www. ElectricalPartManuals. com MicroVersaTriP Conversion Kits Breaker Types AK/AKU/AKT-50, AKS/ AKSU/ AKST -50, AK/AKR-75, AK/AKR-100

Similar documents
ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

MicroVersaTrip Plus and MicroVersaTrip PM Conversion Kits For GE Types AK-25 and AKU-25 Low Voltage Power Circuit Breakers

Frame Sizes: AKJ/ AKJT I AKJU-50 and AKR/ AKRU-30/ 50, AKRT-50

GEF Renewal Pans. low Vohage Power Circuit Breakers. Type AKR-30S and AKRU-30S. www. ElectricalPartManuals. com

Operation and Maintenance Manual

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Power Break Circuit Breakers

www. ElectricalPartManuals. com POWER CIRCUIT BREAKERS TYPES AK-2/3/2A/3A-50, AKU-2/3/2A/3A-50, AKT-2/3/2A/3A-50 GENERAL fj ELECTRIC

Master Connection Diagram Series C R-Frame Circuit Breaker with DIGITRIP RMS Trip Units

RENEWAL PARTS AK-2-15 AK-2-25 AK-3-25 AKF-2-25 AK-2A-15 AK-2A-25 AK-3A-25 AKF-2A-25 AKU-2-25 AKU-3-25 AKU-2A-25 AKU-3A-25

Power Circuit Breakers

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

WESTINGHOUSE / CUTLER HAMMER DS POWER BREAKERS

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

Florham Park, NJ USA Call (ASCO) for sales or service

POWER BREAK Circuit Breakers

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

Low Voltage Power Circuit Breakers

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

Florham Park, NJ USA Call (ASCO) for sales or service

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Instructions for The Digitrip RMS Pole and 4-Pole Trip Unit Installation and Operation with K-Frame Series C Circuit Breakers

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

ELECTRIC SERVICE REQUIREMENTS FOR MEDIUM-SIZED COMMERCIAL INTERCONNECTED DISTRIBUTED GENERATION SOURCES

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

EntelliGuard Power Circuit Breaker Accessories. Network Interlock for Ampere Circuit Breakers. Introduction. Operation

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

INSTRUCTIONS. seconds. the tween the end of the bearing screw and the. top of the shaft. The moving contact is a small silver hemisphere

B CW POWER RELAY

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

Control Transformers

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING

univex INSTRUCTION MANUAL Meat Grinder PDF compression, OCR, web optimization using a watermarked evaluation copy of CVISION PDFCompressor

www. ElectricalPartManuals. com Digitrip Retrofit System for the Westinghouse DA-50 IL 33-DAC-2 WARNING

Power Break II Circuit Breaker Accessories Motor Operator Mechanism

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

Installation Instructions For Motor Control Center (MCC) Units

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

PRODUCT DRAWING WIRING DIAGRAM FIELD CONNECTIONS MILLENNIUM MODEL YT CHILLERS (STYLE J) WITH ELECTRO-MECHANICAL STARTER JOB DATA:

White Paper. Ground Fault Application Guide. WL Low Voltage Power Circuit Breakers

Low Voltage Power Circuit Breakers

Low Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking Operator

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

www. ElectricalPartManuals. com INSTRUCTIONS TYPE CO CONTACT MAKING AMMETER INSTALLATION OPERATION MAINTENANCE I.. L APPLICATION

Power Break II Switchboard

www. ElectricalPartManuals. com MAGNETIC TIME RELAYS GENERAL. ELECTRIC INSTRUCTIONS *IC *Also identified with prefix CR instead of IC.

Operator s Manual Series ACTS Automatic Closed Transition Transfer Switches 150 through 4000 amps A. Rating Label.

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

www. ElectricalPartManuals. com Operator s Manual

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps

Operator s Manual Series ATS Automatic Transfer Switches 30 through 4000 amp. Rating Label. Nameplate C TABLE OF CONTENTS

600 D 220 E 230 J Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

Control System. Part B, Section 1. This section covers the following unit configurations. Model Voltage 1, 2 Pump Piston (E, F, or G)

600PR SERIES ELECTRONIC IRRIGATION CONTROLLER

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps

SURE TRIP SLT-201 SECONDARY TEST SET

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label.

P. Sub 4 184A404. Sub 3 876A220

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches 150 through 4000 amp. Rating Label. Nameplate A

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers

Table of Contents. For latest version, visit:

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2

Programmer Disconnect Accessory Manual for Retrofil CB

Individual breakers in separate enclosures can be applied in low voltage distribution systems through 600 volts Ac, 50/60 Hertz.

DEF 005. WavePro Power Circuit Breakers A Frames, Vac. Renewal Parts

www. ElectricalPartManuals. com GENERAL. ELECTRIC RENEWAL PARTS CR7006-C100, -C101 AND -C102 MAGNETIC STARTERS

SURE-TRIP OEM RELACEMENT TRIP UNIT

3ATS & 3NTS J-design 600 A 3ADTS & 3NDTS A Transfer Switches. Installation Manual. Installation A DANGER. Table of Contents WARNING

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

ches UL File No. E101598

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC

PB-Series. GFCI/ELCI & Panel Seal

www. ElectricalPartManuals. com

www. ElectricalPartManuals. com (fr} lite Imperial Carporatian ''- METAL-ENCLOSED, FUSED-INTERRUPTER SWITCH INSTRUCTIONS

Instructions for Field Testing of Systems Pow-R Breakers. l.l File www. ElectricalPartManuals. com. Effective June, 1979

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII

OPTIONAL EQUIPMENT EL WIRING. If other 873 logic board, refer to Von Duprin instructions Solenoid

Electromagnetic Industries LLP

IL 33-DRC-1 Retrofit System for Westinghouse and Cutler-Hammer DS Power Circuit Breakers. Table of Contents

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Digitrip Retrofit System for the General Electric AKR 6D/7D-30/50 and AKRT 6D/7D-50 Series Breakers

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

CR193 B,C,D and E Vacuum Limitamp * Contactors

AUTOTRANSFORMER-TYPE MANUAL AC STARTERS GENERAL ELECTRIC COMPANY DESCRIPTION

TESCO THE EASTERN SPECIALTY COMPANY Date: 05/04/15 Canal Street and Jefferson Avenue Bristol, PA 19007

www. ElectricalPartManuals. com GENERAL. ELECTRIC RENEWAL PARTS METAL-CLAD SWITCHGEAR TYPES M-26 AND M-36 GEF-4351C Supersedes GEF-4351B

