1 VD e CONTOIL MDO and HFO applications

2 Table of contents 1 Introduction Liability Disclaimer Safety precautions Conventions Supplementary Instructions 4 2 Technical Information CONTOIL Flow Meter Types CONTOIL Flow Meter Materials CONTOIL Flow Meter Application Specifications CONTOIL Flow Meter Specifications CONTOIL Flow Meter Dimensions (for flange version only) CONTOIL Flow Meter Transducer Dimensions 7 3 Design Guidelines Samples of measuring concepts Accuracy comparison of different measurement concepts Temperature Compensation Density Compensation Offset in differential measurement Layout and Installation Strainers / Filters Pulsation Dampers Pressure Loss Installation 14 4 Commissioning / start up 15 5 Maintenance 15 6 Troubleshooting 16 7 Warranty Disclaimer 17 Appendix I. 18 Pressure Drop Curves 2

3 1. Introduction Thank you for your decision to work with Aquametro Fuel Performance Products. This manual describes the installation, commissioning and use of Aquametro s CONTOIL Fuel Meters. For additional information please contact your local sales agent to be found at: Liability Disclaimer The manufacturer cannot monitor the compliance to this manual as well as the conditions and methods during the installation, operation, usage and maintenance of the system regulator. Improper installation can cause damages and endanger people. Therefore, we assume no responsibility and liability for losses, damages or costs that result due to incorrect installation, improper operation, usage and maintenance or in any manner associated therewith. Similarly, we assume no responsibility for patent right or other right infringements of third parties caused by usage of this system regulator. The manufacturer reserves the right, without prior notification, to make modifications concerning the product, technical data or installation and operating manual. 1.2 Safety precautions CONTOIL flow meters must only be used for their intended purpose and comply with local and international safety regulations. All documentation is to be followed exactly. None of the information stated here or elsewhere releases planners, installers and operators from their own careful and comprehensive assessment of the respective plant configuration in terms of functional capability and operational safety. Local applicable working regulations must be complied with, during all work on the plant and/or ship. All safety-, installation- and operation instruction as described in this manual must be followed. Sensors are sensitive measuring instruments and should be treated carefully. When removing or reinstalling sensors or components from the system, safety instructions in the respective operating manual must be followed. Extra caution is required, when using inflammable cleaning substances, work space must be ventilated well. The clearance distance of the piping must be adhered to when mounting the meter. If using flanged connections, the correct number of connector elements must be fitted and they must be tightened with the correct torque in accordance with the screw manufacturer s instructions. Always comply with the permissible operating data as specified and mentioned on the type plate. The meter must at all times be completely filled with liquid during operation. Check the meter periodically for tightness of the connections and for proper functioning. Make sure that no hazardous fumes can build up in the piping and in the meter during commissioning, decommissioning and dismantling. Prior to disassembly, the measuring instruments must be free from dangerous or noxious residues. Clean and rinse thoroughly! The unit must be installed to VDC and must not be installed to 110 VAC or 230 VDC. Electrical wiring and installations are subject to statutory regulations, which must be taken into account when planning the system. CONTOIL flow meters are not for installation in zones subject to explosion hazards. Make sure that no hazardous fumes can build up in the piping and in the meter during commissioning, decommissioning and dismantling. If work is to be done on the installation, before each intervention: a) Release the pressure in the installation b) If hazardous fluids are used, wear protective clothing and safety goggles. Prior to disassembly, the measuring instruments must be free from dangerous or noxious residues. Clean and rinse thoroughly! c) Place collecting vessel underneath the installation. 3

4 1.3 Conventions A/E Auxiliary Engine CFM-S CONTOIL Fuel Monitor - Ship CFM-T CONTOIL Fuel Monitor - Tug-boat DN Diameter Nominal ECR Engineering Control Room ER Engineering Room ETO Electro Technical Officer FM x Fuel Meter FPA Fuel Performance Analyser FPM Fuel Performance Management FPR Fuel Performance Recorder PLC Programmable Logic Controller GPS Global Positioning System HFO Heavy Fuel Oil MDO Marine Diesel Oil MGO Marine Gas Oil M/E Main Engine MT Main Tank Pt100 Standard Resistance thermometer (R0 = 100 Ohm) Tx Temperature Sensor (Pt100) W/H Wheel House (= bridge) 1.4 Supplementary Instructions Bedienungsanleitung / Operating instructions / Mode d emploi CONTOIL control: VZF / VZFA Art. No

5 2. Technical Information CONTOIL flow meters work on the volumetric principle of rotary piston meters (positive displacement meters). The main features of this measuring principle are large measuring ranges, high accuracy, suitability for high viscosities and independence from power supply; flow disturbances do not influence proper operation Rotary piston, guide roller and drive are the only moving parts in contact with the liquid. Their movement is transmitted by a magnetic coupling through a sealing plate. The hydraulic part is completely separated from the totalising module. 2.1 CONTOIL Flow Meter Types Type Display Displayed Units Accuracy Accuracy values displayed Standard Paired calibration VZF Digital Display - Total volume - m3 1 % of reading Not available - Resettable vol. - Litre 0.2 % repeatability - Current Flow - US Gallons - Total hrs used - Max. Flow VZFA Digital Display - Total volume - m3 0.5 % of reading 0.1 % supply meter - Resettable vol. - Litre 0.1 % repeatability 0.3 % return meter - Current Flow - US Gallons - Total hrs used - Max. Flow VZO Roller Counter - Total volume - Litre 1 % of reading Not available - US Gallons 0.2 % repeatability VZOA Roller Counter - Total volume - Litre 0.5 % of reading 0.1 % supply meter - US Gallons 0.1 % repeatability 0.3 % return meter 2.2 CONTOIL Flow Meter Materials Part Material Remark Housing with flanges Spheroid graphite iron (GGG) Not in contact with measured fluid Measuring chamber PN 16 & 25 Cast brass in contact with measured fluid Measuring chamber PN 40 Stainless Steel in contact with measured fluid Seals FPM fluor-elastomer in contact with measured fluid Rotary Piston Anodized aluminium in contact with measured fluid Ancillaries Plastic Not in contact with measured fluid Cover of meter Plastic Not in contact with measured fluid Colour of housing Enamelled red RAL

6 2.3 CONTOIL Flow Meter Application Specifications General specifications, which are same for all type of CONTOIL Flow Meters: Minimum ambient temperature: -25 C Maximum ambient temperature: +70 C Maximum viscosity to keep pressure loss 1 bar is 300 cst To keep the maximum Viscosity below 300 cst a minimum temperature for different oil types has to be kept: Recommended Min. Temp. for 300 cst IFO 1000 Fuel oil: 90 C Recommended Min. Temp. for 300 cst IFO 700 Fuel oil: 80 C Recommended Min. Temp. for 300 cst IFO 500 Fuel oil: 70 C Recommended Min. Temp. for 300 cst IFO 380 Fuel oil: 60 C General specifications, which are same for all type of CONTOIL Flow Meters: Maximum fuel temperature for below listed CONTOIL Flow Meters: 180 C Maximum pipe pressure for below listed CONTOIL Flow Meters: 25 bar Maximum filter mesh size is given in the table below. In general it is recommended to install the flow meters after the automatic filter, before the engine, which anyway requires a much lower mesh size. Type (preferred choise) for Art. No. Required min. Recommended Max. filter mesh size different specs please refer flow rate max. flow rate* (before flow meter) to our website l/h l/h mm VZF 20 FL 180/25 DIN VZF 25 FL 180/25 DIN VZF 40 FL 180/25 DIN VZF 50 FL 180/25 DIN VZF 20 FL 180/JIS 20K VZF 25 FL 180/JIS 20K VZF 40 FL 180/JIS 20K VZF 50 FL 180/JIS 20K VZFA 20 FL 180/25 DIN VZFA 25 FL 180/25 DIN VZFA 40 FL 180/25 DIN VZFA 50 FL 180/25 DIN VZFA 20 FL 180/JIS 20K VZFA 25 FL 180/JIS 20K VZFA 40 FL 180/JIS 20K VZFA 50 FL 180/JIS 20K VZO 20 FL 180/25 DIN VZO 25 FL 180/25 DIN VZO 40 FL 180/25 DIN VZO 50 FL 180/25 DIN VZO 20 FL 180/JIS 20K VZO 25 FL 180/JIS 20K VZO 40 FL 180/JIS 20K VZO 50 FL 180/JIS 20K VZOA 20 FL 180/25 DIN VZOA 25 FL 180/25 DIN VZOA 40 FL 180/25 DIN VZOA 50 FL 180/25 DIN VZOA 20 FL 180/JIS 20K VZOA 25 FL 180/JIS 20K VZOA 40 FL 180/JIS 20K VZOA 50 FL 180/JIS 20K * depending on the individual conditions on board, like pumping, piping system, vibration, viscosity, fuel condition, etc. this value can vary. 6

