FAIRCHILD T5420 DIGITAL-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

Similar documents
FAIRCHILD T5220 SERIES ELECTRO-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

FAIRCHILD T5200 SERIES ELECTRO-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

FAIRCHILD T8001 SERIES STANDARD RANGE MINIATURE TWO-WIRE, P/I PRESSURE TRANSDUCER. Installation, Operation and Maintenance Instructions

Type 500X. Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions. Ordering Information.

Type 500X. Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions. Ordering Information.

The Series I/P Current to Pressure Transducer

ROTORK FAIRCHILD MODEL T7500 LOW PRESSURE TRANSDUCER Installation, Operation and Maintenance Instructions

C3000 SIGNAL TRANSMITTER. Introduction

Pneumatic Division North America Richland, MI 49083

The T5220 Series Electro-Pneumatic Transducer converts a DC current or voltage input signal to a directly proportional pneumatic output.

Type 2000 Transducer Product Instructions

Adjustable Differential Relay A1

CIRCLE SEAL CONTROLS

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual

Type Type 1001 Transducers. I/P & E/P Transducers

T-1001 TYPE 1001 I/P & E/P TRANSDUCERS

LNW-5. Installation... 2 Lift Truck Conditions Indicator Installation Hose Installation

COMPANY. Pneumatic Flow Meters Installation, Operating & Maintenance Manual AW-Lake Company. All rights reserved. Doc ID:PNEUMAN082516

CP-8551 & CP Application. Features. Applicable Literature. Electronic to Pneumatic Transducers General Instructions

DO NOT INSULATE BELOW THIS LINE. * For sizes 1/2" to 1 1/2" add 2 1/2" to 'C' dimension.

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual

QB4 PRESSURE CONTROL VALVE INSTALLATION & MAINTENANCE INSTRUCTIONS

Model No. 668D3. COFFEPUMP Part No Product Code: O/C GJAN21.DB6B-DC310B

Electro-Pneumatic Positioner Series 830/831-WP/EX. Operation & Maintenance Manual

100 Series Flow Switches Technical Reference Manual

Temperature Sensor Series

CIRCLE SEAL CONTROLS

INSTRUCTION MANUAL. CR Series A/B

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls

45 VALVE SERIES. 2-Position 4-Way 5-Ports, Installation & Service Instructions. Valve with Stem Operator, Installation & Service Instructions

Apex 5000 Positioner

Series 20 Installation Instructions

Model Series 66 Amplifying and Reducing Relays

Operation and Maintenance Manual

INSTRUCTION AND MAINTENANCE MANUAL FR95 PRESSURE REGULATOR

K10 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual

GH-BETTIS SERVICE INSTRUCTIONS DISASSEMBLY & REASSEMBLY FOR MODELS HD521-M4, HD721-M4 AND HD731-M4 DOUBLE ACTING SERIES PNEUMATIC ACTUATORS

MODEL 1100 TURBINE FLOW METER

I & M 8000 Series. Ideal Installation Schematic. Preferred Installation. Trouble Shooting

I-BFV.KIT Butterfly Valve Gear Operator Replacement

MM1/MM2 INSTALLATION & MAINTENANCE INSTRUCTIONS

TRAC-3 TENSION READOUT AND CONTROL

P200 P/I Transducer. Installation, Operation, and Maintenance Instructions INTRODUCTION

BULLETIN NO.ELEC IM121/10A Replaces IM121/09A

MPV1 INSTALLATION & MAINTENANCE INSTRUCTIONS

MPV1 INSTALLATION & MAINTENANCE INSTRUCTIONS

Moniteur INSTALLATION & OPERATING INSTRUCTIONS. SERIES 40 Positioners. Installation and Operating Instructions Series 40 Positioners.

Pneumatic Cylinder 14 Bore X 22 Stroke Part No. R (Formerly P )

COMPANY. Liquid Flow Meters Installation, Operating & Maintenance Manual AW-Lake Company. All rights reserved. Doc ID:FLOWLIQUIDMETERMAN082516

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

INSTALLATION & SERVICE INSTRUCTION MANUAL W.A. KATES FLOW CONTROLLERS FC VALVE MODELS E THRU M

I & M Mark 708ME. Ideal Installation. Start-Up Procedure. Installation & Maintenance Instructions for Mark 708 & Motor Actuator

INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM)

QPV1 Electronic Pressure Regulator INSTALLATION AND MAINTENANCE INSTRUCTIONS

LEVEL AND FLOW MEASUREMENT WS131 FLOW METER USER MANUAL.

