1 GP1/GP2 INSTALLATION & MAINTENANCE INSTRUCTIONS Description & identification General specifications Connection procedure Recalibration procedure Repair procedure Dimensions, ordering and accessories Before you get started, please read these warnings: Examine the product. Ensure that you received what you ordered. Read this guide first before you start and save it for later use. You must have a good understanding of what the adjustments are on this product before using them. All compressed air and power should be shut off before installing, removing or performing maintenance on this product. Installation and use of this product should be under the supervision and control of properly qualified personnel in order to avoid the risk of injury or death. DESCRIPTION / IDENTIFICATION The GP series control valve is an electronic pressure regulator designed to precisely control the pressure of gaseous media proportional to an electronic signal. The GP1 operates using two normally closed solenoid valves, a pressure sensor, and a control circuit. One valve is actuated to allow unregulated supply media into the system. The second valve is actuated to allow working media to vent to atmosphere. The pressure sensor provides feedback to the control circuit. The control circuit compares the pressure sensor feedback to the user supplied electronic command signal and actuates the appropriate valve until the two signals match. The GP series can be teamed with a variety of onetoone ratio high pressure volume boosters for even greater flow. When using a volume booster, the GP2 can be used to achieve accuracy similar to the GP1 alone with higher flow capacity. GP series product comes with a monitor output signal. This output is an electrical signal originating from the internal sensor used in the control circuit of the GP1 valve. On GP2 units this signal originates from the external transducer. This allows the system parameters to be monitored and provides a signal for data acquisition needs. The output of this signal can be configured to either 0 10Vdc or 420mA. The GP2 is similar to the GP1 but uses a double loop control scheme. In addition to the internal pressure transducer, the GP2 also receives a 010Vdc feedback signal from an external sensing device. The external signal functions as the primary feedback and is compared to the command signal. A difference between the two comparisons causes one of the two solenoid valves to open allowing flow in or out of the system. A ProportionAir DSY or DSTY will work as a second loop feedback to the GP2 (See ordering information). The GP series has several other beneficial features. An on board split power supply allows true zero for command and monitor even though the GP is powered by a conventional single ended power supply. The GP utilizes advanced on board power management hardware to minimize current draw and heat build up. The GP also features status indicating LEDs for power and TTL. The TTL signal is a conditional on/off signal to use for diagnostic purposes. This signal is LOW when the pressure is within 1% of final setting. 1 INGP12
2 GENERAL SPECIFICATIONS & PERFORMANCE CHARACTERISTICS ELECTRICAL MINIMUM TYPICAL MAXIMUM Supply Voltage Supply Current Command Signal Voltage Current Command Signal Impedance Voltage Current Analog Monitor Output Voltage Current (Sourcing) TTL Satisfied NotSatisfied 2nd Loop Input 15VDC 100mADC (standby state) 4mADC 4mADC 10KΩ 100Ω 5VDC 24VDC 985mADC (operating) 1 20mADC 1 20mADC 1 PNEUMATIC MINIMUM TYPICAL MAXIMUM Input Pressure Pressure Range Flow Rate Filtration Required Accuracy (Pressure) Accuracy (Monitor) Hysteresis/Linearity Repeatability Port Size (all) Critical Volume Vacuum Vacuum 0 SCFM (0 m³/hr) 40 micron ±0.1%F.S. 0%F.S. 110% of full scale calibration 5 SCFM (8.5 m³/hr) 20 micron ±0.25%F.S. ±0.3%F.S. ±0.2%F.S. ±0.05%F.S. 1/8 inch NPT female 3 in³ 1100 psig (75.84 bar) 1000 psi (68.95 bar) 10 SCFM (17 m³/hr) ±0.5%F.S. ±0.5%F.S. ±0.5%F.S. Depends on Hysteresis PHYSICAL MINIMUM TYPICAL MAXIMUM Operating Temperature Environment Protection Weight Electrical Connector (Note 1) (Note 2) (Note 3) (Note 4) (Note 5) (Note 6) 32ºF (0ºC) 3.75 lbs (1.75 kg) 6 pin molded 16 gauge wire 158ºF (70ºC) NEMA 4/IP65 (Note 1) (Note 2) (Note 3) (Note 4) (Note 5) (Note 6) Pressure ranges are customer specified. Pressure range up to 250 PSI (17.24 BAR) may be ordered as PSIG or PSIA. Pressure range above 251 PSI (17.3 BAR) may be ordered as PSIS or PSIA. User adjustable The minimum downstream closed volume is determined by the pressure range, orifice size, hysteresis window, plumbing, as well as other factors. Consult factory for small volume applications. CE approval pending Depends on density of manifold material Fig 1 Pressure [% of scale] LINEARITY Command [Volts] This chart shows linear characteristics of GP products when given a ramp signal from 010 volts. Characteristics would be similar for 420 ma units. Fig 2 % of Scale RESPONSE TO STEP INPUT Command Pressure Time (seconds) Volume = 5 cu.in. [82mL] Times for GP to fill/exhaust a closed chamber. Step command signal is superimposed over pressure trace. Time is determined by difference between command signal and pressure achieved. 2 *Dependent on orifice size, pressure range and supply pressure. INGP12
