CONTRACT DOCUMENTS FOR 2700 W. Argyle Street WSU ELECTRICAL RELIAILITY UPGRADES - ID PACKAGE No. 6 OWNER Facilities Planning & Management Design & Construction Services 5454 Cass Avenue Detroit Mi 48202 FOR ID 1-21-2015 CONSULTANT 2700 W. Argyle Street ELECTRICAL RELIAILITY UPGRADES PROJ. No. 5454 CASS AVENUE DETROIT, MICHIGAN INDEX OF SHEETS NEW OR REVISED SHEET IN THIS ISSUE NON-REVISED SHEET IN THIS ISSUE SHEET C-0 COVER SHEET G-1 GENERAL NOTES AND DESIGN CRITERIA 12-17-2014 1-21-2015 DESCRIPTION FOR ID OWNERS REVIEW DLM MARK ISSUED FOR/REVISIONS FOR ID 1-21-2015 FILE NAME: C:\pw_work\pw_proj\dlmaier\d0448397\C-0.dwg PLOTTED : 1/16/2015 12:24 PM PLOTTED Y: Daniel L. Maier PROJECT LOCATION CS MOTT LDG. CAMPUS MAP E-0 ASEMENT FLOOR PLAN E-2 SECOND FLOOR PLAN E-3 THIRD FLOOR PLAN E-101 ELECTRICAL ONE LINE DIAGRAM E-102 UPS RISER DIAGRAM AR1-02A AR1.02 AR1-03A AR1-0GA AR1.0G REFERENCE DRAWINGS SECOND FLOOR REFLECTED CEILING PLAN AREA 'A' SECOND FLOOR REFLECTED CEILING PLAN AREA '' THIRD FLOOR REFLECTED CEILING PLAN AREA 'A' GROUND FLOOR REFLECTED CEILING PLAN AREA 'A' GROUND FLOOR REFLECTED CEILING PLAN AREA '' CLIENT 320006 AS SHOWN COVER SHEET C-0
2700 W. Argyle Street ELECTRICAL RELIAILITY UPGRADES PROJ. No. 5454 CASS AVENUE DETROIT MICHIGAN DLM MARK ISSUED FOR/REVISIONS FOR ID 1-21-2015 FILE NAME: C:\pw_work\pw_proj\dlmaier\d0448397\G-1.dwg PLOTTED : 1/14/2015 2:22 PM PLOTTED Y: Daniel L. Maier CLIENT 320004 N/A GENERAL NOTES AND DESIGN CRITERIA G-1
2700 W. Argyle Street EXIST. PP-CT UPS-RP-00 #14 UPS-RP-00 #13 UPS-RP-00 #11 UPS-RP-00 #15 004.1 ENCH UPS-RP-00 # 16 UPS-RP-00 # 20 UPS-RP-00 # 22 UPS-RP-00 # 25 UPS-RP-00 # 26 UPS-RP-00 # 27 UPS-RP-00 # 09 UPS-RP-00 # 05 UPS-RP-00 # 10 12 SEE DWG. E-2 FOR CONTINUATION ENCH UPS-MDP 028 040 033 033.1 0039 2 3 ENCH UPS UPS-T UPS-RP-00 EXIST. LP-A EXIST. PP-1 ENCH 1 E-0 ENCH ENCH ENCH ENCH TALE UPS-RP-00 # 02 UPS-RP-00 # 01 UPS-RP-00 # 03 UPS-RP-00 # 04 UPS-RP-00 # 17 UPS-RP-00 # 19 21 UPS-RP-00 # 18 TALE UPS-RP-00 # 23 UPS-RP-00 # 24 TALE UPS-RP-00 UPS-RP-MDP ELECTRICAL RELIAILITY UPGRADES PROJ. No. 5454 CASS AVENUE DETROIT, MICHIGAN UPS-RP-00 # 07 ENCH UPS-RP-00 # 08 UPS-RP-00 # 06 DLM NORTH ASEMENT FLOOR LEVEL 3/32" = 1'-0" 0 10' 20' MARK ISSUED FOR/REVISIONS FOR ID 1-21-2015 FILE NAME: C:\pw_work\pw_proj\dlmaier\d0448397\E-0.dwg PLOTTED : 1/16/2015 10:22 AM PLOTTED Y: Daniel L. Maier UPS-RP-00 UPS-MDP *4"* *4"* 1 E-0 EXIST. PP-CT XFMR UPS-T *2'-6"* *1'-0"* *11'-2"* UPS *7'-0"* 2 E-0 HOUSEKEEPING PAD PLAN 