Pressure Reducing Valve Type 2114/2415

Similar documents
Mounting and operating instructions EB EN. Differential Pressure and Temperature Regulator with Flow Limiter Type 2479/2430 K

Mounting and operating instructions EB 8093 EN. Series 240 Pneumatic Control Valve for Cryogenic Temperatures. Type and

Mounting and Operating Instructions EB 8053 EN. Series 250 Type and Type Pneumatic Control Valves

Series 250 Pneumatic Control Valves Type and

Self-operated Pressure Regulators Type Universal Excess Pressure Valve

Self-operated Pressure Regulators Type Universal Excess Pressure Valve

Mounting and Operating Instructions EB 8111/8112 EN. Series V2001 Valves Type 3321 Globe Valve

Mounting and Operating Instructions EB 8091 EN. Pneumatic Control Valve Type and Type Type with 120 cm 2 actuator

Mounting and operating instructions EB Pneumatic Control Valve Type and Type Globe Valve Type 3522 ANSI Class 300

Pneumatic Control Valve Assembly Type 3331/3278

Globe Valve Type Fig. 1 Type 3241 Globe Valve. Mounting and Operating Instructions EB EN

Mounting and Operating Instructions EB 8111/8112 EN. Valve Series V2001 Globe Valve Type 3321

Mounting and Operating Instructions EB 5894 EN. Electric control valves with jet pump. Flanged version of valve with jet pump

Mounting and Operating Instructions EB 5863 EN. Electric Control Valves. Pneumatic Control Valve

Series 42 Self-operated Regulators. Type RS Check Valve (backflow protection)

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil

ANSI version. The valve closes when the differential pressure rises

Self-operated Pressure Regulators Universal Pressure Reducing Valve Type 41-23

Mounting and Operating Instructions EB 8039 EN. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve

Mounting and Operating Instructions EB 8097 EN. Type and Type Pneumatic Control Valves

Mounting and Operating Instructions EB 8048 EN. Type and Type Pneumatic Control Valves Type 3249 Aseptic Angle Valve

Mounting and Operating Instructions EB 8097 EN. Pneumatic Control Valves Type and Type

Mounting and Operating Instructions EB 5868/5869 EN

Self-operated Pressure Regulators Type Universal Pressure Reducing Valve

Valve Series V2001 Three-way Valve Type 3323

Strainers with flanged connections Type 2 N Type 2 NI. Type 2 N/2 NI Strainers. Mounting and Operating Instructions EB 1015 EN

Type 3379 Pneumatic Actuator. Mounting and Operating Instructions EB 8315 EN

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

Pneumatic Rotary Actuator Type 3278

Mounting and Operating Instructions EB 8227 EN. Pneumatic Control Valve Type 3331/BR 31a Special version Type 3331/3278. Type 3331 Butterfly Valve

Series 46 Self-operated Regulators Differential Pressure and Flow Limiters Type 46-5 Type 46-6

Series 240 Pneumatic On-off Valve Type 3351

Type 3271 Pneumatic Actuator. Actuator area: cm². Mounting and Operating Instructions EB EN

Combined Self-operated Regulators Regulators for Differential Pressure, Flow Rate and Temperature

SAMSON special tools. Fig. 1 Seat wrenches and supporting flanges WA 029 EN

Series 240 Type and Type Pneumatic Control Valves Type 3248 Cryogenic Valve

EB EN. Type 3372 Electropneumatic Actuator. Translation of original instructions

Mounting and operating instructions EB 8220 EN. Pneumatic Butterfly Valve Type 3335/AT and Type 3335/3278. Fig. 2 Type 3335/AT

Lined Butterfly Valve Pfeiffer Type BR 10a

Self-operated Temperature Regulators Type 1u Temperature Regulator

Series 250 Pneumatic Control Valve Type and Type High Pressure Valve Type 3252

Pressure relief controller V22 D28

Pneumatic Controller for Temperature. Type Pneumatic Controller for Temperature. Type Mounting and Operating Instructions EB 7065 EN

Type 3271 and Type 3277 Pneumatic Actuators. Actuator areas: 175 and 750 cm². Type 3271 Type Mounting and Operating Instructions EB EN

Series W&T Pneumatic Control Valve Type RVG Globe valve and angle valve

Series 240 Type Gas and Type Gas Automatic Shut-off Valves for Gases (valve class D)

Fisher 644 and 645 Differential Pressure Pump Governors

Self-operated Temperature Regulators Type 1u Temperature Regulator

Mounting and operating instructions EB 5801 EN. Electric Actuators Type 5801 (Rotary Actuator) Type 5802 (Linear Actuator)

Series 240 Type and Type Pneumatic Control Valves Type 3248 Cryogenic Valve

Self-operated Temperature Regulators Temperature Regulator Type 1u

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

Type 644 and 645 Differential Pressure Pump Governors

Typetested versions With Type 3213 Globe Valve, unbalanced. With Type 3214 Globe Valve, balanced