3 GP CONNECTION PROCEDURE Pneumatic Connections: 1. A typical 20 micron (minimum 40 micron) inline filter is recommended on the inlet of the GP. 2. Connect supply pressure to the I inlet port (figure 1) not to exceed rated supply pressure. (Table 1) 3. Connect one of the O outlet port (figure 1) to the device being controlled and plug the unused one. 4. Proceed with electrical connection. TABLE 1 RATED PRESSURE FOR GP VALVES MAX calibrated pressure of: Vacuum up to 15 psig (Vac. to 1.03 bar) Max inlet pressure is: 30 psig (2.07 bar) 16 up to 30 psig (1.1 to 2.07 bar) 60 psig (4.14 bar) 31 up to 50 psig (2.14 to 2.45 bar) 100 psig (6.89 bar) 51 up to 100 psig (3.52 to 6.89 bar) 200 psig (13.79 bar) 101 up to 250 psig (6.96 to bar) 500 psig (34.47 bar) 251 up to 500 psig (17.31 to bar) 600 psig (41.37 bar) 501 up to 1000 psig (34.54 to bar) 1100 psig (75.84 bar) Electrical connections: 1. Ensure all power is off before making any electrical connections. 2. Figure 2 shows the location of the GP electrical connector and figure 3 shows the connector. Table 2 identifies the color codes Note: Both current and voltage command units require that both the command (+) and command ( ) pins be connected. 3. See figure 4 and 5 for second loop connections. TABLE 2 O OUTLET PORT I INLET PORT Figure 1 Figure 2 O OUTLET PORT WIRE COLOR* FUNCTION WHITE COMMAND (+) RED GREEN ORANGE ANALOG OUTPUT DC COMMON TTL OUT BLACK 1524 VDC POWER BLUE COMMAND () Figure 3 * H6DC6 POWER CORD COLORS 3 INGP12
4 GP2 second loop connections: For GP2 valves to work properly a 010Vdc second loop input source must be connected to the GP2. 1. Make electrical connections according to the section titled Voltage command valves for a voltage command unit or Current command valves for a current command unit 2. If ProportionAir DS series transducer is used as the external feedback source, attach it to the auxiliary receptacle on the GP2 unit. (Figure 4) 3. If another source of transducer is used, H23 cable must be ordered to facilitate connection of that source to the GP2. (Figure 5) Note: Power & common connections on the 2nd loop receptacle are fed through from the main connector and are provided to facilitate wiring of the 2nd loop sensor. 2nd LOOP FEEDBACK RECEPTACLE ON GP2 Figure 4 Figure 5 H23 COLOR CODE Red/White Signal In Red/Black Green Power Common RECALIBRATION PROCEDURE All GP valves come precalibrated from the factory using precision calibration equipment. If the GP valve needs recalibration, use the procedure described below: GP1 VALVES: 1. Wire servo according to the section titled Electrical Connections. 2. Connect a precision measuring gage or pressure transducer to the unplugged outlet port of the GP. 4. Locate the calibration access cap on top of the GP valve and locate the ZERO and SPAN adjustment potentiometers (figure 6). The 420mA potentiometers should be set at the factory and do not need to be recalibrated. NOTE: Only use this step if your device is totally out of calibration. If it is slightly out of calibration, omit this step and move on to paragraph 5. Using a small screwdriver, turn both potentiometers 15 turns clockwise. Then turn them 7 turns counter clockwise. This will put the GP roughly at mid scale. 5. Set the electrical command input to MAXIMUM value. Adjust the SPAN potentiometer until MAXI MUM desired pressure is reached (clockwise to increase pressure). 6. Set the electrical command input to 10 percent of full value (1Vdc for 010Vdc unit or 5.6mA for 420mA unit). 7. Adjust the ZERO potentiometer until 10 percent of maximum desired pressure is reached. (clockwise increases pressure). 8. If at any time during the calibration procedure the servo oscillates or becomes unstable for more than one second, turn the hysteresis potentiometer HW (see figure 12 for location) clockwise until the oscillation stops, then turn it one more complete turn (same direction). 9. The ZERO and SPAN potentiometers interact slightly. Repeat steps 510 until no error exists. 10. Verify unit shuts off by going to zero command. Check linearity by going to at least six pressures throughout the full range. GP2 VALVES: This calibration procedure assumes there is a properly scaled and calibrated transducer for use as 2nd loop feedback signal. (The GP2 series accepts a 010Vdc 2nd loop signal.) Follow, in order, steps 110 as noted in the section titled GP1 VALVES. Make sure the 2nd loop is connected before you start the calibration. NOTE: There must be a closed volume of at least 3 cu.in. (49cc) between the valve outlet and the measuring device for the valve to be stable. 3. Provide supply pressure to the inlet port of the GP. (See figure 1). Make sure supply pressure does not exceed the rating for the valve. (see table 1) Figure 6 4 INGP12
5 REPAIR PROCEDURE: 1.) Disassemble GP unit: A. Remove the two 832 flat head screws and o rings on the GP lid. Figure 7 B. Unplug main connector wires and LED wires from the board. Figure 8 C. Remove lid, lid o ring and can assembly from manifold. Figure 9 D. Unplug valve and sensor wires from board. Figure 8 E. Remove the two 832 SHCS screws and o rings from manifold to remove both the regular tall standoff and the board standoff. Figure 10 F. Of each valve assembly, remove hex nuts and disassemble valve tube from coil and valve housing. (Keep coil washer, valve housing and hex nut because they are not included in the repair kit and can be reused) Figure 14 G. Using span wrench (figure 11), remove valve tube from manifold cavity. H. Remove poppet and o ring spacer from manifold. See figure 12 for o ring spacer location and figure 14 for valve orientation I. If sensor needs to be replaced, unthread sensor from manifold. See figure 13 for sensor location CA FIGURE 7 FROM MAIN CONNECTOR FIGURE 9 FROM SENSOR EXHAUST VALVE INLET VALVE FIGURE 10 2ND LOOP INPUT FROM 3 PIN MICRO CONNECTOR. (IF TTL LED POWER LED FIGURE 8 FIGURE 11 FIGURE 12 5 INGP12
