SE-3SCR-LM MANUAL MOTOR LOAD MANAGER

Similar documents
SE-400 MANUAL GROUND-FAULT-RELAY TEST UNIT

SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

SE-100T MANUAL GROUND-FAULT-RELAY TESTER

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

Fincor Series 2230 MKII/2240

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

POWR-GARD Relay Testing Equipment PGT-0400 Series Ground-Fault Relay Test Unit PGT Ground-Fault Relay Test Unit

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

CONTROL FEATURES AVAILABLE OPTIONS

RVS-DN Digital Reduced Voltage Motor Starter

MaxPak Plus Analog DC V S Drive

Application Engineering

Application Engineering

GENSET CONTROL MODULE A121A / A241A

CENTROIDTM. AC Brushless Drive. Product Spec Sheet

SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN

Type SOQ Negative Sequence Time Overcurrent Relay

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

1/6 through 5 HP Adjustable Speed, DC Motor Controllers

PORTABLE CURRENT SOURCE FOR CIRCUIT BREAKER AND MOTOR OVERLOAD TESTING INSTRUCTION MANUAL PI-250B. Release 1.0 April 5, 2013

DC Variable Speed Drive Panel

TRIPS AND FAULT FINDING

RCP200 Series Motor Controls. Instruction Manual Model RCP Model RCP Model RCP202-BC1 Model RCP202-BC2 Model RCP205-BC2

600 Series Troubleshooting Guide for C651 and C654 Alternators

5001TCP SPEED CONTROLLER

XR500B Universal Voltage Regulator

POWER SUPPLY MODEL XP-800. TWO AC VARIABLE VOLTAGES; 0-120V and 7A, PLUS UP TO 10A. Instruction Manual. Elenco Electronics, Inc.

5001TCP SPEED CONTROLLER

SCR Power Controllers

G213V STEP MOTOR DRIVE REV 7: March 25, 2011

Installation & Operation Manual

GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.

N1387 Series Troubleshooting Guide for N Alternators

C802/C802D/C802TD/C820 Alternators Troubleshooting Guide

User Manual. T6 Tachometer. Online: Telephone: P.O. Box St. Petersburg, Florida 33736

RVS-DX Digital Reduced Voltage Motor Starter

G203V / G213V MANUAL STEP MOTOR DRIVE

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

KD LV Motor Protection Relay

SECTION 2 - PROCEDURES. Features. 2.6 MOTOR CONTROLLER. Modes of Operation JLG Lift 2-5

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

500 Series Troubleshooting Guide for C520 Alternators

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

Graham. Vari Speed S1000 Instruction Manual. TRANSMISSIONS, Inc. Installation, Operation and Maintenance Manual

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.

Explanation 1 Input External Switch 2 Input Hipot Safety Switch

CTi Automation - Phone: Fax: Web:

with lcd display 12-42v

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors

Yaskawa Electric America Unit Troubleshooting Manual Section One: Introduction & Checks Without Power GPD 506/P5 and GPD 515/G5 (0.

UL/cUL FILE NUMBER E CE See last page of manual for CE Declaration of Conformity.

C.E. Niehoff & Co. N1601, N1602, N1603, and N1604 Alternator Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

RVS-AX Instruction Manual

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

8036-A0 Motor Drives Training System (Stand-Alone)

efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75

4.0 OPERATION Type ITH-T Relay

C.E. Niehoff & Co. C703/C703A and C706 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

User Guide 4Q kW D.C.Motor Regenerative Speed Controller. Part Number: Issue Number: 3

Electronic Ballast EVG 2000-T

24-00 ELECTRICAL POWER

BLHV, BLHV-1. High Voltage Step Motor Driver. User s Guide. (714) fax: (714) website:

Aura Interior Wiring Manual (5-Wire and BACnet)

CENTRIFEEDER ELECTRONICS

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

Power Switching Principles

DENISON HYDRAULICS Jupiter 500 Driver Card Series S

2001 Dodge Durango ACCESSORIES & EQUIPMENT' 'Anti-Theft Systems - Dakota & Durango 2001 ACCESSORIES & EQUIPMENT

Fincor DC Drives. Flexible & Powerful TYPICAL APPLICATIONS. Conveyor Rugged. Extruder Reliable. Conveyor Simple. Mixer Flexible

