BUSHINGS: GENERAL INFORMATION

Similar documents
Bushing Insulators according to DIN and UNEL Standards

PORCELAIN BUSHINGS ED Series

ABB SpA COMEM Operating Unit Power Grids Division Strada Regionale 11, Signolo Montebello Vicentino (VI) - ITALY

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

THROTTLE VALVES FOR RELAYS AND RADIATORS Series 2009

Bushings for High Voltage AC Applications

Transformer bushings, type GOH. Technical guide

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

Transformer bushings, type GOA 250. Installation and maintenance guide

Transformer bushings, type GSA-OA Technical guide

INSTRUCTION MANUAL CRS Combined insulation bushing

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

1ZSE en, Rev. 9. Transformer bushings, type GSA-OA Technical guide

PORCELAIN INSULATORS

Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC

PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper

SERIES TAP-CHANGER

THERMOMETERS For distribution transformers

Medium Voltage. KOFD Indoor Type Current Transformers Cast Resin Insulated. Catalogue. 12, 13.8, 17.5, 24 and 36 kv KOFD 1 GB

Outdoor Bushings DIN kv / A Freiluft Durchführungen DIN kv / A

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

Zinc Oxide Surge Arrester EXLIM R

Condenser Bushings. OIL-TO-AIR - Oil-Impregnated Paper ANSI STANDARDS IEEE C AND IEEE C AN ALSTOM COMPANY

TERMINAL BOXES FOR OIL IMMERSED TRANSFORMERS (Series 2009)

DM Condenser bushings, kV DURESCA

Zinc-Oxide Surge Arrester TEXLIM Q-C

Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv

Combined instrument transformers

OIL LEVEL GAUGES FOR DISTRIBUTION TRANSFORMERS

Energy Division. PCA Single Column Polymeric Surge Arrester

PABS. AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS ANSI STANDARDS AN ALSTOM COMPANY

Inductive voltage transformers

Inductive voltage transformers

INTERFACE E - 5/8" MEDIUM VOLTAGE SEPARABLE CONNECTORS AND BUSHINGS CATALOGUE 2017

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

Inductive voltage transformers

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

a Nexans company Catalogue 2009

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

MICAFIL RIP Transformer Bushings AirRIP / RTKF kv

Crimpmate Range pitch 5.00

Inductive voltage transformers

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

POLYMER INSULATOR. Index

DAQO Technical Differences of Isolated Phase Bus Standards. Study of Design Standard Variances, Insulator Design and Shipping Section Design

OTAA Oil Impregnated Paper (OIP) Bushing for IEEE/ANSI Market

EARTHING AND SHORT CIRCUIT LANCE DEVICE RAILWAYS

LK Position Switches TECHNICAL DATASHEET.

a Nexans company Catalogue 2008

Technical Specification of 11KV 200Amp. (3-Pole/2-Pole) Air Break Switch Scope Description of the materials Standards Insulator make

3EQ Composite Housed Surge Arresters Saving Money and Space, Gaining Reliability

Euroload Changeover Switch

WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO. GUARANTEED TECHNICAL PARTICULARS 1 of 2

a Nexans company Catalogue 2007

INTERFACE A MEDIUM VOLTAGE SEPARABLE CONNECTORS AND BUSHINGS CATALOGUE 2017

Semiconductor (AC) fuses

Disconnectors and earthing switches up to 25 kv AC

3EK7 Medium Voltage Silicone Insulated Surge Arresters

3EP6 porcelain surge arrester

OIL TO AIR BUSHINGS SERIES PNO. VOLTAGE FROM 52 kv TO 245 kv

High Voltage Accessories up to 72.5 kv

a Nexans company Catalogue 2015

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

Zinc Oxide Surge Arrester PEXLIM Q

High Voltage Surge Arresters Station Class

a Nexans company Catalogue 2009

MULTIBLOC 1.RST8 Size 1, 250A, 690VAC, Design for bus bar installation, Triple Pole

Transformer Bushings Type COT COT kv to 245 kv up to 3150 A IEC 137

CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION

3EQ Composite Housed Surge Arresters

Nexans Network Solutions Div. Euromold

شركة كهرباء محافظة القدس المساهمة المحدودة

TECHNICAL SPECIFICATION FOR 11 KV AIR BREAK (A.B.) SWITCHES:

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

MOULDED CASE CIRCUIT BREAKERS BC160N

THORNE & DERRICK UK TEL FAX TEL FAX

MULTIBLOC 2.RST8 Size 2, 400A, 690VAC, Design for bus bar installation, Triple Pole

5 SPECIAL CRIMPING TECHNOLOGY

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

a Nexans company Catalogue 2011

VALFONTA PRESSURE REGULATOR WITHOUT AUXILIARY ENERGY EXCESS PRESSURE VALVE (PRESSURE RELIEF VALVE) MODEL S1 MAIN CHARACTERISTICS

MULTIBLOC 1.ST8 Size 1, 250A, 690VAC, Design for Bottom Fitting, 1-,2-,3-,4-pole

www. ElectricalPartManuals. com Instructions for Cast Resin Bushing, 15 KV & Below

Datasheet. System pitch mm (0.400 inch) - SU/BU BUZ 10.16HP/02/180F AG BK BX

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

Nexans Network Solutions Div. Euromold

DynaVar Arresters IEC Line Discharge Classes 2, 3, 4 & 5

HVDC bushing without oil side porcelain Type GOF, for outdoor mounting. Installation and maintenance guide