7 2.4 CONTOIL Flow Meter Specifications Type (preferred choice) Approx. volume of Approx. weight measuring chamber cm3 kg VZF, VZFA, VZO, VZOA 20 FL 180/25 DIN/JIS VZF, VZFA, VZO, VZOA 25 FL 180/25 DIN/JIS VZF, VZFA, VZO, VZOA 40 FL 180/25 DIN/JIS VZF, VZFA, VZO, VZOA 50 FL 180/25 DIN/JIS CONTOIL Flow Meter Dimensions (for flange version only) ØF b h1 h2 H B L Type (preferred choice) L B F b h1 mm mm mm mm mm VZF, VZFA, VZO, VZOA 20 FL 180/25 DIN/JIS VZF, VZFA, VZO, VZOA 25 FL 180/25 DIN/JIS VZF, VZFA, VZO, VZOA 40 FL 180/25 DIN/JIS VZF, VZFA, VZO, VZOA 50 FL 180/25 DIN/JIS CONTOIL Flow Meter Transducer Dimensions Transducer dimension for VZF(A): DN 15 - DN 50 Transducer dimension for VZO(A): DN 15 - DN VZF(A) VZO(A) 7

8 3. Design Guidelines Flow sensors are accurate measurement devices, which need some considerations in design and care during installation. Any measuring sensor can only perform in the optimum range, when it is used within it s specific requirements. Please check chapter CONTOIL Flow Meter Application Specifications for application specific limit values. Further we want to give some consideration for the whole fuel pipe installation: Tank CONTOIL Filter Pulsation dampers Engine Pressure release valve Pump Pulsation dampers Auto Filter CONTOIL Pulsation dampers Pressure release valve 3.1 Samples of measuring concepts Measuring concept 1 (MC1) Service Tank FM0 MT M/E In the first measuring concept, there is only one fuel meter after the service tank. Hence all consumption displayed is the oil consumption coming from the service tank, regardless to which engine it will flow. M/E consumption = FM0 Disadvantage: Depending on the tank level changes of MT the consumption of M/E is not instantly displayed it has to be averaged over time as FM0 actually measures the consumption of MT and not directly the consumption of M/E. Advantage: No pulsation issues from the engine. Measuring concept 2 (MC2) Service Tank FM1 MT A/E M/E Measuring concept 2 shows 2 different consumption values. One for the auxiliary engine (A/E) and one for the main engine (M/E). M/E consumption = FM0 and A/E consumption = FM1 Disadvantage: same as MC1. Advantage: same as MC1. MT FM0 Measuring concept 3 (MC3) Service Tank 8 MT FM1 FM0 M/E Measuring concept 3 offers a more precise measurement result of the main engine (M/E) consumption, as it is a differential measuring concept and our meters (VZFA) are calibrated in pair to ensure highest accuracy. The consumption is measured in the M/E fuel circulation and calculated as M/E consumption = FM0 - FM1 Disadvantage: Pulsation issues, if there is no pulsation damper. Advantage: The consumption values are instant values as there is no tank before the engine. Flow meters can be calibrated in pair and have a better accuracy.

9 Measuring concept 4 (MC4) Service Tank FM0 MT This concept is not recommended FM3 FM2 A/E M/E Measuring concept 4 offers a more precise measurement result of the auxiliary engine (A/E) consumption, as it is a differential measuring concept and our meters are calibrated in pair to ensure highest accuracy. It shows very precise the consumption of A/E. The consumption is measured in the A/E fuel circulation and calculated as A/E consumption = FM1 - FM2 and M/E consumption = FM0 - A/E consumption = FM0 - (FM1 - FM2). Disadvantage: The M/E consumption has to be averaged over some time as the MT is buffering between the real consumption of the engines and the consumption of the Service Tank. Also the dimensioning of the A/E flow meters is not optimal, as it must be as big as the maximum consumption of M/E or A/E (which ever is bigger). Pulsation issues for the A/E are possible, if no pulsation dampers are used. Advantage: The A/E consumption values are instant values, as there is no tank before the engine. Measuring concept 5 (MC5) Service Tank MT FM3 FM2 FM1 FM0 A/E M/E Measuring concept 5 offers the most precise measurement result for both the main engine (M/E) and the auxiliary engine (A/E) consumption, as it is a differential measuring concept in both circulation lines and our meters are calibrated in pair to ensure highest accuracy. A/E consumption = FM2 - FM3 and M/E consumption = FM0 - FM1. Disadvantage: Pulsation issues, if there is no pulsation damper. Advantage: The A/E and M/E consumption values are instant values, as there is no tank before the engines. Flow meters can be dimensioned according to engine consumption. Flow meters can be calibrated in pair and have a better accuracy. Measuring concept 6 (MC6) Service Tank FM0 MT FM2 FM1 A/E M/E Measuring concept 6 is better then measuring concept 4, as usually the M/E are the bigger engines. If a more precise measurement of both engines is required measurement concept 5 is preferred. MC6 shows very precise the consumption of M/E. The consumption is measured in the M/E fuel circulation and calculated as M/E consumption = FM1 - FM2 and A/E consumption = FM0 - M/E consumption = FM0 - (FM1 - FM2). Disadvantage: The A/E consumption has to be averaged over some time as the MT is buffering between the real consumption of the engines and the consumption of the Service Tank. Pulsation issues for the A/E are possible, if no pulsation dampers are used. Advantage: The M/E consumption values are instant values, as there is no tank before the main engine. 9

10 3.2 Accuracy comparison of different measurement concepts Calculation example for low consumption Flow meter type and accuracy choice M/E Supply line assumption (l/h) 9000 VZO/VZF VZOA/VZFA VZOA/VZFA M/E Return line assumption (l/h) % 0.5 % 0.1 % 0.3 % A/E Supply line assumption (l/h) 500 A/E Return line assumption (l/h) 300 Measuring Concept Accuracy Standard Standard Pair calibration calibration calibration MC1 & MC2 M/E 8.0 % 4.0 % n.a. measure actually MT consumption A/E 4.0 % 2.0 % n.a. MC3 M/E 8.0 % 4.0 % 1.5 % same results, if used for A/E A/E 4.0 % 2.0 % 0.7 % MC4 M/E 1.5 % 0.8 % 0.6 % with limitation of max flow over A/E A/E 4.0 % 2.0 % 0.7 % MC5 M/E 8.0 % 4.0 % 1.5 % A/E 4.0 % 2.0 % 0.7 % MC6 M/E 8.0 % 4.0 % 1.5 % A/E 15.0 % 7.5 % 20.5 % For Fuel Performance Management systems like FPR, CFM-S or CFM-T our CONTOIL VZFA meters with pair calibration, used in differential measurement are always strongly recommended (MC3 or MC5). Explanation & Sample calculation of measuring concept 4 versus 5 Sample calculation measurement concept 4 / ASSUMPTIONS: All Flow meter 1 % accuracy M/E consumption l/hr A/E consumption 200 l/hr Booster pump l/hr Service Tank FM3 FM2 A/E M/E Accuracy M/E with A/E running MT A/E circulation approx l/hr (assumption) FM2: 1 % of l/hr 10 l/hr FM0 FM3: 1 % of 800 l/hr 8 l/hr l/hr = 18 l/hr of 200 l/hr A/E consumption 9 % error (max) FM0: 1 % of l/hr 42 l/hr Total accuracy of M/E = = 60 l/hr of 4000 l/hr M/E consumption 1,5 % error (max) Booster 1,5 % of 96 tons/day = 1.44 tons/day difference! (max) 1.44 tons/day x 330 days x US$ 300 = US$ / year Sample calculation measurement concept 5 / ASSUMPTIONS: All Flow meter calibrated in pair (0.1 % / 0.3 accuracy) M/E consumption l/hr A/E consumption 200 l/hr Booster pump l/hr Service Tank FM3 FM2 A/E M/E Accuracy M/E with A/E running A/E circulation approx l/hr (assumption) FM2: 0.1% of l/hr 1.0 l/hr FM3: 0.3% of 800 l/hr 2.4 l/hr l/hr = 3.4 l/hr of 200 l/hr A/E consumption 1.7 % error (max) FM0: 0.1% of l/hr à 10.0 l/hr (assume supply = 2.5 x consumption M/E) FM1: 0.3% of l/hr à 18.0 l/hr Total accuracy of M/E=10+18=28.0l/hr of 4000 l/hr M/E consumption 0.7 % error (max) MT Booster pump FM1 FM0 10

