plate, Meter Adapter, AX18/ C0-007, Rev. J (04/2016)

9 1.0 Introduction Safety Fuse Power-Ring Converter: a modular power converter that slides into the Power-Ring. The Safety Fuse Power-Ring Converter converts 240Vac at the meter to a nominal 12Vdc which feeds either the outdoor battery module, or when a UPS is not required, directly to the subscriber s NID/NIU/ONT. AX30-12D-SFPC (30 Watts) Weight (lb/kg) 1.141/0.52 Dimensions (in/mm) 9.2"H x 6.0"W x 1.75"D/233.7H x 152.4W x 44.5D FlexPoint AX components (indoor installation) Home Converter: An indoor version of the Safety Fuse Power-Ring Converter. It is located inside the subscriber s home and plugs into a standard AC utility outlet to convert the AC voltage into a nominal 12Vdc. Low voltage feeds from the Home Converter to an indoor or outdoor battery module. When the battery module or NID/NIU/ONT is located outside, a cable passes through an exterior wall to connect this product to the outdoor battery module or directly to the subscriber s NID/NIU/ONT. AX30-12D-HC, 120Vin, 15V 30W CR-AX30-12D-HC, 240VIN, 15V 30W, EU Line Cord CR-AX30-12D-HC, 240VIN, 15V 30W, AU Line Cord CR-AX30-12D-HC, 240VIN, 15V 30W, BS1363 Weight (lb/kg) 0.7/0.32 Dimensions (in/mm) 2.75"H x 8.25"W x 1.5"D/70H x 209.6W x 38D Battery Modules: Small plastic clamshell housings for UPS batteries available in two sizes. It is typically located outdoors on the subscriber's residence. The Battery Module connects to either the Safety Fuse Power-Ring Converter or Home Converter and provides 30 Watts of 12V DC power and alarms to the NID/ NIU/ONT. Battery Backup Power Supply (BBPS) w/alarms and LED indicators; supports battery from-40 C/-40 F to 65 C/149 F. AX-12D-BBPS-7.2 (7.2Ah Battery Backup Power Supply) Weight (lb/kg) 1.5/.68 Dimensions: (in/mm) 8.0"H x 9.0"W x 4.0"D/203H x 228W x 102D AX-12D-BBPS-17 (17Ah Battery Backup Power Supply) Weight (lb/kg) 4.5/2.04 Dimensions: (in/mm) 14"H x 9.5"W x 5.0"D/355.6H x 241W x 127D AX-12D-BBPS Ah Battery Backup Power Supply AX-12D-BBPS-17 17Ah Battery Backup Power Supply C0-007, Rev. J (04/2016) 9

10 1.0 Introduction FlexPoint AX components (outdoor installations) UPS Modules (Microprocessor Modules): 30 Watt UPS Module 12Vdc w/alarms and indicators. The FlexPoint AX UPS modules are small microprocessor-based battery management systems providing UPS power to residential and multiple dwelling FTTp optical network terminals (ONT). The UPS modules are comprised of the same electronics as used in the AX-12D-BBPS products without battery and without battery heating. They are used with the three wire FlexPoint AX Home Converter (HC) and Power Converter (PRC). AX-12D-7.2Ah (for 7.2Ah battery) AX-12D-17Ah (for 17Ah battery) AX-12D-7.2Ah UPS Module (wire harness terminated with Fast-On connectors) AX-12D-17Ah UPS Module (wire harness terminated with ring lugs) Batteries (separately ordered and shipped) AX-STDBAT-7 Weight (lb/kg): 5/2.27 (1-year warranty) AX-LONGBAT-7 Weight (lb/kg): 5/2.27 (3-year warranty) AX-STDBAT-17 Weight (lb/kg): 13/5.9 (1-year warranty) AX-STDBAT-7 AX-LONGBAT-7 7.2Ah Battery AX-STDBAT-17 17Ah Battery C0-007, Rev. J (04/2016)

11 2.0 Applications The FlexPoint AX system can be arranged in four basic configurations/applications as shown on the following pages. The cable from the Safety Fuse Power-Ring/Home Converter and the Battery Module is a 3-conductor, multi-conductor cable. The cable from the Battery Module and the NID/NIU/ONT can be a 4-wire to 7-wire cable (depending on NID/NIU/ONT requirements). Refer to the accompanying Notes for information regarding the specified cable lengths. 2.1 Outdoor Non-UPS Configuration Outdoors Cable length under 30' No UPS AX30-12D-SFPC installed in AX-POWER-RING NID/NIU/ONT NID/NIU/ONT 11.6Vdc nominal output voltage Less than 30' of two wire (+, -) cable (See NOTE) 2.2 Indoor to Outdoor Non-UPS Configuration Indoors to Outdoors Cable length under 30' No UPS Indoor 120Vac or 230Vac Outlet 11.6Vdc nominal output voltage NID/NIU/ONT AX18-12-HC Cable through wall 2-conductor Line Cord 8' in length Less than 30' of two wire (+, -) cable (See NOTE) NOTE: Use 14AWG (preferred) to 16AWG (minimum) for the cabling between the Home Converter/ Safety Fuse Power-Ring Converter and NID/NIU/ONT. Use only cable rated for the outdoor environment. The output voltage of the Home Converter or Safety Fuse Power-Ring Converter determines the actual cable length C0-007, Rev. J (04/2016) 11

12 2. Applications 2.3 Outdoor UPS Configuration Outdoors Cable length under 100' UPS required NID/NIU/ONT AX-POWER-RING and AX18-12D-SFPC Assembly installed in meter base AX-12D-BBPS Battery Housing (shown) 11.4Vdc to 16Vdc nominal output voltage Up to 100' of three wire (+, -, and control) cable (See NOTE 2) Less than 10' of cable (+/- and Alarms) (See NOTE 3) 2.4 Indoor to Outdoor UPS Configuration Indoors to Outdoors Cable length under 100' UPS required NID/NIU/ONT Indoor 120Vac outlet AX18-12-HC Vdc output voltage AX-12D-BBPS Battery Housing (shown) Cable through wall 8' in length Up to 100' of three wire (+, -, and control) cable (See NOTE 1) Less than 10' of cable (+/- and Alarms) (See NOTE 2) NOTE: Distance 0' 50' 50' 100' Wire Size #16 AWG #14 AWG 1. Use 14AWG (preferred) to 16AWG (minimum) for the cabling between the Home Converter/ Safety Fuse Power-Ring Converter and battery housing. Use only cable rated for the outdoor environment. The maximum cable length is determined by the maximum output voltage of the Power Converter/Home Converter minus the voltage drop required by the Battery Module to properly charge the battery. 2. Use 18AWG (minimum) stranded cable for the +/- connections, and 18AWG to 22AWG cable for the alarm connections between the battery housing and the NID/NIU/ONT. Use only cable rated for the outdoor environment. The maximum cable length is calculated such that the minimum input voltage of the ONT used in the configuration is less than or equal to the lowest battery voltage (just above battery cutoff) minus the voltage drop of the cable C0-007, Rev. J (04/2016)

13 3.0 Specifications 3.1 System Specifications, Power Supply and Battery Box FlexPoint AX Module Input AX30-12D-SFPC with AX-12D-BBPS-7.2 AX30-12D-HC with AX-12D-BBPS-17 AC Input Voltage (120) N/A 85/132 Selectable (when ordered) AC Input Voltage (230) /264Selectable (when ordered) AC Input Frequency 60Hz 50/60Hz Output DC Output Voltage 10.5V 14.4V 10.5V 14.4V Continuous Output Power 30W at nominal battery float voltage 30W at nominal battery float voltage Maximum Output Power (<10s) 45W (when used in conjunction with Battery Box) 45W (when used in conjunction with Battery Box) Short Circuit Protection Yes Yes Ripple Voltage, Maximum 150mVrms with battery 150mVrms with battery Nominal Efficiency (at 75% max load) 75% 75% Environment Operating Temperature Range -40 F to +113 F/-40 C to +45 C, 0 to 95% humidity -40 F to +149 F/-40 C to +65 C, 0 to 95% humidity Battery Storage: +5 F to +149 F/-15 C to +65 C, 0 to 95% humidity +5 F to +149 F/-15 C to +65 C, 0 to 95% humidity Battery Type Maintenance free, leak-proof, sealed VRLA (valve regulated lead acid) Maintenance free, leak-proof, sealed VRLA (valve regulated lead acid) Recharge time 12 Hours with 24W load 36 Hours with 24W load Status Alarms Local (LED Indicators) Green Steady Output OK Output OK Green Blinking Standby Operation Standby Operation Red Steady Replace Battery Replace Battery Red Blinking Battery Missing/Battery Low Battery Missing/Battery Low Status Alarms Remote AC Fail Output Power drawn from battery Output Power drawn from battery Replace Battery Battery has failed periodic self test Battery has failed periodic self test Battery Missing Battery is disconnected Battery is disconnected Battery Low Indicates battery has 20% remaining runtime available Indicates battery has 20% remaining runtime available Regulatory Approvals Home Converter N/A UL Listed System, FCC Part 15, Class B, EN55022, Class B Power Ring UL RIC UL414 UL Recognized Components Power Ring Converter UL RIC UL Recognized Components Power Ring & Power Ring Converter UL Listed UL SU 2745 N/A Power Ring, Power Ring Converter & Battery UL N/A Battery Box CSA, CENELEC CSA Warranty Electronics 2 years 2 years Battery Standard 1 years 1 years Battery Long Life 3 years 3 years FlexPoint AX UPS Typical Runtimes (minutes) 7.2Ah 17Ah Temperature Temperature F/ C -40/-40-4/-20 77/25 F/ C -40/-40-4/20 77/25 Load (W) Time (Minutes) Load (W) Time (Minutes) N/A C0-007, Rev. J (04/2016) 13