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Supplementary Instructions for Mechanical Latch Attachment for Type SJA or SJO Contactor Single or Dual Trip, 360 Amp~re

Instructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers

Transcription:

nstallation Manual GEK-64468 MicroVersaTriP Conversion Kits Breaker Types AK/AKU/AKT-50, AKS/ AKSU/ AKST -50, AK/AKR-75, AK/AKR-100 GENERAL fl ELECTRC

MicroVersaTrip Conversion Kits Table of Contents CONTENTS Description Page Description -------------------------------------- SECTON 1-lntroduction..................... 3 1.1 General nformation............................. 3 SECTON 2-Front Frame Conversion... 5 2.1 General nformation.......... 5 2.2 Breaker Disassembly............ 5 2.3 Remounting Wand Relays.............. 5 2.4 Flux Shifter nstallation....................... 6 2.4.1 Trip Paddle nstallation................... 7 2.4.2 Adjustments................. 7 2.5 Programmer Mounting nstallation................ 8 2.6 Programmer Harness nstallation................. 8 SECTON 3-Back Frame Conversion...... 9 3.1 General nformation............................. 9 3. 2 Crossbar Modification........................... 9 3.3 Phase Sensors-AK/AKS-50...... 10 3.4 Phase Sensors-AKR-75/100..... 10 3. 5 Phase Sensors-AK-75/1 00............... 11 3. 6 Back Frame Harness nstallation... 11 Page SECTON 4-Four-wire Ground Fault....... 13 4.1 General nformation... 13 4.2 Breaker Conversion-AK/AKS-50 Drawout...... 13 4.3 Breaker Conversion-AK/AKS-50 Stationary... 14 4.4 Breaker Conversion AK/AKS-75/1 00 Drawout.... 14 4. 5 Breaker Conversion AKR-75/1 00 Stationary... 15 4.6 Equipment Conversion... 15 4.7 Neutral Sensors................................ 19 SECTON 5-Programmer nstallation..... 23 5.1 General nformation... 23 5. 2 AK/AKS-50 nstallation... 23 5.3 AK/AKR-75/100 nstallation...... 23 SECTON 6-Testing and Troubleshooting 24 6.1 General nformation... 24 6.2 Testing......................................... 24 6. 3 Troubleshooting... 24 6.3.1 Resistance Values... 24 6.4 False Tripping-Breakers Equipped with Ground Fault...... 25 6. 5 MicroVersaTriprM Cabling Diagrams... :... 25 THESE NSTRUCTONS ARE NTENDED FOR USE BY QUALFED PERSONNEL FOR NSTRUCTON AND MANTE NANCE PURPOSES. REPRODUCTON N WHOLE OR N PART S NOT PERMTTED WTHOUT THE EPRESS PERMS SON OF THE GENERAL ELECTRC COMPANY. 1983 GENERAL ELECTRC COMPANY 2 www. ElectricalPartManuals. com

SECTON 1-lntroduction 1.1-General lnformation These instructions cover installation of the MicroVersaTripTM solid-state, trip-device, conversion kits on the AK/AKR-75/1 00 and AK/AKS-50 breakers listed in Table 1-1. Each kit contains the necessary material to convert from existing EC, Power Sensor, ECS or SST trip device systems. Kit installation is straightforward but does require careful workmanship and attention to these instructions. Familiarity with the breaker itself is highly desirable. The general approach is to first strip the breaker of its existing trip devices, then install the MicroVersaTripTM components. Following this procedure, the converted breaker is performance tested, prior to restoring the breaker to service. For the majority of breaker models listed in Table 1-1, kit installations do not require any customized assembly work. However, some conversions may involve unusual mounting circumstances or accessory combinations which necessitate minor modification/relocation of a component(s). n most instances this supplementary work can be done on site. Preparatory to beginning the conversion, the installer should verify that the correct kit, current sensors and programmer unit have been furnished-see Tables 1-2 through Table 1-5. Whenever the Ground Fault trip element is furnished for breakers applied on 4-wire systems, note that, in addition to Table 1-1-Basic MicroVersaTrip Conversion Kits Breaker Type AK-50 AKT-50 AKU-50 AKS-50 AKST-50 AKSU-50 Drawout Cat. No. 343L821G Stationary With Without With Without 4th Wire 4th Wire 4th Wire 4th Wire Ground Ground Ground Ground Fault Fault Fault Fault 4 5 6 5 11 12 13 12 AK-75 7 8 N/A N/A AK-1 00 9 10 N/A N/A AKR-75 23 24 25 24 AKR-1 00 17 18 19 18 AKR-W-100 20 21 22 21 N/A-Not Available installing the kit on the breaker, an associated neutral sensor (CT) is required for separate mounting in the equipment. nsure also that retrofitted breakers are applied within their short circuit ratings; for example, assuming that as part of a conversion the breaker's trip elements are to be changed from Ll to LS, then the short time rating would govern the application. As a service related consideration, the installation of the MicroVersaTripTM kits provides an excellent opportunity to perform normal maintenance on the breaker proper, particularly while the front and back frames are separated. Such procedures are described in the Maintenance Manuals listed in Table 1-6. Also, any renewal parts required are listed in the Renewal Parts Bulletins given in Table 1-6.1f required, copies of these publications are available from the factory. NOTE: Although designed specifically for the breaker models in Table 1-1; these kits in many instances can be employed for conversion of the earlier AK-1-50/75/1 00 types. Undertaking such conversions should be a local decision and may involve additional modification depending upon the breaker's vintage and its accessory complement. Table 1-2-Neutral Sensors Breaker Frame Size 1600 Sensor Ampere Range Cat. No. 300-800 TSVG508BK 600-1 600 TSVG516BK 2000 800-2000 TSVG620BK 3000 1200-3000 TSVG830BK 3200 1200-3200 TSVG832BK 4000 1600-4000 TSVG940BK 3