Loadcell Tension Control

INSTALLATION, OPERATION & MAINTENANCE SERIES ABC11B-120-XX BATTERY CHARGERS

DUAL SWIVEL REEL OPERATING INSTRUCTIONS

Model Number Structure. Power Controllers G3PX. Single-phase Models. Model Number Legend

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

Softstarters. Softstarters Power electronic brakes Type PEB

C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

THE MODEL D1025 MKII BI-DIRECTIONAL GENERATOR FIELD REGULATOR INSTRUCTION MANUAL # S-276

SERIES 2335 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-2 HP)

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

Exercise 7. Thyristor Three-Phase Rectifier/Inverter EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Thyristor three-phase rectifier/inverter

Power electronic brakes

CABINET REEL OPERATING INSTRUCTIONS

5. OVERCURRENT RELEASE (OCR)

DCT SERIES CASE SIZE 3A FILTERED BATTERY CHARGER 12V/200A 24V/ A 48V/100A 120V/50A 240V/25A OPERATION & MAINTENANCE GUIDE

FT-10 Network Digital I/O Module Kits and

Kelly HSR Series Motor Controller with Regen User s Manual V 3.3. Kelly HSR Opto-Isolated Series Motor Controller with Regen.

Exercise 5-1. Primary Resistor Starters EXERCISE OBJECTIVE DISCUSSION. Understand how primary resistor starters operate.

Model 930 Power Control System Instruction Manual

MVC4MEDIUM VOLTAGESOLIDSTATESOFTSTARTER

C.E. Niehoff & Co. C505, C527, C531, and C534 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING

INSTALLING, OPERATING AND MAINTAINING THE MODEL D1028 COMPUTER INPUT BI-DIRECTIONAL GENERATOR FIELD REGULATOR INSTRUCTION MANUAL # S-225

This chapter contains information on DC Generation, External Power, and Electrical Load Distribution.

Instruction Manual. Installation Operation Maintenance. KCR 760 Voltage Regulator

Installation, Operation and Maintenance Manual

MODEL No s: PP3, PP3K

PARKING LOT CONTROLLER WITH LOGIC & MAIN CONTACTOR

DMC-500 TM. DC Motor Drive Control. Operation / Installation Manual Manual Part Number: S8M5003 Date: August 11, Computer Weld Technology, Inc.

Transcription:

3714 Kinnear Place Saskatoon, SK Canada S7P 0A6 Ph: (306) 373-5505 Fx: (306) 374-2245 www.littelfuse.com/relayscontrols SE-3SCR-LM MANUAL MOTOR LOAD MANAGER MARCH 5, 2013 REVISION 4 MOTOR LOAD MANAGER PHASE LOSS PHASE REVERSE POWER RUN SHED ENABLED CURRENT LIMIT OVERCURRENT CURRENT LIMIT TACH SIGNAL HOLD LOSS JOG TEMPERATURE SETUP CURRENT FEEDBACK ANTIJOG EMERGENCY TRIP CIRCUIT FULL VOLTAGE REDUCED VOLTAGE RESET SHED MOTOR 1 MOTOR 2 MOTOR 3 MOTOR 4 SE-3SCR-LM Copyright 2013 by Littelfuse Startco Ltd. All rights reserved. Publication: SE-3SCR-LM-M Document: S95-S3LM-00000 Printed in Canada.