14 3.0 Specifications 3.2 Safety Fuse Power-Ring Converter AX30-12D-SFPC Input Vmin 216 Vmax 254 Frequency 60Hz Frequency Tolerance ±10% Max Current Limit 3.2A Power Factor 0.4 Max Surge Current 10A RMS Protection Fuse, MOV Interface Side Slide Pressured contacts for input power. Surge Resistance UL SU2745 Sec22 Output Voltage Control (for use with battery module) 5Vdc 50mA DC Max Output Power Capability Voltage 30 Watts coninuous at -40 to 55 C 18 Watts Continuous at 65 C 11.6 Vdc nominal (11.4 to 16Vdc auto-adjust if used with battery box) Number of Outputs 1 Startup Overshoot Voltage Frequency Transient Response Ripple Voltage, Maximum <120% of nominal for 0.5s max DC Not to exceed 1s 150mV with battery Nominal Efficiency >75% Output Grounding Short Circuit Protection Overload Protection Interface Enclosure Material Mounting Color Floating, SELV Yes Integral 3 position terminal strip or connector suitable for accepting #12 to 20AWG wire. Plastic Inserted inside a Meter Adapter Gray Cooling Natural Convection Physical Size, approximate (in/ mm) 9.2"H x 6.0"W x 1.75"D/233.7H x 152.4W x 44.5D Weight (lb/kg) 1.141/0.52 Acoustic Noise, All Modes Environmental Temperature UL Rated Not to exceed 50dBA at 1 meter. -40 C to +65 C, unit derate after +55 C Humidity 5% to 95% Altitude Location Reliability Telcordia Reliability Prediction Agency Compliance EMC > 5K feet, derate max. temp by 2 C per additional 1K feet Outdoors, all environmental conditions > 200,000 hours 15% of 50ºC, 2% of 60ºC FCC Part 15, Class B Safety UL C0-007, Rev. J (04/2016)

15 3.0 Specifications 3.3 Home Converter Input Vmin AX30-12D-HC 85/170 Selectable (when ordered) Vmax Frequency 132/264 Selectable (when ordered) 50/60Hz Frequency Tolerance ±10% Acceptable Source Imp. <5% FL equivalent impedance Max Current Limit 1.6A Power Factor.60 Max Surge Current Protection Interface Surge Resistance Output Voltage Control (for use with battery module) Output Power Capability Voltage 10A RMS Fuse, MOV Hard-Wired AC Line Cord IEEE Std. C level C 5Vdc. 5mA DC Max 30W continuous (if used with battery box) 24 W continuous if used in standalone configuration) 12Vdc Nominal Number of Outputs 1 Startup Overshoot Voltage Frequency Transient Response Ripple Voltage, Maximum <120% of nominal for 0.5s max DC Not to exceed 1s 500mV w/o battery, 150mV with battery Nominal Efficiency 75% Output Grounding Short Circuit Protection Overload Protection Interface Enclosure Material Mounting Color Cooling Physical Size, approximate (in/mm) Floating, SELV Electronic Integral 3 position terminal strip or connector suitable for accepting #12 to 20AWG wire. Plastic Wall-mount Gray Natural Convection 2" H x 3" W x 8.5" D/ 51H x 76W x 216D Weight (lb/kg) 1/.45 Acoustic Noise, All Modes Environmental Temperature UL Rated: Not to exceed 50dBA at 1 meter. -40 C to W load Humidity 5% to 95% Altitude Location Reliability Telcordia Reliability Prediction: Agency Compliance EMC Safety: Mark Standard CENELEC > 5K feet, derate max. temp by 2 C per additional 1K feet Indoors, semi-protected, non-water-dripping environment > 200,000 hours FCC Part 15, Class B USR, CNR UL60950 EN55022 Class B and EN50082 Class B ROHS C0-007, Rev. J (04/2016) 15

16 3.0 Specifications Ah and 17Ah Battery Modules Input Voltage Interface Output These specifications apply to configurations incorporating 30W Home Converters and Power Converters. Power Capability AX-12D-BBPS-7.2 DC input from Power-Ring or Home Converter (See Section "2.0 Applications" for maximum length of interconnecting wire) 3 position terminal strip or connector suitable for accepting #14 to #20AWG wire. 30W continuous 45W max. (<10s) AX-12D-BBPS-17 DC input from Power-Ring or Home Converter (See Section "2.0 Applications" for maximum length of interconnecting wire) 3 position terminal strip or connector suitable for accepting #14 to #20AWG wire 30W continuous (see Note 1) 45W max., <10s Voltage 10.5 to 14.4Vdc 10.5 to 14.4Vdc Number of Outputs 1 1 Frequency DC DC Transient Response Not to exceed 1s Not to exceed 1s Ripple Voltage, Maximum 150mV 150mV Nominal System Efficiency 77% >77% Output Grounding Floating, SELV Floating, SELV Short Circuit Protection Electronic Electronic Overload Protection Integral Integral Interface Charging 7 position terminal strip or connector suitable for accepting #18 to 22AWG wire carrying 12V and PacketCable alarms 7 position terminal strip or connector suitable for accepting #18 to 22AWG wire carrying 12V and PacketCable alarms Voltage 12Vdc nominal 12Vdc nominal Charge Current 1.8A maximum Unlimited within the power supply rating Typical Recharge Time Watt load Watt load <36 24 Watt load Charge Voltage Temp. Comp. Range -10 C to +40 C (14ºF to 104ºF) -10 C to +40 C (14ºF to 104ºF) Charge Compensation Voltage 20mV/ C 20mV/ C Charge Voltage, Float 25 C (77ºF) 25 C (77ºF) Charge Voltage, Accept 25 C (77ºF) 25 C (77ºF) EOD Voltage before battery disconnection Less than or equal to 10.5 Vdc for a minimum of 5s Less than or equal to 10.5 Vdc for a minimum of 5s Quiescent Current < 5mA after EOD < 5mA after EOD Battery Grounding Float, SELV Float, SELV Battery Type AGM Valve-Regulated Lead Acid AGM Valve-Regulated Lead Acid Battery Capacity 7.2Ah 17Ah Quantity 1 1 Battery Heater Integral operation to -40 C Integral operation to -40 C Alarms Packet Cable AC Line Fail, No Battery, Replace Battery, Low/missing Battery, Replace Battery (all signals isolated from output) AC Line Fail, No Battery, Replace Battery, Low/missing Battery, Replace Battery (all signals isolated from output) LEDs Above alarm conditions indicated by LEDs Above alarm conditions indicated by LEDs Note 1: Due to the temperature differences between indoor and outdoor devices, Alpha recommends a maximum continuous load of 24W if an indoor home converter (AX30-12-HC) is used with a battery module located outside C0-007, Rev. J (04/2016)

17 3.0 Specifications Ah and 17Ah Battery Modules, continued These specifications apply to configurations incorporating 18W, and 30W Home Converters and Power Converters. Enclosure AX-12D-BBPS-7.2 AX-12D-BBPS-17 Material, Color Plastic, Gray Plastic, Gray Mounting Wall-mount Wall-mount Cooling Natural Convection Natural Convection Physical Size, approximate (in/mm) 9" W x 8" H x 4" D/228.6W x 203H x 102D 10" W x 14" H x 5" D/254W x 355.6H x 127D Weight without battery (lb/kg) 1.5/ /2.04 Weight with battery (lb/kg) 6.5/ /7.94 Acoustic Noise, All Modes Not to exceed 50dBA at 1 meter. Not to exceed 50dBA at 1 meter. Environmental Designed to Temperature -40 C to 65 C (-40ºF to 149ºF) -40 C to 65 C (-40ºF to 149ºF) UL-rated -40 C to +63 C (-40ºF to 18W load -40 C to +63 C (-40ºF to 18W load Humidity 5% to 95% 5% to 95% Altitude > 5K feet, derate max. temp by 2 C per additional 1K feet > 5K feet, derate max. temp by 2 C per additional 1K feet Location Outdoors, all environmental conditions Outdoors, all environmental conditions Reliability Telcordia Reliability Prediction 200,000 hours (System Rating) > 200,000 hours (System Rating) Agency Compliance (Battery Box) EMC FCC Part 15, Class B FCC Part 15, Class B Safety: Mark USR, CNR UL/CUL Standard UL60950 ROHS UL60950 ROHS C0-007, Rev. J (04/2016) 17