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators

Pneumatic or Electropneumatic Positioner for Rotary Actuators Type Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Application Pressure reducing valves for the food and pharmaceutical industries

Typetested for liquid fuels and liquefied petroleum gas (LPG) in the liquid phase (see Data Sheet T 8022 EN) Version according to ANSI standards

Type 3761 Pneumatic or Electropneumatic Positioner for Rotary Actuators. Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

System 6000 Electropneumatic Converters for DC ranges I/P Converter Type 6102 Type 5288

Type and Type Pneumatic Control Valves Type 3510 Micro-flow Valve

Valve Series V2001 Globe Valve Type 3321 with Pneumatic or Electric Actuator

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

I & M 8000 Series. Ideal Installation Schematic. Preferred Installation. Trouble Shooting

Type 3273 Hand-operated Actuator Type 3273 Side-mounted Handwheel

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

Series 240 Type 3351 Pneumatic On/off Valve

Series 2200/2220 Control Valve. Operation and Maintenance SCOPE OF MANUAL MAINTENANCE DESCRIPTION VALVE INSTALLATION

System 6000 Electropneumatic Converter for Direct Current Signals i/p Converter Type 6126

Pneumatic Control Valve Type and Type Micro-flow Valve Type 3510

Mounting and Operating Instructions EB 8256 EN. Type 3286 Steam Conditioning Valve

Mounting and Operating Instructions EB 8392 EN. Series 3710 Type 3710 Reversing Amplifier

Series V2001 Valves Type 3531 Globe Valve for Heat Transfer Oil with pneumatic or electric actuator

Mounting and Operating Instructions EB EN. Type 3372 Electropneumatic Actuator. Actuator area: 120 and 350 cm² With Type 3725 Positioner

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

Serie 2003/2013. Three-way Control Valve, mixing/diverting. Wörth am Main. Service. Control Valve Division

Series V2001 Valves Type 3531 Globe Valve for Heat Transfer Oil with pneumatic or electric actuator

Series 240 Pneumatic Control Valve Type and Type Three-way Valve Type 3244

Series 2371 Pressure Regulators Excess pressure valves for the food and pharmaceutical industries

Technical Data TYPE A SERIES AIR ADJUSTED PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4011 OPERATING PRINCIPLE

Series 240 Type and Type Pneumatic Control Valves Type 3244 Three-way Valve

Differential pressure relief controller (PN 16, 25, 40) AFPA / VFG 2(1)

Series 240 Pneumatic Control Valve Type and Type Globe Valve Type 3241

KLINGER Piston Valves KVN DN PN 16 I/III with valve ring KX-GT Modul

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1-1/2-2 )

Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil with pneumatic or electric actuator

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1/2-1 )

Pneumatic Butterfly Valve Pfeiffer Type BR 14b/AT

Series 240 Type and Type Pneumatic Control Valves Type 3347 Hygienic Angle Valve

Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil with pneumatic or electric actuator

Mounting and Operating Instructions EB 8252 EN. Type 3281 Steam Conditioning Valve

Series 240 Pneumatic Control Valves Type and Type Three-way Valve Type 3244

Pneumatic Butterfly Valve Type 3335 / AT

J Flow Controls Model Numbering

Type EZR Relief Valve or Backpressure Regulator

INSTALLATION & MAINTENANCE MODEL mm

DO NOT INSULATE BELOW THIS LINE. * For sizes 1/2" to 1 1/2" add 2 1/2" to 'C' dimension.

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

specification DAtA V R0 pilot operated tank blanket VAlVe, pressure regulating VAlVe SERIES V500

Flow Control Valve IOM 770-U

Transcription:

Pressure Reducing Valve Type 2114/2415 Fig. 1 Type 2114/2415 1. Design and principle of operation The Type 2114/2415 Pressure Reducing Valve consists of the Type 2114 Valve and the Type 2415 Actuator. The pressure reducing valve is designed to maintain the pressure downstream of the valve to an adjusted set point value. The valve closes when the downstream pressure rises. Edition September 1996 Mounting and operating instructions EB 2512-1 E