1/2" = 1'-0" 0 5' * - ASTERISK DENOTES DIMENSIONS THAT MUST E COORDINATED WITH APPROVED EQUIPMENT SHOP DRAWINGS PRIOR TO POURING HOUSEKEEPING PAD. *4"* *2'-6"* *4"* *2'-10"* 6x6-W2.9xW2.9 WWF IN FLAT SHEET MATCH EXIST. FLOOR COATING 3 4 " CHAMFER ALL AROUND #3 DWL'S @ 18" O.C. EPOXY 4" INTO EXIST. SLA. REMOVE EXISTING COATINGS. ROUGHEN SURFACE AND APPLY EPOXY ONDING AGENT PRIOR TO POURING NEW PAD. 4" 2 E-0 SECTION 1" = 1'-0" 0 3' NOTES: 1. SEE DRAWING G-1 FOR GENERAL NOTES AND LEGEND 2. IN FINISHED AREAS, CEILINGS ARE LAY-IN CEILING TILE. 3. EXISTING RECEPTACLES DESIGNATED TO E FOR THE UPS TO HAVE NEW CONDUIT AND WIRE INSTALLED FROM THE UPS RANCH CIRCUIT PANEL TO THE NEW RECEPTACLE. RECEPTACLES NOT DESIGNATED FOR UPS UT PRESENTLY SHARING THE EXISTING CIRCUIT ARE TO E DISCONNECTED FROM THE UPS RECEPTACLE, AND ARE TO MAINTAIN THEIR CONNECTION TO THE EXISTING PANEL. 4. NOT USED 5. NOT USED 6. NOT USED 7. CORE DRILLING SHALL E COORDINATED WITH WSU REP AND ADJACENT CORED HOLES TO E NO CLOSER THAN 2 TIMES DIAMETER SPACING. 8. SEE UPS RISER DIAGRAM ON DWG. E-102 FOR DIAGRAMMATIC VIEW OF CONDUIT ENTERING THIS ROOM. 9. PROVIDE FIRE STOPPING AROUND ALL CONDUITS AND AROUND ALL SLEEVES PASSING THROUGH FIRE RATED WALLS AND FLOORS PER SHT. G-1. 10. INSTALL CONDUIT RISER IN A LOCATION AND MANNER THAT DOES NOT CAUSE INTERFERENCE WITH EXISTING ACCESS, EQUIPMENT, DEVICES, ETC. COORDINATE WITH WSU REP. 11. COORDINATE WITH WSU REP FOR ENTRY INTO RESTRICTED AREAS. CLIENT 320006 AS SHOWN ASEMENT FLOOR PLAN E-0
UPS-RP-02 #22 UPS-RP-02 #21 UPS-RP-02 #23 UPS-RP-02 #28 UPS-RP-02 #27 UPS-RP-02 #24 UPS-RP-02 #20 UPS-RP-02 #19 UPS-RP-02 #29 271 UPS-RP-02 #32 UPS-RP-02 #35 291 2700 W. Argyle Street UPS-RP-02 #26 UPS-RP-02 #25 UPS-RP-02 #33 UPS-RP-02 #31 295 UPS-RP-02 #02 216 UPS-RP-02 #34 UPS-RP-02 #01 UPS-RP-02 #15 UPS-RP-02 #16 UPS-RP-02 #17 UPS-RP-02 #18 267 UPS-RP-02 #03 UPS-RP-02 #14 UPS-RP-02 #13 UPS-RP-02 #12 278 UPS-RP-02 SEE DWG. E-0 AND E-3 FOR CONTINUATION 2 3 UPS-RP-02 #30 ELEC 237 286 UPS-RP-02 #04 ELECTRICAL RELIAILITY UPGRADES PROJ. No. 5454 CASS AVENUE DETROIT, MICHIGAN UPS-RP-02 #07 UPS-RP-02 #10 UPS-RP-02 #08 JAS UPS-RP-02 #06 UPS-RP-02 #11 UPS-RP-02 #09 MARK ISSUED FOR/REVISIONS UPS-RP-02 #05 FOR ID 1-21-2015 FILE NAME: C:\pw_work\pw_proj\dlmaier\d0448397\E-2.dwg PLOTTED : 1/14/2015 2:24 PM PLOTTED Y: Daniel L. Maier UPS-RP-02 NORTH SECOND FLOOR LEVEL 1/8" = 1'-0" 0 5' 10' 15' 20' NOTES: 1. SEE DRAWING G-1 FOR GENERAL NOTES AND LEGEND 2. IN FINISHED AREAS, CEILINGS ARE LAY-IN CEILING TILE. 3. EXISTING RECEPTACLES DESIGNATED TO E FOR THE UPS TO HAVE NEW CONDUIT AND WIRE INSTALLED FROM THE UPS RANCH CIRCUIT PANEL TO THE NEW RECEPTACLE. RECEPTACLES NOT DESIGNATED FOR UPS UT PRESENTLY SHARING THE EXISTING CIRCUIT ARE TO E DISCONNECTED FROM THE UPS RECEPTACLE, AND ARE TO MAINTAIN THEIR CONNECTION TO THE EXISTING PANEL. 