SINGLE-PHASE PUMP START AND PROTECTION BOX Type V1M, V1N, V1E, V1F

Similar documents
Pump controller and protection for one pump Multicontrol. +info: INSTALLATION AND OPERATION. Mod. Vigilec mini (V1N)

Vigilec doble. Pump controlller and protection for two (3ph/1ph) pumps INSTALLATION AND OPERATION

Application Engineering

331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH

Owners Manual. Features

Owners Manual. Features

KD LV Motor Protection Relay

MODEL 422 Submersible Pump Controller

Electronic Products ELECTRONIC MAINTENANCE

Application Engineering

CONTENTS. Earth leakage and overload/short circuit protection systems with self-reclosing Associated breaking element

Owner s Manual. Features

DRENOX SUBMERSIBLE SUMP PUMPS FOR DRAINING CLEAR WATER. Usage limitations

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

DIN Rail UPS Model: DIN-UPS Installation/Operation Manual

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

R & D SPECIALTIES ROTROL I USER'S MANUAL

Valcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

Control panel. For 3 three-phase electric pumps with thermal protection and exchanger

Installation, Operation and Maintenance Manual

MODEL 235P INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 08/2009 II_235P_B1

MCD 500 Service Manual. Functional Tests 5 Power Circuit Test 5 Start Performance Test 5 Run Performance Test 6 Trip Messages 6 General Faults 10

BIOXDPV 160/6 IT - ISTRUZIONI ORIGINALI IN LINGUA ITALIANA

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

User Manual. T6 Tachometer. Online: Telephone: P.O. Box St. Petersburg, Florida 33736

ADVANCED PID TROUBLESHOOTING

INSTALLATION AND OPERATING INSTRUCTIONS MANUAL Owner s manual FIXED SPEED BOOSTER SETS SERIES:

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

.2 Section Waste Management and Disposal..5 Section Thermometers and Pressure Gauges Piping Systems.

Motor. Document # Vari-Green Motor and Controls. Table of Contents. Features, Operation, Wiring and Troubleshooting

MODEL 233P/111P/233P-1.5

Install a module ME or MT

P.1 CONTENTS. Industrial Earth Leakage Protection. Page

Instruction Manual. Q Series 2 Motor Control Modules - OEM

Mizer Single Pump and Starter Box

Trouble Shooting Guide EWA, 3-phase (D2422)

Installation and Operating Instructions

USERS MANUAL MCD REMOTE OPERATOR

DIN Rail UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS Installation/Operation Manual

8 Troubleshooting and Maintenance

Combined Ventilation Controller RVWS-T-224HA

Troubleshooting: Door Jamming and Door Handing 6. Troubleshooting: Keypad 11. Troubleshooting: Smart Home Systems 12. Troubleshooting: Battery 14

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

ABB Softstarter Benefits Charnchanok Thongprad

SKC400U SLIDING GATE OPENER OWNER S MANUAL

1332 TROUBLESHOOTING GUIDE. Remarks: If this function is not appropriate for the application, it can be eliminated by turning off DSWl, switch 3.

Troubleshooting: Installation 8. Troubleshooting: Door Jamming and Door Handing 9. Troubleshooting: Keypad 13. Troubleshooting: Smart Home Systems 14

Installation, Operation and Maintenance Manual

Installation and Operating Instructions

AA4006 Speed Sensitive Trip Unit. User Manual

MAGNETIC MOTOR STARTERS

BIGLA30-T/BIELA14-T Event Codes Quick Reference EXPLANATION CORRECTIVE ACTION PARTS TO CARRY ON SERVICE CALL

A problem with the motor windings. A phase loss on mains terminals L1, L2, or L3 during run mode. Parameter 2-3 Current Imbalance Delay.

Start Up Instructions for the Kiln, Page 1 of 2

PUR (A, B, C, D) INSTRUCTION FOR VARIABLE SPEED WITH WIRING DIAGRAM FOR EMX P10 ROTOR SIZE

SPECIFICATIONS NB SKILLS TRADE 19 AUTOMATION AND CONTROL

3200NT Timer Service Manual

Technical data. WARNING! Residual voltage is present for 1 minute after disconnecting mains voltage.