The medium to be controlled flows through the free area between the seat (2) and the plug (3) in the direction indicated by the arrow. The position of the valve plug determines the flow rate and hence the pressure ratio across the valve. The downstream pressure is transferred via the control line (19) to the operating diaphragm (9) where it is converted into a positioning force. This force is used to position the valve plug according to the force of the positioning springs (11). The spring force can be adjusted at the set point adjustment nut (13). The control valves have a balancing bellows (5). The downstream pressure acts on the inner bellows surface, while the upstream pressure acts on the outer surface. Thus the forces produced by the upstream and downstream pressures, acting on the plug, are balanced. Type 2114 Control Valve 1 21 20 2 3 4 5 6 7 8 19 16 4 6.1 8 9 10 17 15 18 DN 125 to 250 Actuator stem (8) and plug stem (4) are screwed together 14 11 12 13 Fig. 2 Sectional view Type 2415 Actuator 1 Valve body 2 Seat 3 Plug 4 Plug stem 5 Balancing bellows 6 Bellows housing 6.1 Venting screw 7 Coupling nut 8 Upper actuator stem 9 Operating diaphragm 10 Springs (depending on set point range) 11 Positioning springs 12 Spring plate 13 Set point adjustment nut 14 Lower actuator stem 15 Nut and bolt 16 Nut ( DN 125 and higher with pin) 17 Diaphragm plate 18 Control line connection with screw joint 19 Control line 20 Condensation chamber 21 Filler plug 2

2. Installation 2.1 Assembly The valve and actuator can be assembled together prior to or after the control valve has been installed in the pipeline. Release the tension of the positioning springs by turning the set point adjustment nut and attach the actuator to the bellows housing (6) with the coupling nut (7). Attention for valve sizes DN 125 to 250, the diaphragm stem and plug stem must be screwed together! When the control valve and the actuator are assembled together later, it is important to check first whether the versions fit: The control valve must have a tapped hole at the end of the plug stem. Valve versions intended for the attachment of a thermostat (Type 4 Temperature Regulator) have a threaded nipple screwed in the end of the plug stem - this nipple must be removed! The actuator must have a threaded diaphragm stem! Versions without this threaded stem cannot be used. Release the tension of the positioning springs of the actuator by turning the set point adjustment nut (13). Place the actuator under the valve bonnet and carefully screw it on as tight as possible and then unscrew it one turn at the maximum. Hold the actuator and screw on tight the coupling nut. 2.2 Installation position The pressure reducing valve must be installed in a horizontal pipeline and with the actuator suspended downwards. The medium must flow through the valve in the direction indicated by the arrow on the valve body. When selecting the installation location, ensure that the regulator remains easily accessible after the plant has been installed. Make sure that the regulator is installed in the pipeline free of stress. If necessary, support the piping near the valve flanges. Do not mount any supports on the valve or on the actuator. When used with a medium which condensates, for example, steam, the pipeline should be laid both sides of the valve with a slight downward slope in order to allow any condensation forming to drain off. If the pipeline upstream and downstream of the valve is laid vertically, always install a steam trap (Samson Type 13 E Steam Trap). Never install any devices between the pressure tap point and the control valve which restrict the piping s cross-section (e.g. a temperature regulator or shut-off valves). If a bypass pipe is to be equipped, it must be connected downstream of the pressure tap point. A shut-off valve must be installed in the bypass pipe. Before installing the regulator, flush out thoroughly the pipeline, in order to ensure that any sealing parts, globules and other impurities carried along by the medium cannot impair the proper functioning of the valve, especially the tight shut-off. Always install a strainer (Samson Type 2) upstream of the pressure reducing valve (see section 2.4). 2.3 Control line, condensation chamber and screw joint with throttle A control line (to be provided by the customer) using a 3/8" pipe must be installed. If a copper pipe is to be used, a 12 x 1 mm pipe is recommended. A condensation chamber is necessary for liquids above 150 C and for steam. If the regulator has a tendency to hunt, the installation of a needle valve in the control line is recommended. Connect the control line at least 1 metre away from the valve outlet to the downstream pressure line (Fig. 3.1). If a manifold is installed downstream of the pressure reducing valve (Fig. 3.2), the control line must be connected to the manifold even if this is located several metres away. If the downstream pressure line behind the valve is extended with a conical expansion piece, the control line must be connected at the extended part of the pipeline. Weld the 3

control line onto the side of the pipeline and in the middle and with an approx. 1:10 slope up towards the condensation chamber. The installation position of the condensation chamber is labelled and marked with an arrow and the word "Top" on the top of the tank. It is essential to keep to this installation position otherwise the reliable operation of the pressure reducing valve cannot be guaranteed. Weld the control line from the pressure tap point to the 3/8" pipe socket on the condensation chamber. Always position the condensation chamber at the highest point of the pipeline, i.e. the control line between the condensation chamber and the actuator must be run with a downward slope. In this case, use a 3/8" pipe with screw glands. If the control line is connected below the center of the valve outlet flange, the condensation chamber must be positioned at the same level as the outlet flange (Fig. 3.3). In this case, a 1/2" pipe at the minimum must be used for the control line from the pressure tap point. When the control line is connected above the center of the valve outlet flange, the condensation chamber must be positioned at the same height as the downstream pressure tap point (Fig. 3.4). The additional pressure of the condensate head must be compensated for by adjusting the set point to a higher value. 1 2 3 5 4 6 7 min. 1/2" Fig. 3.1 Control line connection (pipeline) 1 2 3 5 6 Fig. 3.3 Connection below the center of flange Fig. 3.2 Control line connection (manifold) 8 Additional condensate head Fig. 3.4 Connection above the center of flange Fig. 3 Installation examples 1 Shut-off valve 2 Upstream pressure gauge 3 Strainer 4 Condensation chamber 5 Pressure reducing valve 6 Downstream pressure gauge 7 Shut-off valve 8 Steam trap 4