11 3.3 Temperature Compensation The installation of temperature sensors at the flow meter positions are absolutely essential for, without temperature compensation of the flow data, the errors in the measurements can become extremely large, depending on the process conditions. As a rule of thumb you can assume almost 1 % volume difference for each 10 C Temperature difference. (Usually there is a temperature difference between the oil temperature in the supply line and in the return line.) With Aquametro Fuel Performance Management Systems like: Fuel Performance Recorder (FPR) CONTOIL Fuel Monitor-S (CFM-S) CONTOIL Fuel Monitor-T (CFM-T) These compensation calculations are done automatically, according to DIN Density Compensation If you need to compare fuel oil consumption in mass instead of volume, it is important to know that the mass is changing with the density, which itself is changing with the temperature. To obtain most precise measurement results, it is recommended to measure the density online on board. If there is no sensor available you have to use the density, which is given in each bunkering report and calculate volume values at different temperatures back to the corresponding mass values. However there is difference in HFO qualities over the world and you should consider that the density mentioned on the bunkering report refers to the required specification. The real density of bunkered fuel is usually not the same. A density difference of 10cSt results approximately in a 1 % different mass value. With Aquametro Fuel Performance Management Systems like: Fuel Performance Recorder (FPR) CONTOIL Fuel Monitor-S (CFM-S) CONTOIL Fuel Monitor-T (CFM-T) These compensation calculations are done automatically, according to DIN Offset in differential measurement Sample calculation for differential measurement ASSUMPTION: Standard calibration 1 % accuracy (CONTOIL VZF): Supply (FM#0) l/h ±1 % = ±100 l/h Return (FM#1) l/h ±1 % = ±100 l/h Max. difference (theoretically) 2 % = 200 l/h Service Tank MT FM1 FM0 M/E ASSUMPTION: pair calibration 0.1 % & 0.3 % accuracy (CONTOIL VZFA): Supply (FM#0) l/h ± 0.1 % = ±10 l/h Return (FM#1) l/h ± 0.3 % = ±30 l/h Max. difference (theoretically) 0.4 % = 40 l/h As seen there remains an offset, even with the better pair calibration, of theoretically 40 litres different values read on supply meter (FM#0) versus return meter (FM#1). With Aquametro Fuel Performance Management Systems like: Fuel Performance Recorder (FPR) CONTOIL Fuel Monitor-S (CFM-S) CONTOIL Fuel Monitor-T (CFM-T) we are able to set an offset value, to avoid this kind of confusion. 11

12 3.6 Layout and Installation Rotary piston meters (such as our CONTOIL ) do not require flow conditioners or inlet runs after bends, T-pieces or fittings. CONTOIL flow meters might be installed in a horizontal, vertical or inclined position. The only requirement is, that the transducer is not pointing downwards. Stop valves / non-return valves must be installed after the flow meter in order to prevent backflow and draining. Backflow and draining can cause measuring errors and can damage the meter. This concept is recommended Formation of gas is to be avoided. Hence the layout of the piping must ensure, that the meter is at all time filled with liquid and that no inclusions of air or gas may occur do not install the meter at the highest point of the installation. This concept is recommended Flow meters must be installed in such a way, that all flow to the consumer and in differential measurement also away from the consumer is counted. Flow via bypass has to be limited to exceptions. Most classifications require a bypass with pressure relieve or manual valve in the fuel supply system, to ensure that the engine can still be operated at full power, even if the filter is heavily contaminated or if the flow meter is blocked due to any reason. The pressure release valve opens as soon as the pressure drops below a defined level and the engine can be temporarily operated without measuring the consumption. This value must be set carefully, to prevent undesirable flow over the bypass - the correct setting must be ensured over the whole range of flow rates and for all possible viscosities (the higher the viscosity the higher the pressure loss). When switching over to the bypass, attention may be drawn to necessary maintenance via an alarm output. 12

13 Tank CONTOIL Filter Pulsation dampers Engine Pressure release valve Pump Pulsation dampers Auto Filter CONTOIL Pulsation dampers Pressure release valve 3.7 Filters / Strainers Filters are any way required in the system to protect engines and pumps to keep their performance and live time. For flow meters this is not different - that s why we recommend installing the flow meters (in flow direction) always directly after the filter. Some particles in the fuel are also from engine s wear and tear, that s why we also recommend a filter in the fuel return line. Usually basket type filters are best choice for the return line and automatic filters in the supply line. Major engine producers recommend a mesh size of 5-10 μm (automatic filters), especially to filter out very abrasive cut fines - it would be best for the flow meter to install it between this automatic filter and the engine. 3.8 Pulsation Dampers Engines and pumps can cause pressure peaks, which are transmitted throughout the whole fuel piping system and can cause damage to all parts in the system like filters, the viscosity control system, pumps themselves as well as the flow meters. It is recommended to install pressure pulsation dampers directly after the device, which is generating such pressure peaks (usually after the pump and after the engine). Sample pictures 3.9 Pressure Loss For the dimensioning of oil meters not only the flow rate, but also the pressure loss is important. All components in the fuel piping system and the piping layout itself cause a pressure loss. In general a higher flow and a higher viscosity cause a higher pressure loss over the flow meter. Piping bends, valves, reduction of pipes, as well as strainers and flow meters do also have a pressure loss, which must be taken into account when dimensioning the fuel supply system. Please check the pressure drop at each flow meter with the help of following pressure drop curves (Appendix I.) For a pressure drop of more than 1 bar, it is recommended to use the next larger flow meter size. Ideally the flow meters are installed on the pressure side of the pump. If the flow meters are on the suction side of the pump there is under pressure, which can cause out-gassing of the oil (1 % gas in the oil causes 1 % measurement failure). Depending on the viscosity of the oil you have to check the pressure loss and decide if there is still enough pressure after the flow meter. Pressure drop curves can be found for all meters from DN 15 to DN 50 in Appendix I. 13

14 3.10 Installation Mechanical Flow meters are sensible sensors, to maintain its high accuracy they have to be treated with care and installed in the correct way. Flow meters with pair calibration are marked / labelled with supply or return and must be installed respectively. supply meter must be installed in the supply line (fuel flow from tank to engine) return meter must be installed in the return line (fuel flow from engine back to tank) Mount flow meters according to the flow direction (see arrow on meter body) Electromagnetically effects are to be avoided (e.g., magnetic valve of the burner). As a basic rule a safety distance of about 40 cm of any potential electromagnetic source is recommended. Insulation of pipe and flow meter must not cover the transducers, as the maximum operating temperature is 70 C. This example is not recommended This example is recommended This example is not recommended This example is recommended 14

