INSTALLATION 2.1 SELECTION OF SITE

Size: px
Start display at page:

Download "INSTALLATION 2.1 SELECTION OF SITE"

Transcription

1 INSTALLATION MANUAL

2 INSTALLATION 2.1 SELECTION OF SITE Proper space should be there for placement and opening of doors of the Silent DG Set. There should be at least 2 meter free space around the DG Set for proper access to initial product delivery and installation, operation, service i.e. for general maintenance and inspections and working space for major work such as overhauls or component removal/replacement. There should be cross ventilation and free flow of cool, clean and fresh air flow from alternator end to engine to ensure proper cooling of DG Set. Exhaust gases and hot air discharge should not re-circulate inside the acoustic enclosure (canopy). For basement installations, supply of fresh air and forced ventilation through air ducts is required to remove heat. There should be no restriction for fresh air suction and hot air discharge. If 02 DG sets are installed at the site, ensure that hot air outlet of the one DG set does not become the fresh air intake of the 2nd DG set. A low height shelter for the Silent DG set should be avoided. It should not obstruct the hot air outlet. It is preferable to install the DG Set in an open area. No shade (roof) is required over it. However, if the AMF Panel is outside the Acoustic Enclosure, then a shelter is recommended for the Panel. For Roof Top Installation, ensure that the civil structure is capable to bear the static and dynamic load of DG set. The load of the Silent DG set should be borne by Columns and Beams of the building. Proper space should be there for earthing. If there are no space constraints, the DG set should be placed near the distribution panel. The DG set should be located away from polluted surrounding such as corrosive fumes, cement dust, fibres, cotton and toxic chemicals to avoid overheating of the DG set. For Humid / Coastal atmospheric applications, anti condensations heaters are mandatory for alternator.

3

4 2.2 FOUNDATION DETAILS AND GUIDELINES A. Ground base Foundation (RCC/PCC) The length and width of the Foundation should be at least 200mm to 400mm more than Acoustic enclosure length and breadth respectively. Check the base/foundation level diagonally as well as across the length for even flatness and same should be within ± 0.5 degree of any horizontal plane. Ensure that the concrete is completely set and hardened before positioning the enclosure Do not install acoustic enclosure on lose sand or clay. A rigid foundation ensures the least vibration. Sand Filling should be there around the foundation. Rubber matting can also be used over the foundation to minimize the vibration effect and noise leakage. Please refer to the dimension of DG set for deciding the foundation length, width and depth. Note: Please ensure that the foundation should not be made over any basement, Water tank or Sewer line.

5 B Roof Top Foundation The weight of Silent DG se should be on Column and Beam through proper foundation. The RCC foundation should be on the Beam or supported on two Beams. ISMC Channel or MS "I" Section may also be used to cater the load of the DG set with the canopy. Load of ISMC Channel or MS "I" Section should be on the column of the building. M.S. Sheet is to be provided at the bottom of the base frame of the Silent DG set for roof top installation. Whenever seismic events are a consideration, a qualified structural engineer should be consulted. Note: An inadequate foundation may lead to excessive genset vibrations resulting in Radiator leaks, failure of the auto electric and safety system, or failure of gauge, Coupling or other engine parts.

6 2.3 EARTHING SYSTEM An Earthing system is required for the protection of equipment and human being, as per Indian electricity Rules 1956.Grounding should be done in accordance with applicable National, local code or regulation. Separate earth should be used for body and neutral earthing. 4 Nos. earthing pits are required for DG set, 2 each for neutral & body. The min. distance between 2 earthing pits should be 2.0 meters. An earth pit cover should be provided. A watering pipe of 19mm with a funnel should be provided for each pit, wherever depth of the earthing pit is not at water level. Earthing system should be checked with meagre and maximum 1.0 ohm resistance should be ensured. The earthing plate/pipe and strip should be selected as per the rating of the DG set.

7 2.4 VENTILATION AND COOLING: The radiated heat given off by the engine, generator and exhaust piping can result in a temperature high enough to adversely effect operating and maintenance personal or the performance of the genset. Locate the genset in a room or area that will provide or allow sufficient ventilation to remove this heat as well as the heat radiated from the engine cooling water by the radiator. If the enclosures are placed in an enclosed place, ensure that enclosure is well ventilated and exhaust gases are driven out of the enclosure. Points to remember in any type of installation: Ensure that hot air is positively discharged from the building by fitting a flexible connection between the radiator and duct. The size of the openings should be calculated to ensure that excessive restriction is not imposed on the flow of cooling air. Openings should atleast be as big as the radiator core area but, as a guide, an area on 150% of the core area of the radiator should be allowed for. VENTILLATION SYSTEM FOR LIQUID COOLED/WATER COOLED DG SETS

8 2.5 EXHAUST PIPING The exhaust system is used to direct exhaust gases to non-confined areas and reduce the noise to tolerable levels. The exhaust system must be designed to keep the resistance to hot gases (back pressure) as low as possible. Excessive back pressure in exhaust system will create horse power loss and increase the engine operating temperature and emissions. The following may please be noted. The load of the extended exhaust pipe/silencer should not be on the engine manifold. There should not be any load or stress on the exhaust below. A uniform gap has to be maintained between bellow flange and exhaust pipe flange. There should be proper support for the exhaust pipe if required dampers are used at points of high vibration & pipes should be extended through proper flanges only. At points where the piping passes through a wall or roof, a metal thimble guard 300mm in diameter slightly larger than the pipe should be installed. When bends are required in an exhaust system, always make the radius atleast 150% of the inside diameter of the pipe. The exhaust pipe should be routed in a path that offering the least amount of turns or bends so not to increase back pressure more than 50 mm of Hg. Short bends should be avoided. Exhaust pipe outside the enclosure should be wrapped with high temperature insulation along with aluminum sheet cladding or installing fitted insulated sections will aid in preventing excessive heat radiation with in room. Always use proper size M.S. pipes (G.I. pipe and bend should not be used in exhaust piping). Exhaust outlet should be in the direction of prevailing winds. There should be rain trap to avoid rain water entry. If rain cap is used the distance between exhaust pipe and rain cap should be higher than diameter of the pipe. It is also recommended that horizontal run of exhaust piping should slope downwards away from engine to the condensate trap. Silencer should install with drain plug at bottom. Each genset installation should have its own exhaust system and should not be connected to a system accommodating more than one genset as the possibility of exhaust gas and condensation backflow may cause permanent damage to an idle engine.