6 2.) Sensor Assembly: A. Install the sensor before installing the valves. B. Place sealant compatible with media in use on the second or third full threads of the pressure sensor (exercising care not to get sealant into the manifold passages), and thread into 1/8 NPT port on top of manifold. See Figure 13 for sensor location. 4.) Final Assembly: A. Place o rings on two 832 SHCS screws line up with holes through bottom side of manifold. Figure 10 B. Place board standoff, pots facing up, on valve side, opposite sensor, and fasten with 832 SHCS screw. Figure 10 C. Place regular tall standoff on sensor side of manifold and fasten with 832 SHCS screw tighten 78 in. lb. of torque. Figure 10 D. Plug valve, sensor wires into board. Figure 8 E. Place can on manifold until edge of can is flush with manifold. NOTE: Turn can while pressing downward. D. Obtain an assembled lid and plug the main connector and LED wires to the board. Figure 8 FIGURE 13 3.) Valve Assembly: Note: Do not use any kind of thread sealant. A. Remove repair kit V52PAK from box. Figure 14. V52PAK (repair kit) includes: (2) O ring spacers, (2) poppets, (2) valve tubes & span wrench (figure 11) B. Place new o'ring spacers in valve cavity of manifold. Figure 12 C. With poppet installed in the valve tube, thread valve tubes into manifold cavities tightly using span wrench. See figure 14 for poppet orientation. D. Check to make sure valve tubes are tight! Place coil washer and valve housing on valve tube, refer to figure 14 for assembly order. Turn square end of valves toward sensor. Figure 13. Tighten the hex nuts 1/8 turn past finger tight. Do not over tighten! 5.) Closing Lid: A. Assemble o ring to 832 flat head screws. Figure 7 B. Place lid o ring on inner edge of can. Figure 9. If not already done, plug the main connector wires and LED wires into the board, refer to figure 8 NOTE: Make sure while fastening the lid to the can that the o ring is flat and seals evenly with lid. C. Orient lid so the power LED is inline with the inlet port of the manifold. Figure 15 D. Fasten lid down with 832 flat head screws. Figure 7 FIGURE 15 HEX NUT VALVE HOUS COIL VALVE TUBE POPPET O RING SPACER V52PAK (Repair Kit) FIGURE 14 6 INGP12
7 DIMENSIONS GP1/GP2 Inches [mm] SERIES GP=1/8 in NPT GX=1/8 in NPT Cleaned for O2 service GL=1/8 in BSPT GN=1/8 in BSPT Cleaned for O2 service ORDERING INFORMATION GP 1 0 A 1000 E C B 2 A I 1=Single loop MINIMUM CALIBRATED PRESSURE RANGE (PSI) A=Absolute G=Gauge S=Sealed gauge COMMAND SIGNAL E=01 I=420mADC (both differen MAXIMUM CALIBRATED PRESSURE RANGE (PSI) MONITOR SIGNAL E=01 C=420mADC (Sourcing) ACCESSORIES MANIFOLD MATERIAL B=Brass S=303 Stainless ORIFICE SIZE 1=0.012 inch 2=1/32 3=3/64 Factory determined ELECTRICAL CONNECTOR A=6 pin Brad Harrison standard VALVE WETTED PARTS I=Teflon/Viton standard H6DC6 H23 V52PAK DSY 100 DSTY 1000 BKT01 6 Pin, 6 Foot Power Cord * Required for all GP units Consult factory for other length 3 Pin Mini Connector 3 Foot Cord * Required to facilitate connection to the external sensing device (GP2). Consult Factory for other length Valve Repair Kit Includes Inlet and Exhaust Valve Replacement Parts With Spanner Wrench Pressure Range Specify (psi) External Pressure Transducer For Range Up to 500 psi (34.47 bar) Pressure Range Specify (psi) BRACKE Stainless Steel External Pressure transducer For Range psi (82.6 bar) ProportionAir products are warranted to the original purchaser only against defects in material or workmanship for one (1) year from the date of manufacture. The extent of ProportionAir's liability under this warranty is limited to repair or replacement of the defective unit at ProportionAir's option. ProportionAir shall have no liability under this warranty where improper installation or filtration occurred. All specifications are subject to change without notice. THIS WARRANTY IS GIVEN IN LIEU OF, AND BUYER HEREBY EXPRESSLY WAIVES, WARRANTIES OR LIABILITIES, EXPRESS, IMPLIED OR STATUTORY, INCLUDING WITHOUT LIMITATION ANY OBLI GATION OF PROPORTIONAIR WITH REGARD TO CONSEQUENTIAL DAMAGES, WARRANTIES OF MERCHANTABILITY, DE SCRIPTION, AND FITNESS FOR A PARTICULAR PURPOSE.... WARNING: Installation and use of this product should be under the supervision and control of properly qualified personnel in order to avoid the risk of injury or death. PROPORTIONAIR, INC. BOX 218 MCCORDSVILLE, IN USA PHONE: (317) FAX: (317) INTERNET info@proportionair.com 7 INGP12
MM1/MM2 INSTALLATION & MAINTENANCE INSTRUCTIONS
MM1/MM2 INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION / IDENTIFICATION The MM series proportional control valves utilize ProportionAir's unique closed loop control technology for superior control
More informationMPV1 INSTALLATION & MAINTENANCE INSTRUCTIONS
MPV1 INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION / IDENTIFICATION The MPV1 series valve uses Proportion- Air closed loop technology for pressure control. It gives an output pressure proportional
More informationMPV1 INSTALLATION & MAINTENANCE INSTRUCTIONS
MPV1 INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION / IDENTIFICATION The MPV1 series valve uses Proportion- Air closed loop technology for pressure control. It gives an output pressure proportional
More informationQB4 PRESSURE CONTROL VALVE INSTALLATION & MAINTENANCE INSTRUCTIONS
QB4 PRESSURE CONTROL VALVE INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION The QB4 is a closed loop electronic pressure regulator consisting of two solenoid valves, an internal pressure transducer,
More informationELECTRONIC CONTROLLER
BRQB011206E THE INSIDE STORY OF THE QB3: IP65 enclosure allows it to withstand the elements and be washed down without harm Precision pressure control vacuum to 150 psi (10.34 bar ) at high flow rate saves
More informationTHE INSIDE STORY OF THE QPV OR MPV:
BRQPVMPV0305E THE INSIDE STORY OF THE QPV OR MPV: Access Hole Permits Field Adjustments Electronic Control Circuit Available in a Wide Range of Electrical Control Inputs and Analog Outputs Many Connector
More informationQPV1 Electronic Pressure Regulator INSTALLATION AND MAINTENANCE INSTRUCTIONS
INSTALLATION AND MAINTENANCE INSTRUCTIONS DESCRIPTION / IDENTIFICATION The QPV1 is a high resolution electronic pressure regulator. The QPV1 provides a regulated output pressure that is proportional to
More informationTHE INSIDE STORY OF THE QPV OR MPV:
BRQPVMPV0305E THE ISIDE STORY OF THE QPV OR MPV: Access Hole Permits Field Adjustments Electronic Control Circuit Available in a Wide Range of Electrical Control Inputs and Analog Outputs QPV2 or MPV2
More informationType 500X. Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions. Ordering Information.