15 4. Commissioning / start up Before first use of the whole fuel oil system the pipes are usually flushed to remove all dirt and particles in the system. Flushing must not be done via the flow meters, as they would immediately block the safety filters, or in worst case block the ring piston. If water would be used for flushing, there would be no lubrication, which would also damage the flow meter. Please close all valves before and after the flow meters and open the respective bypasses. Pressure shocks must be avoided in order not to damage the meter. Please open valves slowly and fill pipeline network gradually to avoid pressure surges. Avoid inclusions of air or gas, as both will cause measuring errors and in operation air or gas may damage the meter. If you expect the formation of gas a degasser is strongly recommended. 5. Maintenance CONTOIL Flow Meters are basically maintenance free. Please make sure that no unfiltered fuel flows via the flow meter (close valve before and after flow meter and open bypass). Filters prior to the flow meters must be cleaned periodically, initially at short intervals. Please do not open the flow meter, as long as it is in the guarantee period, as an opened flow meter will loose its guarantee. Warrantee seal measuring chamber DN 25 Warrantee seal measuring chamber DN Warrantee seal transducer group Warrantee seal DFM Meters 15

16 6. Troubleshooting Please check according to this fault finding list before placing a complaint. Fault symptoms Possible causes Solution Pointers on roller counter rotate This is normal at some flow rates and No action required. irregularly has no effect on accuracy of measurement. Counter runs backwards Meter mounted in wrong direction Install meter with arrow pointing in flow direction Counter not running Flow rate outside allowed range Check flow rate. On meters VZF/VZFA: (below Qmin or above Qmax of meter). If too high, reduce flow or install larger sized No flow rate indication. meter. Indicated quantity or flow rate too small. If too low, increase flow or install smaller sized meter. Moving parts heavily worn out due to Install larger sized meter. continuous overload. Dirt trap / filter heavily soiled. Clean dirt trap, replace filter. Safety filter in meter intake clogged. Replace safety filter. Install dirt trap / filter with correct mesh size. Moving parts jammed. Clean measuring chamber, replace defective parts. Separating plate broken by. Check and rectify operating conditions and meter Pressure hammers. position. Gas inclusions. Fill pipe system slowly. De-aerate pipes thoroughly Indicated quantity or flow rate too high Meter positioned wrongly (e.g. at highest Check and rectify operating conditions and meter point). position. Gas or air inclusion in fluid. De-aerate pipes carefully. Pressure drop at meter too high Dirt trap or filter heavily soiled Clean dirt trap, replace filter On meters VZF/VZFA: No power supply. Check wiring. No reading Transducer defective. Replace transducer. Electronic counter defective. Replace transducer. No frequency signal No flow. Check flow using Indication. No current signal Wrong parameterisation. Set correct parameters for outputs. No pulse output signal Transducer defective. Replace transducer. Pulse sensor defective. Replace sensor. Pulse module defective. Remove sensor and check if pulser disk does rotate. Pulser disk does not rotate. Remove pulser module, place counter on first. module, and check flow indication. If indication is positive, replace pulser module, otherwise see Counter not running. Reed pulser defective. Replace roller counter. Please do not open the flow meter, as long as it is in the guarantee period, as an opened flow meter will loose its guarantee. 16

17 7. Warranty Disclaimer Aquametro guarantees the quality of the product in the context of its General Terms of Business. The ship yard, owner or operator will be liable for the correct installation as well as the appropriate handling of the equipment upon its receipt. Please observe the application-, mounting- and operation- instructions! Use the unit exclusively for its designed purpose. Maintain the unit and service it according to prescriptions. Use accessories only if their applicability is technically safe. Warranty shall not cover in particular the following cases: Inadequate installation works (please follow installation instructions) Unsuitable or improper use Faulty or negligent treatment Excess load Unsuitable operating equipment Natural wear and tear Product has been opened Faulty assembly or start-up by the customer or third parties Improper maintenance Chemical, electronic or electrical influences Corrosive media Excessively high media and/or ambient temperatures Broken separating plates due to missing pulsation dampers Blocked flow meters due to missing strainers before the fuel meters. Force majeure 17

18 Appendix I.Pressure Drop Curves DN 15 DN Pressure drop in mbar 10 F E Pressure drop in mbar 10 F E D 1 D C 1 C 0,1 B 0.1 A A 0,01 Flow rate in l/h Flow rate in l/h Q min 10 l/h Q max 600 l/h Q min 30 l/h Q max 1500 l/h DN 25 DN Pressure drop in mbar 10 F E Pressure drop in mbar F 10 E D C 1 D 1 C 0,1 0,1 A A 0,01 Flow rate in l/h ,01 Flow rate in l/h Q min 75 l/h Q max l/h Q min 225 l/h Q max l/h 18

19 DN Pressure drop in mbar 10 F E D 1 C 0,1 A 0,01 Flow rate in l/h Q min 750 l/h Q max l/h Example Mineral oil, viscosity 450 mpa.s VZO 25 mounted on pressure side of pumps ç 1000 ❶ Viscosity curves DN 25 select closest curve F = 500 mpa.s 100 ❷ Assume max. permissible pressure drop = 1 bar Pressure drop in mbar 10 F E å ❸ The intersection of curve F with the line corresponding to 1bar gives a flow rate of l/h. 1 D C 0,1 A 0,01 Flow rate in l/h é Q min 75 l/h Q max l/h 19

20 Änderungen vorbehalten / Sous réserve de modifications Modification rights reserved / Copyright Aquametro AG DISTRIBUTOR: Contact, Adress and Stamp HEAD OFFICE: AQUAMETRO AG Ringstrasse 75 CH-4106 Therwil Phone Fax info@aquametro.com A Art. Nr

Make sure that no hazardous fumes can build up in the piping and in the meter during commissioning, decommissioning and dismantling.

Make sure that no hazardous fumes can build up in the piping and in the meter during commissioning, decommissioning and dismantling. The device and its accessories must only be used for their intended purpose and comply with safety regulations. Aquametro devices are manufactured according to valid standards and guidelines. Aquametro

More information

1/2-2 INSTALLATION INSTRUCTIONS

1/2-2 INSTALLATION INSTRUCTIONS 1/2-2 INSTALLATION INSTRUCTIONS ZE Table of contents General Meter Configuration 1 Application, planning and installation 1 Safety precautions 1 Plant design Layout of piping 2 -Meter installation 2 -Correct

More information

VZO Pressure drop curves See Meter data. Option: Reed pulser or RV / IN pulser

VZO Pressure drop curves See Meter data. Option: Reed pulser or RV / IN pulser VZO 15...50 Technical data 1) Volume display on roller counter, in litres fuel oil meter with threaded or flanged ends for horizontal, vertical or inclined mounting Option: Reed pulser or RV / IN pulser

More information

CONTOIL VZFA/VZOA , versions for higher requirements / applications

CONTOIL VZFA/VZOA , versions for higher requirements / applications CONTOIL VZF/VZO 4...50, versions for higher requirements / applications For applications requiring an increased accuracy of ±0.5 % or better, such as: Measurement of L heating fuel or diesel in testing

More information

VZFA/VZOA MISURATORI DI PORTATA FUEL OIL METERS. CONTOIL VZFA/VZOA , versions for special requirements / applications

VZFA/VZOA MISURATORI DI PORTATA FUEL OIL METERS. CONTOIL VZFA/VZOA , versions for special requirements / applications VZFA/VZOA FUEL OIL METERS MISURATORI DI PORTATA CONTOIL VZFA/VZOA 5...50, versions for special requirements / applications For applications requiring an increased accuracy of ± % or better, such as: Versions

More information

CONTOIL Fuel oil meters

CONTOIL Fuel oil meters CONTOIL Fuel oil meters Applications Flow measurement of mineral oils for heaters and fixed installations. VD 4-410 e 07.2012 Features Classical version with mechanical display State-of-the-art design

More information

VZD / VZP and DFM Consumption measurement

VZD / VZP and DFM Consumption measurement CONTOIL VZD / VZP and DFM Consumption measurement Applications Fuel consumption measurement for trucks, buses, trains, construction and agricultural machinery, small boats and generators. Features Quick

More information

CONTOIL Fuel oil meters

CONTOIL Fuel oil meters CONTOIL Fuel oil meters Applications Flow measurement of mineral oils such as heating or propellant fuels In burners, on board ships, land vehicles and fixed installations Marine and metrological type

More information

INSTALLATION INSTRUCTION & TECHNICAL MANUAL FLOWMETER

INSTALLATION INSTRUCTION & TECHNICAL MANUAL FLOWMETER Sep 2003 INSTALLATION INSTRUCTION & SERIES: MICA (FL & RC) INSTALLATION INSTRUCTION & Type: MICA Series: MICA Page: INSTALLATION CONCEPT... 2 2 MOUNTING POSITION OF THE METER... 2 2. General remarks...