9 EXHAUST PIPING EXTENSION Note: Health Warning: Inhalation of exhaust fumes is potential lethal. Correct installation of exhaust systems to prevent accumulation of exhaust gas cannot be over emphasized. Air Cooled Description Unit 15 KVA - 35 KVA 40 KVA KVA 75 KVA Exhaust pipe Dia mm Water cooled R- Series Description Unit 15 KVA - 35 KVA 40 KVA KVA 75 KVA 100 KVA-125 KVA Exhaust pipe Dia mm SL Series Description Unit 140 KVA KVA Exhaust pipe Dia mm 125 K Series Description Unit 275 KVA 320KVA 400KVA-625 KVA Exhaust pipe Dia mm x 150

10 2.6 FUEL SYSTEMS The fuel system must be capable of delivering to the engine a clean and continuous supply of fuel. When designing a fuel system, always incorporate the requirements of Local, State, or National Codes, which may pertain to either the fuel system or the electrical apparatus utilized by the system. FUEL SYSTEM LAYOUT A. Diesel Fuel Bulk Storage Bulk fuel storage is the most preferable method of providing fuel supply. This method allows bulk fuel purchases which will minimize dirt and contamination possibilities, especially when the fuel is seldom used. The bulk storage tank may be located either above or below the ground. A vent must be installed on the main tank to relieve the air pressure created by filling the tank as well as preventing a vacuum within tank as fuel is consumed. The tank bottom should be rounded and placed on a 2 degree tilt to assure a concentrated settling of both water and sediments. At the low point of the tank a drain valve should be installed to remove water that may accumulate due to condensation. Underground tanks must be pumped periodically to remove this water. This is best done by placing a tube through the filter pipe to the low end of the tank. For these reasons it is imperative that the tank be placed in or on stable ground to assure that eventual settling does

11 not change the location of the low point of the tank. Burying the tank below the frost line will help in avoiding seasonal settling. Another consideration to be made when locating the main tank is the height difference between it and the auxiliary tank (day tank). The maximum vertical lift capability of a standard electric motor driven fuel transfer pump is 5m. Do not place either tank at a level that would exceed the pump lift capabilities. Also keep in mind the possibilities of pressure drop created by excessive horizontal distances and pipe work bends. The fuel delivery line carrying fuel to the engine and the fuel return line for carrying excessive fuel back to the tank should be no smaller than the fitting sizes on the engine. For longer runs or extremely low ambient temperatures increase the size of these lines to ensure adequate flow. The fuel lines can.be made of any fuel compatible material such as steel pipe or fuel line tube that will tolerate ambient conditions. Overflow piping should be of the same material and one size larger. The fuel return line should enter the tank at the top and contain no shut-off valve. This line should be designed with a minimum amount of bends or dips to prevent an air lock in the system. The fuel delivery line should pick up the fuel from the point no lower than 20mm from the bottom of the tank. If at all possible locate this line at the end of the tank opposite that of the return line and at the high end of the tank. Flexible fuel lines should be used at a point between the tank and engine (preferably adjacent to the genset) to avoid the potential damage that could be created by vibration. B. Day Tanks Auxiliary tanks or day tanks as they are commonly referred to are recommended. All standard gensets with acoustic enclosure are provided with tank fitted in the base frame. This day tank will produce a ready fuel supply.

12 2.7 LUBRICATING SYSTEM The engine's lubricating system is designed to: Reduce friction Cool Seal Scavenge Dampen shocks Lub oil specifications: The operating life of an engine depends on the use of the correct type of lub. oils. To ensure this, oils recommended by the engine manufacturer should be used. Oil confirming to IS: 496( 1979 HD type 5 or U.S. Military standard MIL-L-2104-C must be used for industrial/ automotive naturally aspirated and turbo charged diesel engines.all standard lubricating oils have a brand name and the SAE number. The brand name indicates the oil specification. The SAE number denotes the oil viscosity. Oil viscosity is selected according to the ambient temperature as shown below: Temperatures above 45 C SAE 40 Temperatures 10 C to 45 C SAE 30 Temperatures -5 C to 10 C SAE 20 W Temperatures -15 C to -5 C SAE 10 W Where the temperature variation between minimum and maximum is very wide, multigrade oils should be used. Also multi-grade oil is better than mono-grade oil. Example : SAE 20W40 is a multi-grade oil and can be used where atmospheric temperature is between -5 C to 45 C and above. (Which is applicable to normal Indian climatic condition.) KOEL recommends to use K-Oil which confirms to the following specifications: US Military: MIL- L-2104C. Indian Std.: IS: HD type 5 OR IS: E-DL3. API: SC/CD Recommended for all types of NA & Turbocharged Diesel Engines. KOEL recommends to use K-Oil A premium quality heavy duty multi-grade 20W40 Engine Oil which exceed specification of US MIL-L-2104C/APSC/CD & IS EDL-3. MACK T-7 Engine Test Approved. Recommended for all types of NA & Turbocharged Diesel Engines.

13 The oil sump is usually fitted on the lowest part of the engine. It is provided with a drain plug to Enable oil draining. Oil sumps are of two types: Standard Sump - for stationary applications. Deep sump - for industrial automotive applications. LUBRICATING SYSTEM The dipstick measures the quantity of oil in the sump. It is usually grooved with low and high markings to help users maintain the correct oil level in the sump. DIPSTICK CAUTION: Oil level to be checked when the engine is in cold condition.

14 2.8 Filters and Traps Clean fuel will aid in attaining maximum engine life and dependability. Primary filters are recommended for use between the engine filters and the transfer pump. Water and sediment traps should also be included upstream of the transfer pump. However, on border line pump installations do not increase fuel line restrictions to a point exceeding the capabilities of the pump. 2.9 FIRE PRECAUTIONS When designing a genset installation the following points should be noted: The room should be designed so that there is an easy escape route for operating personnel in the event of fire within the room. A recommended type of fire extinguisher or fire extinguishing system should be provided to fight the fire. Gravity operated fire valves operated by fusible links, mounted above the engine, can be installed in the fuel lines. The room should be kept clean and free from accumulated rubbish which can be a fire hazard ELECTRICAL CONNECTION Only fully qualified and experienced electrical technicians should be allowed to carry out electrical installation work. The electrical connection to the genset should be made with flexible cable to prevent the transmission of vibration and possible damage to the alternator or circuit breaker terminals If it is not convenient to use flexible cable throughout then a link box can be installed close to the set with a flexible connection between it and the set. The cable may be laid in a duct or on cable tray. When bending cable reference must be made to the recommended minimum bending radius. No rigid connection should be made between the set and the cable support system, e.g., cable tray. When single core cables are used the gland plates must be of non-ferrous material, e.g., aluminum, brass or a non-metallic material such as Teflon. The cable must be suitable for the voltage being used and adequately sized to carry the rated current with allowances made for ambient temperature, method of installation, proximity of other cables, etc. All electrical work should be carried out in accordance with any applicable National, Local Standards, Codes or Regulations. All connections should be carefully checked for integrity. Phase rotation must be checked for compatibility with the installation. This is vitally important when connection is made to an auto transfer switch, or if the machine is to be paralleled. NOTE: A. correct size Cable glands should always be used for holding the cable. B. Control Wiring should always be done with 2.5sq.mm copper cable.