18 4.0 Installation 4.1 Installing the Power-Ring ATTENTION: You MUST secure utility permission and/or assistance prior to installing FlexPoint AX. WARNING! ELECTRICAL HAZARD Wear electrically insulating gloves! Removing and reinstalling the meter will open and close the meter s live 240Vac (non-fused) terminals during the following procedure. Arcing may occur. CAUTION! Adhere to your power utility s safety procedures. Incorrect installation can result in personal injury or damage to equipment. NOTE: 1. Remove security band from meter base or lift cover plate if meter has a ringless base. 2. Carefully pull the meter from its base and set it safely aside. 3. With the Blanking Plate in the 6 o'clock position (aiming toward the ground), firmly push the the Power Ring in to the meter base. Ringless meter bases may need to have the cover installed at this time. 4. If you are not installing the Safety Fuse Power-Ring Converter at this time, ensure the Blanking Plate is securely snapped in at the bottom of Power-Ring. 5. Correctly orient the meter over the Power-Ring and firmly push it into the Power-Ring. 6. Attach security bands between the meter and Power-Ring, and Power-Ring and meter box (or close cover plate). 7. Attach security tags to security bands, if required. Install the Power-Ring along with meter installation or any time thereafter. The Safety Fuse Power-Ring Converter can be installed now, or at a later date. Equipment AX-POWER-RING-A (power tap after meter) -OR- AX-POWER-RING-B (power tap before meter) Tools & Supplies 0.100" Jeweler s Screwdriver Security Ring Blanking Plate Cable Ties Security Tag C0-007, Rev. J (04/2016)

19 4.0 Installation 4.2 Installing the Safety Fuse Power-Ring Converter NOTE: Prior to powering the converter, verify that the NIU/NID is properly grounded and connected to either the 12V Lead (pin 2) of the battery module, pin 3 of the Safety Fuse Power-Ring Convertor or pin 1 of the Home Converter. The FlexPoint AX does not make contact with Earth Ground through the meter socket; Earth Ground is provided by connection to the NIU/NID. Prior to connection to the NIU/NID Earth Ground, the FlexPoint AX output floats and may have enough leakage current to cause any one of the output leads to measure high voltage with reference to Earth Ground. The energy represented by the high voltage does not represent a safety hazard, but may cause a slight undesirable tingling sensation. CAUTION! Improperly connecting these wires will result in equipment damage or non-operation of the unit. NOTE: The converter can be installed at the same time as the Power-Ring, or at a later date. Refer to NOTE in Section 2 on wire size and distance. 1. Loosen the screw from the rear left side base of the Safety Fuse Power-Ring Converter and remove the cover plate from the front of the Safety Fuse Power-Ring Converter. 2. Remove the keyed, 3-pin plug from the base of the converter. 3. Strip 1/4" from the cable wire ends. Minimize the gap between the outer jacket of the cable and the end of the insulation for each individual wire. Connect the cable from the Power-Ring into the 3-pin plug in the following order: + c Pin 3 ( ) - Pin 1, Output Negative (+) - Pin 2, Output Positive Minimize Gap (C) - Pin 3, Control (BBPS) 4. Tighten the plug screws with a 0.100" jeweler s screwdriver. To reduce the potential for a short circuit, verify no bare wire is showing, or loose strands of wire are present between the cables. 5. Insert plug into socket. For strain relief, loop a cable tie around the wire and trim excess. Replace cover and resecure with screw removed in step 1. CableTie C0-007, Rev. J (04/2016) 19

20 4.0 Installation 4.2 Installing the Safety Fuse Power-Ring Converter, continued 5. Use flat-bladed screwdriver to remove blanking plate from the Safety Fuse Power-Ring. 6. Insert AX-30 module into meter base. The module will lock into place when fully inserted. Blanking Plate Insert screwdriver here, twist to remove plate AX-30 NOTE: If. the Safety Fuse Power-Ring Converter is part of an Outdoor Non-UPS configuration, proceed to Section 6.1, Activating the Safety Fuse Power-Ring Converter. Otherwise, continue to Section 5.0, Installing the Battery Module. 4.3 Installing the Home Converter NOTE: Refer to the NOTE in Section 2.0, Applications for wire size and distance. 1. Mount the Home Converter horizontally in a convenient interior location near an AC outlet, using two (2) 8-32 pan head screws (for placement over studs) or Molly bolts (for mounting on drywall) long enough to support a 1-lb. unit. + c Pin 3 2. Strip 1/4" from the cable wire ends. Connect the cable from the Power-Ring into the 3-pin plug in the following order: Minimize Gap Pin 1, Output Negative (-), Pin 2, Output Positive (+), Pin 3, Control (BBPS). Tighten the plug screws with a 0.100" jeweler s screwdriver. To reduce the potential for a short circuit, verify no bare wire is showing, or loose strands of wire are present between the cables. 3. Verify orientation of plug and snap the 3-pin plug into the Home Converter. Do not force the plug into the converter. Strain Relief 4. Use a cable tie as a strain relief as shown to the left. Tighten the cable tie and trim the excess. NOTE: If the Home Converter is part of an Indoor to Outdoor Non-UPS configuration, proceed to Section 5.2, Activating the Home Converter" C0-007, Rev. J (04/2016)

21 4.0 Installation 4.4 Installing the Battery Module NOTE: Installing the AX-12D-BBPS-17 The battery module enables the FlexPoint AX system to be configured as an outdoor UPS, or as an Indoor-to-Outdoor UPS system. The cable length between the Battery Module and Power Ring Converter must be 100 feet or less. The cable length between the Battery Module and NID/NIU/ ONT should be less than 10 feet. Refer to the NOTE in Section 2.0, Applications for wire size and distance. 1. Select Battery Module installation location. 2. Remove module door and drill mounting holes as indicated for customer-supplied # 12 mounting hardware (wood screws or Molly-bolts as needed) and secure. For seismic compliance the unit must be mounted to wall studs. 3. Install 12V, 17Ahr battery with the terminals facing out (do not connect battery at this time). 4. Determine the necessary cable lengths to provide appropriate drip loops from the Power-Ring or Home Converter assembly to Battery Module and from Battery Module to NID/NIU/ONT. 5. Pierce the Battery Module s rubber gasket and insert both the converter cable and NID/NIU/ONT cable ends through the gasket " " LED indications, unit installation label 4 Cable port input from HC/PRC 2 Model information label 5 Cable port output to NID/NIU/ONT 3 Battery shelf 6 UPS module input/output voltages, alarms Fig. 4-1, Interior view, AX-12D-BBPS C0-007, Rev. J (04/2016) 21

22 4.0 Installation 4.4 Installing the Battery Module, continued Installing the AX-12D-BBPS Select a location to install the Battery Module. 2. Determine the necessary cable lengths, providing appropriate drip loops between the HC/PRC, AX, and NIU/NID/ONT. 3. Route the Home Converter/Power Ring Converter cable in from the rear through either the side or bottom slot, around the strain relief, and up through the larger access hole. 4. Mount the BBPS horizontally with two customer-supplied #12 x 2" wood or drywall screws. Direct attachment to a stud is required Battery Compartment 8 Battery Wiring Harness (removable) 2 Battery Retaining Strap 9 Tab for Locking Door 3 Battery Locking Clip 10 Mounting Holes for Customer-supplied # 12 Hardware 4 Battery Heater (beneath shelf) 11 Cable to ONT 5 Cable to HC or PRC 12 HC or PRC Cable Entry 6 Cable to NID/NIU/ONT 13 Cable Entry 7 Input, Output Connection Points on Microboard 14 Strain Relief Fig. 4-2, Front and Rear view, AX-12D-BBPS C0-007, Rev. J (04/2016)

23 4.0 Installation 4.4 Installing the Battery Module, continued Battery Replacement / Maintenance WARNING! ELECTRICAL HAZARD Risk of explosion if battery is replaced by an incorrect type. Dispose of batteries according to the instructions. 1. Remove (if present) the security tag from the BBPS Locking Tab. 2. Loosen the lower right screw and remove the battery module door. 3. Check the LEDs on the Battery Module. The LED Status should be solid red indicating the need to replace the battery. Table 5-1 shows a complete list of LED Status indications. 4. Open the velcro cinch strap around the battery. Disconnect the two pin connector from the BBPS back wall connector. 5. Locate the battery wire kit. Disconnect the black wire from the black battery tab (-) and the red wire from the red battery tab (+). 6. Wait for the LED to change from solid red to blinking red indicating that the battery is missing. 7. Install the replacement battery following the instructions found on the inside of the battery module door. 8. Ensure the wire ends in the 7-wire connector (Fig. 4-3) are secure. If necessary, tighten the connector screws with a.100" jeweler's screwdriver. Torque the terminal block screws to 1.7inlb. Torquing past this specification can damage the wires and connector. 9. The LED Status should be solid green indicating a charged battery has been installed. 10. To verify that the backup battery is functioning properly, disconnect the cable from the HC or PRC. The LED Status should be blinking green indicating Standby Operation / AC Fail. 11. Reconnect the cable to the HC or PRC. The LED should change from blinking green to solid green. 12. Replace the battery module door and secure it with the lower right screw C0-007, Rev. J (04/2016) 23