SECTON 1 (CONT'D}-ntroduction Table 1-3-Current Sensors Breaker Type Sensor Ampere Range AK/AKS-50 300-800 AKU/AKSU-50 600-1600 AKT/AKST-50 800-2000 AK-75 1200-3000 AKR-75 1200-3200 AK/AKR-100 1600-4000 Cat. No. 193A1 439G14 193A1 439G15 193A1 439G16 ncluded With Basic Kit Table 1-4-Basic Programmer Catalog No. Breaker Frame Size Table 1-5-MicroVersaTrip Programmer Functions Long Time Short-Time Note: Add suffix letters to basic programmer Cat. No. in sequence shown Adjustable current setting STD Adj long-time pickup Adj long-time delay Long-time timing light Adj short-time pickup Adj short-time delay Short-time Ft switch@ nstantaneous Adj instantaneous pickup Ground Fault Other Functions No suffix is required for standard. Adj ground fault pickup@) -1 -ph, 2-w; 3-ph, 3-w; 3-ph, 4-w -Ground return Adj ground fault delay Trip indication targets -Overload & short circuit -local only -0/L S/C and ground fault -local only Table 1-6-Related Publications 4 Breaker Maintenance Renewal Parts Type Manual Bulletin AK AKU/ AKT -50 AK-75 AK-1 00 AKS/ AKSU/ AKST -50 GEK-7303 GE-86135 @ Req uires short-time function. GEF-4150 GEF-4395 GEF-4396 GEF-4150 AKR-75 GEK-64460 GEF-4552 AKR-100 GEF-4552 s 1600 2000 3000 3200 Cat. No. TA9VT20 TA9VT32 4000 TA9VT40 Programmer Suffix Letters -or M Optional Functions L G -or GR 0 Order neutral current transformer for conversion kit by catalog number when present. See Table 1-2. A1

SECTON 2-Front Frame Conversion 2.1-General lnformation The Front Frame Conversion consists of the following: 1. Relocating the W Relay on quick-close, electrically operated, Type AK-50/75/1 00 breakers equipped with EC trip devices. 2. Remounting the Relay on the same breakers described above. 3. nstalling the Flux Shifter device. 4. nstalling the Programmer Mounting bracket. 5. nstalling the Programmer Wire harness. 2.2-Breaker Disassembly WARNNG: BEFORE STARTNG ANY WORK, DS CONNECT THE BREAKER FROM ALL POWER SOURCES (PRMARY AND SECONDARY) AND PLACE N A CLEAN WORK AREA. Verify the breaker is OPEN. Referring to the appropriate Maintenance Manual, See Table 1-6, separate the breaker's front and back frames. - BEFORE FRONT VEWS OF BREAKER 2.3-Remounting W and Relays Type AK-2/2A Breakers (EC trip devices) electricallyoperated with quick-close may require the relocation of their anti-pump, W-Relay to insure proper space for the MicroVersaTriprM programmer unit. On these breakers, the W Relay normally mounts on the left side of the center channel, sharing a common mounting bracket with the Relay as shown in Fig. 2-1. Remove the W-relay and using the new mounting bracket provided, See Fig. 2-2, relocate the mounting bracket to the upper-left side of the front frame, as shown in Fig. 2-1. Remove"the Relay and its mounting bracket. Using the new bracket provided, see Fig. 2-2, remount the Relay in its existing location, as shown in Fig. 2-1. Type AKA and AKS Breakers do not require remounting of their Wand Relays. ( - --... )... - a CJCJ b ' ---- - AFTER Fig. 2-1. Relocating W- relay and remounting -relay 5

SECTON 2 (CONT'D}-Front Frame Conversion Fig. 2-2. New Wand relay mounting brackets 2.4-Fiux Shifter nstallation The Flux Shifter device is shown in Fig. 2-3. For breakers equipped with an ECS or SST Trip Device system: 1. Remove the ECS or SST Programmer. 2. Remove the existing flux shifter device and the programmer control harness. 3. nstall the new flux shifter device, positioning the insulator and programmer connector bracket as shown in Fig. 2-4. For AK Breakers equipped with EC or power sensor systems, the flux shifter mounting holes must be added to the left side of the front frame. The drill pattern for the required, three (3) 0.209 diameter holes is given in Fig. 2-5. nstall the flux shifter as described in Section 2.4 Step 3 and as shown in Fig. 2.4 6 NOTE: f the breaker is an AKU-50 fused type, take care to position the Flux Shift Trip device sufficiently upward to avoid interference with the coil of the Open Fuse Lockout (OFLO) device. ' 4 1. Actuator 2. Actuator arm 3. Trip rod 4. Trip rod adjuster end 5. Reset linkage 6. Actuator bracket 7. Mounting base Fig. 2-3. MicroVersaTrip flux shifter Fig. 2-4. Flux shifter installed 2

7.56 REFERENCE 1.125 1-.. ADD (3) 0.209 DAMETER HOLES (DMENSONS N NCHES) ESTNG 0.28 DAMETER HOLES Fig. 2-5. Flux shifter mounting hole pattern 2.4.1-Trip Paddle nstallation For breakers equipped with an ECS or SST system, the existing Flux shifter trip paddle will be used with the new flux shifter. For all other breakers, the flux shifter trip paddle must be assembled to the trip shaft as shown in Fig. 2-6. TRP PADDLE N "MECHANSM RESET" POSTON SDE LNK TRP ROD N "RESET" POSTON ADJUSTER END CROSSBAR BREAKER OPEN Fig. 2-6. Flux shifter adjustments 2.4.2-Adjustments Once the flux shifter and its trip paddle are installed and the breaker frames are reassembled, the following adjustments must be made. 1. With the mechanism in the RESET position set the gap between the trip paddle and the end of the flux shifter Plate Assembled to Channel Mounting Bracket nstalled To Plate Fig. 2-7. Programmer mounting bracket and plate 7

trip rod to 0.100 inches. Use a 0.100 inch diameter rod as shown in Fig. 2-6. Set the adjuster end of the trip rod and lock it in place with the jam nut. 2. As the crossbar travels between the "breaker closed" and "breaker open" positions, the tang of the actuator bracket must clear the buffer stud. f insufficient clearance exists, loosen it's two mounting screws and rotate the bracket clockwise to take up mounting hole slack. Retighten screws. 2.5-Programmer Mounting nstallation The MicroVersaTripTM Programmer mounts to the left side of the front channel. A mounting bracket is shock mounted to a plate that is assembled to the front channel as shown in Fig. 2-7. Use Loctite or an equivalent retaining material on the mounting screws for the plate assembled to the front channel. For breakers equipped with an ECS or SST system, replace the existing plate and mounting bracket with the new ones provided. Assemble the mounting bracket to the plate using the holes closest to the front of the breaker. See Fig. 2-7. For EC or Power Sensor equipped breakers, the holes for the new plate may have to be added to the front channel. The drill 8 '!.-20 TAP 3-HOLES 0.66 LEFT SDE VEW OF CRANK BEARNG -+-(0) () --- (DMENSONS N NCHES) o.9lt- 1.5oo... FRONT 4.625 Fig. 2-8. Mounting plate hole pattern pattern for these holes is given in Fig. 2-8. Once the plate is installed, assemble the mounting bracket to the plate using the holes closest to the front of the breaker, See Fig. 2-7. 2.6-Programtner Harness nstallation The programmer harness consists of the mating 36 pin programmer connector and the 16 pin front frame half of the front/back frame connector. nsert 36 pin programmer connectors' beveled edges on the right-hand side (front view). Bend Z securing tabs with screwdriver to secure. The 16-pin connector is inserted into the programmer connector bracket which is part of the flux shifter assembly. See Fig. 2-4. nsert this connector so that the Number 1 pin is towards the breaker's top, right-hand side. Route the harness under the flux shifter base. Attach the harness to this base using the wire keeper provided. nstall the programmer harness as shown in Fig. 2-4. nclude the flux shifter leads with this harness. Before installing the programmer bracket to the mounting bracket, the flux shifter leads must be inserted into the programmer connector. These leads are color-coded RED and WHTE. The required connector pins are factory installed on the leads. nsert the RED lead into Pin Number 32 and the WHTE lead into Pin Number 28. nsert the pins until they snap into place. Verify that the pins are fully inserted by comparing them with the other pins. Assemble the programmer bracket to the mounting bracket as shown in Fig. 2-9. Fig. 2-9. Programmer plate installation