15 2.11 BATTERY CHARGING PROCEDURE A. Battery charging procedure If dry battery is supplied along with the DG set then initial charging of the battery is required. Please get initial charging of the battery done from an authorized service dealer of the battery manufacturer. The initial charging process is of 72 hours. Specify gravity of acid inside the battery should be 1.23 to 1.28 kg/liter. B. Method to use charged battery If charged battery has been provided along with the DG set, and the DG set is not in use then ensure that at positive terminal battery lead is not connected. It should be connected at the time of the commissioning of the DG set. Charged battery may be used for commissioning of DG set within days; else recharging of charged battery is required. Always connect the battery with the proper battery charger. The battery should be connected to the battery charger, which is connected with 230V AC supply. The Battery charger is provided with an AMF Panel (Auto Mains Failure Panel) under the standard scope of supply. 230V AC supply is essential for battery charger operation. Note: Battery charger is not supplied with a standard manual Panel. So, it is Suggested that the DG set must run once a day for minutes so that Battery is charged by engine dynamo/ charging alternator. C. Precaution to be taken during handling of battery. Do not charge the battery at a wet a place. Flame, Candle and matchbox should not be used near charged battery. Use hand gloves while handling the charged battery. Electrolyte level should be below the neck. Always switch off the charger first before disconnecting the battery from the DG set. Never put tools etc. on the battery.

Installation manual. Intake system and ventilation. Industrial engines DC09, DC13, DC16 OC16. 01:02 Issue 10 en-gb. Scania CV AB 2018, Sweden

Installation manual. Intake system and ventilation. Industrial engines DC09, DC13, DC16 OC16. 01:02 Issue 10 en-gb. Scania CV AB 2018, Sweden Installation manual Intake system and ventilation Industrial engines DC09, DC13, DC16 OC16 01:02 Issue 10 en-gb Changes from the previous issue...3 Intake air...4 Intake air taken from outside engine room...

More information

Eclipse GEN 2.0 CAFSystem, Model 150-ECL CAFS PTO Kit Installation Instructions

Eclipse GEN 2.0 CAFSystem, Model 150-ECL CAFS PTO Kit Installation Instructions Eclipse GEN 2.0 CAFSystem, Model 150-ECL CAFS PTO Kit Installation Instructions Read Read through the the safety installation information instructions overhaul carefully instructions before carefully beginning

More information

Installation manual. Exhaust system. Marine engines DI09, DI13, DI16. 02:04 Issue 9.0 en-gb. Scania CV AB 2017, Sweden

Installation manual. Exhaust system. Marine engines DI09, DI13, DI16. 02:04 Issue 9.0 en-gb. Scania CV AB 2017, Sweden Installation manual Exhaust system Marine engines DI09, DI13, DI16 333 380 02:04 Issue 9.0 en-gb Changes from the previous issue...3 Important data... 30 Sound reduction...3 Exhaust noise... 3 Exhaust

More information

Light condition and operation Windshield glass condition Wiper blade condition Paint condition and corrosion Fluid leaks Door and hood lock condition

Light condition and operation Windshield glass condition Wiper blade condition Paint condition and corrosion Fluid leaks Door and hood lock condition GENERAL CHECKS Engine Compartment The following should be checked regularly: Engine oil level and condition Transmission fluid level and condition Brake fluid level Clutch fluid level Engine coolant level

More information

5.5KVA GENERATOR MODEL NO: PG6500DVES OPERATION & MAINTENANCE INSTRUCTIONS PART NO: LS0616

5.5KVA GENERATOR MODEL NO: PG6500DVES OPERATION & MAINTENANCE INSTRUCTIONS PART NO: LS0616 5.5KVA GENERATOR MODEL NO: PG6500DVES PART NO: 8857810 OPERATION & MAINTENANCE INSTRUCTIONS LS0616 INTRODUCTION Thank you for purchasing this CLARKE 5.5KVA Generator. Before attempting to use this product,

More information

CATERPILLAR 3516B DP2 System

CATERPILLAR 3516B DP2 System CATERPILLAR 3516B DP2 System CONTENTS System Overview 3 Offshore Rig or Ship DP2 Package 3 Main Generator Diesel Skid 3 Main Generator Diesel Engines 3 Instrument, Alarms and Automatic Start/Stop System

More information

3KVA DUAL VOLTAGE GENERATOR MODEL NO: PG3800DV

3KVA DUAL VOLTAGE GENERATOR MODEL NO: PG3800DV 3KVA DUAL VOLTAGE GENERATOR MODEL NO: PG3800DV PART NO: 8857815 OPERATION & MAINTENANCE INSTRUCTIONS LS1016 INTRODUCTION Thank you for purchasing this CLARKE 3KVA Dual Voltage Generator. Before attempting

More information

SOS SERIES SOS1 SOS2. Spares On Site Battery Cabinet Installation Guide rEV3

SOS SERIES SOS1 SOS2. Spares On Site Battery Cabinet Installation Guide rEV3 Atlantic Battery Systems 1065 Market Street Paterson, NJ 07513 Phone: (800) 875-0073 Fax: (973) 523-2344 sales@atbatsys.com www.atbatsys.com SOS1 SOS2 SOS SERIES Spares On Site Battery Cabinet Installation

More information

Transformer Installation, Operation, and Maintenance Manual

Transformer Installation, Operation, and Maintenance Manual Transformer Installation, Operation, and Maintenance Manual CONTENTS INTRODUCTION......................................... 2 INSPECTION UPON RECEIVING... 2 STORAGE...............................................

More information

Eclipse GEN 2.0 CAFSystem, Model 150-ESECL as used with TC20 Series PTO Installation Instructions

Eclipse GEN 2.0 CAFSystem, Model 150-ESECL as used with TC20 Series PTO Installation Instructions Eclipse GEN 2.0 CAFSystem, Model 150-ESECL as used with TC20 Series PTO Installation Instructions Read Read through the the safety installation information instructions overhaul carefully instructions

More information

Tubular Centrifugal Fans

Tubular Centrifugal Fans Tubular Centrifugal Fans Model TCB Inline - Horizontal or Vertical Roof Upblast and Roof Supply March 2007 Tubular Centrifugal Fans The TCB series of inline centrifugal fans is designed for ducted inline,

More information

Installation Instructions for Aux 101 Kit A044Z055

Installation Instructions for Aux 101 Kit A044Z055 Instruction Sheet 7-2013 Installation Instructions for Aux 101 Kit A044Z055 1 Introduction The information contained within is based on information available at the time of going to print. In line with

More information

AC Induction Motors. Installation and operating instructions

AC Induction Motors. Installation and operating instructions AC Induction Motors Installation and File No: 48.80 Date: january 28, 2014 Supersedes: 48.80 Date: july 30, 2013 contents Receiving inspection and handling 4 Installation / mounting 4 Location 5 Electrical

