Series 009. Reduced Pressure Zone Assemblies. Installation Service Repair Kits Maintenance. Sizes: 8 80mm. 80mm 009LF RP/IS-009-AUS

Similar documents
Series 867 Reduced Pressure Zone Assemblies

Installation, Maintenance, & Repair Series 995 Reduced Pressure Zone Backflow Preventers

THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT.

Series 007. Double Check Valve Assembly. Installation Service Repair Kits Maintenance. Sizes: 1 2" 3" Watts 3 4" 007M3QT RP/IS-007

Series 957, 957N, 957Z, 957RPDA, 957NRPDA, 957ZRPDA

Series 990/990RPDA. Reduced Pressure Zone Backflow Preventer. Sizes: 4", 6", 8" (100mm, 150mm, 200mm)

THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT.

Installation, Maintenance, & Repair Series 919 and LF919

Installation Service Repair Kits Maintenance RP/IS-774/774DCDA/774X/774XDCDA

Colt Series C400, C500

4000SS. For other repair kits and service parts, send for Ames Repair Parts Price List, PL-A-RP-BPD.

Installation, Maintenance, & Repair Series 4000CIV

Series 995/995RPDA. Sizes: 3" - 6" Reduced Pressure Zone Backflow Preventer/ Reduced Pressure Detector Assemblies RP/IS-995/995RPDA

Watts Series CSM-61. Flow Measurement/Balancing Valves Sizes: 1 1 4", 1 1 2", 2", 2 1 2", and 3" (32, 40, 50, 65 and 80mm) Installation Instructions

THIS WARRANTY IS IN LIEU

Installation, Maintenance, & Repair Series 909, LF909, 909RPDA, LF909RPDA Reduced Pressure Zone Assemblies Reduced Pressure Detector Assemblies

Watts Series CSM-91. Grooved/Flanged Flow Measurement/Balancing Valves. Installation and Operating Instructions. Table of Contents. 1.

Maintenance Manual Double Check and Double Check Detector Assemblies Series 850, 856, 870V & 876V 2 1 /2" - 10" (65 250mm)

Digital Print-out Test Kit for Backflow Preventer Assemblies

TERMS OF USE TERMS AND CONDITIONS. Plumbing and Heating Products (PL-WR)

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual

AMES 2015 Price List. Backflow Prevention Repair Kits and Parts. Effective March 30, Includes Our. Product Offering.

INSTALLATION & MAINTENANCE MODEL mm

FLOOD PROTECTION SHUT DOWN VALVE (3 and smaller)

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Installation Instructions

Maintenance Manual Reduced Pressure Assembly Models 860 & 880V 2 1 /2" 10"

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve

Cash-Flo. Operation & Maintenance Manual. BackFLOW PREVENTERS. A Division of the Reliance Worldwide Corporation

Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.

AMES 2016 Price List. Backflow Prevention Products and Repair Kits and Parts. Effective February 29, 2016

Price List. Backfl ow Prevention Products, Repair Kits, and Parts. Effective July 2, AmesFireWater.com 2018 AMES FIRE & WATERWORKS PRICE LIST

DC-501 Double Check Backflow Preventer OPERATIONS, MAINTENANCE AND TROUBLESHOOTING GUIDE

2 ½ 12. Installation, Operation, and Maintenance Manual. Reduced Pressure Principle Backflow Preventer. Reduced Pressure Detector Assembly

Sanitary Yard Hydrant Installation Instructions

Sanitary Roof Hydrant Installation Instructions

2 ½ 12. Model RP 4A Model RPDA 4A Model RPDA2 4A. Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Series LFF113FP Wireless Smart Universal Flood Protection ACV System with SentryPlus Alert Technology

LEAD FREE * LFF115 (Globe) LFF1115 (Angle)

APCO CRF-100A RUBBER FLAPPER SWING CHECK VALVES

LEAD FREE * LFM115 (Globe) LFM1115 (Angle)

INSTALLATION INSTRUCTIONS. Automatic Sensor Retrofit Kit For Urinals and Toilets ZERK-CP Chrome-Plated Cover ZERK-CPM Chrome-Plated Metal Cover