SECTON 3-Back Frame Conversion 3.1-Generallnformation The back frame conversion consists of the following: 1. Modifying the crossbar assembly for the flux shifter installation. 2. nstalling the phase sensors. 3. nstalling the back frame harness. LEFT HAND LNK-LEFT HAND POLE UNT (DMENSONS N NCHES) Fig. 3-2. Actuator bracket- mounting hole pattern 3.2-Crossbar Modification Fig. 3-1. Flux shifter actuator bracket installation The flux shifter's reset linkage is driven by the actuator bracket. See Fig. 2-3. The actuator bracket must be assembled to the left side link of the left pole, as shown in Fig. 3-1. f the actuator bracket mounting holes are not in the left side link, the holes must be added. Drill and tap two (2) fivesixteenths (511s) of an inch x 18-inch holes using the hole pattern given in Fig. 3-2. 9

SECTON 3 (CONT'D)-Back Frame Conversion 3.3-Phase Sensors-AK/AKS-50 For EC and Power Sensor equipped breakers: 1. Remove the existing trip devices and harnesses. 2. nstall the lower adaptor connector, as shown in Fig. 3-3. 3. nstall MicroVersaTrip phase sensor. Secure sensor to lower adaptor with RTV or equivalent adhesive. nstall upper adaptor connector. See Fig. 3-4. For SST equipped breakers. 1. Replace the existing SST phase sensor with the new MicroVersaTriprM sensor. 10 2. nstall as shown in Fig. 3-4. Fig. 3-3. Lower adapter connector Fig. 3-4. MicroVersaTrip phase sensors and harness installed- AK/AKS-50 3.4-Phase Sensors-AKR-75/1 00 For SST and ECS equipped breakers: 1. Remove the back frame harness from the sensor terminal boards. 2. Remove the primary finger disconnect assemblies from AKD-6 or Substructure breakers (Z long bolts). 3. Remove the locking ring and slide off the phase sensor. 4. Remove the sensor terminal. 5. nstall the MicroVersaTriprM phase sensors as shown in Fig. 3-5. Engage the sensor's anti-turn lugs with the notches in the locking ring. 6. nstall the new sensor terminal board. See Fig. 3-5. Fig. 3-5. MicroVersaTrip phase sensors installed

3.5-Phase Sensors-AK-75/1 00 For EC and Power Sensor equipped breakers: 1. Remove the existing trip devices and harnesses. 2. The MicroVersaTriprM sensors mount on the upperbreaker studs. The sensors are held on the stud with the locking rings, as shown in Fig. 3-6. Leave enough of the stud exposed for the primary fingers to engage. Engage the sensor's anti-turn lugs with the notch in the locking ring. Before tightening the locking rings, position each sensor so that its leads will exist between the pole bases, as shown in Fig. 3-8. 3. Mount the three sensor terminal boards to the rear of the back frame as shown in Fig. 3-8 using the hardware provided. 4. Form each sensor's leads downward between the pole bases and thru the hole in its terminal board as shown in Fig. 3-8. Wire tie and solder to the terminals as indicated. Be sure to position wire colors as shown. For SST equipped breakers: The MicroVersaTriprM sensor is physically identical to the SST sensor. Follow the basic procedure given above and replace the SST with the MicroVersaTriprM sensor. Fig. 3-6. Phase sensors installed- AK-75/100 3.6-Backframe Harness nstallation nstall the Backframe Harness as shown in Fig. 3-4 or Fig. 3-7. Wire ties used to form and secure the harness are provided. FRONT/BACK FRAME CONNECTOR Fig. 3-7. Back frame harness installation AK AKR-75/1 00 11

MOUNTNG HOUSNG 12 RGHT POLE TE MAKE ONE COMPLETE WRAP AND SOLDER N PLACE (5 TERMNALS) CENTER POLE ROUTE LEADS BETWEEN POLE BASES LEFT POLE ' 11'-'-----t,,_.---l PHASE SENSOR lf)oolll+-----++ MOUNTNG HOUSNG WHEN USED, THE 4TH-WRE NEUTRAL SENSOR DSCONNECT BLOCK MOUNTS ON TOP OF TAP TERMNAL BOARD VA TS TWO LOWER MOUNTNG SCREWS. THE AKD-5 TYPE MOUNTNG S LLUSTRATED. THE ARRANGE MENT FOR AKD TYPES S DENTCAL ECEPT FOR USE OF A DFFERENT MOUNTNG BRACKET -SEE FG. 4-3. Fig. 3-8. Typical AK-75/1 00 brackframe conversion - rear view

SECTON 4-Four Wire Ground Fault 4.1-General lnformation The MicroVersaTripTM Ground Fault option requires an additional neutral sensor when used on a four-wire system having its neutral grounded at the transformer. The phase sensors are mounted on the breaker. However, the neutral sensor is inserted in the neutral which is part of the equipment. The neutral sensor is connected to the breaker through the 4th-wire neutral disconnect. 0.38 DAMETER HOLE (DMENSONS N NCHES) REAR VEW 4.2-Breaker Conversion AK/AKS-50 Drawout The 4th-wire disconnect for the AK/AKS-50 Drawout breaker mounts to the lower-back frame as shown in Fig. 4-1. 1. f the disconnect is existing, just replace the control harness. Maintain the following color code: WHTE-COMMON BLACK-TAP 2. f the disconnect is being added, mount the disconnect assembly as shown in Fig. 4-1. DSCONNECT ASSEMBLY Fig. 4-1. 4th-wire neutral disconnect installed - BOTH LEADS HAVE RNG TERMNALS. AK/AKS-50 drawout 13