More information

Installation and Commissioning of Auxiliary Power Unit

Installation and Commissioning of Auxiliary Power Unit Models PC6012 PC6013 PC6014 PC6015 PC6022 PC6023 PC6024 Installation and Commissioning of Auxiliary Power Unit 30-871-21 Rev. E Warning & Cautions Vehicles with longer wheel bases should have the APU mounted

More information

TECHNICAL SPECIFICATIONS FOR 380/410 KVA, 6 CYLINDER DIESEL GENERATOR SET PACKAGED BY SCOPE OF SUPPLY FOR DIESEL GENERATING SET PACKAGE

TECHNICAL SPECIFICATIONS FOR 380/410 KVA, 6 CYLINDER DIESEL GENERATOR SET PACKAGED BY SCOPE OF SUPPLY FOR DIESEL GENERATING SET PACKAGE MAHINDRA TECHNICAL SPECIFICATIONS FOR 380/410 KVA, 6 CYLINDER DIESEL GENERATOR SET PACKAGED BY ENGINE: Mahindra Scania Internal Combustion (IC) Diesel Engine conforming to BS5514 Standards CPCB Emission

More information

Installation Instructions

Installation Instructions GEMINI SELECT 38APS025-065, 38APD025-130 Air-Cooled Condensing Units with PURON Refrigerant (R-410A) 50/60 Hz Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

MULTIVOLTAGE PORTABLE BATTERY CHARGER MVM

MULTIVOLTAGE PORTABLE BATTERY CHARGER MVM _ M MULTIVOLTAGE PORTABLE BATTERY CHARGER MVM User's MANUAL Code: MVM Version: 01-BF Date: OCT 2005 Page 1/10 _ 1. INTRODUCTION Before starting to use your Energic plus MVM battery charger, please take

More information

AIR COOLED CHILLERS WATER COOLED CHILLERS

AIR COOLED CHILLERS WATER COOLED CHILLERS AIR COOLED CHILLERS WATER COOLED CHILLERS STANDARD UNIT SPECIFICATIONS OF COMMERCIAL AIR COOLED CHILLERS General Description & Assembly Air Cooled Chillers are commercial packaged systems complete with

More information

P239-1 Supply Pumper Instructions

P239-1 Supply Pumper Instructions P239-1 Supply Pumper Instructions STOP! READ THIS SECTION NOW. The following information is critical to the proper installation and operation of this Oil Supply System! Read it carefully before starting

More information

Cooling system components, removing and installing

Cooling system components, removing and installing Page 1 of 40 19-1 Cooling system components, removing and installing WARNING! The cooling system is pressurized when the engine is warm. When opening the expansion tank, wear gloves and other appropriate

More information

1/2" AIR DRIVEN DIAPHRAGM PUMP

1/2 AIR DRIVEN DIAPHRAGM PUMP 1/2" DRIVEN DIAPHRAGM PUMP OPERATION AND SERVICE GUIDE O-1225D NOV. 2008 Page 1 of 6 Refer to Bulletin P-605, Parts List P-9151 DRIVEN, DOUBLE DIAPHRAGM PUMP MANUAL Congratulations on purchasing one of

More information

Parsun Portable 4-Stroke Outboard Motor Winterize or Storing DIY Service Guide

Parsun Portable 4-Stroke Outboard Motor Winterize or Storing DIY Service Guide Parsun Portable 4-Stroke Outboard Motor Winterize or Storing DIY Service Guide To help keep your engine in tip-top condition for years to come, it is important that you winterize your outboard for off-season

More information

Polypropylene Piston Drum Pumps

Polypropylene Piston Drum Pumps Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

PIPINGSOLUTIONS, INC.

PIPINGSOLUTIONS, INC. Piping Stress Analysis Where do I start? The following information will take you step-by-step through the logic of the data collection effort that should occur prior to beginning to model a piping system

More information

Application & Installation Guide. Crankcase Ventilation Systems LEBW

Application & Installation Guide. Crankcase Ventilation Systems LEBW Application & Installation Guide Crankcase Ventilation Systems LEBW4958-04 Contents Crankcase Ventilation Systems... 1 Crankcase Emissions... 2 Blow-by... 2 Crankcase Ventilation... 3 Ingestive... 3 Low

More information

JCB DIESEL GENERATOR TECHNICAL SPECIFICATIONS

JCB DIESEL GENERATOR TECHNICAL SPECIFICATIONS JCB DIESEL GENERATOR TECHNICAL SPECIFICATIONS G2000QX G2000X Powered by MITSUBISHI ELECTRICAL PRIME STAND BY Output Rating kva 1892 2035 kw 1514 1628 Frequency Hz 50 Rated Speed RPM 1500 Standard Voltage

More information

BSS Examination Record Form for Privately Owned and Managed Vessels

BSS Examination Record Form for Privately Owned and Managed Vessels BSS Examination Record Form for Privately Owned and Managed Vessels [Edition 1.04 April 2013] Current boat name Former name Reg. number or index Length (m) Berths Hull material Hull colour Superstructure

More information

INSTALLATION AND OPERATING INSTRUCTIONS FOR CONCRETE VAULT TYPE UNITS

INSTALLATION AND OPERATING INSTRUCTIONS FOR CONCRETE VAULT TYPE UNITS INSTALLATION AND OPERATING INSTRUCTIONS FOR CONCRETE VAULT TYPE UNITS CONTENTS Introduction Safety Operating Principle System Installation Initial Startup System Operations Troubleshooting Maintenance

More information

SERIES COOLING TOWER. MULTI-CELL HRT COOLING CAPACITY Modular Design Crossflow Type LOW NOISE SUPER LOW NOISE ENERGY SAVING SUPER LOW NOISE

SERIES COOLING TOWER. MULTI-CELL HRT COOLING CAPACITY Modular Design Crossflow Type LOW NOISE SUPER LOW NOISE ENERGY SAVING SUPER LOW NOISE TX-S SERIES COOLING TOWER MULTI-CELL 100-2000 HRT COOLING CAPACITY Modular Design Crossflow Type LOW NOISE SUPER LOW NOISE ENERGY SAVING SUPER LOW NOISE TX-S Series is an induced draft cross-flow, film

More information

Integral Horsepower DC Motor & Generator Application Data CA608D

Integral Horsepower DC Motor & Generator Application Data CA608D Integral Horsepower DC Motor & Generator Application Data CA8D Table of Contents Air Requirements DPSV.................................................................... D-45 Altitude Temperature.......................................................................