24 4.0 Installation 4.5 Component Interconnection CAUTION! Incorrectly connecting these wires will result in non-operation of the unit or cause equipment damage Cable Input Wiring Locator Pin 1. Ensure Power Ring Converter/Home Converter is disconnected from AC power, then strip all input wire ends 1/4". 2. Connect the input cable from the Power- Ring/Home Converter into the 3-pin "Input 12Vdc" plug in the following order: Pin 1 Pin 1 Pin 1, white (negative) Pin 2, black (positive) Pin 3, green (control). Tighten the plug screws with a 0.100" jeweler s screwdriver Output Cable Wiring 1. Strip 1/4" from the output cable wire ends. 2. Install wire ends in 7-wire connector (Fig. 4-3), Tighten connector screws with.100" jeweler's screwdriver. 3. Press connector onto "Output 12Vdc" header. The locator pin prevents misalignment of the connector. The connector pins are labeled with their function. Refer to the specific instructions from the ONT supplier to determine what alarms are accepted from the BBPS to the ONT. 4. Connect the ONT cable according to ONT manufacturer instructions. 5. Once the connections are complete, the battery may be connected to the system. The Green Status LED should light indicating a charged battery has been installed. Table 5-1 shows a complete list of LED Status indications. Status LEDs Input from PRC or HC Input 12VDC CNTRL Output 12VDC ALARM RETURN AC FAIL REPLACE BATT Fig. 4-3, Input/Output Connection Points Pin Function 1 POS (+) 2 NEG (-) 3 TEL COMM 4 AC FAIL 5 REPL BATT 6 BATT MISS 7 BATT LOW Output to NID/NIU/ONT Table 4-1, Pin Out, Battery Module 7-pin connector BATT MISSING BATTERY LOW 6. Secure the battery and replace the battery module door. Fig. 4-4, Inner Label, AX-12D-BBPS C0-007, Rev. J (04/2016)

25 4.0 Installation Alternate connection method for AX-12D BBPS-17 It may be necessary to pivot the microboard assembly slightly to facilitate the installation or replacement of the input and output cables (Applicable to either the AX-12D-BBPS-7.2, or AX 12D-BBPS-17 models). Alternate connection procedure: 1. Disconnect one lead from the battery to assure power to the load is removed. 2. Verify power to load is not currently supplied by the battery. 3. Disconnect one leg of the battery. 4. Loosen the upper mounting screw. 5. Remove the lower mounting screw. 6. Rotate microboard for ease of access. 7. Make necessary connections/repair to input and/or output cables. 8. Return microboard assembly to original position, replace hardware. 9. Reconnect battery. 10. Replace Battery Module Cover. Loosen Remove Fig. 4-5, Rotating the Microboard C0-007, Rev. J (04/2016) 25

26 5.0 Activation 5.1 Activating the Safety Fuse Power-Ring Converter You MUST secure the power utility s permission and/or assistance prior to installing FlexPoint AX. Adhere to your power utility s safety procedures. Poor installation can result in personal injury or damage to equipment. 1. Remove the security band (and tag, if present) from the meter. 2. Remove the Blanking Plate from the Power-Ring by inserting a slotted screwdriver tip into a slot located on either side of the Blanking Plate. Slowly twist the screwdriver to lift the Blanking Plate from the Power-Ring. Set the Blanking Plate aside. 3. Insert the Safety Fuse Power-Ring Converter through the Power-Ring base. Ensure the converter clicks into place. 4. Check the LEDs on the Battery Module or NID/NIU/ONT to ensure the Safety Fuse Power-Ring Converter and cable are correctly installed. If the Battery Module or NID/NIU/ONT is not receiving power check the wire connections and/or replace the Safety Fuse Power-Ring Converter. 5. Replace the security band on the meter. You can attach a security tag through the band and the small flange extending from the side of the converter. 6. Close the Battery Module and attach a security tag Security Band 4 AX30-12D-SFPC Power-Ring Converter 2 Security Tag 5 Cable to ONT 3 Blanking Plate 6 BBPS Locking Tab Fig. 5-1, Power-Ring and BBPS Installation Components C0-007, Rev. J (04/2016)

27 5.0 Activation 5.2 Activating the Home Converter 1. Plug the Home Converter into the AC outlet. 2. Check the LEDs on the Battery Module or NID/NIU/ONT to ensure the Home Converter and cable are correctly installed. If the Battery Module or NID/NIU/ONT is not receiving power, check the wire connections and/or replace the Home Converter. The table below provides operation information. Condition Status LED Status Connector Description Normal Green solid Red off Pins 4, 5, 6, 7 are pulled down to Pin 3. All conditions normal. AC powers load, charges battery. Battery is connected and in good condition. AC Fail Green blinking Pin 4 is in open collector state The FlexPoint AX system sets an alarm during an AC line outage or brownout and if the AC supply voltage is insufficient to maintain battery charge. In order to prevent nuisance alarms and consequent service disruptions, the FlexPoint AX system monitors the battery status and sets the alarm when the battery is discharging. Depending on load conditions, this may take a few minutes. Conversely, the alarm is cleared when the battery again receives consistent charge. Please note that this algorithm will also indicate an alarm when AC is present, but the system is overloaded to the point where the battery is required to supplement the power supply to satisfy the load current requirement. If an AC fail alarm is indicated despite a solid AC line voltage, check if the load is within specification and if the lead lengths and wire sizes are per the table in the installation instructions. Replace Battery Red solid Pin 5 is in open collector state The unit will automatically initiate battery test approx. 30 days after last significant battery discharge (>10% of full energy charge). The test lasts <30 mins. System notifies for battery replacement if voltage changes excessively during test. Battery Missing Red blinking Pin 6 is in open collector state. Approx. 20 secs after battery removal, system detects for battery, and repeats every 20 secs, to verify battery disconnection. After 5 seconds, system initiates Battery Missing alarm and maintains this state until a valid battery (open circuit voltage >12.3V) is reconnected to the system. Battery Low Red blinking Pin 7 is in open collector state If battery voltage <11V ±100mV >5 secs, system initiates Battery Low alarm. Overload Green-Red blinking This system is in overload, >120% of rated load. Table 5-1, LED Indications C0-007, Rev. J (04/2016) 27

28 5.0 Activation 5.3 System Runtime and Battery Charging The tables below show typical UPS runtimes in minutes as a function of temperature and load and battery charging capacity retention ratio as a function of storage time and temperature. UPS Runtimes -40 F/ F/ F/25 C LOAD (W) Table 5-2, AX-12D-BBPS-7.2 UPS Runtimes as a function of Temperature and Load UPS Runtimes -40 C/ F/ F/25 C LOAD (W) Table 5-3, AX-12D-BBPS-17 UPS Runtimes as a function of Temperature and Load C0-007, Rev. J (04/2016)

29 5.0 Activation 5.4 Battery Management Batteries have limited shelf life and must be put into service in a timely manner. The chart below provides general storage guidelines and illustrates the relationship between capacity retention and storage temperature over time. Consult battery documentation for product specific information. Capacity Retention Ratio % 100% 80% 60% 40% 40 C (104 F) 30 C (86 F) 25 C (77 F) 5 C (41 F) No supplementary charge required. (Carry out supplementary battery charge before use if 100% capacity is required). Supplementary charge required before use. This charge will help recover the capacity and should be made as early as possible. Supplementary charge may often fail to recover the capacity. The battery should never be left standing till this state is reached Supplementary charge and storage guidelines Storage Period (Months) Table 5-4, Battery Capacity Retention and Charging C0-007, Rev. J (04/2016) 29

30 6.0 Frequently Asked Questions 1. What would happen to the FlexPoint AX if the 3rd pin on the Home Converter connector or the 1st pin on the Safety Fuse Power Converter connector was turned 180 degrees around and plugged in? While the unit would not power the load properly, no damage would occur. The system will work properly once the connection is corrected. 2. What would happen if the positive and negative leads going to the batteries were reversed (i.e., pin 1 & 2 of the three pin connector on Home Converter or pin 2 and 3 on Safety Fuse Power- Ring Converter)? The design features reversed battery protection. Battery back up is not available but no damage will occur. 3. How long does it take to recharge a battery back to 90% charge after the unit reaches Low Voltage Disconnect (LVD) value of 10.5V? hours under typical load. 4. How long must a battery be charged via trickle charge to reach 100% capacity? 24hrs to 100% capacity. 5. Does this unit have temperature compensation in the design? If so, what is the Voltage Per Cell (VPRC) voltage? It does, at a rate of -3.3mV/cell/ C or 19.8mV/battery/C from 0 C to +40 C. Maximum charged voltage is 14.4V and minimum is 13.3V. 6. If I replace a battery when the replace battery LED is illuminated, why does the LED not go out? Will the alarm reset itself? When replacing a battery, it is necessary to wait approximately 20 seconds and allow the "Replace Battery" LED to change from steady to blinking. Once the LED blinks, the fully-charged replacement battery can be connected. The LED will go out, indicating the alarm has been cleared, and the system will begin normal operation C0-007, Rev. J (04/2016)