SECTON 4 (CONT'D}-Four-wire Ground Fault 4.3-Breaker Conversion- AK/AKS-50 Stationary The 4th-wire disconnect for stationary breakers is a terminal board which is mounted to the lower front channel as shown in Fig. 4-2. 1. f the terminal board already exists, just replace the control harness. Maintain the following color code: WHTE-COMMON BLACK-TAP 2. f the terminal board assembly is being added, mount as shown in Fig. 4-2. The mounting holes may have to be added to the front channel. See Fig. 4-2. (DMENSONS N NCHES) TERMNAL BOARD ASSEMBLY MOUNTNG HARDWARE DRLL (2) 0. 219 DAMETER HOLES 4.4-Breaker Conversion AK/AKR-75/100 Drawout There are two 4th-wire disconnect designs used with these breakers. One design is used on breakers for AKD Type equipment. The other design is used on breakers for AKD-5/6 Type equipment. The difference in the designs is the bracket used for mounting the disconnect to the breaker. Figure 4-3 depicts the two designs. The Conversion Kits are shipped with the AKD-5/6 Type assembled with only the bracket for the AKD Type. f an AKD Type is required, remove the AKD-5/6 Type bracket and replace it with AKD Type bracket. FRONT VEW Fig. 4-2. 4th-wire terminal board installed- AK/AKS-50 stationary BREAKER r 14

AKD-5 Type As received in kit, block is assembled to the AKD-5 type bracket. AKD Type For AKD installation, remove block from AKD-5 bracket and remount it on bracket 239. ---239 Fig. 4-3. 4th-wire disconnects for AK/AKR-75/100 drawout breakers The 4th-wire disconnect for the AKR-AKR-75/1 00 Drawout breaker mounts to the lower-back frame as shown in Fig. 3-8. 1. f the disconnect is existing, just replace the control harness. Maintain the following color code: WHTE-COMMON BLACK-TAP 2. f the disconnect is being added, mount the disconnect assembly as shown in Fig. 3-8. 4.5-Breaker Conversion- AKR-75/100 Stationary The 4th-wire disconnect for stationary AKR-75/100 breakers is similar to the terminal board used by the AKS-50 breakers. See Section 4.3 for details. 4.6-Equipment Conversion The equipment compartment contains the mating portion of the 4th-wire disconnect and the neutral sensor. The neutral sensor is discussed in Section 4.7. The AKD, AKD-5/6, and Substructure Type equipment compartments use the same disconnect assembly. There are different disconnect mounting brackets depending on the type of breaker and equipment involved. The specific breaker conversion kit provides the mounting brackets for each equipment type in which the breaker is used. Refer to Fig. 4-4 through Fig. 4-10 for details on mounting-bracket installation. 15

16 (DMENSONS N NCHES) 225. Breaker portion of 4th-wire disconnect 226. Equipment portion of 4th-wire disconnect 230. 10-32 x 1.375-inch mounting screws (DMENSONS N NCHES) LEFT POLE j--6.001 DRLL (2) 0.224 DAMETER 1 HOLES N COMPARTMENT CENTER POLE 232. 10# lock washer 233. 10# flat washer 245c OF BRACKET 245. Mounting bracket AK!AKS-50 for AKD-5 type compartments Fig. 4-4. AK/AKS-50 4th-wire disconnect installation AKD-5 type 14----8.62 ------1 231 246 COMPARTMENT 3.75 ==1::2>- == _l_... SDE VEW OF COMPARTMENT CENTER POL 6.00 225. Breaker portion of 4th-wire disconnect 235. %-20 flat washer r246 226. Equipment portion of 4th-wire disconnect 236. '1-20 lock washer 230. 10-32 x 1.375-inch mounting screws 237. '1.-20 nut LEFT POLE OF BRACKET HOLES N COMPARTMENT <k DRLL (2) 0.218 DAMETER -= VEW LOOKNG AT REAR OF COMPARTMENT 231. nsulation 238. '1.-20 x 1.25-inch mounting screws 232. 10# lock washer 246. Mounting bracket AK/AKS-50 for AKD type compartments 233. 1 0# flat washer Fig. 4-5. AK/AKS-50 4th-wire disconnect installation AKD type

REAR OF ' BREAKER-...1 PHASE SENSOR REAR OF TEMNAL BOARD BREAKER 230 1 225 232 233 226 COMPARTMENT SDE VEW OF COMPARTMENT (DMENSONS N NCHES) 225. Breaker portion of 4th-wire disconnect 226. Equipment portion of 4th-wire disconnect CENTER LEFT POLE POLE AK75-7.00 AK100-9.75 DRLL (2) 0.224 DAMETER ACKET HOLES N 227 1 COMPARTMENT VEW LOOKNG AT REAR OF COMPARTMENT 232. 1 0# lock washer 233. 1 0# flat washer 227. Mounting bracket AK-75/1 00 for AKD-5 type compartments 234. 1/,-20 thread forming 230. 10-32 x 1.375-inch mounting screws (DMENSONS N NCHES) Fig. 4-6. AK-75/1 00 4th-wire disconnect installation AKD-5 type PHASE SENSOR TERMNAL BOARD SDE VEW OF COMPARTMENT 225. Breaker portion of 4th-wire disconnect 226. Equipment portion of 4th-wire disconnect 228. Mounting bracket AK-75 for AKD type compartments 230. 10-32 x 1.375-inch mounting screws 231. nsulation 232. 1 0# lock washer CENTER LEFT POLE POLE REAR OF COMPARTMENT }--7.00---J 1BRACKET<i;.--l 1!DRLL (2) 0.281 DAMETER 228 HOLES N COMPARTMENT -r: 3.75 VEW LOOKNG AT REAR OF COMPARTMENT 233. 10# flat washer 235. '/,-20 flat washer 236. %-20 lock washer 237. '/,-20 nut 238. %-20 x 1.25-inch mounting screws 239. Bracket Fig. 4-7. AK-75 4th-wire disconnect installation AKD type 17