More information

MMA 160S ARC/MMA WELDER OPERATION INSTRUCTIONS

MMA 160S ARC/MMA WELDER OPERATION INSTRUCTIONS www.r-techwelding.co.uk MMA 160S ARC/MMA WELDER OPERATION INSTRUCTIONS 2 Thank you for selecting the R-Tech MMA160S Inverter Arc Welder. The MMA160S has many benefits over traditional Arc welders, including

More information

Program IV: ProStar TM. Performance A/C International. Series. Study Guide Performance A/C Program IV: International ProStar Series TMT

Program IV: ProStar TM. Performance A/C International. Series. Study Guide Performance A/C Program IV: International ProStar Series TMT Performance A/C International A N AV I S TA R C O M PA N Y Program IV: ProStar TM Study Guide TMT-160701 Series Study Guide Performance A/C Program IV: International ProStar Series TMT-160701 2007 International

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual Manual Polymer Makedown Systems Manufacturers of Quality Pumps, Controls, and Systems Standard Product Operations 27101 Airport Rd., Punta Gorda, FL 33982

More information

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION:

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION: DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION: These instructions are provided to familiarize the user with the seal and its use. The instructions must be read carefully

More information

Expert Design...Trusted Power

Expert Design...Trusted Power Expert Design...Trusted Power 350 750 kva Range Performance I Durability I Serviceability A new power standard has arrived. The 350 750 kva range from FG Wilson is designed by our expert engineers to

More information

EPLX and D2LX lighting panelboards Installation & maintenance information IF 1813 APPLICATION D2LX/EPLX IF SHEET TABLE OF CONTENTS WEIGHTS

EPLX and D2LX lighting panelboards Installation & maintenance information IF 1813 APPLICATION D2LX/EPLX IF SHEET TABLE OF CONTENTS WEIGHTS EPLX and D2LX lighting panelboards Installation & maintenance information APPLICATION EPLX and D2LX panelboards provide a centrally controlled switching system and short circuit protection for feeder or

More information

4.2 Component Identification

4.2 Component Identification Digital Control Panels Deep Sea Electronics 5220 4.1 General 4.2 Component Identification 4.3 The YML5220 Controller 4.4 Description of Controls 4.5 Navigation 4.5.1 General Navigation 4.5.2 The Event

More information

1106A-70TAG4. Series kwm 1500 rpm ElectropaK. Basic technical data. General installation

1106A-70TAG4. Series kwm 1500 rpm ElectropaK. Basic technical data. General installation 1106A-70TAG4 196.3 kwm (Gross) @ 1500 rpm ElectropaK Basic technical data Number of cylinders.......................................................6 Cylinder arrangement................................................in-line

More information

Cylindrical Silencers

Cylindrical Silencers Cylindrical Silencers A200 Series and 300 Series Installation and Operation Manual Rev. B (c) Copyright 2012, GT Exhaust, Inc. All Rights Reserved Published: April 30, 2012 NOTICE The instructions herein

More information

Compressor Enclosures. Motorised Sliding Doors. Air Handling Units, Ventilation Systems & Ducting. IP56 Genset Enclosures for offshore application

Compressor Enclosures. Motorised Sliding Doors. Air Handling Units, Ventilation Systems & Ducting. IP56 Genset Enclosures for offshore application Product Line Military Application Project Modular Enclosures Containers Generators Pumps Power supply for Missile Launcher System Power supply for Radar Control System Vehicle mounted mobile workshop vehicle

More information

Pyrolance, LLC SPECIFICATIONS FOR DIESEL ENGINE DRIVEN ULTRA HIGH PRESSURE FIRE FIGHTING SYSTEM B2000 M-D

Pyrolance, LLC SPECIFICATIONS FOR DIESEL ENGINE DRIVEN ULTRA HIGH PRESSURE FIRE FIGHTING SYSTEM B2000 M-D SPECIFICATIONS FOR DIESEL ENGINE DRIVEN ULTRA HIGH PRESSURE FIRE FIGHTING SYSTEM B2000 M-D 1 HIGH PRESSURE FIRE FIGHTING SPECIFICATIONS Scope and General Design Requirements A fire fighting system shall

More information

John Crane Type 5620 and 5620PR Dual O-Ring Cartridge Seal Assembly and Installation Instructions

John Crane Type 5620 and 5620PR Dual O-Ring Cartridge Seal Assembly and Installation Instructions I-5620/5620PR-A John Crane Type 5620 and 5620PR Dual O-Ring Cartridge Seal Assembly and Installation Instructions Foreword These instructions are provided to familiarize the user with the seal and its

More information

Air Compressor. Operating & Maintenance Instructions 1110 ENGINE DRIVEN - 1 -

Air Compressor. Operating & Maintenance Instructions 1110 ENGINE DRIVEN - 1 - Air Compressor ENGINE DRIVEN Operating & Maintenance Instructions 1110-1 - Read these safety instructions before using the equipment. INTRODUCTION Thank you for purchasing this Clarke portable compressor.

More information

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO) REVISION 1 REFERENCE EEAM-Q-002 (ORIGINAL SPECIFICATION HE9.2.2 Ver6) DOCUMENT TYPE: SPECIFICATION TITLE: SPECIFICATION FOR HYDRAULIC EQUIPMENT PAGE 0 of 09 COMPILED BY REVIEWED BY REVIEWED BY PROJECT

More information

Crispin Valves Operating Guide. Crispin

Crispin Valves Operating Guide. Crispin Crispin Valves Operating Guide Crispin Since 1905 Crispin Multiplex Manufacturing Co. 600 Fowler Avenue Berwick, PA 18603 1-800-AIR-VALV T: (570) 752-4524 F: (570) 752-4962 www.crispinvalve.com sales@crispinvalve.com

More information

GMN - 22P 29/07/2016 GMN - 022P (ACP KPR) Main Features Frequency Hz 50 Voltage V 400 Power factor cos ϕ 0.8 Phase and connection 3

GMN - 22P 29/07/2016 GMN - 022P (ACP KPR) Main Features Frequency Hz 50 Voltage V 400 Power factor cos ϕ 0.8 Phase and connection 3 GMN - 22P Main Features Frequency Hz 50 Voltage V 400 Power factor cos ϕ 0.8 Phase and connection 3 Power Rating Standby power LTP kva 21.50 Standby power LTP kw 17.20 Prime power PRP kva 20.10 Prime power

More information

OPERATION INSTRUCTIONS

OPERATION INSTRUCTIONS www.r-techwelding.co.uk Email: sales@r-techwelding.co.uk Tel: 01452 733933 Fax: 01452 733939 ProArc 175 INVERTER ARC WELDER OPERATION INSTRUCTIONS Version 2017-10 2 3 Thank you for selecting the R-Tech

More information

STEP-BY-STEP INSTALLATION GUIDE

STEP-BY-STEP INSTALLATION GUIDE Battery Backup System STEP-BY-STEP INSTALLATION GUIDE Operating Instructions & Parts Manual ESP25 Please read and save these instructions. Read carefully before attempting to assemble, install, operate

More information

IEEE IAS Atlanta Chapter

IEEE IAS Atlanta Chapter Stationary Battery Sizing IEEE IAS Atlanta Chapter Presented by: Lesley Varga, P.E. Quality Standby Services, LLC 1649 Sands Place, SE, Suite C Marietta, GA 30067 (770) 916-1747 lesley@qualitystandbyservices.com

More information

TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID

TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID S.NO. HEAD DESCRIPTION AMOUNT (Rs.) 1 A DG SETS & ACCESSORIES

More information

INSTALLATION, START-UP AND SERVICE INSTRUCTIONS

INSTALLATION, START-UP AND SERVICE INSTRUCTIONS INSTALLATION, START-UP AND SERVICE INSTRUCTIONS P705 Refrigeration Condensing Units CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INTRODUCTION.................................. 1 HANDLING.......................................