Type 500X Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions Ordering Information Type 500X I/P Transducers Output Range Part Number Input psi kpa Impedance 500-AA
More informationData Sheet. I/P and E/P converters. RS stock numbers ,
Data Pack G Issued March 997 3-4998 Data Sheet I/P and E/P converters RS stock numbers 79-47, 79-48 Standard (electro-mechanical) Construction Housing Zinc diecastings, passivated and black epoxy paint,
More informationMiniature I/P, E/P Transducer
Miniature I/P, E/P Transducer Accurate and economical electronic pressure control The Type 550X is an electronic pressure regulator that converts a variable signal (current or voltage) to a proportional
More informationType 500X. Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions. Ordering Information.
Type 500X Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions Ordering Information Type 500X I/P Transducers Output Range Part Number Input psi kpa Impedance 500-AA
More informationSentronic D 608 Series and 609 Series
Sentronic D 608 Series and 609 Series Proportional Technology www.asco.com PRESSURE CONTROL: 608/609 SERIES SENTRONIC D Sentronic D Sentronic D is a digitally operated pressure regulator valve. Sentronic
More informationEQUIVALENT BASIC CIRCUIT
FEATURES Reliable semiconductor technology Calibrated and temperature compensated Rugged, stainless steel package NEMA 4 design Small size Absolute, gage, sealed gage, vacuum gage pressures 0 psi to 3
More informationMiniature I/P, E/P Transducer for Electronic Air Pressure Control
Miniature I/P, E/P Transducer for Electronic Air Pressure Control Self-correcting to maintain precise control The Type-900X I/P, E/P transducer converts an electrical signal (current or voltage) to a proportional
More informationSentronic PLUS 614 Series
Sentronic PLUS 64 Series Proportional Technology www.asco.com PRESSURE CONTROL: 64 SERIES SENTRONIC PLUS Sentronic PLUS Sentronic PLUS is a digitally operated pressure regulator valve. This valve accurately
More informationSSI Technologies MediaSensor
SSI Technologies MediaSensor P51 Pressure Transducers Product Description SSI s line of bulk micro-machined, absolute and gage pressure transducers and transmitters for both harsh and benign media with
More informationMiniature I/P, E/P Transducer for Electronic Air Pressure Control
Type 900X Miniature I/P, E/P Transducer for Electronic Air Pressure Control Self-correcting to maintain precise control Available with zero-based ranges The Type-900X I/P, E/P transducer converts an electrical
More informationMid-West Instrument. Series 700 "Wet/Wet" Installation and Operating Instructions. Differential Pressure Transmitter
Mid-West Instrument IM_700/A Series 700 "Wet/Wet" Installation and Operating Instructions Differential Pressure Transmitter 6500 Dobry Dr. Sterling Heights, MI USA Toll Free: 800-648-5778 Ph 586-254-6500
More informationProduct Catalog Pressure Regulators. Proportional Valves
Product Catalog 2008 Pressure Regulators Proportional Valves Corporate Overview Mission Statement Kelly Pneumatics Inc. is dedicated to creating, designing, and manufacturing unique, compact Pneumatic
More informationE22 Proportional Technology
E22 Proportional www.numatics.com Pressure Control: E22 Proportional E22 Series Unlike SENTRONIC valves, E-Series valves operate with pulsed pilot valves which change the pressure in a control chamber.