18 PHASE SENSOR TERMNAL BOARD (DMENSONS N NCHES) SDE VEW OF COMPARTMENT 225. Breaker portion of 4th-wire disconnect 226. Equipment portion of 4th-wire disconnect 229. Mounting bracket AK-1 00 for AKD type compartments 230. 10-32 x 1.375-inch mounting screws 231. nsulation 232. 1 0# lock washer PHASE SENSOR TERMNAL BOARD REAR OF BREAKER._! (DMENSONS N NCHES) 0.44 VEW LOOKNG AT REAR OF COMPARTMENT 233. 10# flat washer 235. '1-20 flat washer 236. '1.-20 lock washer 237. '14-20 nut 238. '1.-20 x 1.25-inch mounting screws 239. Bracket Fig. 4-8. AK-1 00 4th-wire disconnect installation AKD type SDE VEW OF COMPARTMENT 225. Breaker portion of 4th-wire disconnect 226. Equipment portion of 4th-wire disconnect 228. Mounting bracket AK-75 for AKD type compartments 230. 10-32 x 1.375-inch mounting screws 231. nsulation 232. 1 0# Lock washer 233. 1 0# Flat washer 235. '1.-20 Flat washer 236. ';.-20 Lock washer 237. '1.-20 Nut 238. ';.c. 2o x 1.25-inch mounting screws Fig. 4-9. AKR-75/1 00 4th-wire disconnect installation AKD-6 type

110 4TH CT DSCONNECT 112 BREAKER PORTON 111! _l tr FRAM _: -ll!!- (DMENSONS N NCHES) 4.7-Neutral Sensors... -----12.50 ---.J NOTE: ESTNG HOLES N SUBSTRUCTURE ARE 0.272 DAMETER 132 114 BREAKER & SUBSTRUCTURE 115 SUBSTRUCTURE 110. (2) Screws (#10-32 x 1'/a-inch) 114. (2) Flat washers 111. (2) Lock washers 115. (2) lock washers 112. (2) Flat washers 132. (2) Screws (V.-20 1 v.) Fig. 4-10. AKR-75/100 4th-wire disconnect installation substructure The neutral sensor is an electrical duplicate of the phase sensor, including the taps. Therefore, when taps are changed on the phase sensors, the taps on the neutral sensor must be correspondingly positioned. Mount the neutral sensor in the outgoing neutral lead, normally in the equipment's bus or cable compartment. Be sure to observe the sensor's LNE and LOAD directional markings. See Fig. 4-11 and Fig. 4-12, for the sensor's bar drilling plan. Check to insure that the neutral and phase sensors match, i.e., have the same ampere range. Refer to Fig. 4-13 for additional neutral sensor installation information. 19

20, 10.75 1.75 $--$- 1 1 -EFT-fi7 (DMENSONS N NCHES} :!:0.032 -----o_j_! SENSOR CAT. NO. TSVG830BK TSVG940BK Fig. 4-11. Outline of the AKR-75/1 00 and AK-75/1 00 neutral sensor AMPERES 1200-3000 1600-4000

1 "D" "E" t " C " 1.75-1 LNE (DMENSONS N NCHES) Sensor Cat. No. MAMUM 1.25... 1 STRAP Ampere Range TSVG508BK 300-800 TSVG516BK 600-1600 TSVG620BK 800-2000 A 0.250 0.500 0.625 GEN. 0 ELECTRC OBSERVE LNE ANO LOAD - - CONNECTONS BOND OR GROUND ON LNE SDE ONLY B 3.25 3.62 3.25 c 0.75 0.94 0.75 D 3.20 Fig. 4-12. Outline of the AK/AKS-50 neutral sensor 0.562 DAMETER HOLES MAMUM f----1.25 STRAP --+;:n E 1.30 3.20 1.30 3.33 1.18 21

22 NSTALLATON NOTES OBSERVE LNE AND LOAD MARKNGS WHEN MAKNG BUS OR CABLE CON NECTONS. BOND SENSOR ON LNE SDE ONLY. MANTAN POLARTY OF SENSOR SEC ONDARY LEADS WHEN CONNECTNG TO BREAKER,.E., TAP TO TAP, COM TO COM. STATONARY DSCONNECT BLOCK N DRAWOUT BREAKER COMPARTMENT \ SEE BELOW. OR, TERMNAL BOARD TB4 ON STATONARY BREAKERS EQUPMENT PORTON OF 4TH-WRE DSCONNECT (2 28) FRONT VEW LOOKNG NTO BREAKER COMPARTMENT. TAP TAP COMMON COMMON #6 PAN HEAD SCREW 4TH-WRE NEUTRAL SENSOR STATONARY DSCONNECT BLOCK ON DRAWOUT BREAKERS. (DMENSONS N NCHES) #5 BNDNG HEAD SCREW Fig. 4-13. Connecting the 4th-wire neutral sensor NEUTRAL SENSOR

SECTON 5-Programmer nstallation 5.1-General lnformation The programmer is attached to the bracket mounted to the left side of the breaker's center channel as shown in Fig. 2-9. The guide pins on this bracket mate with the holes on either side of the programmer connector. The guide pins provide the necessary alignment for the connector engagement. The locking lever engages with the pin which is assembled to the programmer frame and secures the programmer to the mounting bracket. 5.2-AK/AKS-50 nstallation The AKS-50 mounting bracket is shown in Fig. 5-1. nstallation is as follows: 1. nsert the guide pins into the hole and push on the programmer. This will engage the connectors and release the locking lever which will move upwards. 2. Verify that the locking lever actually engaged the programmer pin. To remove the programmer: 1. Move locking lever to horizontal position, thus releasing the programmer pin. 2. Remove programmer. Fig. 5-1. AKS-50 programmer mounting 5.3-AK/AKR-75/1 00 nstallation The AK/AKR-75/100 mounting bracket is shown in Fig. 2-9. nstallation is as follows: 1. nsert the guide pins into the holes and push on the programmer, engagig the connectors. 2. The locking lever is released, securing the programmer. 3. Verify that the locking lever actually engaged the programmer pin. To remove the programmer pull out the locking lever which will release the programmer pin. Remove the programmer. 23