Page i TABLE OF CONTENTS PAGE 1. General... 1 2. Current-Feedback Operation... 1 2.1 Minimum Acceleration Time... 1 2.2 Current-Limit-Hold Level... 1 2.3 Current-Limit-Hold Trip Time... 1 2.4 Initial Voltage... 3 3. Tachometer-Feedback Operation... 3 4. Trip Indications... 3 4.1 Phase Loss... 3 4.2 Phase Reverse... 3 4.3 Current Limit... 3 4.4 Overcurrent... 3 4.5 Setup... 3 4.6 Anti Jog... 3 4.7 Current Feedback... 3 4.8 Emergency-Trip Circuit... 5 5. Other Indication... 5 5.1 Run... 5 5.2 Shed Enabled... 5 5.3 Current-Limit Hold... 5 5.4 Tach Signal Loss... 5 5.5 Jog Temperature... 5 5.6 Motor Voltage... 5 6. Initial Setup and Commissioning... 5 6.1 Motors In Use... 5 6.2 Initial Voltage... 5 6.3 Current-Feedback Start... 5 6.4 Tachometer-Feedback Start... 5 6.4.1 Analog Tachometer... 5 6.4.2 Digital Tachometer... 6 6.5 Configuration... 6 6.6 Shed... 6 6.7 Reduced-Voltage Run... 6 7. Motor-Shed Control... 6 8. Reduced-Voltage Run... 6 9. Troubleshooting... 7 9.1 I/O Control... 7 9.1.1 Standard Mode... 7 9.1.2 Legacy Mode... 7 9.2 Output Signals... 7 10. Technical Specifications... 8 FIGURE LIST OF FIGURES PAGE 1 SE-3SCR-LM Rear View... 2 2 SE-3SCR-LM Outline and Mounting Detail... 4 3 I/O Control... 9 4a Troubleshooting Guide... 10 4b Troubleshooting Guide... 11 DISCLAIMER Specifications are subject to change without notice. Littelfuse Startco is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction.

Page 1 1. GENERAL Each Startco solid-state starter uses one Load Manager to control the power applied to three-phase, squirrel-cage induction motors in one-, two-, three-, or four-motor configurations. The SE-3SCR-LM Motor Load Manager control module replaces the SE-2SCR-LC, SE-2SCR, and SE-1SCR control modules. The Load Manager is standard in new equipment and it can be retrofitted to existing Startco starters to provide the following additional features: On-board, active and passive digital-tachometer inputs. Adjustable current-limit-hold trip time. Isolated run-signal and remote-reset inputs. Run, trip, and full-conduction relay outputs. On-board, emergency-trip circuit with an output contact for shunt or undervoltage breaker control. Individual control of each motor for smooth shed and share transitions. Choice of current-shed or forced-shed operation. Reduced-voltage-run adjustment for each motor in a multiple-motor drive to allow load sharing. A silicon-controlled rectifier (SCR) is an electrically operated switch that can be gated into conduction by applying a trigger pulse to its gate terminal. Once an SCR is gated on, it will remain on until current drops below a low value called the holding current. In ac applications, this happens each cycle on the negative zero crossing; consequently, SCR's can be used to control ac voltage by triggering the SCR's into conduction once each cycle. The portion of the cycle in which current flows is called the conduction angle. In Startco Solid-State Starters, conduction-angle signals from the Load Manager initiate SCR trigger pulses generated by firing circuits in the power modules. A Startco power module has an SCR and a diode in a parallel, back-to-back configuration. Three power modules are used to control the voltage applied to a three-phase motor. The Load Manager uses either current or tachometer feedback to adjust SCR conduction angles during a start to bring a load smoothly up to speed. A reduced-voltage indicator flashes whenever a conduction angle is changing. Once full speed has been achieved and full voltage is indicated, the SCR's are gated full-on so that currents are the same as they would be if the power modules were replaced by contacts. 2. CURRENT-FEEDBACK OPERATION Load Manager adjustments are functionally grouped as shown in Fig. 1. For current-feedback starts, the top switch in the TACHOMETER FEEDBACK START group must be in the NO position. When this switch is in the NO position, all other controls in the TACHOMETER FEEDBACK START group are disabled. 2.1 MINIMUM ACCELERATION TIME The MINIMUM ACCELERATION TIME control is a 16-position selector switch that sets the time for motor voltage to increase from initial voltage to full voltage without a current-limit hold. Each clockwise step above 3 seconds increases the minimum time to reach full voltage by 1.5 seconds. The REDUCED VOLTAGE indicator flash rate is proportional to the rate at which motor voltage is changing. 2.2 CURRENT-LIMIT-HOLD LEVEL The CURRENT LIMIT HOLD LEVEL control is a 16- position selector switch that sets the current limit during a current-feedback start. The selection range is 200% to 500% of motor full-load current (FLA). Each clockwise step increases the current-limit-hold level by 20% FLA. During a current-feedback start, voltage will increase at a rate set by the MINIMUM ACCELERATION TIME control; however, if the load is sufficient to cause any motor current to reach the current-limit-hold level, the CURRENT LIMIT HOLD indicator will come on, the REDUCED VOLTAGE indicators will stop flashing, and the conduction angle will not advance until all motor currents fall below the current-limit-hold level. As the load accelerates, current decreases and voltage will continue to increase until full conduction is reached. 2.3 CURRENT-LIMIT-HOLD TRIP TIME The CURRENT LIMIT HOLD TRIP TIME control is a 16-position selector switch that sets the cumulative trip time for current-limit hold. The selection range is 2 seconds to 32 seconds in 2-second increments. When configured for DOUBLE TRIP TIME in the CONFIGURATION group, the selection range is 4 seconds to 64 seconds in 4-second increments. In most applications, the CURRENT LIMIT HOLD indicator should come on momentarily during a heavily loaded start. If unnecessary current-limit trips occur, increase MINIMUM ACCELERATION TIME, increase CURRENT LIMIT HOLD LEVEL, or increase CURRENT LIMIT HOLD TRIP TIME.

