Oil/Air Cooler Units. Compact application with AC Motor OK-ELC Type

Similar documents
Oil/Air Cooler Units. Compact application with AC Motor OK-ELC Type. Test procedure certified following EN 1048

Oil/Air Cooler Units. Mobile series with DC motor OK-ELD Type. Test procedure certified following EN 1048

Oil/Air Cooler Units. Mobile application and Hydraulic motor OK ELH Type. Test procedure certified following EN 1048

Oil/Air Cooler Units. Standard series OK-P type. Test procedure certified following EN

Oil/Air Cooler Units. Standard series EL Type. Test procedure certified following EN 1048

Oil/Air Cooler Units

Air Cooler Mobile OK-ELD 0-6 with DC motor

Air Cooler Industry AC-LN 8-14 / ACA-LN 8-11 / ACAF-LN 8-11

Cooling Systems FLKS - 3S/1.0/W... FLKS - 3L/1.0/W DESCRIPTION

Coolers. OK Series. Air Cooled Oil Coolers Hydraulic Symbol OK 1-11 OKF Cooling Systems Catalog. Applications

Cooling Systems Air Cooled / Liquid Cooled

Air Cooler Mobile AC-LNH 8-14 with hydraulic motor

Coolers. Air Cooled / Liquid Cooled

Feed Pumps Direct Drive Series 1.1.

Oil/air cooler BLK. Fluidcontrol

ELD Series - DC Motor Drive

MINI POWER PACKS WITH SUBMERSED MOTOR AND PUMP

ELH Series - Hydraulic Fan Drive

ELD Series - DC Motor Drive

Oil/Air Cooler Units Standard series - Accessories

Oil/air cooler BLK. Fluidcontrol

Oil/air coolers. Table of contents. Features. Possible applications. RE 50111/12.06 Replaces: Types KOL and KOLP

Vane pumps, direct controlled Type PV7...A

Circulation pumps BFP-ATEX-T3/T4

Filter cooler unit with inline filter according to DIN Type ABUKG. Contents. Features. RE Edition: Replaces: 50126

Hydraulic primary unit Type ABPAG

HEAT EXCHANGERS AIR/OIL TYPE LAC. - ATEX Version. Approved for applications where there may be an explosive environment above ground.

Oil/air cooler BLK ATEX-3GD

Off-line filter / cooler unit FGSL

Feed Pumps Direct Drive Series 1.1.

UD and UC Gear pump unit

Variable Vane Pump, Direct Controlled PV7...A Series 1X / 2X

Filter-cooler circulation circuit with in-line filter according to DIN 24550

Oil / air cooler Series BLK-DC

A-L O C COOLING SYSTEM OLAER COOLERS. Olaer A-LOC with integrated circulation pump for industrial hydraulic systems

Feed Pumps VP / VPB / VPBM

Drive module. Table of contents. Features. Applications. RE 51145/06.12 Replaces: Type UPE 5

NCF fans 60Hz. Protection class IP 55

GMP-Type. Key Features: Integrated Motor-Pump Units

HYDAC nitrogen charging units facilitate fast and cost effective filling or topping up of the required gas pre charge pressure in bladder, diaphragm

HYDAC (Three-Phase Current) Compact Power Units CO1

RA / Internal Gear Pump Model GP3, Series 3X Fixed Displacement. Typical application:

Industrial Diesel Generator Set KD1100-F 50 Hz Fuel Consumption Optimized

Industrial Diesel Generator Set KD2500-F 50 Hz Fuel Consumption Optimized

Clamping and drive module

IGP /117 ED INTERNAL GEAR PUMPS SERIES 10 OPERATING PRINCIPLE TECHNICAL SPECIFICATIONS HYDRAULIC SYMBOL

PUMP SIZE Flow rate at 1500 rpm lt/min Operating pressures bar

Proportional Pressure Reducing Valve PDM08130

Radial piston pump, fixed displacement

V.I.R.T.U.O. Ventilation boxes. Comfort ventilation boxes

Industrial Diesel Generator Set KD1650-E 50 Hz - Emission Optimized EPA Tier 2 Compliant

NCF 60 Hz. Protection class IP 55

RA / Internal Gear Pump Model GP2, Series 2X Fixed Displacement. Typical application:

IPVP High-pressure Internal Gear Pumps for Variable Speed Drives

IE3. Motor-pump groups. Type ABAPG and ABHPG. Features. Contents. RE Edition:

SLH 1202 to Air-to-Water Reverse Cycle Heat Pumps. With Screw Compressors. 261 to 775 kw. 287 to 853 kw

Versatility. Features. By installing the SILENT MV, you will never experience the disturbance of noisy ventilation again. Benefits