Series 44 Installation Instructions

T21 Thermal Differential Switch

Figure 1: WPR2 Dimensions and Hardware

INSTRUCTION AND MAINTENANCE MANUAL GFH45 PRESSURE REGULATOR

LM-200 MECHANICAL LUBE METER Owner s Manual

Damper Actuator Installation

Pneumatic Cylinder 14 Bore X 21 Stroke Part No. P Replaces Part No. P

Model 124 Filter Minder & Model 124

MAXIGARD A2000 SPEED SWITCH. Introduction

AUTO-PUMP 120 VAC AIR COMPRESSOR SYSTEM INSTRUCTION MANUAL. 170 Cherry Avenue West Sayville, NY

I & M Mark 708. Ideal Installation. Start-Up Procedure. Installation & Maintenance Instructions for Mark 708 & 14M Actuator and Motor Valve

MicroCoat. System Operating Manual MC2000 Series. MC785, MC785-WF Spray Valves. US: UK: Mexico:

OPERATIONS & INSTALLATION MANUAL

OPERATION AND PARTS MANUAL

INSTRUCTIONS FOR INSTALLATION, START-UP, AND OPERATION

TWO-STAGE HYDRAULIC PUMP. RWP55-IBT-Air

DO NOT INSTALL, OPERATE, OR MAINTAIN AN ATI PRODUCT UNLESS TRAINED AND QUALIFIED IN PRODUCT AND ACCESSORY INSTALLATION, OPERATION AND MAINTENANCE.

Pressure Sensor No Series

200 Series Flow Meters

1-BUTTON DISPENSER INSTALLATION INSTRUCTIONS

MECHANICAL FUEL METER. FM-100 and FM-200 Series Owner s Manual

SPRAY RUN-UP CONTROL KIT ( 4-20 ma Version)

Ph: (07) Fax: (07) Pump Manual

ACCESSORY KIT INSTALLATION INSTRUCTIONS

B2000 SERIES TACHOMETERS DIGITAL OR ANALOG DISPLAYS

P5510. Users Manual. Pneumatic Comparison Test Pump. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

Pneumatic Positioner RTX - Series USER S MANUAL. ROTEX P/P Ver. 0.1 Dated: MAY / 2009 REV 01: SEP/2010 Page 1 of 16

V200 POSITIONER r14 1

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators

GP1/GP2 INSTALLATION & MAINTENANCE INSTRUCTIONS

Table of Contents. Proportional & Precision Regulator Instrumentation

CBC-300 & CBC Series Dual Channel Adjust Clutch/Brake Controls

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

BOILER BLOWDOWN CONDUCTIVITY CONTROLLER (CONTINUOUS METHOD)

HIGH PRESSURE CONTROL VALVE PISTON BALANCED

Installation, Operation & Maintenance Manual

80 Series 4 Post Brake Instructions

Asepsis 21 Delivery Unit

Model 1100 Turbine Flow Meter

SETRA Operating Instructions Series DPT 230 Pressure Transducers

534HS Pressure Transmitter

NEMA 4 High Pressure High Set Point High Accuracy Pressure Switch SPECIFICATIONS

CRICKET Alphasonic Level Transmitter Model LA12 Owner s Manual

PRG 350 Series Stainless Steel Regulators

USER MANUAL LVC-200TC DIGITAL THERMOCOUPLE VACUUM GAUGE

Transcription:

FAIRCHILD T5420 DIGITAL-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions Figure 1. T5420 Outline Dimensions. INSTALLATION The Model T5420 can be mounted directly onto a flat surface using the two 10-32 tapped mounting holes in the base of the housing. For more information, see Figure 1. T5420 Outline Dimensions above. The Model T5420 can be Panel Mounted using the mounting bracket supplied in Mounting Kit 15268. For more information, see Figure 2. on page 2. 1

Installation (continued) The Model T5420 can be mounted on a 2" pipe using the Optional Mounting Kit 14596. For more information, see Figure 3. below. NOTE: If the T5420 Transducer is not mounted in an upright position, the Zero & Span Adjustments must be re-calibrated. Figure 2. Mounting Kit 15268. (Sold Separately) Figure 3. Optional Mounting Kit 14596. (Sold Separately) 2