More informationT-1001 TYPE 1001 I/P & E/P TRANSDUCERS
TYPE 1001 I/P & E/P TRANSDUCERS T-1001 The Type 1001 is a patented family of electro-pneumatic instruments that is used to reduce a supply pressure to a regulated output pressure which is directly proportional
More informationType Type 1001 Transducers. I/P & E/P Transducers
Type 1001 I/P & E/P Description The Type 1001 is a patented family of electropneumatic instruments that is used to reduce a supply pressure to a regulated output pressure which is directly proportional
More informationElectropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN
Electropneumatic Converters i/p Converters Type 6111 Fig. 1 Type 6111 in standard version Fig. Type 6111 mounted on a supply air manifold Fig. 3 Type 6111 in field enclosure Mounting and Operating Instructions
More informationFlow Line Controls Positioner Specifications Series 55 3-15 psi Pneumatic Series 56 4-20 ma Electro-Pneumatic Series 55 Series 56 Flow Line Controls, Inc. P.O. Box 677 Schriever, LA 70395 Phone: 985-414-6003
More informationPaddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual
COMPANY Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual Mechanical Specifications Flow Meter with Polypropylene Body (ES version) Maximum Operating Pressure: 150 PSIG Maximum
More informationType Installation, Operation and Maintenance Instructions. Ordering Information. Contents CA20 -
Type 2000 Pneumatic and Electropneumatic Valve Positioner Installation, Operation and Maintenance Instructions Ordering Information Use this coding system to order Model CA20 - Type of Positioner 00 P/P
More informationWelker Sampler. Installation, Operation, & Maintenance Manual. Model GSS-4HP
Installation, Operation, & Maintenance Manual Welker Sampler Model GSS-4HP The information in this manual has been carefully checked for accuracy and is intended to be used as a guide to operations. Correct
More informationSSI Technologies Application Note PS-AN2 MediaSensor Absolute & Gage Pressure Transducers & Transmitters Product Overview
Product Description The MediaSensor (P51) family of bulk micro-machined, absolute, gage and sealed pressure transducers and transmitters are for both harsh and benign media with the superior typical accuracy
More informationPaddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual
COMPANY Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual 2016 AW-Lake Company. All rights reserved. Doc ID:PADDLEMAN082416 Mechanical Specifications Flow Meter with Polypropylene
More informationTable of Contents. Proportional & Precision Regulator Instrumentation
Table of Contents Proportional & Precision Regulator Instrumentation...3-27 Features and Benefits... 3 Electropneumatic Transducer...4-5 Economy Miniature Electropneumatic Transducer...6-7 Miniature Electropneumatic
More informationREMOTE MOUNT SOLENOID DRIVER (0-5 VDC/0-20 ma/10k Potentiometer Input)
REMOTE MOUNT SOLENOID DRIVER (0-5 VDC/0-20 ma/10k Potentiometer Input) Part No.: PCB Board - RSD-PCB-5V-x DIN Rail Mount RSD-DR-5V-x Packaged Driver (board installed in metal box) Available with no cable
More informationThe Series I/P Current to Pressure Transducer
Dwyer Instruments, Inc. Michigan City, IND. 46361 Phone (219) 879-8868 Fax (219) 872-9057 The Series I/P Current to Pressure Transducer Installation, Operation and Maintenance Instructions Pilot Pressure
More informationPRESSURE BENCH OPERATING INSTRUCTIONS
PRESSURE BENCH OPERATING INSTRUCTIONS Overview: The pressure bench system allows the user to apply a variety of calibrated pressures to a variety of high and low pressure transducers. In addition the system
More informationSETRA Operating Instructions Series DPT 230 Pressure Transducers
SETRA Operating Instructions Series DPT 230 Pressure Transducers GENERAL INFORMATION Your Setra Pressure Transducer has been carefully tested and calibrated before shipment. Specific performance information
More informationIntroduction Section 1 Section 2 Section 3
V A L V E S Page Introduction Section 1 Section 2 Section Proportional Pressure Controller 9 Proportional Quick Exhaust 65 Pressure Control Systems 77 1 Consult Precautions page 94 before use, installation
More informationCompact Vacuum Regulator. How to Order. Nil. ATMc. Base type Nil M
Compact Vacuum Regulator Series ITV RoHS For single unit and single unit for manifold ITV Pressure range kpa Power supply voltage 4 VDC ±% to VDC How to Order N Cable connector N Without cable connector
More informationF-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide
F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 1054-7 / 34405 www.onicon.com sales@onicon.com
More informationElectric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 inch NPT
Electric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 inch NPT SERIES Features Full Port 16 Stainless Steel ball valve LED light gives continuous status indication IP67 weatherproof polyamide
More informationSentronicPLUS IO-Link CLASS A Electronic Pressure Regulator. Installation Manual
SentronicPLUS IO-Link CLASS A Electronic Pressure Regulator Installation Manual Sentronic PLUS ASCO NUMATICS Sentronic PLUS Electronic Pressure Regulator Sentronic PLUS is a 3-way proportional valve with
More informationElectric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 inch NPT
Electric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 inch NPT SERIES Features Full Port 16 Stainless Steel ball valve LED light gives continuous status indication IP67 weatherproof polyamide
More informationElectric Actuated Ball Valves 3-Piece Stainless Steel, Full Port 1/4 to 3 inch NPT
Electric Actuated Ball Valves 3-Piece Stainless Steel, Full Port 1/4 to 3 inch NPT SERIES Features Direct mount Full Port 316 Stainless Steel ball valve 3-piece swing out body designed for easy maintenance
More informationType 2000 Transducer Product Instructions
Type 2000 Transducer Product Instructions The Type 2000 is an electro-pneumatic device that regulates an unregulated supply pressure down to an electronically-controlled output pressure. There are two
More informationMoniteur INSTALLATION & OPERATING INSTRUCTIONS. SERIES 40 Positioners. Installation and Operating Instructions Series 40 Positioners.
INSTALLATION & OPERATING INSTRUCTIONS SERIES 40 Positioners Form IO2-0406 Description of Device Moniteur's Series 40 pneumatic (3-15psi) and electropneumatic (4-20mA) positioners are advanced control devices
More informationProportional Technology Precise Control of Pressure and Flow
Precise Control of Pressure and Flow www.numatics.com Numatics, Inc. is a leading manufacturer of pneumatic products and motion control products. Our broad spectrum of standard, custom developed products
More informationSection 2 Proportional Quick Exhaust
V A L V E S Section 2 Proportional Quick Exhaust OPERATION OF THE PQE 1. The pilot operated regulator and the PPC5C are both fed from a common inlet. 2. The out port of the PPC5C sends pressure to the
More informationNEO-DYN MODEL 100P ENCLOSURE 7 ADJUSTABLE EXPLOSION-PROOF PRESSURE SWITCH
NEO-DYN MODEL 100P ENCLOSURE 7 ADJUSTABLE EXPLOSION-PROOF PRESSURE SWITCH INSTALLATION AND OPERATION MANUAL PN 610-0006 Rev E WARNING CAUTION SPECIAL CONDITIONS FOR SAFE USE NOTE Manual No. 610-0006 Rev
More informationMultiCal. Operation Manual for MultiCal mmhga/psia Pressure Module
MultiCal Operation Manual for MultiCal mmhga/psia Pressure Module Contents Overview.... 1 Introduction... 1 Operation.... 2 Functions.... 2 Pressure Measurement... 2 Battery Replacement... 3 Calibration....