More information

CONTOIL Fuel oil meters

CONTOIL Fuel oil meters CONTOIL Fuel oil meters Applications Flow measurement of mineral oils for heaters and fixed installations. VD 4-410 e 11.2012 Features Classical version with mechanical display State-of-the-art design

More information

VZ-01. Features. Oil Counter for Light to Heavy Fuel Oil. Description: Application: / Mounting on pressure or suction side

VZ-01. Features. Oil Counter for Light to Heavy Fuel Oil. Description: Application: / Mounting on pressure or suction side VZ-01 Oil Counter for Light to Heavy Fuel Oil Description: Features / Mounting on pressure or suction side The VZ-01 series of volume counters are rotary piston meters that function without auxiliary electrical

More information

T O PA S Applications Features Your benefits

T O PA S Applications Features Your benefits TOPAS Hot water Applications The TOPAS hot water meter is a velocity flowmeter based on the well-established multijet measuring principle. It operates over a wide measuring range and is used in all areas

More information

ISTEC Corporation Distributor of CONTOIL Fuel oil meters 1/2"... 2" DN

ISTEC Corporation Distributor of CONTOIL Fuel oil meters 1/2... 2 DN ISTEC Corporation Distributor of CONTOIL Fuel oil meters 1/2"... 2" DN 15...50 GALLONS A versatile flow meter for oil, heavy oil and many other oil-like liquids. It is used for efficient consumption measurement

More information

CONTOIL Fuel oil meters DN

CONTOIL Fuel oil meters DN CONTOIL Fuel oil meters DN 15...50 A versatile flow meter for oil, heavy oil and many other oil-like liquids. It is used for efficient consumption measurement of heat burners and various combustion engines.

More information

Starting up hydraulic systems

Starting up hydraulic systems General / Installation A hydraulic system that operates economically, safely, and trouble-free requires careful planning, as well as proper installation and start-up. Conscientious maintenance has a considerable

More information

NEOTECHA NTB-NTC BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

NEOTECHA NTB-NTC BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installation these instructions must be fully read and understood 2 SAFETY Please also read through these notes carefully. 2.1 General potential danger due to: a. Failure to observe the instructions

More information

FPO 80 FPOC FPOS FPON, FPOS Tank truck vane pump

FPO 80 FPOC FPOS FPON, FPOS Tank truck vane pump FPOC 100 -... FPOS 100 -... FPO 80 Tank truck vane pump Operating instructions FPOD, FPOG, FPOJ, Index Page Proper use 2 Type code 3 Technical data 4 Application notes 4 Dimensions 5 Flow charts 9 Input

More information

These installation and maintenance instructions must be read in full and completely understood before the installation!

These installation and maintenance instructions must be read in full and completely understood before the installation! These installation and maintenance instructions must be read in full and completely understood before the installation! 1. General information on the installation and maintenance instructions These instructions

More information

Rotary Displacement Meter RMG 132-A

Rotary Displacement Meter RMG 132-A Rotary Displacement Meter RMG 132-A OPERATING INSTRUCTIONS Serving the Gas Industry Worldwide STATUS FEBRUARY 2011 by Honeywell Note: Unfortunately, paperwork does not automatically update itself but technical

More information

MidFlow _ 135. Sliding Vane Meters DN (1-2 ) Model PT / Fuel Oil Flowmeters135. Product Bulletin

MidFlow _ 135. Sliding Vane Meters DN (1-2 ) Model PT / Fuel Oil Flowmeters135. Product Bulletin MidFlow Model PT / Fuel Oil Flowmeters135 Sliding Vane Meters DN 25-50 (1-2 ) _ 135 Product Bulletin WWW.VAF.NL 1 Introduction VAF Instruments MidFlow Model PT positive displacement sliding vane type liquid

More information

Operating and installation instructions

Operating and installation instructions Strainer PN6-160 1.0 General information on operating instructions...2-2 2.0 Notes on possible dangers...2-2 2.1 Significance of symbols... 2-2 2.2 Explanatory notes on safety information... 2-2 3.0 Storage

More information

ProFlow TO BE REALLY SURE. Vane Meters. Experience in flow measurement. Introduction

ProFlow TO BE REALLY SURE. Vane Meters. Experience in flow measurement. Introduction ProFlow N142 P R O D U C T B U L L E T I N Vane Meters Special versions This brochure comprises only VAF Instruments standard delivery program. Special flowmeter variants can be offered as tailor-made

More information

CONTOIL Fuel oil meters DN

CONTOIL Fuel oil meters DN CONTOIL Fuel oil meters DN 15...50 A versatile flow meter for oil, heavy oil and many other oil-like liquids. It is used for efficient consumption measurement of heat burners and various combustion engines.

More information

Backflushing Filter AutoFilt RF3

Backflushing Filter AutoFilt RF3 Backflushing Filter AutoFilt C 2,5 4 6 8 1. TECHNICAL SPECIFICATIONS 1.1 GENERAL The automatic back-flushing filter AutoFilt is a self-cleaning system for extracting particles from lowviscosity fluids.

More information

Installation and operating manual

Installation and operating manual LK product no: 901002 and 901102 501002 and 501102 (JIS) Article no: 74500 Revision: 9 Article no: 74500 Revision: 9 2 (23) Contents 1. General information... 5 2. Safety precautions... 5 2.1 Significance

More information

Profluid and Gap-type tube filters. Automatic filters

Profluid and Gap-type tube filters. Automatic filters and Gap-type tube filters Automatic filters and Gap-type tube filters the efficient answer for multi-purpose applications Identical technology two different cleaning principles Automatic filters such as

More information

Operating manual Separator

Operating manual Separator Operating manual Separator Sheet no. AS/4.1.141.1.1 issue 20.08.2014 Contents Section Title Page 0 Introduction... 1 1 Intended use......1 2 Marking of the fitting... 1 3 Safety instructions... 2 4 Transport

More information

Gerotor pump, fixed displacement volume

Gerotor pump, fixed displacement volume Gerotor pump, fixed displacement volume RE 10545/12.11 1/12 Type GZ Component series 1X Maximum operating pressure 15 bar Maximum displacement 140 cm³ H7572_d Table of contents Contents age eatures 1 Ordering

More information

Residential Water Meters

Residential Water Meters EnergyMetering Residential Water Meters Multi-jet wet dial meters Multi-jet dry dial meters Positive displacement meters AMR-technology All that counts. Technology of the highest standard Quality and reliability

More information

RMG Meßtechnik GmbH. Publication No E

RMG Meßtechnik GmbH. Publication No E Turbine meter TRZ 03 RMG Meßtechnik GmbH Publication No. 3.161-E P.O.Box 80 D-3550 Butzbach (Germany) Phone: +49 (0)6033 897-0 Fax: +49 (0)6033 897-130 E-mail: messtechnik@rmg.de Web site: http://www.rmg.de

More information

Rotary Displacement Meter DKZ 02

Rotary Displacement Meter DKZ 02 Rotary Displacement Meter DKZ 02 OPERATING INSTRUCTIONS Serving the Gas Industry Worldwide STATUS APRIL 203 by Honeywell Note: Unfortunately, paperwork does not automatically update itself but technical

More information

Fuel Consumption Measurement _ 124. Application Bulletin

Fuel Consumption Measurement _ 124. Application Bulletin Fuel Consumption Measurement _ 124 Application Bulletin WWW.VAF.NL 1 Introduction Due to the increasing awareness of the impact of exhaust emissions on the environment, combined with the continued increases

More information

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 1054-7 / 34405 www.onicon.com sales@onicon.com