Pneumatic Connections Clean all pipelines to remove dirt and scale before installation. Apply a minimum amount of pipe compound to the male threads of the fitting only. Do Not use teflon tape as a sealant. Start with the third thread back and work away from the end of the fitting to avoid the possibility of contaminating the transducer. Install the transducer in the air line. The inlet and outlet ports are labeled on the end of the transducer. Tighten connections securely. Avoid undersized fittings that will limit the flow through the transducer and cause a pressure drop down stream. For more information, see Figure 1. Outline Drawing on page 1. NOTES: Instrument quality air, per ISA Standards D7.3-1981, is required. Use a filter to remove dirt and liquid in the air line ahead of the transducer for correct performance. If an air line lubricator is used, it MUST be located downstream, beyond the transducer. The user is responsible for insuring that the environment in which the unit will be installed, and the operating gas, are compatible with the materials in the transducer. Electric Connection For the T5420 Transducer, make connections to the Terminal Blocks through the two 1/2 NPT conduit holes as shown below in Figure 4. Electrical Connections. CAUTION: Do Not tie Data Return from TB2 and Case Ground from TB1 together. The Data Return MUST be taken back to the microprocessor or manual entry device ground to prevent ground loop problems. For signal lines of six feet or less, use 22 gage wire. For longer signal lines, use 18 gage wire due to voltage drop considerations. Shielded cable Must Be Used for the signal lines for noise immunity. NOTES: To prevent ground loop problems, shield must be connected at the controller end ONLY. The power supply is internally grounded to the transducer housing. The housing should be connected to a good earth ground. 24 VDC Board and 115/230 VAC Board For 5 Volt Logic Operation, cut jumper W4 and leave VR2. For 15 Volt Logic Operation, cut the Voltage Regulator VR2 and leave W4. For more information, see Figure 4. Electrical Connections. 115 / 230 VAC Board 24 VDC Board Terminal Block (TB1) VAC VAC Case Ground W4 VR2 Terminal Block (TB2) DB7 DB6 DB5 DB4 DB3 DB2 DB1 DB0 Enable Data Return 10 9 8 7 6 5 4 3 2 1 Model T5420 W4 VR2 1/2 NPT Ground 24 VDC (+) Case Ground Terminal Block (TB1) Shielded Cable WARNING Read Caution 1/2 NPT Figure 4. Electrical Connections. 3

CALIBRATIONS / ADJUSTMENTS Equipment Required for Calibration: Pneumatic Supply capable of delivering up to 50 psig. Gage capable of a digital readout up to 50 psig with an accuracy of 0.1%. FULL RANGE OPERATION NOTE: Turn Power off, disconnect data inputs, enable and data return lines. Forward Acting Mode Adjustment 1. Connect Air Supply and Power Supply to the transducer. Forward Acting Calibration-Zero 2. Set switch SW1-1 to the OPEN position and set switch SW1-2 to the CLOSED position. Turn Power On. 3. Adjust the Zero screw for minimum output pressure. Turn screw counterclockwise to increase pressure and clockwise to decrease pressure. Forward Acting Calibration-Span 4. Set switch SW1-1 to the CLOSED position and set switch SW1-2 to the CLOSED position. 5. Adjust the Span on the potentiometer for maximum output pressure. Turn screw clockwise to increase pressure and counterclockwise to decrease pressure. 6. Repeat steps 2-5 until desired output range is obtained. 24 VDC Board Switches SW1-1 & SW1-2 7. Reverse Acting Mode Adjustment 8. Reverse the coil wire connections on the underside of the PC Board as shown in Figure 5. below. Reverse Acting Calibration-Zero 9. Set switch SW1-1 to the OPEN position and set switch SW1-2 to the CLOSED position. 10. Reverse Acting Calibration-Span 11. Set switch SW1-1 to the CLOSED position and set switch SW1-2 to the CLOSED position. 12. 13. 14. SPAN ADJUSTMENTS Set switch SW1-1 to CLOSED position and SW1-2 to OPEN position. Unit is now set for high logic input on all channels for maximum output pressure. Adjust the Zero screw for maximum output pressure. Turn screw counterclockwise to increase pressure and clockwise to decrease pressure. Adjust the Span on the potentiometer for minimum output pressure. Turn screw clockwise to increase pressure and counterclockwise to decrease pressure. Repeat steps 9-12 until the desired output range is obtained. Set switch SW1-1 to CLOSED position and SW1-2 to OPEN position. Unit is now set for high logic input on all channels for minimum output pressure. Decrease Terminals Increase See Step 7. for Reverse Acting Mode Terminals Span Adjustment 1/4 NPT Outlet 1/4 NPT Inlet 115 / 230 VAC Board CAUTION Avoid Magnetic Particles Near Magnet 1/4 NPT Gauge 1/2 NPT 1/4 NPT Inlet Wire ZERO Zero Adjustment ZERO ADJUSTMENTS Increase Decrease Figure 5. Calibration Configuration. 4