Page 2 FIGURE 1. SE-3SCR-LM Rear View.

Page 3 2.4 INITIAL VOLTAGE The INITIAL VOLTAGE control is a 16-position selector switch that sets the voltage applied to the motors at the beginning of the start. The selection range is 35% to 50% of full voltage in 1% increments. A setting of 38% to 42% will be sufficient for most applications. The INITIAL VOLTAGE control should be set so that torque is applied smoothly and shaft rotation begins without delay. If the initial-voltage setting is too high, the Load Manager will trip on overcurrent at the beginning of the start. 3. TACHOMETER-FEEDBACK OPERATION Load Manager adjustments are functionally grouped as shown in Fig. 1. For tachometer-feedback starts, the top switch in the TACHOMETER FEEDBACK START group must be in the YES position. When this switch is in the YES position, all controls in the TACHOMETER FEEDBACK START group are enabled, and all controls in the CURRENT FEEDBACK START group must be set to their maximum settings. The tachometer-feedback circuit accepts an analog tachometer, an active digital tachometer, or a passive digital tachometer. Separate inputs are provided for analog and digital tachometers. The SE-3SCR-LM must be configured for the type of tachometer used. See Section 6.4. Set one of the SYNC SPEED switches to program the tachometer circuit for 900, 1200, or 1800 rpm. In tachometer-feedback start, motor voltage is adjusted automatically to cause the motors to accelerate at a constant rate. The TACHOMETER FEEDBACK START ACCELERATION TIME potentiometer adjusts acceleration time from 10 seconds to 20 seconds. When DOUBLE ACCEL TIME is selected, acceleration time is doubled. REDUCED VOLTAGE indicators flash slowly while the tachometer-feedback circuit has control of motor voltage. When 97% of synchronous speed is reached, motor voltage is increased to full voltage in 1.5 seconds. In tachometer-feedback start, the function of the INITIAL VOLTAGE selector is changed it limits maximum motor voltage during starting. If the INITIAL VOLTAGE selector is set too high, an OVERCURRENT trip can occur during a heavily loaded start. For most applications, an initialvoltage setting of 44% will be adequate; however, the setting should be increased if load acceleration droops during a start. If the INITIAL VOLTAGE selector is set correctly, motors will be permitted to draw up to 450% fullload current during a heavily loaded start. 4. TRIP INDICATIONS All Load Manager trips are annunciated by the frontpanel indicators shown in Fig. 2. Trips remain latched until the trip condition is removed and RESET is pressed or the supply voltage is cycled. 4.1 PHASE LOSS A phase-loss trip will occur if any of the zero-crossing signals are not detected, or if the zero-crossing signals are not displaced 120 with respect to each other. 4.2 PHASE REVERSE A phase-reverse trip will occur if all zero-crossing signals are detected and their phase sequence is not A-B-C. 4.3 CURRENT LIMIT A current-limit trip will occur if motor current exceeds the current-limit-hold level for the current-limit-hold trip time. 4.4 OVERCURRENT An overcurrent trip will occur if current to any motor exceeds the overcurrent-trip level. The overcurrent-trip level can be selected at 550% or 600% FLA by a switch in the CONFIGURATION group. 4.5 SETUP A setup trip will occur if the SHED switches and REDUCED VOLTAGE RUN potentiometer settings do not allow at least one of the motors in use to run at full voltage. A valid setup requires at least one of the motors in use to have its SHED switch set to NO and its REDUCED VOLTAGE RUN potentiometer set to FULL. To assist in setup, the rear-panel INVALID SETUP indicator mimics the front-panel SETUP trip indicator. 4.6 ANTI JOG An anti-jog trip will occur if JOG TEMPERATURE reaches a count of 14. An anti-jog trip will remain latched until JOG TEMPERATURE counts down to 4. The top two switches in the CONFIGURATION group can be used to enable or disable anti-jog trips and to double the time to trip. See Section 5.5. 4.7 CURRENT FEEDBACK A current-feedback trip will occur during starting or running if less than 12% FLA is detected for any motor in use.