More information

Today, we re going to talk about battery safety. We ll discuss all the key issues associated with using batteries safely, including battery hazards,

Today, we re going to talk about battery safety. We ll discuss all the key issues associated with using batteries safely, including battery hazards, Today, we re going to talk about battery safety. We ll discuss all the key issues associated with using batteries safely, including battery hazards, battery charging, and battery maintenance. Although

More information

Chassis Access Fans Motors Speed Control Coils The Condensate Tray Insulation Spigots Controls Enclosure Control Valves Filters Rev A

Chassis Access Fans Motors Speed Control Coils The Condensate Tray Insulation Spigots Controls Enclosure Control Valves Filters Rev A Chassis panelwork is all In House manufactured from nominally 1.2mm Galvanised steel. Where at all possible, flanges are formed inward facing to prevent exposure to bare metal edges. Sufficient forms and

More information

Edelbrock EFI Universal Fuel Sump System - Adjustable Part #36031, INSTALLATION INSTRUCTIONS

Edelbrock EFI Universal Fuel Sump System - Adjustable Part #36031, INSTALLATION INSTRUCTIONS Edelbrock EFI Universal Fuel Sump System - Adjustable Part #36031, 36032 INSTALLATION INSTRUCTIONS PLEASE study these instructions carefully before beginning this installation. This installation can be

More information

1. SPECIFICATION. Altitude of motor installation. Information: Resistance and temperature specifications of the PTC thermistor / posistor/.

1. SPECIFICATION. Altitude of motor installation. Information: Resistance and temperature specifications of the PTC thermistor / posistor/. 1. SPECIFICATION 5 GENERAL INFORMATION Motors with parameters according to the data sheet comply with the requirements of the IEC 60034-1 standard, and IEC 60034-30 class efficiency IE2 Motor versions:

More information

MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER

MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER MODEL TUB MODEL FEATURES Exhaust air up to 60,116 CFM in static pressure applications up to 1 w.g. Straight-through air flow design results in maximum exhaust efficiency Motor and drives are located outside

More information

January, 2014 Page 1 of 6

January, 2014 Page 1 of 6 Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying chemical fume hood modifications or installations. These standards are not intended to restrict or replace

More information

The following standards of installation and maintenance are provided as a guide to good practice.

The following standards of installation and maintenance are provided as a guide to good practice. RiskTopics Standby Diesel Engine Reliability September 2016 Diesel Engines are frequently used as the Prime Movers for standby or emergency systems such as Fire Pumps, Generators, Barring Drives and so

More information

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION:

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION: DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION: These instructions are provided to familiarize the user with the seal and its use. The instructions must be read carefully

More information

Deep Cycle Battery Safety. First. Battery Handling, Maintenance & Test Procedures

Deep Cycle Battery Safety. First. Battery Handling, Maintenance & Test Procedures Deep Cycle Battery Safety. First. Battery Handling, Maintenance & Test Procedures Crown deep cycle batteries employ a low-maintenance design. They do require periodic maintenance and effective charging

More information

BUREAU OF INDIAN STANDARDS DRAFT FOR COMMENTS ONLY. (Not to be reproduced without the permission of BIS or used as an AMENDMENT)

BUREAU OF INDIAN STANDARDS DRAFT FOR COMMENTS ONLY. (Not to be reproduced without the permission of BIS or used as an AMENDMENT) Doc: ET 25(6345) BUREAU OF INDIAN STANDARDS DRAFT FOR COMMENTS ONLY (Not to be reproduced without the permission of BIS or used as an AMENDMENT) DRAFT AMENDMENT NO. 3 TO IS 14665 (Part 2 / Sec 1) : 2000

More information

Installation manual. Cooling system. Industrial engines DC09, DC13, DC16 OC16. 01:05 Issue 12 en-gb. Scania CV AB 2018, Sweden

Installation manual. Cooling system. Industrial engines DC09, DC13, DC16 OC16. 01:05 Issue 12 en-gb. Scania CV AB 2018, Sweden Installation manual Cooling system Industrial engines DC0, DC13, DC OC 333 3 01:05 Issue en-gb Changes from the previous issue...3 Design and dimensioning...3 Expansion tank...4 and earlier emission levels...

More information

Unit D: Agricultural Equipment Systems. Lesson 1: Understanding Applications of Fluids and Lubricants in Agricultural Equipment

Unit D: Agricultural Equipment Systems. Lesson 1: Understanding Applications of Fluids and Lubricants in Agricultural Equipment Unit D: Agricultural Equipment Systems Lesson 1: Understanding Applications of Fluids and Lubricants in Agricultural Equipment 1 Terms Ash content bottom dead center cloud point compression ratio coolant

More information

Crankcase Ventilation Manager (CVM) Installation Instructions

Crankcase Ventilation Manager (CVM) Installation Instructions Crankcase Ventilation Manager (CVM) Installation Instructions CVM280 CVM424 Parts List E D C B A A B C D E Part Description No. Included A Shell 1 B Collar 1 C *O-Ring 1 D *Element 1 E Head 1 Part Number

More information

Professional Séries. Professional Séries. Model T03828 SUBMERSIBLE SUMP DUPLEX SYSTEM SUBMERSIBLE SUMP DUPLEX SYSTEM. 1/3HP 2400 GPH Head of 20 (6 m)

Professional Séries. Professional Séries. Model T03828 SUBMERSIBLE SUMP DUPLEX SYSTEM SUBMERSIBLE SUMP DUPLEX SYSTEM. 1/3HP 2400 GPH Head of 20 (6 m) Model T0828 Primary pump 1/HP 200 GPH Head of 20 (6 m) SUBMERSIBLE SUMP DUPLEX SYSTEM Professional Séries Discharge: 1 1/2 ABS DWV pipe Electric cable: 9 piggyback type Oil cooled Cast iron construction

More information

KVAR POWERHOUSE RANGE 140 KVA 200 KVA

KVAR POWERHOUSE RANGE 140 KVA 200 KVA KVAR POWERHOUSE RANGE 140 KVA 200 KVA 50 hz Three phase - 415 v Model Engine Manufacturing Alternat PRP Output ESP Output country of engine or and alternator Kva Kw Kva Kw PM140 1106A-70TG1 ECP34-2L UK

More information

SPECIFICATION OF TRUCK MOUNTED MOBILE OIL SPILL RECOVERY UNIT MOSRU Lts.