31 6.0 Frequently Asked Questions 7. If I replace a battery under a no alarm condition and the battery voltage was 12.6Vdc, and an outage occurs and the battery voltage drops to less than 12.2Vdc, will this cause a replace battery alarm, or will the unit try to recharge that battery until the next 40 day test? No, the replace battery indicator will only be activated during the self test routine. Under normal operation, including power failure, the alarm is not activated. Under these conditions the unit will try to recharge the battery until the next self test. 8. Does the charger disconnect or ramp back when a replace battery alarm is illuminated? If not, how does the unit prevent batteries from being cooked, which may cause a gas build up inside the enclosure? No. It will continue to charge the battery to the safe level per the battery manufacturer's specifications. The enclosure provides adequate venting and minimal volume to keep gas build-up from becoming a concern. 9. If I have a Safety Fuse Power-Ring Converter (SFPC) reading of 11.8Vdc on the output, is this unit considered bad? What should be the voltage measured at the output of the device with no cable attached? There is a high possibility that the voltage-controlled wire, between the battery unit and the power supply, is not properly connected. Without the control wire, the power supply will only put out a ~11.6V; 11.8V is pretty close to that voltage. If the connection is properly verified, then the unit may have a defective voltage regulation circuitry. 10. What is the line load regulation of the SFPC? Within the proper load, (no overload) the line load regulation of the PRC is excellent. It is very tightly regulated since it provides the float voltage to charge the battery. 11. Does this unit have a positive disconnect from the utility mains when operating under battery conditions? There is no physical disconnect from the main, and no chance for back-feed due to the High- Frequency (HF) DC isolation transformer. Also, the unit is agency-qualified under stringent double insulation criteria for SELV (Safety Extra Low Voltage). 12. Does the green wire (control wire for the battery) have a readable voltage that means anything? The functional voltage on the green wire could be any value between 0V to +4V, depending on the battery condition and load. Therefore, it is not a very useful troubleshooting tool C0-007, Rev. J (04/2016) 31

FlexPoint TM. Series Power Supplies. Technical Manual FlexPoint 1215 / 1232 / 1250 Series Indoor Power Supplies Effective: August, 2015

FlexPoint TM. Series Power Supplies. Technical Manual FlexPoint 1215 / 1232 / 1250 Series Indoor Power Supplies Effective: August, 2015 FlexPoint TM Series Power Supplies Technical Manual FlexPoint 1215 / 1232 / 1250 Series Indoor Power Supplies Effective: August, 2015 Safety Notes Review the drawings and illustrations contained in this

More information

Fiber Backhaul Enclosure

Fiber Backhaul Enclosure Fiber Backhaul Enclosure Fiber Backhaul Enclosure (FBE) Installation Manual Effective: July 2009 Alpha Technologies Power Alpha Technologies Fiber Backhaul Enclosure Installation Manual 021-081-B0-001,

More information

MODEL ELC-12/40-CVM-D BATTERY CHARGER

MODEL ELC-12/40-CVM-D BATTERY CHARGER NATIONAL RAILWAY SUPPLY MODEL ELC-12/40-CVM-D BATTERY CHARGER Installing, Operating and Service Instructions for the ELC-12/40-CVM-D Solid State Charger PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING

More information

AT30 SERIES BATTERY CHARGER

AT30 SERIES BATTERY CHARGER STANDARD FEATURES 5 YEAR WARRANTY 5 Year Product Warranty Universal main control board operates in any AT Series charger Alarm assembly with local LEDs and summary relay contact for AC Failure, DC Failure,

More information

FlexPoint TM. Series UPS. Technical Manual FlexPoint 1208-F / 1232-D / 1250-D Series Indoor UPS Effective: September, 2015

FlexPoint TM. Series UPS. Technical Manual FlexPoint 1208-F / 1232-D / 1250-D Series Indoor UPS Effective: September, 2015 FlexPoint TM Series UPS Technical Manual FlexPoint 1208-F / 1232-D / 1250-D Series Indoor UPS Effective: September, 2015 Safety Notes Review the drawings and illustrations contained in this manual before

More information

Technical Manual MPS48-7F/T. Alpha Technologies

Technical Manual MPS48-7F/T. Alpha Technologies TM Technical Manual MPS48-7F/T Effective: January 2008 Alpha Technologies Power Alpha Technologies MPS48-7F/T Technical Manual 021-511-B0-004, Rev. D Effective Date: January 2008 Copyright 2008 Alpha Technologies,

More information

DIN Rail UPS Model: DIN-UPS Installation/Operation Manual

DIN Rail UPS Model: DIN-UPS Installation/Operation Manual DIN Rail UPS Model: DIN-UPS 24-10 Installation/Operation Manual Table of Contents Section Page Section Page Quick Start 2 1) General Information 4 Materials Provided 4 Optional Equipment 4 2) Safety Information

More information

Cruising Charger Series OWNER S MANUAL

Cruising Charger Series OWNER S MANUAL R Cruising Charger Series OWNER S MANUAL ON BOARD BATTERY CHARGERS Models DC Amperage No. Of Banks Volts 2614A 5,10 Amps 2 Bank 12/12 2614A-230 2621A 5,5,10 Amps 3 Banks 12/12/12 2621A-230 2622A 10,10

More information

VRLA Batteries. Battery Installation And Start up Guide

VRLA Batteries. Battery Installation And Start up Guide TECHNICAL MANUAL 41-7525 VRLA Batteries 26-206 Ampere-Hour Capacity Battery Installation And Start up Guide (For Rack Mounted Systems) 41-7525/0514/CD www.cdtechno.com Table of Contents 12V VRLA Battery

More information

DIN Rail UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS Installation/Operation Manual

DIN Rail UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS Installation/Operation Manual DIN Rail UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS 24-10 Installation/Operation Manual Table of Contents Section Page Section Page Quick Start 2 1) General Information 4 Materials Provided

More information

SMU-F Valve Regulated Lead Acid Battery

SMU-F Valve Regulated Lead Acid Battery AlphaCell TM SMU-F Valve Regulated Lead Acid Battery Installation and Operation Manual AlphaCell TM SMU-F Valve Regulated Lead Acid Battery Effective: December 2009 Alpha Technologies Power Alpha Technologies

More information

PREMIER POWER PACK INSTRUCTION MANUAL EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL. GLT.MAN-138 Issue: /05/2016 N.R.P.J.

PREMIER POWER PACK INSTRUCTION MANUAL EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL. GLT.MAN-138 Issue: /05/2016 N.R.P.J. EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL GLT.MAN-138 CONTENTS Introduction to the Premier Power Pack PSU... 2 Changes to EN54-4 (The Fire Alarm Equipment Power Supply Standard)... 3 Indications... 4

More information

SOS SERIES SOS1 SOS2. Spares On Site Battery Cabinet Installation Guide rEV3

SOS SERIES SOS1 SOS2. Spares On Site Battery Cabinet Installation Guide rEV3 Atlantic Battery Systems 1065 Market Street Paterson, NJ 07513 Phone: (800) 875-0073 Fax: (973) 523-2344 sales@atbatsys.com www.atbatsys.com SOS1 SOS2 SOS SERIES Spares On Site Battery Cabinet Installation

More information

Powerware Vdc Extended Battery Cabinet User s Guide.

Powerware Vdc Extended Battery Cabinet User s Guide. Powerware 9125 48 Vdc Extended Battery Cabinet User s Guide www.powerware.com FCC Part 15 Class A EMC Statements NOTE This equipment has been tested and found to comply with the limits for a Class A digital

More information

Installation And Operation Instructions

Installation And Operation Instructions Installation And Operation Instructions For MPS Series Micro-Inverter Power Sytems Lead Calcium Battery Models: MPS-32 and MPS-55 Nickel Cadmium Battery Models: MPS-20 and MPS-35 Surface (-S), Recessed

More information

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Dycon D2430 EN54-4 Fire Alarm Power Supply Series Dycon D2430 EN54-4 Fire Alarm Power Supply Series Technical Description Installation and Operating Manual Construction Product Regulation 0359-CPR-00434 Page 1 of 14 Contents 1. General... 3 1.1 Product

More information

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.

More information

EnergyCell FLA Series. Owner s Manual

EnergyCell FLA Series. Owner s Manual Series Owner s Manual About OutBack Power Technologies OutBack Power Technologies is a leader in advanced energy conversion technology. OutBack products include true sine wave inverter/chargers, maximum

More information

Users Manual. Defender 1 8.0KW to 14.0KW Online Emergency Lighting Inverter. Technical Manual # Revision B

Users Manual. Defender 1 8.0KW to 14.0KW Online Emergency Lighting Inverter. Technical Manual # Revision B Users Manual Defender 1 8.0KW to 14.0KW Online Lighting Inverter Technical Manual #018-0102-01 Revision B Phone: 1.877.DSPM.POWER 1.877.377.6769 Fax: 909.930.3335 Website: www.dspmanufacturing.com E-Mail:

More information

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries RS-2046 Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries FOLLOW MANUFACTURER S PUBLISHED INSTRUCTIONS WHEN INSTALLING, CHARGING AND SERVICING BATTERIES.