Page 4 221.5 45.7 (1.80) MAXIMUM 37.7 (1.48) (8.72) 146.1 (5.75) 37.7 (1.48) PHASE LOSS CURRENT LIMIT SETUP CURRENT FEEDBACK RESET 31.8 (1.25) 9.5 (0.38) 419.1 (16.50) 482.6 (19.00) 463.6 (18.25) MOTOR LOAD MANAGER POWER PHASE REVERSE RUN SHED ENABLED CURRENT LIMIT HOLD TACH SIGNAL LOSS OVERCURRENT JOG TEMPERATURE ANTIJOG EMERGENCY CIRCUIT TRIP FULL VOLTAGE REDUCED VOLTAGE SHED MOTOR 1 MOTOR 2 MOTOR 3 MOTOR 4 SE-3SCR-LM 31.8 (1.25) 6.4 (0.25) 4 LOCATIONS NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M5 x 12 OR 10-32 x 0.50. FIGURE 2. SE-3SCR-LM Outline and Mounting Detail.

Page 5 4.8 EMERGENCY-TRIP CIRCUIT An emergency-trip-circuit trip will occur if motor current (above 12% FLA) continues for more than 3.5 seconds after the run signal is removed. Emergency-trip-circuit protection is similar to "welded-contact" protection. Circuit operation is SHUNT or UV selectable with a switch located in the CONFIGURATION group. Output contacts can be used in a breaker or interposed contactor control circuit. 5. OTHER INDICATION 5.1 RUN The green LED labelled RUN indicates a 12- to 24-Vdc run signal on terminal 201 when the Load Manager is not tripped. 5.2 SHED ENABLED The yellow LED labelled SHED ENABLED indicates that at least one of the motors in use has its SHED switch set to YES. 5.3 CURRENT-LIMIT HOLD The red LED labelled CURRENT LIMIT HOLD indicates that motor current has reached the current-limithold level. 5.4 TACH SIGNAL LOSS The yellow LED labelled TACH SIGNAL LOSS indicates that the tachometer-feedback signal lags the reference speed signal by more than 6% of synchronous speed. Tach-signal loss does not cause a trip. 5.5 JOG TEMPERATURE An MPU Motor Protection Unit or an MPS Motor Protection System is recommended for each motor; however, the jog-temperature circuit can provide protection in the event of repeated starts. Four yellow LED's labelled JOG TEMPERATURE indicate the recent starting history of the starter. The LED's have a binary weighting of 8, 4, 2, and 1 from left to right and the number in the jog temperature display is obtained by adding the binary value of the LED's that are on. Values assigned to this display are: 0 is cold, 4 is normal run, and 14 is trip. Two, successive, maximum-acceleration-time starts are allowed if the motors are stopped on normal run; however, if a third start is attempted, the anti-jog circuit will trip at 14 and not allow a reset until the display decrements to 4. This will take approximately 11 minutes. Time to trip can be doubled with a switch in the CONFIGURATION group. The top switch in the CONFIGURATION group can be used to disable anti-jog trips. 5.6 MOTOR VOLTAGE The status of the voltage applied to each motor in use is indicated by three LED s. The bottom LED indicates if the motor is SHED, the middle LED indicates if the motor is operating at REDUCED VOLTAGE and it flashes when motor voltage is changing, and the top LED indicates FULL VOLTAGE. 6. INITIAL SETUP AND COMMISSIONING 6.1 MOTORS IN USE Set the MOTORS IN USE switches to the YES position for each motor used. If a motor is selected but not used, feedback current will not be detected and a current-feedback trip will occur within 3 seconds. If a motor is connected but not selected, it will not receive power. All unused feedback inputs (261, 262, 263, 261A, 261B, 261C, and 261D) should be connected to terminal 260. NOTE: To prevent a feedback trip during troubleshooting when no motor is connected, set the MINIMUM ACCELERATION to 2 seconds. 6.2 INITIAL VOLTAGE Set the INITIAL VOLTAGE selector to 40% for currentfeedback starts or 44% for tachometer-feedback starts. See Sections 2.4 and 3. 6.3 CURRENT-FEEDBACK START If current feedback is used, set the top switch in the TACHOMETER FEEDBACK START group to NO, set the MINIMUM ACCELERATION TIME selector to 15 seconds, set the CURRENT LIMIT HOLD LEVEL selector to 460% FLA, and set the CURRENT LIMIT HOLD TRIP TIME to 6 seconds. 6.4 TACHOMETER-FEEDBACK START If tachometer feedback is used, set the top switch in the TACHOMETER FEEDBACK START group to YES and set all controls in the CURRENT FEEDBACK START group to their maximum settings. 6.4.1 ANALOG TACHOMETER 1. Set switch to ANALOG TACH. 2. Connect the positive output of a 100-Vdc/1000-rpm tachometer to the terminal labelled ANALOG TACH INPUT and connect the negative output to terminal 260. 3. Set one SYNC SPEED switch for 900, 1200, or 1800 rpm. 4. Set the acceleration-time switch to ACCEL TIME x1. 5. Set the ACCELERATION TIME potentiometer to 15 seconds.