More informationElectric Actuated Ball Valves 150 lb Flanged Stainless Steel, Full Port 1/2 to 4 inch Pipe Sizes
Electric Actuated Ball Valves 150 lb Flanged Stainless Steel, Full Port 1/2 to 4 inch Pipe Sizes SERIES Features Direct mount Full Port 16 Stainless Steel ball valve 2-piece ANSI Class 150 flanged body
More informationElectropneumatic Transducer
Electropneumatic Transducer Model EP-311/313 RoHS No air consumption 100% solid state piezoresistive silicon pressure sensor High air flow capacity Field selectable 4-20 ma, 0-5 VDC or...0-10 VDC input
More informationDMT PERFORMING UNDER PRESSURE DMT. Pressure Scanner Features. Applications. Description 1/7
Features User Accessible Memory for Test Configuration Management ±0.05% FS System Accuracy EU Throughput Rates of 500 Hz Auto-Negotiating 10/100 BaseT Ethernet with TCP & UDP Protocol Pressure Ranges
More informationFAIRCHILD T5420 DIGITAL-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions
FAIRCHILD T5420 DIGITAL-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions Figure 1. T5420 Outline Dimensions. INSTALLATION The Model T5420 can be mounted directly onto a flat surface
More informationCENTAC Inlet and Bypass Valve Positioners
CENTAC Inlet and Bypass Valve Positioners INGERSOLL-RAND AIR COMPRESSORS INLET AND BYPASS VALVE POSITIONERS Copyright Notice Copyright 1992, 1999 Ingersoll-Rand Company THIS CONTENTS OF THIS MANUAL ARE
More informationApex 5000 Positioner
Apex 5000 Positioner Principles of Operation: The Apex 5000 positioner causes rotation (or linear movement) of valve actuator in proportion to an input signal. This signal may take the form of pneumatic
More informationInstallation, Operation and Maintenance Instructions Output Range Part Number Input psi bar Impedance Output Range
Type 500X Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions Ordering Information Type 500X I/P Transducers Output Range Part Number Input psi bar Impedance Pilot
More informationPrecision Regulators.
Precision www.numatics.com Table of Contents Features and Benefits 3 Electropneumatic Transducer 4-5 Economy Miniature Electropneumatic Transducer 6-7 Miniature Electropneumatic Transducer 8-9 Precision
More informationCONTROLS. Bray Pneumatic Actuators & Accessories. Technical Manual. A Division of BRAY INTERNATIONAL, Inc.
CONTROLS A Division of BRAY INTERNATIONAL, Inc. Bray Pneumatic Actuators & Accessories Technical Manual TM-056 Pneumatic Actuator - 08//00 Bray Pneumatic Actuators & Accessories Technical Manual - Table
More informationSeries ITV0000. Compact Electro-Pneumatic Regulator ITV N Q. IITV00 02 n. How to Order. For single unit and single unit for manifold
Compact Electro-Pneumatic Regulator Series ITV How to Order For single unit and single unit for manifold ITV N Q Pressure range. MPa MPa.9 MPa Power supply voltage 4 VDC ±% to VDC Cable connector N S L
More informationCONTENTS. VIKING PUMP, INC. A Unit of IDEX Corporation Cedar Falls, IA USA SECTION TSM 710.1
TECHNICAL SERVICE MANUAL industrial heavy duty motor speed pumps SERIES 4076 AND 4176 SIZES hle, ate and ale SECTION TSM 710.1 PAGE 1 of 8 ISSUE B CONTENTS Introduction....................... 1 Safety
More informationAccord Logix Series 1000 Digital Positioner
Accord GENERAL INFORMATION The following instructions are designed to assist in unpacking, installing and performing maintenance as required on Logix Series 1000 Digital Positioners. Series 1000 is the
More informationServotronic Digital 615 Series
Servotronic Digital 615 Series Proportional Technology www.asco.com PRESSURE CONTROL: 615 SERIES SERVOTRONIC Digital Servotronic Digital Greater versatility in automated production processes: Due to electronics,
More informationPEAKTRONICS DMC-101 ADDITIONAL FEATURES. DC Motor Controller, 5A DMC-101
PEAKTRONICS The Peaktronics DC Motor Controller is used for proportional positioning of actuators that use either DC motors or DC solenoids. The wide operating range of the (10 to 30 VDC and loads up to
More informationPrecision Control Devices
Precision Control Devices Electro-Pneumatic Servo Pressure Controllers Electro-Pneumatic I/P, E/P, & P/I Transducers Diaphragm Regulators & Relays Diaphragm Cylinders Filter - Regulator - Lubricators Gauge
More informationOM Field-Type I/P Converter Model : KUX113 User's Manual
OM2-5900-1130 Field-Type I/P Converter Model : KUX113 User's Manual Copyright, Notices and Trademarks 1994-2012 Azbil Corporation All Rights Reserved. While this information is presented in good faith
More informationK10 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual
K0 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual Pneumatic Connection Outlet Port Gauge Single Acting Actuator (Spring Return): For single acting actuators Outlet Port 2 is to be plugged.