4. NOT USED 5. NOT USED 6. NOT USED 7. CORE DRILLING SHALL E COORDINATED WITH WSU REP AND ADJACENT CORED HOLES TO E NO CLOSER THAN 2 TIMES DIAMETER SPACING. 8. SEE UPS RISER DIAGRAM ON DWG. E-102 FOR DIAGRAMMATIC VIEW OF CONDUIT ENTERING THIS ROOM. 9. PROVIDE FIRE STOPPING AROUND ALL CONDUITS AND AROUND ALL SLEEVES PASSING THROUGH FIRE RATED WALLS AND FLOORS PER SHT. G-1 10. INSTALL CONDUIT RISER IN A LOCATION AND MANNER THAT DOES NOT CAUSE INTERFERENCE WITH EXISTING ACCESS, EQUIPMENT, DEVICES, ETC. COORDINATE WITH WSU REP. 11. COORDINATE WITH WSU REP FOR ENTRY INTO RESTRICTED AREAS. CLIENT 320006 AS SHOWN SECOND FLOOR PLAN E-2
UPS-RP-03 #13 330 2700 W. Argyle Street UPS-RP-03 #14 GROUP RM 315 UPS-RP-03 #18 UPS-RP-03 #17 UPS-RP-03 #16 NORTH OPEN LA 317 TISSUE CULTURE 331 ROOF STORAGE 310 PENTHOUSE 300 CONFERENCE ROOM 301 STORAGE 309 ELEV 377 ELEV 378 302 LOY RECEPTION 303 DN 314 STORAGE 313 308 305 UP 307 UPS-RP-03 #05 UPS-RP-03 #04 UPS-RP-03 #06 UPS-RP-03 # 01 03 306 UPS-RP-03 #02 MEN 319 WOMEN 320 IMAGING STORAGE LA 321 322 SCOPE 323 ELEC 344 COLD RM 324 342.1 UPS-RP-03 342.2 #15 342.3 342.4 342.5 ANTE ROOM 326 WORK ROOM 327 CYLINDERS 329 337 SOUTH OPEN LA 340.3 MASS SPEC LA 328 SERVICE AREA SEE DWG. E-2 343 369 FOR CONTINUATION UPS-RP-03 #09 341 COMM UPS-RP-03 #08 336 UPS-RP-03 SURFACE MOUNT 340.1 340.2 3 UPS-RP-03 #26 UPS-RP-03 #22 UPS-RP-03 #25 UPS-RP-03 #21 UPS-RP-03 #24 UPS-RP-03 #20 UPS-RP-03 #23 UPS-RP-03 #19 UPS-RP-03 #10 UPS-RP-03 #11 UPS-RP-03 #12 UPS-RP-03 #07 ENCH 338 339 LA SUPPORT 332 UP 333 334 DN ELECTRICAL RELIAILITY UPGRADES PROJ. No. JAS 5454 CASS AVENUE DETROIT, MICHIGAN MARK ISSUED FOR/REVISIONS FOR ID 1-21-2015 UPS-RP-03 #28 UPS-RP-03 #27 UPS-RP-03 #29 FILE NAME: C:\pw_work\pw_proj\dlmaier\d0448397\E-3.dwg PLOTTED : 1/16/2015 10:26 AM PLOTTED Y: Daniel L. Maier UPS-RP-03 NORTH THIRD FLOOR LEVEL 1/8" = 1'-0" 0 5' 10' 15' 20' NOTES: 1. SEE DRAWING G-1 FOR GENERAL NOTES AND LEGEND 2. IN FINISHED AREAS, CEILINGS ARE LAY-IN CEILING TILE. 3. EXISTING RECEPTACLES DESIGNATED TO E FOR THE UPS TO HAVE NEW CONDUIT AND WIRE INSTALLED FROM THE UPS RANCH CIRCUIT PANEL TO THE NEW RECEPTACLE. RECEPTACLES NOT DESIGNATED FOR UPS UT PRESENTLY SHARING THE EXISTING CIRCUIT ARE TO E DISCONNECTED FROM THE UPS RECEPTACLE, AND ARE TO MAINTAIN THEIR CONNECTION TO THE EXISTING PANEL. 