Degree of protection: IP 55 Power supply voltage: 230V/ 1F 50 Hz External dimensions: mm Weight: Kg 0.6

P445 Series Electronic Lube Oil Control

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

DRENOX IT - ISTRUZIONI ORIGINALI IN LINGUA ITALIANA

2. Milk does not heat and the heater is not hot. a. Is there power getting to the pasteurizer heater? Check the incoming voltage to the contactor

SECTION MOTOR CONTROL

Installation Instructions

INSTRUCTION MANUAL IM245. RGS2012E1 S or E Retrofit Kit SUBMERSIBLE GRINDER PUMP INSTALLATION, OPERATION AND TROUBLESHOOTING MANUAL

EBARA COMPACT BOOSTER AM-PC

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual

COOKSON OWNER'S MANUAL

COAST SPAS TSPA-MP SERVICE MANUAL. Visual step-by-step guide to easily identify & correct technical problems! Gecko Electronics Inc.

IMPORTANT SAFEGUARDS READ THIS MANUAL AND FOLLOW ALL SAFETY INSTRUCTIONS THOROUGHLY BEFORE OPERATING THE EMIU INVERTER SYSTEM SAVE THESE INSTRUCTIONS

OWNERS MANUAL ECODIVER

Heavy duty slurry pumps

E Series CE Approved Intermittent Pilot Ignition Control

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

GRUNDFOS PRODUCT GUIDE. Redi-Flo3 and CU 300. Environmental Pumps 60Hz

Mini Multimeter with Non-Contact Voltage Detector (NCV)

Troubleshooting: Installation 10. Troubleshooting: Door Jamming and Door Handing 11. Troubleshooting: Touchscreen 14

Protection and control P. 1 /2. Smart earth leakage protection

One step forward. Multi-pump and Multi-function control panel

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

F ERNI K I T THE FERNI-S KIT CONSISTS OF:

RVS-AX Instruction Manual

PROFESSIONAL 270 o PIR MOTION DETECTOR

DEEP SEA ELECTRONICS PLC

TECHNICAL DATA HYDRAULIC UNIT

GLM SERIES CONTROL Users Manual Rev:

Application Engineering Europe

XCITE Owner s Manual. Reso-not TM Damping System XCITE 1502C HYDRAULIC POWER SUPPLY

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

PHASE PERFECT PHASE CONVERTERS OPERATION & INSTALLATION MANUAL PHASE TECHNOLOGIES, LLC

ELECTRIC FENCE ENERGIZER SERVICE MANUAL MODEL 950 SERVICE MANUAL FOR OLLI 950 FENCE ENERGIZERS

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions.

Driftsinstruks. Utopia kontroller feilkoder PCP-2HTE og PC-ART. Vi håper de får stor glede av et Novema kulde produkt!

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

Transcription:

www.motor-pump-ventilation.com SINGLE-PHASE PUMP START AND PROTECTION BOX Type V1M, V1N, V1E, V1F Owner s manual

Main features An all-in-one control and protection unit for any pump. Multicontrol. Vigilec mini: Three-phase. 230/400 V~. Directon-line starting (DOL). Vigilec mono: Single-phase 230V~. Direct-online starting (DOL). Protection against connection failure to the pump. Protection against overvoltage. Protection against overload. Protection against underload. Protection against phase failure (Vigilec mini). Stormproof. Protection against dry running with 3 possible confi gurations: 1) TWO PROBES: low and high level. 2) ONE PROBE: low level only. 3) Underload: WITHOUT PROBES In case 2 and 3, restarting after 15 min. Adjustable OVERLOAD and UNDERLOAD electronic relays. Alarm trip in 7 s. (overload) or in 4 s. (underload). Protection against pump jamming during long rest periods (only in AUTO mode). Guaranteed against incorrect connections. Remote control output admitting 6 to 400 V~/ V= contact or voltage. All control devices in low voltage. Selection MAN-0-AUT by push-buttons. MAIN SUPPLY led, PUMP RUNNING led, WATER LEVEL ALARM led, OVERLOAD and UNDERLOAD leds. Reset push-button. General alarm output relay. Wide diameters range and high protection cable glands. Common applications WELL & BOREHOLE WELL & TANK 2 PROBES MODE ON 1 PROBE MODE ON DELAY WITHOUT PROBES MODE ON DELAY OFF (Amp) PROBES MODE OFF OFF DRAINAGE & SEWAGE BOOSTER SETS BOOSTER SETS ON DELAY FLOAT MODE PROBES MODE ON OFF OFF Page 2