300 Series INSTRUCTION MANUAL. Compressed Air Filters Models 302 (grade) through 317 (grade)

RSV16 Retro-Fit Cartridge Acorn Controls SV16 Valve Cartridge

FOR TECHNICAL ASSISTANCE

FOR TECHNICAL ASSISTANCE

Backflow Irrigation Control Station BIC-1000

TBM Series 3-Way Ball Valve

JET METER INSTRUCTIONS

APCO ASR-400/450 SEWAGE AIR RELEASE VALVES

MODEL 106/206-PG POWER OPERATED GLOBE VALVE Sizes 1/2" to 8" (106-PG) 3" to 10" (206-PG) Installation, Operating and Maintenance Instructions

Pump/Manifold Kits. Instructions F ENG. To convert E-Flo 4-Ball Piston Pumps to a different size lower. For professional use only.

MAINTENANCE MANUAL. Covering Models: Series (1/4-10 ) S Series (1/4-1 ) Series (3-10 )

LEAD FREE * LFF113FP. Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology. Materials NOTICE NOTICE ES--LFF113FP

Operations Manual. and. Seal Kit Replacement Guide

HALLMARK INDUSTRIES INC

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators

DeZURIK AFR3 Filter Regulator Used on Pneumatic Cylinder Actuators

LEAD FREE * LFF113RFP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology

PRESSURE REDUCING CONTROL VALVE

LEAD FREE * PVS-7000 Engineered Flood Protection Valve Station with SentryPlus Alert

Installation, Maintenance, & Repair Series 994/994RPDA Reduced Pressure Zone Assemblies Reduced Pressure Detector Assemblies

Operating Instructions & Parts Manual. Supa-Lite Lever Grease Gun. Model 48UJ77

Air Control Kit INSTRUCTIONS-PARTS LIST. Table of Contents HIGH VOLUME. 250 psi (1.7 MPa, 17.2 bar) Maximum Air Inlet Pressure

CV Control Valves Installation and Operation Manual

Stainless Steel Air Motor Conversion Kits

Price List. Backflow Prevention Products and Repair Kits. Effective Date October 30, FEBCOonline.com 2017 FEBCO PRICE LIST

AMES 2013 Price List. Backflow Prevention Products. Effective April 1, 2013

Price List. Backflow Prevention Products and Repair Kits. Effective Date July 2, FEBCOonline.com 2018 FEBCO PRICE LIST

Stainless Steel Air Motor Conversion Kits

NYLON & PVC VALVES MINING DIVISION PRESSURE REDUCING VALVES ENSURE DOWNSTREAM PRESSURE PVC NYLON

Heater Manifold REPLACEMENT INSTRUCTIONS. Sta-Rite Pool/Spa Group. 293 Wright Street, Delavan, WI 53115

Mustang Series PRESSURE REDUCING CONTROL VALVE. M115 (Globe) M1115 (Angle) Schematic. Standard Components. Options & Accessories.

Dual/Triple Manifold Water Filtration Systems Instruction Manual

DeZURIK 2 20" BOS BUTTERFLY VALVES

AquaSense TM ZTS6200EV Series

PRESSURE REDUCING VALVE

PRESSURE REDUCING VALVE

Welker Sampler. Installation, Operation, & Maintenance Manual. Model GSS-4HP

PRESSURE REDUCING VALVE

15H882 Slider Bearing Kit

Purging Air From Divider Block Lubrication Systems

FIXED DEPTH INSERTION METER INSTRUCTIONS

INSTALLATION & SERVICE INSTRUCTION MANUAL W.A. KATES FLOW CONTROLLERS FC VALVE MODELS E THRU M

Air Control Kits INSTRUCTIONS-PARTS LIST. Table of Contents HIGH VOLUME. 250 psi (1.7 MPa, 17.2 bar) Maximum Air Inlet Pressure

VELAN TRUNNION-MOUNTED

MGFHVLP. Instructions/Parts. Mini Gravity Feed System E. Part No Includes MGFHVLP Mini Gravity Feed Spray Gun and MGC 125 Gravity Cup.

Installation Manual DIAPHRAGM WELL TANK

MODEL 900 IMPELLER-TYPE FLOW METER

BFMM DC4A SBF EFFECTIVE AUGUST 1, 2016

SLR / SLR-S/N. Instruction Manual. Walrus America Inc

TITAN FLOW CONTROL, INC.