4. NOT USED 5. NOT USED 6. NOT USED 7. CORE DRILLING SHALL E COORDINATED WITH WSU REP AND ADJACENT CORED HOLES TO E NO CLOSER THAN 2 TIMES DIAMETER SPACING. 8. SEE CONDUIT RISER DIAGRAM ON DWG. E-102 FOR DIAGRAMMATIC VIEW OF CONDUIT ENTERING THIS ROOM. 9. PROVIDE FIRE STOPPING AROUND ALL CONDUITS AND AROUND ALL SLEEVES PASSING THROUGH FIRE RATED WALLS AND FLOORS PER SHT. G-1 10. INSTALL UPS RISER IN A LOCATION AND MANNER THAT DOES NOT CAUSE INTERFERENCE WITH EXISTING ACCESS, EQUIPMENT, DEVICES, ETC. COORDINATE WITH WSU REP. 11. COORDINATE WITH WSU REP FOR ENTRY INTO RESTRICTED AREAS. CLIENT 320006 AS SHOWN THIRD FLOOR PLAN E-3
2700 W. Argyle Street UPS 60kVA 2"C WITH 3 #1/0 1 - #6 GND NEW WORK 1 1 2"C WITH 3 #2 1 #2 N 1 #8 GND 1 1 2"C WITH 3 #2 1 #2 N 1 #8 GND UPS-T 75 kva 480-208V/120V 3 PH, 4 WIRE UPS-RP-00 UPS-MDP 400A UPS-RP-02 2"C WITH 3 #1/0 1 - #6 GND 3"C WITH 3-300 KCMILL 1-300 KCMILL N 1 - #4 GND UPS-RP-03 1 1 2"C WITH 3 #2 1 #2 N 1 #8 GND ELECTRICAL RELIAILITY UPGRADES PROJ. No. 5454 CASS AVENUE DETROIT, MICHIGAN DLM MARK ISSUED FOR/REVISIONS NEW WORK FOR ID 1-21-2015 NEW WORK FILE NAME: C:\pw_work\pw_proj\dlmaier\d0448397\E-101.dwg PLOTTED : 1/16/2015 12:52 PM PLOTTED Y: Daniel L. Maier 100A 3P 100A FURNISH AND INSTALL IN UNUSED SPACE NEW 100A, 480V, 3PH. FUSED SWITCH (SPECTRA, GENERAL ELECTRIC TO MATCH EXISTING) CLIENT 320006 AS SHOWN ELECTRICAL ONE LINE DIAGRAM E-101
J J J J J J J J J J J J J J J J J 2700 W. Argyle Street UPS-RP-03 3RD FLOOR 2ND FLOOR RM. 340.1 UPS-RP-03-01 03 UPS-RP-02 RM. 340.1 UPS-RP-03-02 RM. 340.1 UPS-RP-03-04 RM. 340.2 UPS-RP-03-05 J J J J J J J J J J J J J J J J J RM. 216 UPS-RP-02-01 RM. 340.2 UPS-RP-03-06 RM. 216 UPS-RP-02-02 RM. 328 UPS-RP-03-07 RM. 230.1 UPS-RP-02-03 RM. 328 UPS-RP-03-08 RM. 254 UPS-RP-02-04 RM. 328 UPS-RP-03-09 UPS-RP-02-05 RM. 328 UPS-RP-03-10 UPS-RP-02-06 RM. 328 UPS-RP-03-11 UPS-RP-02-07 RM. 328 UPS-RP-03-12 UPS-RP-02-08 RM. 315 UPS-RP-03-13 UPS-RP-02-09 RM. 315 UPS-RP-03-14 UPS-RP-02-10 RM. 342.3 UPS-RP-03-15 UPS-RP-02-11 RM. 317 UPS-RP-03-16 RM. 278 UPS-RP-02-12 RM. 317 UPS-RP-03-17 RM. 278 UPS-RP-02-13 RM. 317 UPS-RP-03-18 RM. 278 UPS-RP-02-14 UPS-RP-03-19 RM. 278 UPS-RP-02-15 UPS-RP-03-20 RM. 267 UPS-RP-02-16 UPS-RP-03-21 RM. 267 UPS-RP-02-17 UPS-RP-03-22 RM. 267 UPS-RP-02-18 UPS-RP-03-23 UPS-RP-02-19 UPS-RP-03-24 