GENERAL. CONSTRUCTION External

CENTER BREAK GROUP OPERATED AIR BREAK SWITCHES RATED 15.5kV THROUGH 170kV EFFECTIVE DATE: 10/25/16 REV B

a Nexans company Catalogue 2007

Transcription:

BUSHINGS: GENERAL INFORMATION 1.0 Electrical characteristics (Ir = rated current; Ur = rated voltage) 1.1Standard insulation levels Rated voltage Ur kv (r.m.s.) 1 3,6 12 24 36 52 One minute power frequency withstand voltage wet and dry kv (r.m.s.) 10 10 28 50 70 95 Dry lighting impulse withstand voltage dry (1,2/50 ms) kv 20 40 75 125 170 250 1.2 Standard values of rated thermal short time current (Ith) 25 times the rated current (Ir) for 2 s ; for Ir equal or greater than 4000A, Ith is always 100kA 1.3 Overload conditions (IEC 354): Bushing selected with Ir not less than 120% of the rated current of the transformers are considered to be able to withstand the overload conditions according to IEC 354. 2.0 Mechanical characteristic 2.1 Cantilever operating load (bushing installed less than 30 from vertical) Ur kv 800 A 1600 A 2500 A 3150 A 36 52 500 N 500 N 625 N 625 N Ir 1000 N 1000 N 1575 N 1575 N 2.2 Cantilever operating load ( bushing installed more than 30 from vertical) Ur kv 800 A 1600 A 2500 A 3150 A 36 52 300 N 300 N 375 N 375 N Ir 600 N 600 N 945 N 945 N 2.3 Cantilever test load Ur kv 800 A 1600 A 2500 A 3150 A 36 1000 N 1250 N 2000 N 3150 N 52 1000 N 1250 N 2000 N 3150 N Ir 3.0 Tightening torque (suggested values, +/- 10% depending on the quality of the tank cover surface) 3.1 On the central conductor LV/HV in brass or copper Size Torque Size Torque M8 M12 M20 M30x2 10 Nm 13 Nm 30 Nm 70 Nm M42x3 M48x3 M55x3 M75x3 110 Nm 180 Nm 250 Nm 250 Nm File : ISOLATORI DISTRIBUZIONE UNCONTROLLED COPY Rev. 3 dtd 10/10/08

3.2 On the steel fixing stud of HV bushings Size M10 M12 M16 Torque 15 Nm 25 Nm 40 Nm 3.3 On the locking bolts of the flags Size M10 M12 M16 Torque 25 Nm 40 Nm 90 Nm 4.0 Surface treatment of active metallic parts Unless by special request, all active metallic parts in brass and copper have self colour surfaces. Upon request, particularly for use in highly polluted enviroment conditions or in tropical climate, above parts can be supplied with electrolytic tinplated surfaces with 6-8 micron average coating thickness. 5.0 N.B.R. gaskets The material of our gaskets is suitable to be used in mineral oil at the max temperature of 100 C (minimum temperature - 20 C) for continous service; for different limit temperatures, please contact our engineering department. During the impregnation of the transformer it is possible to reach the max temperature of 110 C in oil and 120 C in air for 24 hours, without damaging the gaskets. Upon request available cork rubber impregnated gaskets, or in Viton, or in silicon rubber. File : ISOLATORI DISTRIBUZIONE UNCONTROLLED COPY Rev. 3 dtd 10/10/08

Sect. 2 H.V. BUSHINGS FOR DISTRIBUTION TRANSFORMERS Page 2.1: It shows the standard executions according to DIN 42531 (UNEL 38144-74 for Italy, UNE 20-176-89 for Spain). Highlighted the most common connection sketches of the active part : Fig. A1: Bolt drilled with different diameters for brazing the wire Fig. HJ4: The bottom of the bolt pos. 2 is fitted with a short flexible 6 sqmm copper wire to enable crimping connection Fig. HJ5: Same as fig. HJ4, but with an annealed copper rod dia 5mm instead of the copper wire Fig. WC2: With a special longer bolt and one additional M12 brass nut on the air side connection (SCECO specification) Page 2.1EN: It shows the bushing according to the new European standard EN 50180 with pollution level (I-II-III-IV IEC815) Page 2.3: It shows the 36kV bushings, with long creepage, up to 1650mm, using the same components of DIN 42531 with special porcelains Page 2.4-2.5: Single gap (fig. 2.4) or double gap (fig. 2.5) arcing horns REMARK: At page 2.1, the components are marked with ref. pos. according to DIN 42531; just to simplify the ref. pos. numbers according to UNEL 38144-74 and UNE 20-176-89 are shown on the right hand side columns. COMMENTS ON PAGE 2.1 2.1EN 2.2EN 2.3 2.4 2.5 Pos. 2 Pos. 3 Pos. 4-16-23-29-30-31 Pos. 5 Pos. 6 Pos. 7 Pos. 8-11-12-13-28 Pos. 15 Pos. 17 Pos. 22 Pos. 27 Brass top bolt. Different styles of internal connection at page 2.1 Brass cap Arcing horns in mild steel zinkplated. Upon request, in stainless steel AISI 304 NBR ring gasket "J" Fiber gasket "O" NBR flange gasket. Upon request, in impregnated cork Nuts and washers in mild steel zinkplated. Upon request, in stainless steel AISI 304 Fixing ring in zinkplated mild steel, or, upon request, in aluminium 99.5 or in stainless steel AISI 304 (thickness 1,2 mm) Aluminium clamping piece; upon request, in zink alloy "V" bracket in zinkplated mild steel Half collar support in zinkplated mild steel for medium arcing horn File : ISOLATORI DISTRIBUZIONE UNCONTROLLED COPY Rev. 3 dtd 10/10/08