More information

Operating and maintenance instructions VAG RETO-STOP Non-Return Valve

Operating and maintenance instructions VAG RETO-STOP Non-Return Valve Operating and maintenance instructions VAG RETO-STOP Non-Return Valve KAT 1544-B Edition2 02-09 Content 1.General 1.1 Safety 1.2 Proper use 2.Transport and storage 2.1 Transport 2.2 Storage, packaging

More information

ViscoSense 3D. Viscosity & Density Measurement Enabling Mass Flow Measurement. Product Bulletin TO BE REALLY 1 SURE

ViscoSense 3D. Viscosity & Density Measurement Enabling Mass Flow Measurement. Product Bulletin TO BE REALLY 1 SURE ViscoSense 3D Viscosity & Density Measurement Enabling Mass Flow Measurement 774 Product Bulletin WWW.VAF.NL TO BE REALLY 1 SURE 1 Introduction Principle of operation Most of the operating costs of a ship

More information

VERTICAL MULTI-STAGES CENTRIFUGAL PUMPS

VERTICAL MULTI-STAGES CENTRIFUGAL PUMPS Installation and Operating Instructions VERTICAL MULTI-STAGES CENTRIFUGAL PUMPS Models 1, 3, 5, 10, 15, 20, 32, 45, 64, 90, 120, 150 1. Model numbering and nameplate format 1.1 Model numbering Example:

More information

Operating Instruction for Flowmonitor. Model: DF-WM

Operating Instruction for Flowmonitor. Model: DF-WM Operating Instruction for Flowmonitor Model: DF-WM 1. Contents 1. Contents... 2 2. Note... 3 3. Instrument Inspection... 3 4. Regulation Use... 4 5. Operating Principle... 5 6. Mechanical Connection...

More information

VERTICAL MULTI-STAGE CENTRIFUGAL PUMPS

VERTICAL MULTI-STAGE CENTRIFUGAL PUMPS Installation and Operating Instructions VERTICAL MULTI-STAGE CENTRIFUGAL PUMPS Models 1, 3, 5, 10, 15, 20, 32, 45, 64, 90 1. Model numbering and nameplate format 1.1 Model numbering Example: SBI / SBN

More information

Turbine flowmeters Series TM

Turbine flowmeters Series TM Turbine flowmeters Series TM Suitable for liquids Possibility of installation in all flow directions Special design for high pressure available Excellent relationship flow range / flowmeter size Low pressure

More information

Meter FMT II. Operating manual. original operating manual. Translation of the

Meter FMT II. Operating manual. original operating manual. Translation of the Operating manual Meter FMT II Item-No.: 253590000, 253590001, 253590003, 253590004, 253590006, 253590007, 253590008, 253590009, 253590010, 253590011, 253590012, 253590013, 253590020, 253590030, 253590031,

More information

SLR / SLR-S/N. Instruction Manual. Walrus America Inc

SLR / SLR-S/N. Instruction Manual. Walrus America Inc SLR / SLR-S/N Instruction Manual Walrus America Inc 1. Installation and Connection 1.1. Pump Installation The pump should be sited in a well ventilated and frost-free position. The distance between pumps-motors

More information

Swing Piston Compressors and Vacuum Pumps

Swing Piston Compressors and Vacuum Pumps Swing Piston Compressors and Vacuum Pumps NPK 018 AC Pressure NPK 018 DC Pressure NPK 018 AC Vacuum NPK 018 DC Vacuum Operating and Installation Instructions Read and observe these Operating and Installation

More information

Oscillating piston flowmeters Series COVOL Positive displacement flowmeter for liquids

Oscillating piston flowmeters Series COVOL Positive displacement flowmeter for liquids Oscillating piston flowmeters Series COVOL Positive displacement flowmeter for liquids Suitable for all kind of liquids Viscosity up to 120000 mpa s Excellent performance with changing process conditions

More information

Installation and operating manual Quick closing valve (Bellow sealed) LK product no:

Installation and operating manual Quick closing valve (Bellow sealed) LK product no: LK product no: 902002 Article no: 74506 Revision: 2 Contents 1. General information... 3 2. Safety precautions... 3 2.1 Significance of symbols... 3 2.2 Explanatory notes on safety information... 3 3.

More information

NEOTECHA NEOSEAL BUTTERFLY VALVE INSTALLATION AND MAINTENANCE INSTRUCTIONS

NEOTECHA NEOSEAL BUTTERFLY VALVE INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installation these instructions must be fully read and understood 2 SAFETY Please also read through these notes carefully. 2.1 General potential danger due to: a. Failure to observe the instructions

More information

CBU144. Compact Booster Unit - single pump To ensure the quality of potable water according to EN1717. Product specification sheet

CBU144. Compact Booster Unit - single pump To ensure the quality of potable water according to EN1717. Product specification sheet CBU144 Compact Booster Unit - single pump To ensure the quality of potable water according to EN1717 Product specification sheet Version The Compact Booster Unit consists of the following modules, that

More information

Volumeter. RMG Meßtechnik GmbH. Publication No E

Volumeter. RMG Meßtechnik GmbH. Publication No E Volumeter TRZ 03-K RMG Meßtechnik GmbH Publication No. 3.171-E P.O.Box 80 D-3550 Butzbach (Germany) Phone: +49 (0)6033 897-0 Fax: +49 (0)6033 897-130 E-mail: messtechnik@rmg.de Web site: http://www.rmg.de

More information

original operating manual Operating manual Manual flow meter FMOGne Translation of the Item-No.: ,

original operating manual Operating manual Manual flow meter FMOGne Translation of the Item-No.: , Operating manual Manual flow meter FMOGne Item-No.: 027170211, 027170221 Translation of the original operating manual Important! Copyright The operating manual is always to be read before commissioning

More information

SBS Manual for the specialised craftsman. Filling and flushing station. Connection Operation. en Manual

SBS Manual for the specialised craftsman. Filling and flushing station. Connection Operation. en Manual SBS 2000 Filling and flushing station Manual for the specialised craftsman Connection Operation Thank you for buying this RESOL product. Please read this manual carefully to get the best performance from

More information

0.7 m 3 /h - 3 GPM D 07 RE 125 D 07 RE 5. owner s manual

0.7 m 3 /h - 3 GPM D 07 RE 125 D 07 RE 5. owner s manual 0.7 m 3 /h - 3 GPM D 07 RE 125 D 07 RE 5 owner s manual GB You have just become the owner of one of the latest in the line of DOSATRON proportional dosing pumps and we congratulate you on your choice.

More information

PUMP SCPD 56/26 DIN BY-PASS

PUMP SCPD 56/26 DIN BY-PASS GB INSTRUCTION MANUAL THANK YOU FOR CHOOSING SUNFAB You have chosen SCPD 56/26 DIN, a dual flow pump with differentiated flow suitable for combination vehicles with high power take off ratio and high output

More information

Automatic filter AF 173 G

Automatic filter AF 173 G Automatic filter AF 7 G with external pressure cleaning and integrated cyclone effect Connection sizes: G, screw-in flange DN 0 and DN, cast design Short description MAHLE automatic backflush filters are

More information

INSTRUCTION MANUAL. I/P Converter DSG BXXY3Z DSG BXXY4Z

INSTRUCTION MANUAL. I/P Converter DSG BXXY3Z DSG BXXY4Z INSTRUCTION MANUAL I/P Converter DSG BXXY3Z DSG BXXY4Z Revision 2.0 3.626 016136 en Page 1/15 Should you have any questions concerning the I/P converter, please contact the Service Department of the Product

More information

Operating and installation instructions

Operating and installation instructions Check valves Contents 1.0 General information on operating instructions...2-2 2.0 Notes on possible dangers...2-2 2.1 Significance of symbols... 2-2 2.2 Explanatory notes on safety information... 2-2 3.0

More information

Volumeter TRZ 03-K PRODUCT INFORMATION. Reliable Measurements of Gas

Volumeter TRZ 03-K PRODUCT INFORMATION. Reliable Measurements of Gas Volumeter TRZ 0-K PRODUCT INFORMATION Reliable Measurements of Gas Method of operation, Construction Method of operation The TRZ 0-K Volumeter is a flow meter suitable for metering gases, where the rate

More information

Operating and Installation Instructions Swing Piston Compressors and Vacuum Pumps

Operating and Installation Instructions Swing Piston Compressors and Vacuum Pumps Operating and Installation Instructions Swing Piston Compressors and Vacuum Pumps UNPK04DC Pressure UNPK04DCB Pressure UNPK04DC Vacuum UNPK04DCB Vacuum KNF Neuberger, Inc 2 Black Forest Rd Trenton, NJ

More information

Agxcel GX12i Chemical Injection System

Agxcel GX12i Chemical Injection System Agxcel GX12i Chemical Injection System Table of Contents System Contents... 3 Specifications... 4 Safety Precautions and Tips... 5 Operations... 6 Installation... 7 Maintenance... 8-9 Troubleshooting...