Page 6 6.4.2 DIGITAL TACHOMETER The Load Manager accepts speed signals from a passive digital tachometer or a 12-Volt active digital tachometer. 1. Set switch to DIGITAL TACH. 2. Set switch to ACTIVE PICKUP or PASSIVE PICKUP to correspond with the pickup used. 3. Connect the pickup signal lead to terminal TK7 and the ground lead to terminal TK8. Ground the shield only at terminal TK8. If a passive pickup is used, leave terminal TK9 unconnected. If an active pickup is used, connect the 12-Vdc lead to TK9. 4. Set one SYNC SPEED switch for 900, 1200, or 1800 rpm. 5. Set the acceleration-time switch to ACCEL TIME x1. 6. Set the ACCELERATION TIME potentiometer to 15 seconds. 6.5 CONFIGURATION Commission the system with the CONFIGURATION group set as follows: ANTI JOG ON. JOG TIME x1. EMERGENCY TRIP to match breaker operating mode. 550% OVERCURRENT TRIP. CURRENT LIMIT HOLD TRIP TIME x1. 6.6 SHED Commission the system with the SHED switches set to the NO and CURRENT positions. After the system is operational, the benefits of motor shedding for the application can be determined as outlined in Section 7. 6.7 REDUCED-VOLTAGE RUN Commission the system with the REDUCED VOLTAGE RUN potentiometers fully clockwise and the REDUCED VOLTAGE RUN switch to NO. After the system is operational, the benefits of motor sharing for the application can be determined as outlined in Section 8. 7. MOTOR-SHED CONTROL Two shed-control switches are used for each motor. If the upper switch is in the NO position, shed control is disabled for that motor. If the upper switch is in the YES position, the lower switch is active and its position determines if the motor will be forced off 15 seconds after full conduction or if the motor will drop-out and pick-up as the load changes. The DROPOUT CURRENT and PICKUP CURRENT selector switches apply only to motors with their shed switches in the YES and CURRENT positions. The current-shed circuit monitors motor currents from the phase-a feedback CT s of each motor. DROPOUT CURRENT and PICKUP CURRENT selectors adjust the thresholds at which motors drop-out and pick-up. The drop-out current range is 50 to 74% of motor FLA and the pick-up current range is 76 to 100% of motor FLA. If all phase-a currents remain below the drop-out current, the current-shed-enabled motors will be sequentially turned off starting with motor 4. The drop-out rate is one motor per 3 minutes. If any phase-a current is more than the pick-up current, motors will be sequentially turned on starting with Motor 1. The pick-up rate is one motor per 10 seconds. At least one MOTOR IN USE must have its SHED switch in the NO position and its REDUCED VOLTAGE RUN potentiometer set to FULL. Setting the REDUCED VOLTAGE RUN switch to NO is equivalent to setting all REDUCED VOLTAGE RUN potentiometers to FULL. 8. REDUCED-VOLTAGE RUN The Load Manager can reduce the steady-state voltage for all motors except one in a multiple-motor drive. A REDUCED VOLTAGE RUN potentiometer for each motor can reduce applied voltage to 45%. The purpose of voltage reduction is to balance motor currents in a multiple-motor drive; however, if motors are lightly loaded, power factor will be low and load sharing will not be effective. If all motors in a multiple-motor drive run below 80% FLA at 100% voltage, there is little benefit in using the REDUCED VOLTAGE RUN controls. For effective load-share operation, the motor chosen to remain at full voltage should be the motor with the lowest running current. Load will shift to this motor as other motors in the drive have their voltages reduced. After a successful start, full voltage will be applied to all selected motors. After 5 seconds, motor voltages will ramp down (at the MINIMUM ACCELERATION TIME rate) to the voltages set by their respective REDUCED VOLTAGE RUN potentiometers.