Figure DC03. Double check valves for medium hazard rated applications BSP screwed connections. Features

Aquaflush. Z6100 Series Aquaflush Concealed Flushometer Installation, Operation, Maintenance, and Parts Manual Z6140

Hydraulic Transmission Jacks

SERIES G3DB/AG3DB ELEVATOR

INSTRUCTIONS AND SERVICE MANUAL WITH PARTS LIST

ESE Series Cast Iron Sewage Pumps

Manual Concentrate Management System

Transcription:

Series 009 Reduced Pressure Zone Assemblies RP/IS-009-AUS Sizes: 8 80mm Installation Service Repair Kits Maintenance For other repair kits and service parts, send for PL-RP-BPD. For technical assistance, contact your local Watts representative. 80mm 009LF IMPORTANT: Inquire with governing authorities for local installation requirements. NOTE: For Australia and New Zealand: Pipeline strainers should be installed between the upstream shutoff valve and the inlet of the backflow preventer. Its important that this assembly be tested periodically in compliance with local codes, but at least once per year or more as service conditions warrant. If installed on a fire sprinkler system, all mechanical checks, such as alarm checks and backflow preventers, should be flow tested and inspected internally in accordance with NFPA 13 and NFPA 25. Limited Warranty: Watts Regulator Company warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge. This shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no control. This warranty shall be invalidated by any abuse, misuse, misapplication or improper installation of the product. THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED WAR- RANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Any implied warranties that are imposed by law are limited in duration to one year. Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to determine your rights.

Installation Instructions Indoors Figure 1 Figure 1 For indoor installations, it is important that the assembly be easily accessible to facilitate testing and servicing. If it is located in a line close to a wall, be sure the test cocks are easily accessible. A drain line and air gap (see literature ES-AG/EL/TC) should be piped from the relief valve connection as shown, where evidence of discharge will be clearly visible and so that water damage will not occur. Therefore, never install in concealed locations. Main Strainer 009 Air Gap Outside Figure 2 Meter 300mm In an area where freezing conditions do not occur, Series 009 can be installed outside. The most satisfactory installation is above ground and should be installed in this manner whenever possible. In an area where freezing conditions can occur, Series 009 should be installed above ground in an insulated enclosure. Series 009 must be installed in an accessible location to facilitate testing and servicing. A discharge line should be piped from the air gap at the relief valve connection making sure that there is adequate drainage. Never pipe the discharge line directly into a drainage ditch, sewer or sump. Series 009 should never be installed where any part of the unit could become submerged in standing water. Figure 2 009 It is generally recommended that backflow preventers never be placed in pits unless absolutely necessary and then only when approved by local codes. In such cases, a modified pit installation is preferred. 300mm Annual inspection of all water system safety and control valves is required and necessary. Regular inspection, testing and cleaning assures maximum life and proper product function. WattsBox 8 50mm 009 2