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Sentry Battery Charger. Installation and Operations Manual Section 75

Sentry Battery Charger. Installation and Operations Manual Section 75 Sentry Battery Charger Installation and Operations Manual 00-02-0616 03-03-08 Section 75 In order to consistently bring you the highest quality, full featured products, we reserve the right to change our

More information

Installing Power Components

Installing Power Components This chapter provides instructions on how to install and reinstall power components in the Cisco NCS 4016 chassis. It also covers connecting and disconnecting power and powering on the chassis. The Cisco

More information

MODEL ELC-12/60-D BATTERY CHARGER

MODEL ELC-12/60-D BATTERY CHARGER *32198* NATIONAL RAILWAY SUPPLY Installing, Operating and Service Instructions for the 12/60 Solid State Charger MODEL ELC-12/60-D BATTERY CHARGER PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS

More information

SMU-F. AlphaCell TM. Technical Manual. Valve Regulated Lead Acid Battery. AlphaCell SMU-F Valve Regulated Lead Acid Battery Effective: February 2007

SMU-F. AlphaCell TM. Technical Manual. Valve Regulated Lead Acid Battery. AlphaCell SMU-F Valve Regulated Lead Acid Battery Effective: February 2007 AlphaCell TM SMU-F Valve Regulated Lead Acid Battery Technical Manual AlphaCell SMU-F Valve Regulated Lead Acid Battery Effective: February 2007 Alpha Technologies AlphaCell SMU-F Valve Regulated Lead

More information

Guardian Battery Charger Series. Installation and Operations Manual Section 75

Guardian Battery Charger Series. Installation and Operations Manual Section 75 Guardian Battery Charger Series Installation and Operations Manual 00-02-0615 02-29-08 Section 75 In order to consistently bring you the highest quality, full featured products, we reserve the right to

More information

FlexPoint UPS System. Technical Manual. Residential & MDU Applications. FlexPoint FP1230, FlexPoint FP1230F Power Supply Models

FlexPoint UPS System. Technical Manual. Residential & MDU Applications. FlexPoint FP1230, FlexPoint FP1230F Power Supply Models TM FlexPoint UPS System Residential & MDU Applications Technical Manual FlexPoint FP30, FlexPoint FP30F Power Supply Models Effective: September 007 Alpha Technologies Power Alpha Technologies FlexPoint

More information

Users Manual. Cobra Plus Stand-By Emergency Lighting Inverter. Technical Manual # Revision B

Users Manual. Cobra Plus Stand-By Emergency Lighting Inverter. Technical Manual # Revision B Users Manual Cobra Plus Stand-By Lighting Inverter Technical Manual #018-0110-01 Revision B Phone: 1.877.DSPM.POWER 1.877.377.6769 Fax: 909.930.3335 Website: www.dspmanufacturing.com E-Mail: techsupport@dspmanufacturing.com

More information

User s Manual. Automatic Switch-Mode Battery Charger

User s Manual. Automatic Switch-Mode Battery Charger User s Manual Automatic Switch-Mode Battery Charger IMPORTANT Read, understand, and follow these safety rules and operating instructions before using this battery charger. Only authorized and trained service

More information

Installation Operation Parts

Installation Operation Parts OWNER S MANUAL BATTERY BACKUP SUMP Installation Operation Parts For further operating, installation or maintenance assistance, Call 98-8-05 PRINTED IN U.S.A. M-8 (/9) RULES FOR SAFE INSTALLATION AND OPERATION

More information

Self-Testing Industrial Series

Self-Testing Industrial Series Series: AS-I (Maint.-Free) Self-Testing Industrial Series Emergency Lighting Equipment Instructions for INSTALLATION OPERATION SERVICE SPECIFICATIONS 1300650 1300654 1300666 1300754 1300823 1300886 Hubbell

More information

User Manual. Solar Charge Controller 3KW

User Manual. Solar Charge Controller 3KW User Manual Solar Charge Controller 3KW 1 CONTENTS 1 ABOUT THIS MANUAL... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 SAFETY INSTRUCTIONS... 3 2 INTRODUCTION... 4 2.1 Features... 4 2.2 Product Overview... 5

More information

ST - II Series POWER SUPPLIES USER INSTRUCTIONS

ST - II Series POWER SUPPLIES USER INSTRUCTIONS Introduction ST - II Series POWER SUPPLIES These instructions detail the installation and operation requirements for the ST20-II & ST35-II power supplies. These have been designed for operation in RV s

More information

Intelligent Charging System Series

Intelligent Charging System Series R Intelligent Charging System Series OWNER S MANUAL ON BOARD BATTERY CHARGERS Models Amperage No. Of Banks Volts 16061 s 1 Bank 12 16102 6,s 2 Banks 12 or 24 16153 6,6,s 3 Banks 12 or 24 or 36 16202 10,10

More information

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL PHASETEC digital power conditioners are designed to safely operate electrical equipment in the harshest power quality environments. With a wide

More information

5 IN 1 JUMP START OPERATION & MAINTENANCE INSTRUCTIONS MODEL NO: JS5IN1 PART NO: LS0810

5 IN 1 JUMP START OPERATION & MAINTENANCE INSTRUCTIONS MODEL NO: JS5IN1 PART NO: LS0810 5 IN 1 JUMP START MODEL NO: JS5IN1 PART NO: 6240005 OPERATION & MAINTENANCE INSTRUCTIONS LS0810 INTRODUCTION Thank you for purchasing this CLARKE product. Before attempting to use this product, please

More information

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2 1 27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2 STX2401-C STX2401-T FEATURES 0843-CPR-0213 14 Elmdene International Ltd Tel: +44(0)23 9269 6638 3 Keel Close, Interchange Park, Fax:

More information

8 Step Fully Automatic Intelligent BATTERY CHARGER 12V 5A USER S MANUAL. Charges & Maintains. Flooded (WET), MF, VRLA, AGM, GEL & Calcium batteries

8 Step Fully Automatic Intelligent BATTERY CHARGER 12V 5A USER S MANUAL. Charges & Maintains. Flooded (WET), MF, VRLA, AGM, GEL & Calcium batteries 8 Step Fully Automatic Intelligent BATTERY CHARGER 12V 5A Charges & Maintains Flooded (WET), MF, VRLA, AGM, GEL & Calcium batteries USER S MANUAL 5 User s Manual And Guide To Professional Battery Charging

More information

Model: SE-4020-CA Automatic Battery Charger

Model: SE-4020-CA Automatic Battery Charger OWNERS MANUAL Model: SE-4020-CA Automatic Battery Charger PLEASE SAVE THIS OWNERS MANUAL AND READ BEFORE EACH USE. This manual will explain how to use the battery charger safely and effectively. Please

More information

SEAUPS-III Uninterruptible Power Conditioning System. System Manual

SEAUPS-III Uninterruptible Power Conditioning System. System Manual SEAUPS-III Uninterruptible Power Conditioning System System Manual N9246 Hwy 80 South, Suite 7, Necedah, WI 54646 Tel: 608-565-5877 Fax: 608-565-5879 Email: sales@lpc-ups.com Website: www.lpc-ups.com BILS-10012

More information

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Dycon D1532SM EN50131/PD6662 Grade 3, 12V 2A Power Supply Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Tel: +44 (0)1443 471 900 Unit A Cwm Cynon Business Park Mountain

More information

General Precautions. Personnel Precautions

General Precautions. Personnel Precautions USER MANUAL General Precautions 1. Before using Inverex, read all instructions and cautionary markings on : (1) Inverex (2) the batteries (3) this manual 2. CAUTION --To reduce risk of injury, charge only

More information

User Manual Digital Energy Uninterruptible Power Supply ML Series UPS VA GE Digital Energy Power Quality

User Manual Digital Energy Uninterruptible Power Supply ML Series UPS VA GE Digital Energy Power Quality GE Digital Energy Power Quality User Manual Digital Energy Uninterruptible Power Supply ML Series UPS 350-500-700-1000 VA GE imagination at work GB User Manual Digital Energy Uninterruptible Power Supply

More information

Spectron Industrial Series

Spectron Industrial Series 1300650 1300654 1300666 1300754 1300823 1300886 Table B Constant Value per Voltage System Wire Size (Maximum Voltage Drop 5%) System 6 Volt 12 Volt 24 Volt Wire Size #12 #10 #8 #6 #12 #10 #8 #6 #10 #12

More information

A+ Battery Backup Power Supply For use with Hydromatic model B-A1/BV-A1

A+ Battery Backup Power Supply For use with Hydromatic model B-A1/BV-A1 Unit Installation and Service Manual A+ Battery Backup Power Supply For use with Hydromatic model B-A1/BV-A1 NOTE! To the installer: Please make sure you provide this manual to the owner of the pumping

More information

400 Watt Backup Power System Owner s Manual

400 Watt Backup Power System Owner s Manual 400 Watt Backup Power System Owner s Manual WARNING: Read carefully and understand all ASSEMBLY AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions

More information

Installation and Operation Instructions SERVICE BY QUALIFIED PERSONNEL ONLY

Installation and Operation Instructions SERVICE BY QUALIFIED PERSONNEL ONLY ELI-S-600 120 Volt ELI SERIES EMERGENCY LIGHTING INVERTERS Installation and Operation Instructions! IMPORTANT SAFEGUARDS! WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED,