SECTON 6-Testing and Troubleshooting 6.1-General lnformation Once the breaker has been converted and before it is energized, it must be tested as described in Section 6.2. f any problems develop with the trip device system, refer to Section 6.3 and Section 6.4 for troubleshooting details. 6.2-Testing Before installing a converted breaker back into service, perform the following steps: 1. Verify that the programmer is securely installed. The phase sensors MUST NOT be energized if they are opencircuited. 2. Megger breaker primary circuit using a 1,000-Volt Megger. 3. Check the trip device system by either of two methods: 24 A. Conduct high-current, single-phase tests on the breaker using a high current-low voltage test set. NOTE: For these single-phase tests, special connections must be employed for MicroVersaTriprM breakers equipped with Ground Fault. Any singlephase input to the programmer circuit will generate an unwanted "ground fault" output signal which will trip the breaker. This can be nullified either by or 1. Testing two poles of the breaker in series, 2. Using the Ground Fault Defeat Cable as shown in Fig. 6-5. This special test cable energizes the programmer circuit in a self-cancelling, series-parallel connection so that its output is always zero. Compare results with the applicable time-current characteristic curves given in Fig. 6-9 and Fig. 6-10. B. Test the components of the MicroVersaTrip system using portable Test Set Type TVTS1. The applicable test procedures are detailed in nstruction Book GEK-64464. 6.3-Troubleshooting When malfunctioning is suspected, the first step in troubleshooting is to examine the circuit breaker and its power system for abnormal conditions such as: 1. Breaker tripping in proper response to overcurrents or incipient ground faults. 2. Breaker remaining in a trip-free state due to mechanical interference along its trip shaft. 3. nadvertent shunt trip activations. WARNNG: DO NOT CHANGE TAPS ON THE CURRENT SENSORS OR ADJUST THE PRO GRAMMER UNT SET KNOBS WHLE THE BREAKER S CARRYNG CURRENT. Once it has been established that the circuit breaker can be opened and closed normally from the test position, attention can be directed to the trip device proper. Testing is performed as described in Section 6.1, Step 2. 6.3.1-Resistance Values For use in troubleshooting the MicroVersaTrip current sensors, the resistance of the windings is given in Table 6-1. Table 6-1-Current Sensor Resistance Breaker Frame Size Ampere Tap Resistance in Ohms Between Common and Tap Terminals 300 20-24 400 27-32 600 42-50 AK-50 800 58-68 AKS-50 600 42-50 800 58-68 1200 93-109 1600 130-154 800 74-88 AKT-50 1200 116-136 AKST-50 1600 162-190 2000 210-246 1200 20-24 AK-75 1600 28-34 AKR-75 2000 37-44 3000 61-72 1600 36-43 AK-100 2000 47-55 AKR-100 3000 75-88 4000 108-127

6.4-False Tripping-Breakers Equipped With Ground Fault When nuisance tripping occurs on breakers equipped with the Ground Fault trip element, a probable cause is the existence of a false "ground" signal. As indicated by the cabling diagram of Fig. 6-2, each phase sensor is connected to summing circuitry in the programmer. Under no-fault conditions on 3-wire load circuits, the currents in this circuitry add to zero and no ground signal is developed. This current sum will be zero only if all three sensors have the same electrical characteristics. f one sensor differs from the others (i.e., different rating or wrong tap setting), the circuitry can produce output sufficient to trip the breaker. Similarly, discontinuity between any sensor and the programmer unit can cause a false trip signal. f nuisance tripping is encountered on any breaker whose MicroVersaTriprM components have previously demonstrated satisfactory performance via the TVTS1 Test Set, the sensors and their connections should be closely scrutinized. After disconnecting the breaker from all power sources, perform the following steps. 1. Check that all phase sensors are the same type (ampere range). 2. Ensure that the tap settings on all three-phase sensors are identical. 3. Verify that the harness connections to the sensors meet the polarity constraints indicated by the cabling diagram. BREAKER BACK FRAME "! q, A q,b q,c AAA ;t-t-t-1! )===)=.==)=- 4. On Ground Fault breakers serving four-wire loads, check that the neutral sensor is properly connected. See cabling diagram Fig. 6-3. n particular, the following: A. Verify that the neutral sensor has the same rating and tap setting as the phase sensors. B. Check continuity between the neutral sensor and its equipment-mounted secondary disconnect block. Also check for continuity from the breakermounted neutral secondary disconnect block through to the female harness connector. C. f the breaker's lower studs connect to the supply source, then the neutral sensor must have its LOAD end connected to the source. See Fig. 6-4. D. Ensure that the neutral conductor is carrying only that neutral current associated with the breaker's load current (neutral not shared with other loads). 5. f the preceding steps fail to identify the problem, then the sensor resistances should be measured. Since the phase and neutral sensors are electrically identical, their tap-to-tap resistance should closely agree. See Table 6-1. 6.5-MicroVersaTrip Cabling Diagrams FLU SHFT TRP DEVCE LEFT POLE r--t-+---- CURRENT SENSOR r r r LOAD HARNESS CONNECTOR PROGRAMMER UNT ---- --, (AMP 1-350356-9) PROGRAMMER CONNECTOR Fig. 6-1. Cabling diagram- MicroVersaTrip without ground fault 25

SECTON 6 (CO NT' D)-Testing and Troubleshooting 26 PROGRAMMER UNT ------, r r r HARNESS LOAD CONNECTOR _ - - _. (AMP 1-350356-9) PROGRAMMER CONNECTOR Fig. 6-2. Cabling diagram- MicroVersaTrip with ground fault on 3-wire load cpa cpb cp i C A A A BREAKER r.$.--4'-l BACK FRAME""-'! o, O O. LEFT POLE CURRENT. SENSOR! NEUTRAL A NEUTRAL SENSOR DSCONNECT! LNE..--1..l COM 1.,nl--,.,...,..._ EQUPMENT -MOUNTED NEUTRAL SENSOR )===):==)=- OM lc 4-WRE LOAD FLU SHFT TRP DEVCE PROGRAMMER UNT ------, Fig. 6-3. Cabling diagram- MicroVersaTrip with ground fault on 4-wire load

4-WRE LOAD ' 6 t ' 'FLU SHFT A A. A TRP DEVCE BREAKER BACK FRAME-., r..$---4'-1 b)==)==y LEFT POLE CURRENT? OM SENSOR ----r-r-----+o t:>-""""- t _J HARNESS V V V CONNECTOR LOAD cpa cpb cpc (AMP 1-1350356-9) PROGRAMMER UNT -------, PROGRAMMER CONNECTOR Fig. 6-4. Cabling diagram- MicroVersaTrip with ground fault on 4-wire load-breaker reverse feed GROUND FAULT DEFEAT MODULE PROGRAMMER CAT. NO TVTGD9 BREAKER:)_ UNT HARNESS r-- -, CONNECTOR r-l ---- r-- -,- -l o-t-< f1--o o-t-< / <>-+--< o+-< ' /. o+-< /_ / ' / o-t-< ' l o+--< ' 0 o-4--< o-1--< L ' 0 D 0 o+-< f- --, - <>+-< L 4,.4 5 o+-< / 0+-< ' a a 0--l--< / L_j ---- '---- - 3 / ' (-t-o (-t-o ol lol 0 o "\ 4-o (+<> L-J L j ANY MCROVERSATRPTM PROGRAMMER UNT WTH GROUND FAULT ELEMENT Fig. 6-5. Cabling diagram with ground fault defeat module inserted between breaker harness and MicroVersaTrip programmer unit- for use during single-phase, high-current, lowvoltage testing 27