More informationFAIRCHILD T5200 SERIES ELECTRO-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions
FAIRCHILD T500 SERIES ELECTRO-PNEUMATIC TRADUCER Installation, Operation and Maintenance Instructions Identification Number Underwriting Group Factory Mutual Canadian Standard T (F) (C) 500- Approval Class
More informationMounting and Operating Instructions EB 3913 EN. Electropneumatic Converters i/p Converter Type
Electropneumatic Converters i/p Converter Type 3913-0001 Fig. 1 Type 3913-0001 Electropneumatic Converter with pressure gauge and bracket Mounting and Operating Instructions EB 3913 EN Edition August 2011
More information1100 Series Piston Type Differential Pressure Gauges
1100 Series Piston Type Differential Pressure Gauges 1. Safety Before installing, check the Series Number and verify compatibility to the process media and temperature in contact with the wetted parts.
More informationElectropneumatic Transducer (I/P, E/P)
Type 500X Electropneumatic Transducer (I/P, E/P) Economical and reliable electrical conversion to pressure The ControlAir Type 500X converts a current or voltage input signal to a linearly proportional
More informationInstallation, Operation & Maintenance Manual
Installation, Operation & Maintenance Manual MONITORS www.lakemonitors.com Lake Monitors 8809 Industrial Drive, Franksville, WI 53126 P: (800) 850-6110 (262) 884-9800 F: (262) 884-9810 MONITORS 2007 AW-Lake
More informationHDI inch Choke Position Indicator User s Manual Rev Indicator Gauge Linear Potentiometer
HDI 2522 4-inch Choke Position Indicator User s Manual Rev 2 New 2522 Indicator Gauge Linear Potentiometer w/open Housing 2200 Indicator Gauge Linear Potentiometer TABLE OF CONTENTS HDI 2522 4-inch Indicator
More informationFisher 546 Electro Pneumatic Transducer
546 Transducer Product Bulletin Fisher 546 Electro Pneumatic Transducer Fisher 546 transducers receive a direct current input signal and use a torque motor, nozzle flapper, and pneumatic relay to convert
More informationMS4525 SPECIFICATIONS
SPECIFICATIONS PCB Mounted Pressure Transducers Amplified Ratiometric Analog Output Differential, Gage, Absolute, Compound, & Vacuum Temperature Compensated 3.3 or 5.0 Vdc Supply Voltage The MS4525 is
More informationThe T5220 Series Electro-Pneumatic Transducer converts a DC current or voltage input signal to a directly proportional pneumatic output.
GENERAL INFORMATION T5220 SERIES TRANSDUCER Electro-Pneumatic (I/P, E/P) APPLICATIONS The T5220 Series Electro-Pneumatic Transducer converts a DC current or voltage input signal to a directly proportional
More informationElectro-Pneumatic Regulators. Electronic Vacuum Regulators
Electro-Pneumatic Regulator Electronic Vacuum Regulator New Reduced wiring Applicable Fieldbus protocols Compact & light Weight: g Note ) (ITV) Power consumption: 4 W Note ) or less Electro-Pneumatic Regulators
More informationElectro-Pneumatic Regulators. Electronic Vacuum Regulators
Electro-Pneumatic Regulator Electronic Vacuum Regulator New Reduced wiring Applicable Fieldbus protocols Compact & light Weight: g Note ) (ITV) Power consumption: 4 W Note ) or less Electro-Pneumatic Regulators
More informationSeries ITV0000. Compact Electro-pneumatic Regulator ITV N. IITV00 02 n. How to Order F.R.L. AV AU AF AR IR VEX AMR ITV IC VBA VE VY1 G PPA AL
Compact Electro-pneumatic Regulator Series For single unit and single unit for manifold Pressure range 9 Option. MPa. MPa.9 MPa kpa Option How to Order N Power supply voltage 24 VDC ±% 2 to VDC Option
More informationFlo-Way. Measure Granular or Powdered Material. Stand Alone or Connect to Other Devices for Blending. Used by Successful Producers World-Wide
Flo-Way R Solids Impact Flow Meter Measure Granular or Powdered Material Stand Alone or Connect to Other Devices for Blending Used by Successful Producers World-Wide Visit our website: www.beltwayscales.com
More informationHow to Order ITV N. Nil. EXHc. Base type. Nil. ø1/4"
Compact Electro-Pneumatic Regulator Series ITV RoHS How to Order [Option] For single unit and single unit for manifold ITV N Pressure range. MPa. MPa.9 MPa Power supply voltage 4 VDC ±% to VDC Cable connector
More informationOperation and Maintenance Instructions Manual BOOSTER. Volume amplifier
Operation and Maintenance Instructions Manual BOOSTER Volume amplifier 1. GENERAL INFORMATION... 3 2. TECHNICAL SPECIFICATIONS... 3 3. DIMENSIONAL DESIGN... 4 3.1 BOOSTER WITHOUT SIGNAL ADAPTER... 4 3.2
More informationITVX Series. Stepless control of air pressure proportional to an electrical signal. Supply pressure: 5.0 MPa
5.0 MPa Maximum Supply Pressure High Pressure Electro-Pneumatic Regulator X Series This product is only for blowing gas. This product does not have sufficient pressure control for other applications (driving,
More informationFisher 657 Diaphragm Actuator Sizes and 87
Instruction Manual 657 Actuator (30-70 and 87) Fisher 657 Diaphragm Actuator Sizes 30 70 and 87 Contents Introduction... 1 Scope of Manual... 1 Description... 2 Specifications... 2 Installation... 3 Mounting
More informationMODEL 1100 TURBINE FLOW METER
MODEL 1100 TURBINE FLOW METER INSTALLATION & INSTRUCTION MANUAL 8635 Washington Ave. Racine, Wisconsin 53406 Phone: 800.433.5263 Fax: 800.245.3569 www.hedland.com 2 OPERATIONAL START-UP Fluid entering
More informationFisher 4194S Differential Pressure Controllers
Instruction Manual 4194S Controllers Fisher 4194S Differential Pressure Controllers Contents 1. Introduction... 2 Scope of Manual... 2 Description... 2 Specifications... 5 Educational Services... 5 2.