Front configuration A B C D E F G START button: AUTOMATIC mode (green circle Led ON): press the button and the unit will work automatically with the established controls and protections. MANUAL mode (green circle Led fl ashing): holding down the button more than 4 seconds, the pump is forced to start running. The overload and underload motor protections are on in this mode. By releasing the button, the pump stops immediately and the device goes back to the AUTOMATIC mode. STOP ( 0 ) button: the unit stops the motor and blocks the re-start. If voltage failure occurs, the established operation mode remains memorized, continuing in the same mode (STOP-AUTO) once the voltage is restored. Red Led: MOTOR ALARM. Led fl ashing: re-start time after detection of motor alarm (overload: 7 seconds, underload: 4 seconds). Led on: OVERLOAD ALARM. Led on fl ashing each 5 seconds: UNDERLOAD ALARM. Green Led: MOTOR RUNNING. Orange Led: LOW LEVEL. Orange on: lack of water (2 probes mode). ORANGE FLASHING: re-start time of 15 minutes after a lack of water (1 probe with delayed start or without probes mode). RESET button: Re-starts the unit after an alarm for OVERLOAD or UNDERLOAD or stops the LACK OF WATER time delaying. SUPPLY VOLTAGE Green Led: it lights when there is a supply voltage. Page 3

Internal configuration Mod. Vigilec mono A B C D E F G H I J K L Control fuse (0,1A). Current transformer. Power relay. Flat cable connector. Minimum current adjustment (Amp. min). Maximum current adjustment (Amp. max). Control terminal blocks. Capacitor housing (submersible pumps). Main supply cable gland. Motor cable gland. Probes and earth cable gland. Remote / external alarm cable gland. Mod. Vigilec mini A B C D E F G H I J K L M Circuit breaker. Running motor contactor. Control fuses and voltage selection (0,1 A). Current transformer. General alarm output relay. Flat cable connector. Underload adjustment (Amp. min). Overload adjustment (Amp. max). Control terminal blocks. Main supply cable gland. Motor cable gland. Probes and earth cable gland. Remote /external alarm cable gland. Page 4

200 www.motor-pump-ventilation.com Installation There are 4 fixing points for the wall mounting of the unit, located at the corners. As an option you can drill the enclosure in these points and screw it on the wall or 95on a support. If you wish you can install external clevis for wall fixing. 150 Open unit and move up the top to facility the connection and adjustment unit. Types of Clevis mounting in detail Clevis screws to box Mod. Vigilec mono Single phase supply Single phase motor output Single phase motor output + capacitor U V Box (Backside) Clevis screws to wall CAPACITOR (NOT INCLUDED) CLEVIS U V W Mod. Vigilec mini U V W Phase Neutral Capacitor Three phase supply Three phase motor output L1 L1 L2 L2 L3 L3 In single phase installation wire L-N in the input and U-V in the output Page 5

Probes installation The wires must be insulated. The maximum lenght for probes wiring is 200 mts. and the minimum section is 0,5 mm². A CORRECT EARTH CONNECTION is essential for the effective operation of the level control. It is recommended to connect the earth wire to any point of the pipe. A third probe submerged at the bottom of the recipient is required if the tank is insulated (concrete fi ber, glass fi ber and plastics in general). Two probes One probe Without probes Place the probe at least some centimeters higher than the pump intake. REMOTE connection The REMOTE terminals ( 3 y 4 ) can be connected to a remote device such as: radio remote control, pressure switch, fl oat switch, irrigation controller, time switch or a power supply ( 6 to 400 V~/V=). This input is protected against incorrect wiring. A jumper must be placed over Terminal blocks 3 and 4 if not used. Irrigation systems: we recommend to use this unit in 1 probe mode in applications with irrigation controller or other control devices. 3 4 5 6 Via radio Pressure switch Float Programmer Clock Switch Voltage (6 to 400 V~/V=) Page 6

Unit operation TWO PROBES The pump starts when the water level exceeds the high level probe (orange led off), and stops when the water level descends below the low level probe (orange led on). ONE PROBE When the water level descends below the low level probe, the pump stops. If this level is recovered in less than 10 seconds, the unit thinks that we are working in one probe mode, so it will not re-start the pump untill the end of the 15 minutes re-start time, during when the orange led will fl ash. min. Page 7