28 SHORT CRCUT GROUND FAULT BREAKER cpa BACK FRAME "'-'1 )= ==)===f=l PARTAL LEFT POLE CURRRENT SENSOR cf>b q,c AA it-t-t-1 YELLOW --+-+----H la _ r r + LOAD YELLOW YELLOW YELLOW YELLOW YELLOW HARNESS CONNECTOR PROGRAMMER UNT -----, PROGRAMMER CONNECTOR Fig. 6-6. Partial cable diagram- "H" option winding connections PROGRAMMER SECONDARY DSCONNECT EQUPMENT AMP BREAKER AMP (1-350239-9) (1-350246-9) AMP REMOTE FAULT NDCATON CONNECTOR MCROVERSATRP lm PROGRAMMER. ---- ---, YELLOW YELLOW ==-- AMP ( 1-350242-9) ( 1-350235-9) GREEN GREEN BLUE BLUE Fig. 6-7. Cabling diagram- remote fault indication L j

SHORT TME NPUT PROGRAMMER SECONDARY DSCONNECT EQUPMENT BREAKER r +-0-+-< PROGRAMMER HARNESS CONNECTOR SHORT TME OUTPUT l: -+-< -----+r< GROUND FAULT j+ NPUT 1--+<H-< Hn-----+r< GROUND FAULT + OUTPUT 1--r-< Hn-----+r AMP AMP (1-350239-9)( 1-350246-9) Fig. 6-8. Cabling diagram- zone selective interlock MCROVERSATRP PROGRAMMER, --, L J 29

"'.... ld "' :10 ll! - 5. 7. 1 5 7 10 1111..... 710 100 100... 3DO 210 100 10.. 70 10 211 10 1.....7. '.. 30. 5.3.2.1.01.D. 07.D.01.04.03.02.01.5 '.7.8.9 1 1.1 \.ong Time 1. Pickup O.BC to 1.1C Fixed at 1. ic if 0.9 Adj. Element Not 0.8 ' k\. 1\..:\"r-" Provided v 1 \.o ' 1.5 /' v ' \-, Long Time Delay Bands Maximum Total 3 Cktaring Time Minimum Total Clearing Time "2" Y ill. l'\ "N r\n J 2.ii' = Short '-" Time 2.5 ['\.,\. l\ _1-12t ln - la 4.0 v :.A\. \.\ :/\.\. ' \'A \.: 1\_'V: \:f\ 5 12t 0 Ut r---;,. v \ ' v ' i\ 7.0 '( 3.0 l" : 9.0,l ro A \c: l'\. '",, 1'\. " ",'\,. v/ / "."'\: p.. 8; r:v MULTPLES OF CURRENT SETTNG, C Max 211 30 40 50 D 70 1010! DOD 900 BOD 700 [{ l'f lnt Min [\... Application Determines End of Curve LVPCB MC & CCB LVPCB MC & CCB LVPCB MC & CCB 500 300 200 100 1 1 JD 80.. 20...8.7.&,.....3.2 "' Q 1 ll :a:: 07.....! 05 MLTPES 5 0F 8 CR: SETTNG C 30 40 5 0 10 708010! _7!-J D4 03 02 01 H 1 t 9 0.4 r::ro: rfs- Hi-Range nstantaneous "H" Su ffix 60 Hz Operation Only_ 0.8 - Low Volt- Power Circuit == Breaker Total 1.0 Clelrin rvne )').., i L Application / Oetarmineo Total Cloartng l' V/ / / End of Curve ['-. / / /.!/1/VU/ "' [\ nstantaneous Adiustment P ckup setting: 0.4, 0.6, 0 B, 1.0 multiples of breaker short-t1me mterruptmg ratmg (H). Wl 11 4.5.1.7.1. 1 2 3 4 l 111 MULTPLES OF BREAKER SHORT-TME RATNG t f-y H f- f-n j :?. it: tr8 N ll, 13 Fixed nstantaneous!-- 1-hH+t-t-HOverride "D" Option f--- 50160 Hertz,_... Operation Onty l-hh+t-t-h-++---+-+-+-i.2 Molded Casa and nsulated Case Circuit Breaker 'i==::t::::t:::t 1 Total Clearing.. Time fflllmiiefiiz nstantaneous Pickup setting: 1 5, 2.0, 2 5, 3.0, 4.0, 6.0, 8.0, and 10.0 multiples of sensor current tap sem1ng or sensor rohng HHf for 150 amperes thru 3200 amperes semors. Pickup setting l.5, 2 0, 2 5, 3.0. 4 0, 5.0, 7 0, and 9 0 mult1ples of sensor top semmg or rolmg f01 4000 amperes sen!>or... liii::2cie:i:.cr:.ci!., i,.1.xi::::211la':!,.., MULTPLES OF NSTANTANEOUS PCK UP Fig. 6-9 MicroVersaTrip long-time delay, short-time delay and instantaneous time versus current curves. :

- 7111-7DG... ll 110 400 JG 2DG 100 0 10 0 10! 0 7 s ' 2 7 :..., '.1...17.......13.12.11.1..7.. 1 V' A 4 5 7 10.1\ / LVPCB " - MC & CCB - // // Max LVPCB / / / MC & CCB v (/ '/ '/V fo'-1-o LVPCB MC & CCB / '/ r!;. v D li"'7 "!< v 1/v V/ 4 5 7 10 20.. 40 50 10 70 101011-717 20 ;" l/ Vv 30 40 50 10 70 1010! MULTPLES OF GROUND FAULT PCK UP SETTNG!!!! UU - Fig. 6-10 MicroVersaTrip ground fault time versus current curves - 1000 900 100 700 800 500 400 100.. 10 1 1 300 200 70 10 50 40 "" 20...7..s...3.2 ll 1 "' " z.. _ 07 ll..!,. 04 03 02 31

These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to the General Electric Company. These instructions are intended for use by qualified personnel only. Outs1de the U S and Canada wnte Export Sales and Serv1ces. 570 Lex1ngton Avenue. New York. NY 10022 GEK-64468 06/83 PA-E For further information call or write your local General Electric Sales Office or... General Electric Co. Distribution Equipment 41 Woodford Avenue Plainville, CT 06062, USA GENERAL fl ELECTRC