More information

RA / Internal Gear Pump Model GP2, Series 2X Fixed Displacement. Typical application:

RA / Internal Gear Pump Model GP2, Series 2X Fixed Displacement. Typical application: Sizes 6.3 to 16 Internal Gear Pump Model GP2, Series 2X Fixed Displacement up to 576 PSI.397 to.98 in 3 (35 bar) (6.5 to 16 cm 3 ) RA 1 23/6.97 RA 1 23/6.97 Characteristics: Peak pressure of up to 576

More information

GF Spin Finish Pump. Translation of the Original Operating Instruction. Edition:

GF Spin Finish Pump. Translation of the Original Operating Instruction. Edition: Translation of the Original Operating Instruction Edition: released: Status: Document no.: Contract no.: V11 01/2018 1-007-3296 Oerlikon Barmag Zweigniederlassung der Oerlikon Textile GmbH & Co. KG Leverkuser

More information

Operating Instructions Garlock Butterfly Valves DN : mm / 2-24

Operating Instructions Garlock Butterfly Valves DN : mm / 2-24 Operating Instructions Garlock Butterfly Valves DN : 50-600 mm / 2-24 PN : 10 / 16 Type: GAR-SEAL SAFETY-SEAL STERILE-SEAL MOBILE-SEAL Conformity declaration... 14 0 Introduction... 15 1 Proper use...

More information

PNEUMATIC PUMP Series

PNEUMATIC PUMP Series PNEUMATIC PUMP Series 3103... User and Maintenance Manual Original text translation TABLE OF CONTENTS 1. INTRODUCTION 2. GENERAL DESCRIPTION 3. PRODUCT-MACHINE IDENTIFICATION 4. TECHNICAL CHARACTERISTICS

More information

Instruction Manual RZ POSITIVE DISPLACEMENT FLOWMETERS 2AU

Instruction Manual RZ POSITIVE DISPLACEMENT FLOWMETERS 2AU Instruction Manual Anderson Instrument Co. Inc. 156 Auriesville Road Fultonville, NY 12072 1-800-833-0081 Fax 518-922-8997 www.anderson-negele.com Instrument Model Number Instrument Serial Number 2A 2AU

More information

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil Type 3535 Three-way Valve with bellows seal and rod-type yoke (partial view) Mounting and Operating Instructions EB 8135/8136 EN Edition

More information

original operating manual Operating manual Translation of the Item-No.: ,

original operating manual Operating manual Translation of the Item-No.: , Translation of the original operating manual Operating manual Item-No.: 015 431 551, 015 431 581 Important! Copyright The operating manual is always to be read before commissioning the equipment. No warranty

More information

Medium and high pressure pumps

Medium and high pressure pumps Screw pumps Medium and high pressure pumps Installation and Start-up Instruction This instruction is valid for all standard high pressure pumps: E4, D4 and D6 Contents Page Pump identification 2 Installation

More information

Declaration of Conformity as per Directive 97/23/EC

Declaration of Conformity as per Directive 97/23/EC Declaration of Conformity as per Directive 97/23/EC The manufacturer declares that:, 47906 Kempen, Germany PTFE-lined Rotary plug valves Series 23e, with packing with lever for 90 operation with worm gear

More information

PLC-3000 zfa01. Portable Fluid Analysis. Global Filtration Technology

PLC-3000 zfa01. Portable Fluid Analysis. Global Filtration Technology zfa01 Global Filtration Technology 157 Why on-site fluid analysis? Certification of fluid cleanliness levels Immediate and accurate results Early warning tool to help prevent catastrophic failures in critical

More information

Pressure relief controller V22 D28

Pressure relief controller V22 D28 Pressure relief controller V22 D28 For heavy oil and high-viscosity media Instructions for Mounting, Start-up and Maintenance SIBC VI.CB.I1.02 Contents 1. General data Page 1.1 Correct application 1 1.2

More information

Temperature sensors. and accessories for heat and cooling measurement points. Applications. Benefits. Features

Temperature sensors. and accessories for heat and cooling measurement points. Applications. Benefits. Features Temperature sensors and accessories for heat and cooling measurement points Applications Temperature sensors are metrological components for heat or cold measuring points. They are used in pairs and measure

More information

Instruction for RBP250-3 and RBP300-3

Instruction for RBP250-3 and RBP300-3 Framo Anti-heeling Pump 1275-0029 -401 Rev.C Instruction for RBP250-3 and RBP300-3 2 of 13 CONTENTS Page 1 General description 2 1.1 Technical data 3 2 Operating information 3 2.1 Prior to initial start

More information

EGQ 212: Duct transducer, CO 2 and temperature

EGQ 212: Duct transducer, CO 2 and temperature Product data sheet 7.0 EGQ : Duct transducer, CO and temperature How energy efficiency is improved Measuring the CO concentration and temperature for energy-efficient, demand-controlled regulation of the

More information

Angle seat valve with piston actuator VZXA-...-K

Angle seat valve with piston actuator VZXA-...-K Angle seat valve with piston actuator VZXA-...-K Instructions Operating (Translation of the original instructions) Festo AG & Co. KG Ruiter Straße 82 73734 Esslingen Germany +49 711 347-0 www.festo.com

More information

These installation and maintenance instructions must be read in full and completely understood before the installation!

These installation and maintenance instructions must be read in full and completely understood before the installation! NEOTECHA These installation and maintenance instructions must be read in full and completely understood before the installation! 1. General information on the installation and maintenance instructions

More information

Instruction Manual. Pneumatic tank contents gauge Unitel # Distributed by

Instruction Manual. Pneumatic tank contents gauge Unitel # Distributed by Instruction Manual Pneumatic tank contents gauge Unitel # 72513 Distributed by Centre Tank Services Ltd. Unit 41, Minworth Industrial Park, Forge Lane, Minworth, Sutton Coldfield, West Midlands B76 1AH

More information

L.A. Maritime describes the operation of Aquametro Fuel-Switching Devices

L.A. Maritime describes the operation of Aquametro Fuel-Switching Devices L.A. Maritime describes the operation of Aquametro Fuel-Switching Devices L.A. Maritime is pleased to announce a new cooperation with Aquametro AG of Switzerland. As of September 1, 2015, L.A. Maritime

More information

Instruction manual. Installation requirements. Power Take-Off. Pump mounting: Spline shaft DIN 5462 / ISO 14. Mounting flange ISO 7653-D.