2.4 Strainer Install the strainer upstream of the pressure reducing valve. The medium must flow through the valve in the direction indicated by the arrow on the strainer body. The strainer filter must hang downwards. Make sure that sufficient space is available to remove the filter. 3.2 Set point adjustment Adjust the downstream pressure required by turning the set point adjustment nut (13). Turn it clockwise to increase the downstream pressure and anti-clockwise to reduce the pressure. The set point adjusted can be checked by reading the downstream pressure gauge. 2.5 Shut-off valves We recommend the installation of handoperated shut-off valves both upstream of the strainer and downstream of the valve. This allows the plant to be isolated for cleaning and maintenance purposes or when left unused for extended periods. 2.6 Pressure gauge Install a pressure gauge both upstream and downstream of the regulator in order to be able to observe the pressures prevailing in the plant. Do not install the pressure gauge on the downstream pressure side in front of the downstream pressure tap point. 3. Operation 3.1 Start-up When controlling steam: Unscrew the filling plug (21) on the condensation chamber and fill it up with water using the plastic funnel included or a can until the water starts to overflow. Screw tight the filling plug. The pressure reducing valve is now ready for use. Open the hand-operated shut-off valves slowly in order to prevent any condensation hammering. When controlling liquids: Take the pressure reducing valve into operation by slowly opening the hand-operated shut-off valves. For actuators with a diaphragm area of 640 cm 2, loosen the vent screw until all the air has escaped and then retighten. For temperatures above 150 C, first fill the condensation chamber with the medium to be used. 4. Faults If the downstream pressure (see the pressure gauge downstream of the valve) deviates considerably from the set point adjusted, first check the control line for blockages and the operating diaphragm for leaks. When faults occur due to other reasons, such as a damaged seat and plug, we recommend you to contact our after-sales service or to return the valve to the manufacturer for repair. If the operating diaphragm is damaged, see section 4.1.! When performing any assembly work on the pressure reducing valve, first remove the valve from the pipeline. Before doing so, always relieve the pressure from the corresponding part of the plant and drain it, if necessary. 4.1 Exchanging the operating diaphragm Should just the operating diaphragm be damaged, after draining the part of the plant concerned, unscrew the control line. The actuator can be disassembled from the valve without having to remove the whole regulator from the pipeline. However, in this case it is important to make sure that the actuator cone seals the control valve and the medium runs out of the valve when the actuator is being removed. Unscrew the bolts (15) on the actuator and remove the lower diaphragm case with the diaphragm stem (14) and the spring assembly. Unthread the nut (16) while holding the lower 5

diaphragm stem with an appropriate tool (in valve sizes DN 125 and above, the upper diaphragm stem is secured with a pin which must be first knocked out), lift off the diaphragm plate (17) and remove the diaphragm. Insert new diaphragm. To reassemble, proceed in the reverse order. To put back into operation, see section 3.1. 5. Dimensions in mm and weights DN 15 20 25 32 40 50 65 80 100 125 150 200 250 L 130 150 160 180 200 230 290 310 350 400 480 600 730 H1 225 460 590 600 600 H2 55 72 100 120 145 175 215 230 cm 2 ØD 40 170 H 80 170 160 225 645 645 720 775 880 1010 1020 320 285 640 320 705 705 780 835 940 1070 1080 Weight, in approx. kg 40/80 11 12 13 19 20 22 33 38 52 116 166 406 466 cm 2 160 16 17 18 24 25 27 38 43 57 121 171 411 471 320 20 21 22 28 29 31 42 47 61 125 175 415 475 640 30 31 32 38 39 41 52 57 71 135 185 425 485 L H2 H1 H 6. Customer inquiries Should you have any inquiries about the valve, please submit the following details: 1. Type and nominal size of the pressure reducing valve 2. Product and order number (indicated on the name plate) 3. Upstream and downstream pressure 4. Flow rate in m 3 /h 5. Has a strainer been installed? 6. Installation drawing Ø D SAMSON AG MESS- UND REGELTECHNIK Weismüllerstraße 3 D-60314 Frankfurt am Main Postfach 10 19 01 D-60019 Frankfurt am Main Telefon (0 69) 4 00 90 Telefax (0 69) 4 00 95 07 EB 2512-1 E S/C 11.96