Hydraulic drive power unit Low-noise compact unit Whispering power unit

Radial piston pump PR4 Series 1X

Cooling Systems CC Series TT rail 20/30lpm

A E R Z E N S C R E W C O M P R E S S O R S

KE-M02 configuration Configuratie documentatie documentation KE-M02

NCF fans 50 Hz. Protection class IP 55

OFFLINE SERIES GLOBAL STANDARD COOLER

Off-line filter / cooler unit BKF

Company name: GRUDNFOS VisMin Created by: Kimmboy Ancis Phone: Date: 13/03/2017

FNA 008 FNA 016 Operating pressure up to 4 bar / 58 psi Nominal flow rate up to 16 l/min / 4.2 gpm

SINGLE STAGE TWO STAGES

SILENT MV Ultra Quiet In-line Fans

Plate mounted axial flow fans HXBR / HXTR Series

6.3 SIZE 2. Ordering Code External Gear Pump

CM5-5 A-R-A-E-AVBE F-A-A-N

VLH 504 to Air-to-Water Reverse Cycle Heat Pumps. 126 to 294 kw. 133 to 307 kw

Vane pump, direct operated

Heat Exchangers. Evaporator Catalogue

Radial piston pump PR4 series 1X

A-L A C AIR OIL COOLER LUFT/ÖL-KÜHLER OLAER COOLERS. Olaer A-LAC with A.C. motors for industrial hydraulic systems

HXBR / HXTR Series PLATE MOUNTED SICKLE BLADE AXIAL FANS WITH EXTERNAL ROTOR MOTOR. Plate mounted axial flow fans HXBR/HXTR. Corrosion resistance

CONVETT OIL - AIR COOLERS

Operating voltage 120, 230 V AC Air volume 24 m³/h (14.1 CFM) Rated power 13 W Size 1

PLATE MOUNTED SICKLE BLADE AXIAL FANS WITH EXTERNAL ROTOR MOTOR HXBR / HXTR Series. Plate mounted axial flow fans HXBR/HXTR. Corrosion resistance

Industrial Diesel Generator Set KD1250-UE 60 Hz - Emission Optimized EPA Tier 2 Certified

Extremely compact in size to allow direct flange-mounting on vehicle engine or gearbox PTOs.

@Perkins. Technical Data Series 1104C-44TAG1. Diesel Engine ElectropaK. 79, rev/min 88, rev/min. Basic technical data

Motor-pump group. Features. Table of contents RE 51171/ Type ABAPG and ABHPG

PVE /117 ED VARIABLE DISPLACEMENT VANE PUMPS WITH DIRECT PRESSURE ADJUSTMENT SERIES 30 OPERATING PRINCIPLE TECHNICAL SPECIFICATIONS

FA 016 FAPC 016. Oil Service Units. Description. Page 53

FNA 045 Operating pressure up to 7 bar / 101 psi Nominal flow rate up to 45 l/min / 12 gpm

Off-Line Filter BNF. FluidControl

IPVP High-pressure Internal Gear Pumps for Variable Speed Drives Technical Data Sheet

Axial Piston Fixed Pump A17FNO

Pressure Compensated Flow Control Valves SRVR/SRVRP

IPVS High-pressure Internal Gear Pumps Technical Data Sheet

Industrial Diesel Generator Set KD2250-F 50 Hz Fuel Consumption Optimized

CM1-6 A-R-I-E-AQQE F-A-A-N

Industrial Diesel Generator Set KD1750-UF 60 Hz Fuel Consumption Optimized

CM10-3 A-R-A-E-AVBE F-A-A-N

COMFORT AIR CURTAIN. SensAir

Industrial Diesel Generator Set KD1100-F 50 Hz Fuel Consumption Optimized

Voltage 400V 3N 50Hz. L W H Weight Fans Surface. Air Flow [m 3 /h] Primary [m 2 ] Ø [mm]

Transcription:

COMPACT OIL / AIR COOLERS NEW COMPACT DESIGN WITH AC ELECTRIC FANS AND HIGH COOLING PERFORMANCE Application These coolers are designed specifically for hydraulic applications where high performance and efficiency are required and physical size is minimised to allow easy installation. Typical applications include: industrial power units, lubrication systems (i.e. gearboxes) and machine tools. Oil/Air Cooler Units Compact application with AC Motor OK-ELC Type OK-ELC Product Features These coolers use a combination of high performance cooling elements and high capacity, compact AC electrically powered fans to give long trouble-free operation in arduous hydraulic applications. The compact design allows the coolers to fit most equipment and provide the highest cooling performance in heat dissipation whilst minimising the space required. Cooling range 1-34 kw AC motors in 230/400 Volt 50/60 Hz Hydraulic pressure 16 bar dynamic