UPS-RP-02-20 UPS-RP-03-25 UPS-RP-02-21 UPS-RP-03-26 UPS-RP-02-22 UPS-RP-03-27 UPS-RP-02-23 UPS-RP-03-28 UPS-RP-02-24 UPS-RP-03-29 UPS-RP-02-25 UPS-RP-02-26 UPS-RP-02-27 UPS-RP-02-28 UPS-RP-02-29 RM. 286 UPS-RP-02-30 RM. 295 UPS-RP-02-31 RM. 291 UPS-RP-02-32 RM. 291 UPS-RP-02-33 RM. 216 UPS-RP-02-34 RM. 291 UPS-RP-02-35 3RD FLOOR 2ND FLOOR ELECTRICAL RELIAILITY UPGRADES PROJ. No. 5454 CASS AVENUE DETROIT, MICHIGAN JAS MARK ISSUED FOR/REVISIONS 1ST FLOOR 1ST FLOOR FOR ID 1-21-2015 FILE NAME: C:\pw_work\pw_proj\dlmaier\d0448397\E-102.dwg PLOTTED : 1/16/2015 10:41 AM PLOTTED Y: Daniel L. Maier GND. FLOOR TO EXIST. PNLRD. PP-CT SEE E-101 FOR ONE-LINE C1 UPS MAINTENANCE Y-PASS PANEL RECT ATTERY CA WITH NEW REAKER INV UPS CANET C2 Y-PASS REAKER C3 480VDC T-UPS 75KVA XFMR 480V, 3Ø-208V/120V, 3Ø,4W SEE NOTE 2 UPS-MDP 208/120V,3Ø,4W MAIN DISTRIUTION PANEL UPS-RP-00 J RM. 039 UPS-RP-00-01 RM. 039 UPS-RP-00-02 J RM. 039 UPS-RP-00-03 RM. 039 UPS-RP-00-04 J J J J J J J J J J J RM. 033.1 UPS-RP-00-05 RM. 033.1 UPS-RP-06 RM. 033.1 UPS-RP-00-07 RM. 033.1 UPS-RP-00-08 NOTES: RM. 033 UPS-RP-00-09 RM. 033 UPS-RP-00-10 RM. 004.1 UPS-RP-00-11 RM. 004.1 UPS-RP-00-13 RM. 004.1 UPS-RP-00-14 RM. 004.1 UPS-RP-00-15 UPS-RP-00-17 UPS-RP-00-18 1. SEE DRAWING G-1 FOR GENERAL NOTES AND LEGEND UPS-RP-00-19 21 UPS-RP-00-20 UPS-RP-00-22 2. 60 kva TOSHIA UPS, COMPLETE WITH INVERTER, Y-PASS AND ATTERY CAINET. CONTRACTOR MUST PURCHASE FROM PREFERRED WSU VENDOR, ANCONA CONTROLS, 28021 GRAND OAKES CT., WIXOM, MI. 48021. PHONE: 248-880-6351 3. NOT USED 4. NEW CIRCUITS AS INDICATED IN THE CALE/CONDUIT/PANEL SCHEDULES EXTEND FROM LISTED PANELS TO THE DESIGNATED LOADS THROUGHOUT THE CS MOTT UILDING. 5. NOT USED 6. NOT USED 7. NOT USED UPS-RP-00-23 UPS-RP-00-24 RM. 028 UPS-RP-00-25 RM. 028 UPS-RP-00-26 RM. 028 UPS-RP-00-27 UPS-RP-00 #16 GND. FLOOR 8. CORE DRILLING SHALL E COORDINATED WITH WSU AND ADJACENT CORED HOLES TO E NO CLOSER THAN 2 TIME DIAMETER SPACING. 9. NOT USED 10. THE UPS SHALL E GROUNDED PER LATEST VERSION OF NEC. THE GROUNDED CONDUCTOR SHALL E #2 AWG, INSULATED, 90 DEGREE C, COPPER. PROVIDE THE GROUNDING CONDUCTOR FROM THE UPS TO NEAREST UILDING GROUND US. ROUTE GROUNDING CONDUCTOR THROUGH RIGID NON-METALLIC CONDUIT WHERE EXPOSED. USE USHINGS AT ENDS OF CONDUIT. PROVIDE ENOUGH SLACK AT UPS END TO ALLOW THE UPS TO MOVE 4'-0" FOR MAINTENANCE. 11. UPS PANEL OARDS AND EQUIPMENT SHALL E LAELED WITH A YELLOW WITH LACK LETTERING NAMEPLATE. CLIENT 320006 AS SHOWN UPS RISER DIAGRAM E-102