Page 7 9. TROUBLESHOOTING 9.1 I/O CONTROL The relay-control logic representation of the I/O is shown in Fig. 3. Four normally-open output contacts are provided. Control can be wired using standard mode or legacy mode. Legacy mode is used in applications where the SE-3SCR-LM is used with existing Littelfuse Startco conveyor control or interface modules (MIM). 9.1.1 STANDARD MODE Four relay outputs are available for interface to an external control system as shown in Fig. 3: The Emergency Trip breaker contact (BC) operates in fail-safe (UV) or non-fail-safe (SHUNT) mode. The Full-Conduction contact (FC) closes when full-voltage is applied to the motor. The Trip Contact (TC) opens when a trip occurs or when power is off. The RUN input is ignored when in a trip state. The Run Contact (RC) closes when starting or running. Two inputs are provided for RUN and RESET control. The RUN and RESET inputs (coils) are referenced to the common terminal 241G. Input voltage range is 12 to 24 Vdc. The RUN input must be applied continuously for run operation. Trips are reset using the RESET input. The transition from zero to positive voltage generates the reset signal. If an external 12- to 24-Vdc voltage source is not available, the on-board +12 Vdc source can be used but this requires the installation of a jumper between terminal 200 and 241G. This jumper is also installed when legacy mode is used. 9.1.2 LEGACY MODE To provide compatibility with Littlefuse Startco conveyor-control boards, the Full Conduction (FC) and Trip Contacts (TC) have connections to terminals 202A and 204A. In legacy mode, voltage is sourced from the onboard +12 Vdc supply (terminal 203). This requires a jumper to be installed from the +12 Vdc supply terminal 203 to terminals 202C and 204C. In addition, to enable RUN and RESET control, the ground terminal 200 must be connected to the isolated ground terminal 241G. 9.2 OUTPUT SIGNALS Reference: Fig. 4a, Fig. 4b. CAUTION: Power modules, heat sinks, and motor cables can be energized even if a motor is not running. If a motor is stopped, diodes in the power modules provide half-wave rectification with respect to ground. If a motor is disconnected, current through snubber networks in the power modules is sufficient to be lethal. Use the same precautions and safety procedures for both line-side and load-side measurements and service. The following troubleshooting procedure requires a dc voltmeter. All voltage measurements on the SE-3SCR-LM are with respect to terminal 260. 1. Turn all motor circuit breakers off. 2. To prevent a CURRENT FEEDBACK and EMERGENCY TRIP CIRCUIT TRIP during testing, set the MINIMUM ACCELERATION to 2 seconds. It is recommended to disconnect the motor and to use a 3- wire light bulb load for these tests. However when motors are connected, the gate leads at terminals G and C on the firing card should be removed to prevent SCR gate triggering during the test. 3. Set the top switch in the TACHOMETER FEEDBACK START group to NO, the REDUCED VOLTAGE RUN switch to NO, all MOTORS IN USE switches to YES, all SHED switches to NO, and the MINIMUM ACCELERATION TIME switch to 2 seconds. 4. Turn on circuit breaker to motor 1 to restore zerocrossing signals to the Load Manager. If the light bulb load lights are ON or if motor current is detected go to step 6. Press RESET on the Load Manager. Apply a run signal to terminal 201. The reduced-voltage indication should flash until full voltage is reached. Measure the voltages on terminals 210 to 236. Starting at terminal 211 and working clockwise toward terminal 230, the voltage pattern 12, 2, 0 Vdc should be measured. The voltage at odd-numbered terminals is 12 Vdc, and the voltage at even-numbered terminals is 2 Vdc except for terminals ending with a 0. The voltage at terminals ending with a 0 is 0 Vdc. If this voltage pattern is not observed, remove the output connections and repeat the measurements. If the voltage pattern is correct with outputs disconnected, the Load Manager is not defective and there is a problem with the firing boards or the interconnecting cables. The voltages on even-numbered terminals should be 0 Vdc when the run signal is removed. 5. With the Load Manager in full conduction, input signals to the firing boards should also be 12, 2, and 0 Vdc. When using a light bulb load, intensity should be balanced. If intensity is unbalanced, test or replace the three firing boards. To check a firing board, connect a 1-k resistor between terminals G and C and measure