OIL/AIR COOLER DESCRIPTION GENERAL In hydraulic systems energy is transformed and transmitted. During this transformation and transmission losses occur, i.e. mechanical and hydraulic energy is converted into heat. It is the function of the cooler to dissipate this heat. ELC 0 ELC 0 2 PASS ADVANTAGES OF THE OIL/AIR COOLERS: Environmentally friendly. No exchange between water and oil possible For commissioning only electrical energy is required Low operating costs, no additional cooling circuit necessary for the cooling medium, i.e. air ELC 1 ELC 1 CONSTRUCTION Oil/air cooler units consists of the (1) heat exchanger, (2) housing (3) axial motor fan. The oil connections are on the rear side. ELC 2-5 ELC 2-5 ELC 6-7 ELC 6-7 2

COOLER SELECTION Designation: = Power loss [kw] = Specific cooling capacity [kw/ C] V = Tank contents [l] ρ oil = Density of the oil [kg/l] for mineral oil: 0.915 kg/l C oil = Specific heat capacity [kj/kgk] for mineral oil 1.88 kj/kgk T = Temperature increase in the system [ C] t = Operating time [min] T 1 = Desired oil temperature [ C] T 3 = Ambient temperature [ C] Example 1: Measurement of the power loss on existing units and machinery. For this method the temperature increase of the oil is measured over a certain period. The power loss can be calculated from the temperature increase. Parameters: The oil temperature increases from 20 C to 45 C over 15 minutes. The tank contains 100 l. Heat to be dissipated: = T c ρ V oil oil [kw] t 60 = 25 1.88 0.915 100 = 4.78 [kw] 15 60 Cooler selection: Desired oil temperature: 60 C Ambient temperature air: 30 C = T 1 - T 3 [kw/ C] = 4.78 = 0.159 [kw/ C] 60-30 A 10% safety margin is recommended to allow for element contamination, and therefore the specific power is: 1.1 = 0.175 kw/ C. The power loss 0.175 kw/ C must be dissipated by an oil cooler. Suggestion: Cooler OK-ELC3H, = 0.2 kw/ C at 40 l/min Example 2: The power loss can also be estimated. With unrestricted flow approx. 15 to 20% of the drive power. With restricted flow up to 30% of the drive power. 1. TECHNICAL DETAILS 1.1. TABLE OF TECHNICAL SPECIFICATIONS Type of cooler Voltage [V] Oil flow at 1.5 bar pressure drop [l/min] N of poles Motor capacity at 50Hz [W] Speed at 50 Hz [rpm] ELC0: the electrical connection wires are provided ELC1-7: the electrical connection box is included Capacitor is supplied with the cooler and mounted in the connection box when required All motors with IP55 have protection class F, except ELC0 with IP20 Mounting position: all positions possible For direction of rotation see arrow on cooler housing Cooling fluid Mineral oil to DIN 51524 For other fluids, please contact our sales/technical department The noise levels are only a guide as acoustic properties vary and depend on the characteristics of the room, connections, viscosity and resonance. Options: see accessory catalogue Capacitor [µf/vdb] ELC0H 230 30 2 35 2800 20 59 16 130 2000 3.2 ELC1H 230 110 2 120 2700 2/450 55 71 16 130 2000 9 ELC1H 400 110 2 115 2600 2/500 55 71 16 130 2000 9 ELC2H 230 150 2 120 2700 2/450 55 75 16 130 2000 11.9 ELC2H 400 150 2 140 2500 2/500 55 75 16 130 2000 11.9 ELC3H 230 160 2 170 2500 4/450 55 75 16 130 2000 14.7 ELC3H 400 160 2 188 2320 3/500 55 75 16 130 2000 14.7 ELC4S 230 170 4 210 1400 4/450 55 69 16 130 2000 21 ELC4S 400 170 4 230 1380 55 69 16 130 2000 21 ELC5S 230 250 4 210 1400 4/450 55 70 16 130 2000 28 ELC5S 400 250 4 230 1380 55 70 16 130 2000 28 ELC6H 230 120 2 2x170 2500 2x4/450 55 73 16 130 2000 39 ELC6H 400 120 2 2x188 2320 2x3/500 55 73 16 130 2000 39 ELC7S 230 120 4 2x210 1400 2x4/450 55 72 16 130 2000 45 ELC7S 400 120 4 2x230 1380 55 72 16 130 2000 45 Protection class IP [-] Noise level [db(a)] (at 1m distance) Max. operating pressure [bar] Max. oil temperature [ C] Max. viscosity [mm²/s] Weight [kg] 3