More information

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING dv Sentry TM 208V 600V INSTALLATION GUIDE FORM: DVS-IG-E REL. January 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

Installation And Operation Instructions

Installation And Operation Instructions Installation And Operation Instructions For PS Series Mini-Inverter Power Systems Models: PS-55-LP, PS-110-HP, PS-110-LP, PS-220-HP Surface (-S), Recessed (-R) and Ceiling T-Grid (-T) Mounted Versions

More information

Installation And Operation Instructions

Installation And Operation Instructions Installation And Operation Instructions For LPS Series Micro Inverter Power Systems Lead Calcium Battery Models: LPS32 and LPS55 Nickel Cadmium Battery Models: LPS20 and LPS35 Surface (-S), Recessed (-R)

More information

PSJ-2212, PSJ-3612, PSJ-4424

PSJ-2212, PSJ-3612, PSJ-4424 Model: PSJ-2212, PSJ-3612, PSJ-4424 Jump Starter and DC Power Source OWNER S MANUAL PSJ-2212 PLEASE SAVE THIS OWNER S MANUAL AND READ BEFORE EACH USE. This manual will explain how to use your jump starter

More information

7 Stage Automatic Smart Battery Charger (FOR CHARGING 12V / 24V AGM, GEL,SLA AND WET BATTERIES) USER MANUAL

7 Stage Automatic Smart Battery Charger (FOR CHARGING 12V / 24V AGM, GEL,SLA AND WET BATTERIES) USER MANUAL 7 Stage Automatic Smart Battery Charger Desulphuration& Maintainer (FOR CHARGING 12V / 24V AGM, GEL,SLA AND WET BATTERIES) USER MANUAL THIS MANUAL CONTAINS IMPORTANT SAFETY AND OPERATING INSTRUCTIONS 1

More information

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation

More information

OPERATING INSTRUCTIONS. Note: 6V Charging. Requires Manual Shut Off.

OPERATING INSTRUCTIONS. Note: 6V Charging. Requires Manual Shut Off. Requires Manual Shut Off. 6 / 2 AMP,, DUAL RATE BATTER TTERY CHARGER 45005 OPERATING INSTRUCTIONS E224783 E224783 Note: 6V Charging Due to continuing improvements, actual product may differ slightly from

More information

MASTERsine Inverter PXA Series Installation Guide

MASTERsine Inverter PXA Series Installation Guide Backup Power System Expert TM MASTERsine Inverter PXA Series Installation Guide Important Safety Instructions IMPORTANT: Read and save this Installation Guide for future reference. This chapter contains

More information

User Manual. Digital Energy Uninterruptible Power Supply ML Series UPS VA. GE Digital Energy Power Quality. GE imagination at work

User Manual. Digital Energy Uninterruptible Power Supply ML Series UPS VA. GE Digital Energy Power Quality. GE imagination at work GE Digital Energy Power Quality User Manual Digital Energy Uninterruptible Power Supply ML Series UPS 350-500-700-1000 VA GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno)

More information

IMPORTANT SAFEGUARDS

IMPORTANT SAFEGUARDS INSTRUCTION MANUAL NON-INTERRUPTIBLE AC INVERTER SYSTEM MODEL EAC FTM 350 FOR EMERGENCY LIGHTING POWER IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed,

More information

Eclipse Solar Suitcase

Eclipse Solar Suitcase Eclipse Solar Suitcase Renogy 100W 200W 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 Version 1.0 Important Safety Instructions Please save these instructions. This manual contains important

More information

Compact Sine Inverter

Compact Sine Inverter Compact Sine Inverter Instructions for installation & use Applies to the following models: Output power: 700watt, 1000 watt, 1500watt, 2000 watt & 3000 watts Output voltage: and output, 50Hz & 60Hz Output

More information

Go Power! Manual. GP-1750HD Inverter GP-2500 Inverter

Go Power! Manual. GP-1750HD Inverter GP-2500 Inverter Go Power! Manual GP-1750HD Inverter GP-2500 Inverter Go Power! Electric Inc. PO Box 6033 Victoria, BC V8P 5L4 Tel: 866-247-6527 Fax: 866-607-6527 Email: info@gpelectric.com Table of Contents 1. INTRODUCTION...

More information

IEEE IAS Atlanta Chapter

IEEE IAS Atlanta Chapter Stationary Battery Sizing IEEE IAS Atlanta Chapter Presented by: Lesley Varga, P.E. Quality Standby Services, LLC 1649 Sands Place, SE, Suite C Marietta, GA 30067 (770) 916-1747 lesley@qualitystandbyservices.com

More information

12VDC TO 230VAC INVERTERS

12VDC TO 230VAC INVERTERS 12VDC TO 230VAC INVERTERS 12VDC TO 230VAC INVERTERS MODEL Nos: CI-200 CI-400 CI-600 CI-800 CI-1000 CI-1500 OPERATION & MAINTENANCE INSTRUCTIONS 0706 Thank you for purchasing this CLARKE Power Inverter.

More information

Battery Power Inverters

Battery Power Inverters Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.4 Important Safety Instructions Please save these instructions.

More information

SCC-MPPT Solar Charge Controller

SCC-MPPT Solar Charge Controller Table 3: Charging voltage for 4 types of battery Battery Battery 12V battery system 24V battery system Type Type Code Bulk Floating Bulk Floating Vented 01 14.3 V 13.2 V 28.6 V 26.4 V Sealed 02 14.3 V

More information

GSL Electronics Modified Sine Wave Power Inverters

GSL Electronics Modified Sine Wave Power Inverters GSL Electronics Modified Sine Wave Power Inverters Congratulations on choosing one of our Modified Sine Wave Inverters for your application. There are 6 models in the range, which will meet most of your

More information

FLUSH EYES IMMEDIATELY WITH WATER. GET MEDICAL HELP FAST. SULFURIC ACID CAN CAUSE BLINDNESS OR SEVERE BURNS.

FLUSH EYES IMMEDIATELY WITH WATER. GET MEDICAL HELP FAST. SULFURIC ACID CAN CAUSE BLINDNESS OR SEVERE BURNS. 8A & 8G BATTERY INSTALLATION AND OPERATING INSTRUCTIONS This manual is intended to be a guide to optimize battery performance for multiple cyclic & float applications. Consult applicable User Manuals for

More information

ACCUSENSE CHARGE SERIES ON/OFF BOARD FULLY AUTOMATIC BATTERY CHARGER

ACCUSENSE CHARGE SERIES ON/OFF BOARD FULLY AUTOMATIC BATTERY CHARGER ACCUSENSE CHARGE SERIES ON/OFF BOARD FULLY AUTOMATIC BATTERY CHARGER SPECIFICATIONS: *Photo for reference only* Part number 8890439 Mode Select: Selects Battery Type Refer to Section 6. IMPORTANT: READ

More information

AUTO CHARGE 4000 MODEL #: LOW PROFILE CHARGER AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

AUTO CHARGE 4000 MODEL #: LOW PROFILE CHARGER AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL INSTRUCTION MANUAL AUTO CHARGE 4000 LOW PROFILE CHARGER AUTOMATIC DUAL OUTPUT BATTERY CHARGER Unit supplied with this display MODEL #: 091-89-12 INPUT: 120 Volt, 50/60 Hz, 5 Amps OUTPUT: 45 Amps File:

More information

Solar Charge Controller

Solar Charge Controller Table 3: Charging voltage for 4 types of battery Battery Type Battery Type Code SC-600W MPPT Bulk Voltage Floating Voltage Vented 01 28.6 V 26.4 V Sealed 02 28.6 V 26.8 V Gel 03 28.6 V 27.4 V NiCd 04 28.6

More information

BC12M248 7 Stage Automatic Smart Battery Charger, Desulfator & Maintainer 12V, 2 / 4 / 8A FOR AGM, GEL AND WET BATTERIES USER MANUAL

BC12M248 7 Stage Automatic Smart Battery Charger, Desulfator & Maintainer 12V, 2 / 4 / 8A FOR AGM, GEL AND WET BATTERIES USER MANUAL BC12M248 7 Stage Automatic Smart Battery Charger, Desulfator & Maintainer 12V, 2 / 4 / 8A FOR AGM, GEL AND WET BATTERIES USER MANUAL THIS MANUAL CONTAINS IMPORTANT SAFETY AND OPERATING INSTRUCTIONS 1 IMPORTANT

More information

Monicon Instruments Co., Ltd. CHR-1285/2485 CHR-1285/2485 BATTERY CHARGER

Monicon Instruments Co., Ltd. CHR-1285/2485 CHR-1285/2485 BATTERY CHARGER CHR-1285/2485 BATTERY CHARGER TEL:886-4-2238-0698 FAX:886-4-2238-0891 Web Site:http://www.monicon.com.tw E-mail:sales@monicon.com.tw Copyright 2007 Monicon Instruments Co., Ltd. All right reserved. Contents

More information

Elmdene International Ltd

Elmdene International Ltd 1 Elmdene International Ltd Tel: +44(0)23 9269 6638 3 Keel Close, Interchange Park, Fax: +44(0)23 9266 0483 Portsmouth, Hampshire, PO3 5QD, UK Web: www.elmdene.co.uk 13.8Vdc Switch Mode Power Supply GEN3-08-y