WITHOUT PROBES A correct minimum current adjustment is essential. (see section CURRENT ADJUSTMENTS ) When the level approaches the pump intake, the effort done by the pump decreases. The unit uses the motor as sensor: when this one decreases the effort, the intensity consumed decreases. This detection will stop the pump after a time delay of 4 s., during these seconds the alarm pilot will fl ash. 4 min. The pump will automatically start after a pre-defi ned time of 15 minutes (during this period the low level led will fl ash). If we press the RESET button, the time delay will be cancelled and the pump will start. If in less than a minute of operation, the unit stops again the pump, the underload alarm will trip due to motor failure (red led fl ashing). It will be necessary to press RESET to restart the unit. REMOTE (Only automatic mode) The REMOTE control terminal blocks, 3 y 4, can be used to start and stop the pump from an external device. If the level led is off (correct level), when we close a contact connected to this input (fl oat switch, pressure switch, time switch, radio remote control, switch etc) the pump will start and if we open it the pump will stop. We can also apply a voltage to this input from 6 to 400V~/V= (irrigation controller, presscontrol, etc) to start the pump or remove it to stop the pump. Alarm output (terminals 5 y 6) The contact will be closed when the pump stops due to thermal failure. Pumps anti-jamming If the pump is in automatic mode, the unit will activate the motor during 1 second every 23 hours of inactivity, preventing the jamming and the deterioration due to long rest periods. Page 8

Current adjustments LITH ON LIGHT FLASHING LIGHT OFF OVERLOAD adjustment (maximum current) Turn to the right Turn slowly to the left until the warning light starts fl ashing. Turn right until the warning light switches off If the warning light is still on...... press RESET and repeat step 4 increasing the value UNDERLOAD ADJUSTMENT (minimum current) Turn to the left Turn slowly to the right until the warning light starts fl ashing When the warning light switches on... Close valve Open valve PUMP PUMP N.B. 1: If you can t close the valve to do this adjustment, turn the thumbwheel to the right until the light fl ashes and go back a 25%. N.B. 2: To deactivate the underload protection, turn the thumbwheel totally to the left. Page 9

Specifications Vigilec mono (V1M) Vigilec mini (V1N) Supply voltage 230 V~ 230/400 V~ (selectable) Admissible voltage variation ±20% (>30%: auto power-off) ±20% (>30%: auto power-off) Maximum intensity 18 Amp AC3 12 Amp AC3 (16 or 23 a/model) Overload adjustment (Amp. max) 1-18 Amp 1-12 Amp (16 or 23 a/model) Underload adjustment (Amp. min) 1-18 Amp 1-12 Amp (16 or 23 a/model) Overload trip time 7 s 7 s Underload trip time 4 s 4 s Re-start time 15 minutes (fixed) 15 minutes (fixed) Capacitor maximum capacity 80 μf (50 μf inside the equipment) - Probes operating voltage 24 V~ 24 V~ Probes sensitivity 9 KΩ 9 KΩ Remote control connection Contact or voltage 6 to 400 V~/V= Contact or voltage 6 to 400 V~/V= Alarm output contact AC1 : 2 A / 250 V~ AC11 : 1 A / 230 V~ AC1 : 2 A / 250 V~ AC11 : 1 A / 230 V~ Control terminal blocks 4 mm² 4 mm² Mounting Wall mounting with fixing points Wall mounting with fixing points Size (mm) 200 x 150 x 80 255 x 195 x 95 Weight 850 g 1,5 Kg Working temperature -10 + 55 ºC -10 + 55 ºC Protection IP56 IP56 Page 10

Troubleshooting Problem Cause Solution The equipment does not work and the voltage light is off even when the system is connected to a power source. Control fuse is burned out. Excessive power voltage. Wrong input connection (Vigilec Mini). Phase failure (Vigilec Mini). Replace the corresponding fuse. Measure and check the power voltage. Connect correctly. Check phases. The system is working but the contactor does not activated. Voltage selection error (Vigilec mini). Pump alarm trips. Overcurrent adjustment (Amp. max/amp. min) too low or critical. Motor not connected. Input phase failure (Vigilec mini). Abnormal excessive motor consumption. Low motor consumption <0,5A. Level control doesn t work correctly. High and low level probes are reversed. Wrong ground connection. Cut wires (Probes/Remote). Verify voltage selection. Check motor consumption and adjust again the intensity. Connect the motor. Check the three supply phases. Check the motor. The motor is overloaded. Check pump (there is no water in the pump intake, the pipe is clogged, etc.). Place the probes in the correct position. Check the ground connection. Check the wires continuity. Page 11