Page 8 the voltage across the resistor. The voltage should be 6 Vdc when the Load Manager indicates full voltage and 0 Vdc when the Load Manager is off. 6. To check the SCR and the diode, remove the connecting bar on the split heat sink. The diode can be checked by an ohmmeter with a diode-test function and the SCR can be checked with the test circuit shown in Figs. 4a and 4b. 10. TECHNICAL SPECIFICATIONS Supply: 24 Vac (±30%), centre-tapped, 60 Hz, 10 VA Environment: Operating Temperature... -40 C to 60 C Storage Temperature... -55 C to 80 C Output Relays: Trip, Run: Contact Rating... 600 ma Resistive, 120 Vac or 120 Vdc. 2 A Resistive @ 30 Vdc. Contact Configuration... Form A Operating Mode... Fail-Safe Emergency Trip Circuit: Contact Rating... 8 A Resistive, 250 Vac or 30 Vdc Contact Configuration... Form A Operating Mode... Fail-Safe or Non-Fail-Safe Full Conduction: Contact Rating... 8 A Resistive, 250 Vac or 30 Vdc Contact Configuration... Form A Reset Input Voltage (241)... 12 to 24 Vdc with Respect to 241G Run Input Voltage (201)... 12 to 24 Vdc with Respect to 241G Circuit Accuracies: Shed Inputs (261A-261D)... ±4% FLA Current-Feedback Inputs (261-263)... ±4% of Full Scale Tachometer Requirements: Digital: Pulses Per Revolution... 60 Active Pickup Supply Voltage... 12 Vdc Active Input Threshold... 2.5 Vdc Passive Input Threshold... 50 mv Analog: Volts Per 1000 rpm... 100 Vdc

Page 9 NOTES: 1. 201, 241G AND 241 ARE ISOLATED INPUTS. INPUT VOLTAGE RANGE IS 12 TO 24 VDC. 2. TERMINAL 200 IS CIRCUIT GROUND. CONNECT 241G TO 200 TO ENABLE RUN (201) OR RESET (241) CONTROL USING ONBOARD SUPPLY. BC FC TC RC 12V + - RUN NOTE 1 RESET NOTE 2 BC FC TC RC RUN RESET SE-3SCR-LM I/O CONTROL FIGURE 3. I/O Control.

Page 10 FIGURE 4a. Troubleshooting Guide.

Page 11 FIGURE 4b. Troubleshooting Guide.

Page 12 This page left intentionally blank.