SPECIFICATION OF TRUCK MOUNTED MOBILE OIL SPILL RECOVERY UNIT MOSRU Lts. SPECIFICATION OF TRUCK MOUNTED MOBILE OIL SPILL RECOVERY UNIT MOSRU - 6000 Lts. GENERAL:- The Vehicle Mounted Suction Unit shall be robust in construction and shall be used to create a vacuum for syphoning

More information

Proper Torque Values for Connection Hardware. 90 to 100 in-lbs

Proper Torque Values for Connection Hardware. 90 to 100 in-lbs Introduction Trojan Battery Company has been manufacturing lead-acid batteries for more than three generations. Our experience has shown that the key factor to achieving optimum performance and long battery

More information

PRECISION UK Ltd DUPLEX AGSS PLANT

PRECISION UK Ltd DUPLEX AGSS PLANT DUPLEX AGSS PLANT Contents Page Section Page Product Description General 3 AGSS Plant 3 AGSS Remote Switch 3 Operation General 4 Safety General 5 Installation General 5 Mechanical 5 Electrical 7 Wiring

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM)

INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM) INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM) IOM-1088 03-16 Model 1088 Vacu-Gard Blanketing Valve ISO Registered Company SECTION I I. DESCRIPTION AND SCOPE The Model 1088 Vacu-Gard is a tank blanketing

More information

Installation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps

Installation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps Installation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps EI-700-008 Rev -- Table of Contents Safety Guidelines 3 Caution 4 Wiring 4 Maintenance 4 Nameplate format 4 Prior to Operation

More information

GENERATOR MODEL NO: FG3005 OPERATION & MAINTENANCE INSTRUCTIONS PART NO: LS0413

GENERATOR MODEL NO: FG3005 OPERATION & MAINTENANCE INSTRUCTIONS PART NO: LS0413 GENERATOR MODEL NO: FG3005 PART NO: 8857707 OPERATION & MAINTENANCE INSTRUCTIONS LS0413 INTRODUCTION Thank you for purchasing this CLARKE Generator. Before attempting to use this product, please read this

More information

Galaxy VM. Battery Breaker Box Installation 09/

Galaxy VM. Battery Breaker Box Installation 09/ Galaxy VM Battery Breaker Box Installation 09/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred

More information

Series Base mounted pump. Installation and operating instructions

Series Base mounted pump. Installation and operating instructions Series 4030 Installation and File No: 40.80 Date: june 25, 2015 Supersedes: 40.80 Date: october 10, 2009 contents General 4 Inspection 4 Installation - Series 4030 base mounted Pump 4 1.0 Location 4 2.0

More information

SERIES COOLING TOWER SINGLE-CELL UP TO 1500HRT COOLING CAPACITY

SERIES COOLING TOWER SINGLE-CELL UP TO 1500HRT COOLING CAPACITY EX-S SERIES COOLING TOWER SINGLE-CELL UP TO 1500HRT COOLING CAPACITY High Performance Crossflow Type CERTIFICATE NUMBER: 12-41-02 PROVEN PERFORMANCE RELIABILITY EASY INSTALLATION CERTIFICATE NUMBER: LOGO-SGBP

More information

OPTEVA 378 ENHANCED CASH RECYCLER TERMINAL FRONT LOAD LOBBY UNIT PLAN VIEW FRONT VIEW SIDE VIEW

OPTEVA 378 ENHANCED CASH RECYCLER TERMINAL FRONT LOAD LOBBY UNIT PLAN VIEW FRONT VIEW SIDE VIEW L00 CALL -800--600 OPTEVA 8 ENHANCED CASH RECYCLER TERMINAL WITH mm ( ") UL SAFE 4 ( 6 ") 4 ( 6 ") CONSULT WITH DIEBOLD INSTALLATION/SERVICE BRANCH FOR ADDITIONAL DETAILS AND INFORMATION. PLEASE SEE PLANNING

More information

Installation, Operation & Maintenance Manual. For Pro-Fill kits with part numbers beginning in BG

Installation, Operation & Maintenance Manual. For Pro-Fill kits with part numbers beginning in BG Installation, Operation & Maintenance Manual For Pro-Fill kits with part numbers beginning in BG BL-175 6/26/2009 General Information & Precautions This publication provides detailed instructions for installing

More information

DESCRIPTION MECHANICAL FUEL PUMP FUEL FILTER HIGH PRESSURE (35-90 PSI) HIGH PRESSURE (35-90 PSI) (STEEL/INCLUDED)

DESCRIPTION MECHANICAL FUEL PUMP FUEL FILTER HIGH PRESSURE (35-90 PSI) HIGH PRESSURE (35-90 PSI) (STEEL/INCLUDED) Edelbrock EFI Universal Fuel Sump System - Adjustable Part #36031, 36032, 36033, 36034 INSTALLATION INSTRUCTIONS PLEASE study these instructions carefully before beginning this installation. This installation

More information

KVA POWERHOUSE RANGE 1250 KVA 1700 KVA

KVA POWERHOUSE RANGE 1250 KVA 1700 KVA KVA POWERHOUSE RANGE 1250 KVA 1700 KVA 50 hz Three phase 380-415 v Model Engine Alternator Manufacturing country of engine & alternator PRP Output ESP Output Kva Kw Kva 380v/400- Kw 415v 46TWG2A PI734B

More information

GSW22P. Main Features Frequency Hz 50 Voltage V 230 Power factor cos ϕ 1 Phase and connection 1

GSW22P. Main Features Frequency Hz 50 Voltage V 230 Power factor cos ϕ 1 Phase and connection 1 GSW22P Main Features Frequency Hz 50 Voltage V 230 Power factor cos ϕ 1 Phase and connection 1 Power Rating Standby power LTP kva 13.80 Standby power LTP kw 13.80 Prime power PRP kva 13.50 Prime power

More information

Technical Data Series 1206E-E70TTA. Basic technical data. Performance

Technical Data Series 1206E-E70TTA. Basic technical data. Performance Technical Data 1200 Series 1206E-E70TTA Electropak 150 kwe @ 1800 rpm Basic technical data Number of cylinders.....................................................6 Cylinder arrangement...................................

More information

PH1 AIR INTAKE EMERGENCY SHUT-OFF VALVE PULL CABLE ACTUATION.