1.2. HYDRAULIC DETAILS 1.2.1 Cooling capacity depending on oil flow and the temperature differential T between the oil inlet and air inlet. For calculations with low T values (i.e. below 10 C), please contact our technical support staff. Tolerance: ± 5% Heat dissipation at T = 40 C [kw] 32 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 0 ELC 0H ELC 1H ELC 4S ELC 3H ELC 2H 0 50 100 150 200 250 300 350 Oil flow [l/min] ELC 7S ELC 6H ELC 5S 0,8 0.8 0,7 0.7 0,6 0.6 0,5 0.5 0,4 0.4 0,3 0.3 0,2 0.2 0,1 0.1 0.0 Specific heat dissipation [kw/ C] * * Values measured at T = 40 C, may vary at lower T values 1.2.2 Pressure differential p measured at 30 mm²/s using mineral oil Tolerance: ± 5% Pressure drop at 30 mm²/s [bar] 3,6 3.6 3,4 3.4 ELC 7S 3,2 3.2 3,0 3.0 ELC 0H ELC 6H 2,8 2.8 2,6 2.6 ELC 1H 2,4 2.4 2,2 2.2 ELC 5S 2,0 ELC 2H 2.0 1,8 1.8 ELC 3H 1,6 1.6 1,4 1.4 ELC 4S 1,2 1.2 1,0 1.0 0,8 0.8 0,6 0.6 0,4 0.4 0,2 0.2 0,0 0.0 0 0 50 100 150 200 250 300 350 Oil flow [l/min] 2,2 For other viscosities the result must be multiplied by K Viscosity (mm 2 /s) 10 15 22 32 46 68 100 150 Factor K 0.5 0.65 0.77 1 1.3 1.9 2.8 5.3 4

2. MODEL TYPE (also order example) OK-ELC2H / 1.0 / 230V / 1 / S / AITF50 Type of cooler OK-ELC = Oil/air cooler Size / motor speed 0:7 = See hydraulic details 1.2 H = 3000 min -1 S = 1500 min -1 Type code and modification number Electrical motor fan voltage 230V = 230 Volts 50/60 Hz - 1PH 400V = 400 Volts 50/60 Hz - 3PH Paint 1 = RAL 9005 (Standard) Other paint on request and clearly written Air flow direction S = Suction (Standard) Accessories (for more information see accessories brochure ) AITF50 = Thermostat (fixed) LFM = Air filter on the air suction (Note: with clean filter the cooling power decreases by ~8%) LFG = Air filter grid on the air suction (Note: with clean filter the cooling power decreases by ~5%) GP = Vibration absorber 5

3. DIMENSIONS 3.1. ELC0 A1 B C1 C2 D1 D2 D3 E1 E2 W1 W2 Z1 F ±5 ±10 ±4 ±4 ±1 ±2 ±2 ±2 ±5 min min 4xØ ELC0 201 138 240 220 60 190 80 72 79 150 50 G1/2" 6.5 3.2. ELC1 PLUG A1 B C1 D1 D2 D3 D4 E1 E2 E3 W1 W2 Z1 F Plug ±5 ±10 ±8 ±2 ±2 ±2 ±2 ±5 ±5 ±5 min min 6xØ ELC1 300 205 340 110 270 136 50 200 65 300 200 70 G3/4" 8.5 M22X1.5 6

3.3. ELC2-5 PLUG A1 B C1 D1 D2 D3 E1 E2 E3 E4 E5 W1 W2 Z1 F Plug ±5 ±10 ±5 ±2 ±2 ±2 ±5 ±5 ±5 ±2 ±2 min min 4xØ ELC2 328 290 384 255 160 295 199 72 324 288 80 250 150 G1" 9 M22X1.5 ELC3 371 287 420 255 240 295 230 78 370 329 100 300 180 G1" 9 M22X1.5 ELC4 465 292 500 255 255 295 289 95 450 421 150 400 200 G1" 9 M22X1.5 ELC5 475 306 602 255 255 295 350 70 490 200* 580* 400 250 G1 1/4" 9 M22X1.5 * : ELC5 has the front fixing holes in the lateral sides. 3.4. ELC6-7 PLUG A1 B C1 D1 D2 D3 E1 E2 E3 E4 E5 W1 W2 Z1 F Plug ±5 ±10 ±8 ±2 ±2 ±2 ±5 ±5 ±5 ±2 ±2 min min 4xØ ELC6 492 285 810 255 482 295 321 93 750 450 170 400 200 G1 ¼" 9 M22X1.5 ELC7 545 289 950 255 482 295 373 93 890 500 200 500 250 G1 ¼" 9 M22X1.5 4. NOTE The information in this brochure relates to the operating conditions and applications described. For applications or operating conditions not described, please contact the relevant technical department. Subject to technical modifications. 7