More information

GP-1000 Inverter. Go Power! Electric Inc. PO Box 6033 Victoria, BC V8P 5L4 Tel: Fax:

GP-1000 Inverter. Go Power! Electric Inc. PO Box 6033 Victoria, BC V8P 5L4 Tel: Fax: Go Power! Manual GP-1000 Inverter Go Power! Electric Inc. PO Box 6033 Victoria, BC V8P 5L4 Tel: 866-247-6527 Fax: 866-607-6527 Email: info@gpelectric.com Table of Contents 1. INTRODUCTION 3 2. SPECIFICATIONS

More information

Table of Contents 文管中心 發行章

Table of Contents 文管中心 發行章 ST600-XXX Series Pure Sine Wave Power Inverter User s Manual Table of Contents 1. Important Safety Instructions 1-1 General Safety Precautions 1 1-2 Battery Precautions. 1 2. Basic Descriptions 2-1 Mechanical

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

SCC-MPPT Solar Charge Controller

SCC-MPPT Solar Charge Controller Solar Charge Controller Quick Guide 200W 300W 400W 600W 850W V. 2.2 1. Introduction solar charge controller uses PWM-based DSP controller to keep the batteries regulated and prevent batteries from overcharging

More information

Owner's/Installation Manual

Owner's/Installation Manual Owner's/Installation Manual Power Management Module (PMM) and Starter Kit NOTE: The starter kit must be purchased and installed prior to individual PMM usage. Model Numbers: 00686-0 PMM 00699-0 PMM WITH

More information

18VDC ESB6 Series Cordless Screwdrivers Operation Manual

18VDC ESB6 Series Cordless Screwdrivers Operation Manual 18VDC ESB6 Series Cordless Screwdrivers Screwdriver Models : ESB6-8, ESB6-12, ESB6-15, ESB6-22 CAUTION - Please read, understand, and follow all operating and safety instructions in this manual before

More information

Deep Cycle Battery Safety. First. Battery Handling, Maintenance & Test Procedures

Deep Cycle Battery Safety. First. Battery Handling, Maintenance & Test Procedures Deep Cycle Battery Safety. First. Battery Handling, Maintenance & Test Procedures Crown deep cycle batteries employ a low-maintenance design. They do require periodic maintenance and effective charging

More information

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING SineWave Guardian TM 380V 600V INSTALLATION GUIDE FORM: SWG-IG-E REL. October 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of

More information

LMI Watt Models

LMI Watt Models LMI 300-600 Watt Models Service Questions Call: 800-451-9423 INSTALLATION AND OPERATING INSTRUCTIONS IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed,

More information

Pure Sine Wave Inverter GP-HS1500. Owner s Manual

Pure Sine Wave Inverter GP-HS1500. Owner s Manual Pure Sine Wave Inverter GP-HS1500 Owner s Manual 2 Table of Contents Introduction 3 Specifications 4 Name and Main Function 5 Installation 7 Operation 9 Operating Limits 13 Troubleshooting 13 Maintenance

More information

c-go 24V/6A 24V/8A 24V/12A

c-go 24V/6A 24V/8A 24V/12A c-go 24V/6A 24V/8A 24V/12A Battery charger GB Instruction manual 1 Index 1. Product description... 2 2. Safety advices... 3 3. Quick start guide... 4 4. Operation... 4 5. Problem solving... 6 6. Specifications...

More information

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V SOLAR LIGHTING CONTROLLER OPERATOR S MANUAL SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V 10A / 12V 10A / 24V 20A / 12V 20A / 24V 1098 Washington Crossing Road Washington Crossing,

More information

USER MANUAL. Uninterruptible Power Supply Line-interactive VCL Series UPS VA

USER MANUAL. Uninterruptible Power Supply Line-interactive VCL Series UPS VA USER MANUAL Uninterruptible Power Supply Line-interactive VCL Series UPS 800 1100 2000 3000 VA GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 /

More information

Eclipse Plus VA UPS and Surge Suppressor User s Manual

Eclipse Plus VA UPS and Surge Suppressor User s Manual Eclipse Plus 250 250VA UPS and Surge Suppressor User s Manual Compact UPS/Surge Suppressor for Home Office or Small Office Use www.mgeups.com Notes Contents Thank You!.....................................................

More information

DeSoto EMERGENCY LIGHTING UNIT. U.S. Versions: 12V- DM (P2 & P3) / DM / DM INSTALLATION INSTRUCTIONS

DeSoto EMERGENCY LIGHTING UNIT. U.S. Versions: 12V- DM (P2 & P3) / DM / DM INSTALLATION INSTRUCTIONS DeSoto U.S. Versions: 12V- DM80212100 (P2 & P3) / DM80212150 / DM80212450 EMERGENCY LIGHTING UNIT INSTALLATION INSTRUCTIONS U.S. Patent No.s D419,097; 6,135,624; 6,193,395; 6,502,044 B1 Canadian Patent

More information

Dual-Lite Trident TRF 40 Wide Battery Cabinet 20-40kVA Systems USER MANUAL

Dual-Lite Trident TRF 40 Wide Battery Cabinet 20-40kVA Systems USER MANUAL Dual-Lite Trident TRF 40 Wide Battery Cabinet 20-40kVA Systems USER MANUAL 755-00020-DL 5/17/2017 2 755-00020-OEM R01 TABLE OF CONTENTS 1. Important Information About This Manual... 4 1.1 Manual Symbols...

More information

Power Inverter 400 MW Owner s Manual

Power Inverter 400 MW Owner s Manual Power Inverter 400 MW 1204 Owner s Manual For safe and optimum performance, the Power Inverter must be used properly. Carefully read and follow all instructions and guidelines in this manual and give special

More information

PHOTOVOLTAIC SYSTEM CONTROLLERS SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V

PHOTOVOLTAIC SYSTEM CONTROLLERS SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V PHOTOVOLTAIC SYSTEM CONTROLLERS OPERATOR S MANUAL SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V 6A / 12V 10A / 12V 10A / 24V 20A / 12V 20A

More information

Uninterruptible Power Supply

Uninterruptible Power Supply AC/DC Din Rail UPS System Single Phase Input, Single Phase Output Uninterruptible Power Supply 600VA UPS System AC/DC Din Rail Mount Line Interactive (PWM): 600VA User Manual M1201_Din_Rail_AC-DC_600VA_Manual

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS 76-50213-00 Solar Charger Kit This kit provides the necessary parts and instructions to install an optional Battery Solar Charger Kit. The solar panel charging system will help maintain

More information

K25000 & KD25000 Series

K25000 & KD25000 Series K25000 & KD25000 Series Fire Alarm Power Supplies Installation, Commissioning and Operating Manual Man-1128 Issue 14 January 2016 Man-1128_K25400_series_Power_Supply_Manual_14 Page 1 of 20 Section Page

More information

Transfer Switch TS-50. Owner s Manual

Transfer Switch TS-50. Owner s Manual Transfer Switch TS-50 Owner s Manual Table of Contents Introduction 2 Installation 2 Operational Testing 7 Troubleshooting 7 Hi-Pot Testing 8 Generator Note 9 Medical Appliances 10 Caution 10 Disclaimer

More information

Nature Power Inverters. True Sinewave Inverter Modified Sinewave Inverter. Owner s Manual

Nature Power Inverters. True Sinewave Inverter Modified Sinewave Inverter. Owner s Manual Version 1.1 Version 2 Nature Power Inverters True Sinewave Inverter Modified Sinewave Inverter Owner s Manual!!!!!!!!!!! 38304 38204 For safe and optimum performance, the Power Inverter must be used properly.

More information

Match 19" GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match 19" UPS.

Match 19 GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match 19 UPS. Match 19" Uninterruptible Power Supply 700-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com

More information

HIGH FREQUENCY AUTOMATIC BATTERY CHARGER

HIGH FREQUENCY AUTOMATIC BATTERY CHARGER HIGH FREQUENCY AUTOMATIC BATTERY CHARGER MODEL NO: HFBC12 PART NO: 6267000 OPERATION & MAINTENANCE INSTRUCTIONS LS0814 INTRODUCTION Thank you for purchasing this CLARKE High Frequency Automatic Battery

More information

SCC-MPPT Solar Charge Controller

SCC-MPPT Solar Charge Controller Table 4: Alarm point for low battery voltage table Model Alarm point SCC-MPPT-300 10.5 V SCC-MPPT-600 21.0 V Table 5: Charging hour table for reference Battery Capacity To 90% capacity @ 25A charging current

More information

Installation Instructions

Installation Instructions Quick-Mount Visual Instructions for Quick-Mount Visual Instructions 1. Rotate the damper to its failsafe position. If the shaft rotates counterclockwise, mount the CCW side of the actuator out. If it rotates

More information

Combined Ventilation Controller RVWS-T-224HA

Combined Ventilation Controller RVWS-T-224HA Combined Ventilation Controller RVWS-T-224HA 8-stage Control for Power/Natural Applications 2 variable speed stages, 2 curtain winch stages, 2 fixed speed ventilation stages, 1 thermo/mister cycle stage

More information