PH1 AIR INTAKE EMERGENCY SHUT-OFF VALVE PULL CABLE ACTUATION. PH AIR INTAKE EMERGENCY SHUT-OFF VALVE PULL CABLE ACTUATION www.powerhalt.com Thank you for your purchase of a PowerHalt Air Intake Emergency Shut-Off Valve by Pacbrake. INSTALLATION REQUIREMENTS & RECOMMENDATIONS:

More information

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST BELT TYPE IMPORTANT PLEASE MAKE CERTAIN THAT THE PERSON WHO IS TO USE THIS EQUIPMENT CAREFULLY READS AND UNDERSTANDS THESE INSTRUCTIONS BEFORE STARTING

More information

Cable-Tight Wire Management System

Cable-Tight Wire Management System Cable-Tight Wire Management System Installation Guide Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com Safety

More information

TWO-STAGE HYDRAULIC PUMP. RWP55-IBT-Air

TWO-STAGE HYDRAULIC PUMP. RWP55-IBT-Air ORIGINAL INSTRUCTIONS Form No.1000458 5 SPX Corporation 5885 11th Street Rockford, IL 61109-3699 USA Tech. Services: (800) 477-8326 Fax: (800) 765-8326 Order Entry: (800) 541-1418 Fax: (800) 288-7031 Internet

More information

Technical Data Series 1103D-33 G3. Diesel engine - Electropak rpm

Technical Data Series 1103D-33 G3. Diesel engine - Electropak rpm Technical Data 1100 Series Diesel engine - Electropak 1103D-33 G3 32.3 kwm @ 1500 rpm Basic technical data Number of cylinders..................................................... 3 Cylinder arrangement....................................vertical

More information

Technical Specification. for. Supply, installation and commissioning of Diesel Generators for UNDP

Technical Specification. for. Supply, installation and commissioning of Diesel Generators for UNDP United Nations Development Programme Recovery and Crisis Prevention برنامج األمم المتحدة اإلنمائي Iraq Technical Specification for Supply, installation and commissioning of Diesel Generators for UNDP February

More information

26 - COOLING SYSTEM CONTENTS ENGINE COOLING - DESCRIPTION... 3 ENGINE COOLING - OPERATION... 9 COOLING SYSTEM FAULTS... 1

26 - COOLING SYSTEM CONTENTS ENGINE COOLING - DESCRIPTION... 3 ENGINE COOLING - OPERATION... 9 COOLING SYSTEM FAULTS... 1 26 - COOLING SYSTEM CONTENTS Page LAND ROVER V8 DESCRIPTION AND OPERATION ENGINE COOLING - DESCRIPTION... 3 ENGINE COOLING - OPERATION... 9 FAULT DIAGNOSIS COOLING SYSTEM FAULTS... 1 REPAIR COOLANT - DRAIN

More information

SERIES PC INSTRUCTION AND OPERATION MANUAL

SERIES PC INSTRUCTION AND OPERATION MANUAL MEGGA SERIES PC INSTRUCTION AND OPERATION MANUAL Models PCT and PCF Close-coupled and frame-mounted single-stage horizontal end-suction pumps. WARNING: Read this manual before installing or operating this

More information

Cooling system components, removing and installing

Cooling system components, removing and installing 19-1 Cooling system components, removing and installing Note: When the engine is warm the cooling system is under pressure. If necessary release pressure before starting repair work. Hoses are secured

More information

OPERATOR S MANUAL 7(5 & ( 8&. $5.00 P/N REV.B

OPERATOR S MANUAL 7(5 & ( 8&. $5.00 P/N REV.B OPERATOR S MANUAL &281 2817( 7(5 %$/$1&( /,)7 7758& 8&. $5.00 P/N 901345 REV.B As a lift truck operator, you are responsible for a machine that is useful, powerful, and can be hazardous if not operated

More information

PRO Rental Product Range. PRO60-2 (R96 EUIIIa Equivalent) KEY FEATURES. Rental Ready Features. Alternator. Integrated Voltage Regulator (IVR)

PRO Rental Product Range. PRO60-2 (R96 EUIIIa Equivalent) KEY FEATURES. Rental Ready Features. Alternator. Integrated Voltage Regulator (IVR) PRO60-2 (R96 EUIIIa Equivalent) 50/60 Hz Switchable Rating Prime Product 60 kva / 48 kwe KEY FEATURES Rental Ready Features 24 hour dual wall tankbase Forklift pockets Fully certified single point lifting

More information

Installation Instructions for Remote Mount HMI 211 Display Panel Kit A045J206

Installation Instructions for Remote Mount HMI 211 Display Panel Kit A045J206 Instruction Sheet 7-2013 Installation Instructions for Remote Mount HMI 211 Display Panel Kit A045J206 1 Introduction The information contained within is based on information available at the time of going

More information

PROCESS PUMPS (INDIA) PVT LTD

PROCESS PUMPS (INDIA) PVT LTD MANUAL: - M10 HORIZONTAL BPO METALLIC PUMP WITH EXTERNAL MECHANICAL SEAL (GROUP- III & IV) INSTALLATION, OPERATION AND MAINTENANCE MANUAL PROCESS PUMPS (INDIA) PVT LTD Plot No.86, III Phase, Peenya Industrial

More information

Industrial Generator Set Accessories

Industrial Generator Set Accessories Industrial Generator Set Accessories Sound Enclosure and Subbase Fuel Tank Package Applicable to the following models: KD800 - KD2500 (includes KD1250-A) Level 1 Sound Enclosure with Lift Base Sound Level

More information

VXI Closed circuit cooling towers

VXI Closed circuit cooling towers Closed circuit cooling towers Key benefits Reliable Quiet Compact characteristics Counter flow, centrifugal fan, forced draft Capacity range up to 2615 kw Maximum entering fluid temperature 82 C Typical

More information

ARTICLE BEGINNING SERVICE PRECAUTIONS

ARTICLE BEGINNING SERVICE PRECAUTIONS Page 1 of 96 ARTICLE BEGINNING SERVICE PRECAUTIONS WARNING: WARNING: CAUTION: When performing any inspection or service procedure on this vehicle, ensure following service precautions are followed to prevent

More information

ST - II Series POWER SUPPLIES USER INSTRUCTIONS

ST - II Series POWER SUPPLIES USER INSTRUCTIONS Introduction ST - II Series POWER SUPPLIES These instructions detail the installation and operation requirements for the ST20-II & ST35-II power supplies. These have been designed for operation in RV s

More information

Submersible Pump Instructions. Safety Instructions

Submersible Pump Instructions. Safety Instructions Submersible Pump Instructions Safety Instructions Before operating of this pump, read this manual and follow all safety rules and operating instructions. Before operating of this pump, read this manual

More information

Installation Operation and Maintenance Manual

Installation Operation and Maintenance Manual Installation Operation and Maintenance Manual Lubricated high vacuum rotary vane pumps SERIAL NO.: June 2006/5 LUBRICATED HIGH VACUUM ROTARY VANE PUMPS TABLE OF CONTENTS INTRODUCTION 3 Safety 3 STORAGE

More information