MAINTENANCE To clean the Orifice, use the following procedure: 1. 2. 3. Clean with alcohol and dry with compressed air. NOTE: Parts must be completely dry before reassembling. To clean the Inner Valve Assembly, use the following procedure: 1. 2. 3. Shut off the valve that is supplying air to transducer. Remove the Air Line and Fittting from Inlet Port. Remove the Orifice Assembly (9) from the unit by threading a 1/4-20" into the orifice housing and pulling it out through the inlet port. For more information, see Figure 6. Exploded Drawing below. Shut off the valve that is supplying air to transducer. It is not necessary to remove the Transducer from air line. Remove s (7) holding the Retainer Cap (6) and Plate (5) to Booster (1). Pull out Inner Valve Assembly (4) and wash the seat carefully. 4. Wipe off any particles that may be attached to rubber Seat Ring Assembly (2). For more information, see Figure 6. Exploded Drawing below. NOTE: Avoid such solvents as acetone, carbon tetrachloride and trichlorethylene. To clear problems caused by Magnet malfunction, use the following procedure: 1. Shut off the valve that is supplying air to transducer. It is not necessary to remove the Transducer from air line. 2. Remove s (15) and (16) holding Standoff (12) and PC Board (14) to Transducer (8). 3. Remove two s (13) holding Magnet (11) to Transducer (8). Remove Magnet (11) and clean gap of any foreign material with masking tape. For more information, see Figure 6. Exploded Drawing below. 4. Place Magnet (11) over (10) and tighten with two s (13). Using a non-metallic rod, raise up on the arm to make sure (10) is free to move in Magnet (11). NOTE: If is sticking or dragging, loosen s and reposition Magnet then repeat step 4. To replace PC Board, use the following procedure: 1. 2. 3. Disconnect wires from TB1 and TB2 on PC Board (14). Remove Wires from underside of PC Board (14). Remove s (15) and (16) and Standoff (12) holding PC Board (14) to Transducer (8). For more information, see Figure 6. Exploded Drawing below. Replace PC Board (14) with the appropriate PC Board from Table 3. on page 6. Figure 6. Exploded Drawing. 5

Maintenance (continued) Table 3. T5420 Series Components. Item Qty. Part No. 1 1 NS 2 1 NS 3 1 NS 4 1 NS 5 1 NS 6 1 NS 7 2 NS 8 1 NS 9 1 NS 10 1 NS 11 1 NS 12 1 NS 13 2 NS 1 14 1 044-IPI-109-130 1 14 1 044-IPI-109-110 14 1 044-IPI-109-1201 15 1 NS 16 2 NS 1 For T5420 Units Only. Description NS: (Not Serviceable) indicates that the part is not available for field replacement. TROUBLE-SHOOTING Table 4. Trouble-Shooting. Problem Solution (check) No Output Supply Clogged Orifice Power Supply Leakage Low or Improper Span Adjust Erratic Operation Unit Does Not Operate Booster Seat Ring Assembly Screen Inner Valve Assembly Retainer Plate Retainer Cap Transducer Orifice Magnet Standoff 24 VDC PC Board 115 VAC PC Board 230 VAC PC Board Pneumatic Connections Zero and Span Adjust Supply Low Output Leakage DC Signal Loose Wires or Connections Liquid in Air Supply Dirt in Magnet Gap Replace PC Board NOTE: Booster Repair Kits are available for the T5420. Ratio Kit Number 1:1, 1:2, 1:3 15288 1:4, 1:5, 1:6 15656 OPERATION LOGIC After completion of Trouble-shooting, perform the Operation Logic Procedure in Table 5 and 6. For Forward Acting Output options refer to Table 5. below. Table 5. Forward Acting Output Input Data Bits DB6 DB7 DB6 & DB7 DB7 thru DB0 High Logic (SW1-1 Closed) Low Logic (SW1-1 Open) Output Psig [BAR] (kpa) 6 0.4 40 9 0.6 60 12 0.8 80 15 1.0 100 NOTE: For continuous enable apply ground to enable line or close SW1-2. For Reverse Acting Output options refer to Table 6. below. NOTE: wires on underside of PC board MUST be reversed for reverse acting mode. Table 6. Reverse Acting Output Input Data Bits DB6 DB7 DB6 & DB7 DB7 thru DB0 High Logic (SW1-1 Closed) Low Logic (SW1-1 Open) Output Psig [BAR] (kpa) 12 0.8 80 9 0.6 60 6 0.4 40 3 0.2 20 NOTE: For continuous enable apply ground to enable line or close SW1-2. LEGAL NOTICE: The information set forth in the foregoing Installation, Operation and Maintenance Instructions shall not be modified or amended in any respect without prior written consent of Fairchild Industrial Products Company. In addition, the information set forth herein shall be furnished with each product sold incorporating Fairchild's unit as a component thereof. 6 IS-500T5420 Litho in USA Rev. N 0706