Instruction manual. Installation requirements. Power Take-Off. Pump mounting: Spline shaft DIN 5462 / ISO 14. Mounting flange ISO 7653-D. GB PUMP SCPD 76/76 DIN Instruction manual Thank you for choosing Sunfab You have chosen SCPD 76/76, a dual flow pump with the highest displacement-to-size-ratio on the market. It can effectively be directly

More information

K - Flow Meter with Float

K - Flow Meter with Float K - Flow Meter with Float Doc. no.: 18, en_cat_k, 12/2014, rev. 1 Application All-metal flow meters with float type K are used for signaling and measuring of instant flow, flowed volume of liquid and fluent

More information

Installation and Operating Instructions DDM-DS11 DDM-DS11-MS1 DDM-DS11-MS2

Installation and Operating Instructions DDM-DS11 DDM-DS11-MS1 DDM-DS11-MS2 Installation and Operating Instructions Differential-Pressure Flow -MS1 -MS2 2 Table of Contents 1. Foreword...3 2. Safety...3 2.1. Symbol and meaning...3 2.2. General safety directions and exemption from

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Industrial Process Installation, Operation, and Maintenance Manual Cam-Tite Ball Valve Table of Contents Table of Contents Introduction and Safety...2 Safety message levels...2 User health and safety...2

More information

RA / Internal Gear Pump Model GP3, Series 3X Fixed Displacement. Typical application:

RA / Internal Gear Pump Model GP3, Series 3X Fixed Displacement. Typical application: Sizes 20 to 32 Internal Gear Pump Model GP3, Series 3X Fixed Displacement up to 5076 PSI 1.25 to 1.98 in 3 (350 bar) (20.6 to 32.5 cm 3 ) RA 10 234/07.97 Characteristics: Peak pressure of up to 5.076 PSI

More information

Air Operated Valve Control Valve

Air Operated Valve Control Valve Air Operated Valve Control Valve -1 Step 0 Type/Structure/Features Please refer to this for structure and feature of Air Operated Valve and Control Valve. Step 1 Selection Please look at the ID chart to

More information

a q u a c o n c e p t Applications Features Benefits

a q u a c o n c e p t Applications Features Benefits aquaconcept Cold water Swiss Made Applications The unique aquaconcept modular design covers a wide range of water applications. This innovative system offers all types of water measurement right up to

More information

PURE SINE WAVE DC TO AC POWER INVERTER

PURE SINE WAVE DC TO AC POWER INVERTER PURE SINE WAVE DC TO AC POWER INVERTER 60S-12A / 60S-24A 60S-12E / 60S-24E 100S-12A / 100S-24A 100S-12E / 100S-24E 150S-12A / 150S-24A 150S-12E / 150S-24E Instruction manual SINE WAVE INVERTER Please read

More information

Industrial Turbo Meters, Sizes 2" through 6"

Industrial Turbo Meters, Sizes 2 through 6 Industrial Turbo Meters Sizes 2" through 6" TUR-UM-00530-EN-19 (October 2014) User Manual Industrial Turbo Meters, Sizes 2" through 6" User Manual CONTENTS Scope of the Manual 5 Specifications 5 Product

More information

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve Type 3310/AT and Type 3310/3278 Pneumatic Control Valves Type 3310 Segmented Ball Valve Fig. 1 Type 3310/3278 with positioner Fig. 2 Type 3310/AT Mounting and Operating Instructions EB 8222 EN Edition

More information

NECO Pumping Systems

NECO Pumping Systems INSTALLATION OPERATION & MAINTENANCE INSTRUCTIONS For Your NECO Pumping Systems Fuel Oil Transfer System THIS COMPLETELY ASSEMBLED, TESTED, PACKAGED SYSTEM IS OF THE HIGHEST QUALITY AND DESIGN. TO OBTAIN

More information

MAP Sensor. Technical Spec COPY RIGHTS ECOTRONS ALL RIGHTS RESERVED ECOTRONS LLC. -Manifold Absolute Pressure Sensor

MAP Sensor. Technical Spec COPY RIGHTS ECOTRONS ALL RIGHTS RESERVED ECOTRONS LLC. -Manifold Absolute Pressure Sensor MAP Sensor -Manifold Absolute Pressure Sensor Technical Spec ECOTRONS LLC COPY RIGHTS ECOTRONS ALL RIGHTS RESERVED Note: If you are not sure about any specific details, please contact us at info@ecotrons.com.

More information

Instruction Manual. RZ Positive Displacement Flowmeters 2AU

Instruction Manual. RZ Positive Displacement Flowmeters 2AU Instruction Manual AndersonInstrumentCo.Inc.. 156AuriesvilleRoad Fultonville,NY12072 1-800-833-0081 Fax518-922-8997 Www.andinst.com InstrumentModelNumber InstrumentSerialNumber 2A 2AU 3A RZ Positive Displacement

More information

Flow. Oval Wheel Flowmeter Model DOE

Flow. Oval Wheel Flowmeter Model DOE Oval Wheel FIowmeter for low and high viscous liquids measuring monitoring analysing DOE Measuring range: 0.5 36 l/h und 1 40 l/min Viscosity range: 1 1000 cp Accuracy: ±1% of reading Material: stainless

More information

WATERFLUX 3070 Quick Start

WATERFLUX 3070 Quick Start WATERFLUX 3070 Quick Start Battery powered electromagnetic water meter Electronic Revision ER 4.3.0_ up to ER 4.3.4_ (SW.REV 4.2.2_ up to 4.2.5_) KROHNE CONTENTS WATERFLUX 3070 1 Safety instructions 4

More information

CONTOIL Fuel oil meters DN 4...8

CONTOIL Fuel oil meters DN 4...8 CONTOIL Fuel oil meters DN 4...8 Vsupply 0.7VDC 20ms Fuel consumption measurement for trucks, buses, trains, construction and agricultural machinery, small boats and generators as well as for burners.

More information

Operating instructions

Operating instructions Operating instructions Digital tank contents indicator DTA 10 DTA 10 DTA 10 0 4.0 m fuel oil 0 3.5 m water Read instructions before using device! Observe all safety information! Keep instructions for future

More information

Mounting and Operating Instructions EB 5894 EN. Electric control valves with jet pump. Flanged version of valve with jet pump

Mounting and Operating Instructions EB 5894 EN. Electric control valves with jet pump. Flanged version of valve with jet pump Electric control valves with jet pump Type 3267/5824, Type 3267/5825, Type 3267/3374, Type 3267/3274 Pneumatic control valves with jet pump Type 3267-1, Type 3267-7 Flanged version of valve with jet pump

More information

Angle seat valve with diaphragm actuator VZXA-...-M

Angle seat valve with diaphragm actuator VZXA-...-M Angle seat valve with diaphragm actuator VZXA-...-M Instructions Operating (Translation of the original instructions) Festo AG & Co. KG Ruiter Straße 82 73734 Esslingen Germany +49 711 347-0 www.festo.com

More information

IMPORTANT!!!! Read this manual before attempting any installation, wiring or operation.

IMPORTANT!!!! Read this manual before attempting any installation, wiring or operation. Industrial Turbo Meters Sizes 2" through 6" Installation & Operation Manual IMPORTANT!!!! Read this manual before attempting any installation, wiring or operation. BadgerMeter,Inc. IOM-003-15 Part No.

More information

Delta Commercial & Industrial Rotary Meter

Delta Commercial & Industrial Rotary Meter Delta Commercial & Industrial Rotary Meter Itron's Delta range of rotary gas meters comprises innovative and high quality products. Characterized by compact dimensions and easy maintenance, the Delta

More information

MX-SERIES OVAL GEAR FLOW METERS

MX-SERIES OVAL GEAR FLOW METERS Data Sheet MX-SERIES OVAL GEAR FLOW METERS Supplied by.com Call us on +44 (0)118 916 9420 Email info@247able.com MX-Series Oval Gear Flow Meters Features and Advantages P From ¼ DN8 at 0.5LPH to 4 DN100

More information

GL Ludemann Y-Strainers

GL Ludemann Y-Strainers GL Ludemann Y-Strainers Installation, Operation and Maintenance Manual English Issue 1-03/2014 - Page 1/7 GENERAL These instructions are for installing, operation and maintenance of Y-strainers fabricated

More information

Hydraulic Immediate Need Power Pack

Hydraulic Immediate Need Power Pack Safety, Operation, and Maintenance Manual WARNING Improper use of this tool can result in serious bodily injury This manual contains important information about product function and safety. Please read

More information

CONTOIL DN15-50 VZF / VZFA. Table of content. Mounting and operating instructions Page 3 43

CONTOIL DN15-50 VZF / VZFA. Table of content. Mounting and operating instructions Page 3 43 Mounting and operating instructions Page 3 43 CONTOIL DN15-50 VZF / VZFA Table of content 1 Safety 3 2 Scope of supply and accessories 6 3 Installation 7 4 Operation 15 5 Maintenance and Repair 25 6 Troubleshooting

More information