More informationTroubleshooting Bosch Proportional Valves
Troubleshooting Bosch Proportional Valves An Informative Webinar Developed by GPM Hydraulic Consulting, Inc. Instructed By Copyright, 2009 GPM Hydraulic Consulting, Inc. TABLE OF CONTENTS Bosch Valves
More informationType Type I/P & E/P Transducers
Type 1500 I/P & E/P Type 1500 Description Principle of Operation (ee Fig. 2 and 6) The T-1500 Transducer is a force balance device in which a coil is suspended in the field of a magnet by a flexure. Current
More informationCONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (0-10VDC Input Version)
TECHNICAL DATASHEET #TD1101AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (0-10VDC Input Version) Part No.: CAPV-H-10V-x complete with cable CAPV-S7C-yM Where: x = current output (2A, 1.2A or 600MA) y
More informationTECHNICAL PAPER 1002 FT. WORTH, TEXAS REPORT X ORDER
I. REFERENCE: 1 30 [1] Snow Engineering Co. Drawing 80504 Sheet 21, Hydraulic Schematic [2] Snow Engineering Co. Drawing 60445, Sheet 21 Control Logic Flow Chart [3] Snow Engineering Co. Drawing 80577,
More informationMAGPOWR Spyder-Plus-S1 Tension Control
MAGPOWR TENSION CONTROL MAGPOWR Spyder-Plus-S1 Tension Control Instruction Manual Figure 1 EN MI 850A351 1 A COPYRIGHT All of the information herein is the exclusive proprietary property of Maxcess International,
More informationOperation and Maintenance Manual for Multipurpose Actuators. 120 VAC Actuator 12 VDC Actuator 12 VDC Actuator
Joyce/Dayton Corp. Operation and Maintenance Manual for Multipurpose Actuators 120 VAC Actuator 12 VDC Actuator 12 VDC Actuator The recommendations in this manual for installation, operation and maintenance
More informationInline Pressure Control Or Shutoff Valves (Non-digital) And Bypass Pressure Control Or Shutoff Valves (Non-digital)
IN64124 August 15, 1997 Aerospace Group Conveyance Systems Divison Carter Brand Ground Fueling Equipment Applicable additional manuals: Installation Instructions Inline Pressure Control Or Shutoff Valves
More informationINSTRUCTION MANUAL INSTALLATION, OPERATION, AND MAINTENANCE ACTUATOR MANIFOLD
INSTRUCTION MANUAL INSTALLATION, OPERATION, AND MAINTENANCE B-3724M ACTUATOR MANIFOLD MIDLAND MANUFACTURING CORP. 7733 Gross Point Road Skokie, Illinois 60077 Phone (847) 677-0333 FAX (847) 677-0138 WEBSITE
More informationP255 Stainless Steel Pressure Transducer
P255 Stainless Steel Pressure Transducer Description The model P255 is based on Kavlico s fieldproven ceramic capacitive technology with the latest state-of-the-art ASIC. Featuring a 316SS housing, the
More informationElectro-Pneumatic Positioner Series 830/831-WP/EX. Operation & Maintenance Manual
Electro-Pneumatic Positioner Series 830/831-WP/EX Operation & Maintenance Manual Electro-Pneumatic Positioner Model 830/831- WP/EXP This operation & maintenance manual corresponds to Forbes Marshall Arca
More informationEasytork Solenoid Valve IOM
Easytork Solenoid Valve IOM General This installation document is to be read in conjunction with the Easytork Vane Actuator IOM. Description The Easytork Solenoid Valve ( ESV ) series is intended for the
More informationIntroduction. Installation. Maintenance. Bill of Materials
Table of Contents Introduction Specitications... 3 Operation... 4 Installation New Installations... 6 Retrofit Installations... 6 Flow Control Switch... 7 Dimensions... 8 E-7 Valve... 28 E-7 Valve with
More informationEB EN. Type 3372 Electropneumatic Actuator. Translation of original instructions
EB 8313-1 EN Translation of original instructions V2001-IP Control Valve Type 3372 0511/0531 Electropneumatic Actuator with Type 3321 Valve Type 3372 Electropneumatic Actuator Edition July 2013 Note on
More informationEVP SERIES PROPORTIONAL CONTROL VALVES
EVP SERIES PROPORTIONAL CONTROL VALVES 207 Clippard is pleased to add the EVP series proportional control valve to our electronic product line. This product combines the features of the existing EV series
More informationCompact Electric Actuated Ball Valves PVC Body, Teflon/EPDM Seals 1/2 to 1 inch Pipe
Compact Electric Actuated Ball Valves PVC Body, Teflon/EPDM Seals 1/2 to 1 inch Pipe SERIES Features Industrial quality miniature actuator Industrial grade True Union ball valve Visual valve position indicator
More informationPart Number Analog Style 15 PSI Fuel/Boost Pressure Gauge. NOTE: Faceplate Configuration Instructions Included on Separate Sheet
Part Number 30-5144 Analog Style 15 PSI Fuel/Boost Pressure Gauge NOTE: Faceplate Configuration Instructions Included on Separate Sheet AEM Oil/Fuel Pressure Gauge Parts 1 x 35-5144 Pressure Gauge Assembly
More information