Installation Instructions A. The 009 should always be installed in an accessible location to facilitate testing and servicing (See page 2). Check the state and local codes to ensure that the backflow preventer is installed in compliance, such as the proper height above the ground. B. We recommend a strainer be installed ahead of 009 series assemblies to protect the internal components from unnecessary fouling. Caution: Do not install with strainer when backflow preventer is used on seldom-used water lines which are called upon only during emergencies, such as fire sprinkler lines. Start Up: The downstream isolation valve should be closed. Open upstream isolation valve slowly and fill valve. When valve is filled, open the downstream isolation valve shutoff slowly and fill the water supply system. This is necessary to avoid water hammer or shock damage. C. Water discharge from the relief valve should be vented in accordance with code requirements. The relief valve should never be solidly piped into a drainage ditch, sewer or sump. The discharge should be terminated approximately 300mm above the ground or through an air gap piped to a floor drain. NOTE: Discharge Rates The installation of an air gap with the drain line terminating above a floor drain will handle any normal discharge or nuisance spitting through the relief valve. However, floor drain size may need to be designed to prevent water damage caused by a catastrophic failure condition. Please refer to Figure No. 1 for maximum relief valve discharge rates, size and capacity of typical floor drains. NOTE: Do not reduce the size of the drain line from the air gap fitting. Pipe full line size. D. After initial installation, a discharge from the relief valve opening may occur due to inadequate initial flushing of pipe lines to eliminate dirt and pipe compounds. If flushing will not clear, remove the first check valve and clean thoroughly. NOTE: Periodic relief valve discharge may occur on dead end service applications, such as boiler feed lines or cooling tower makeup lines due to fluctuating supply pressure during a static or no flow condition. To avoid this discharge, install a spring-loaded rubber seated check valve ahead of the backflow assembly to lock-in the downstream pressure. E. Backflow preventers should never be placed in pits unless absolutely necessary and then only when and as approved by local codes. In such cases, provision should be made to always vent above flood level or for a pit drain to ensure an adequate air gap below the relief port. F. It is important that Series 009 backflow preventers be inspected periodically for any discharge from the relief valve which will provide a visual indication of need for cleaning or repair of check valves. Also testing for proper operation of the device should be made periodically in compliance with local codes, but at least once a year or more often, depending upon system conditions. Relief vent will discharge water when, during no-flow periods, (1) the first check valve is fouled or (2) the inlet pressure to the device drops sufficiently due to upstream pressure fluctuations to affect the required operating differential between the inlet pressure and reduced pressure zone. Other wise, such relief (spitting) can occur when the second check is fouled during emergency backflow or resulting from a water hammer condition. For troubleshooting guide send for S-TSG. NOTE: Special considerations are necessary when testing assemblies installed on Fire Prevention Systems. Fire Protection System Installations: The National Fire protection Agency (NFPA) Guidelines require a confirming flow test be conducted whenever a main line valve such as the shutoff valves or a backflow assembly have been operated. Certified testers of backflow assemblies must conduct this confirming test. Figure 1 Discharge Rates 15 25mm 009 171 152 133 114 95 76 57 38 19 0 0 69 138 207 276 345 414 483 552 621 689 1034 Zone Pressure kpa 15mm 20mm X 25mm Flow Rate lpm Flow Rate lpm 1330 1140 950 760 570 380 190 32 80mm 009 0 69 138 207 276 345 414 483 552 621 689 1034 Zone Pressure kpa 32 40mm 50mm TYPICAL FLOW RATES AS SIZED BY FLOOR DRAIN MANUFACTURERS: mm LPM mm LPM 50 208 125 1325 80 303 150 1703 100 644 200 2877 3

Servicing the 8 50mm 1. Remove the relief valve cover bolts while holding the cover down. 2. Lift the cover straight off. The stem and diaphragm assembly will normally remain with the cover as it is removed. The relief valve spring will be free inside the body at this point. 3. The relief valve seat is located at the bottom of the body bore, and can be removed, if necessary, for cleaning. The disc can be cleaned without disassembly or the relief valve module. If it is determined that the relief valve diaphragm and/or disc should be replaced, the relief valve module can be readily disassembled without the use of special tools. Note: the disc rubber is molded into the disc holder and is supplied as a disc holder assembly. 4. To re-assemble the relief valve, press the seat firmly into place in the body, center the spring on the seat, and insert the cover and relief valve module as a unit straight into the bore. Press down on the cover to assure proper alignment. Insert and tighten bolts. Caution: If cover will not press flat against body, stem assembly is crooked and damage can result. Re-align stem and cover before bolts are inserted. 4 Test Cock No.1 First Check Module Service Parts Kit Test Cock No.2 Water Outlet Cover Cover O-ring Diaphragm Test Cock No.3 Stem & Diaphragm Retainer O-ring Body Second Check Module Repair Kits 8 50mm When ordering, specify Ordering Code, Kit number and Valve Size. 8 25mm Kits: 0887294 RK 009 VT 8, 10, 15 0887509 RK SS009 VT 15 0887002 RK 009M2 VT 20 0887520 RK SS009M2/M3 VT 8, 20 0888524 RK 009M3 VT 20 0887015 RK 009 VT 20, 25 0887503 RK SS009 VT 25 0887785 RK 009M2 VT 25 Kit consists of:, O-ring, Stem & diaphragm assembly, Stem O-ring, Cover O- ring and RV spring. Rubber Parts Kits: 0887295 RK 009 RV 8, 10, 15 0887510 RK SS009 RV 15 0886998 RK 009M2 RV 20 0887519 RK SS009M2/M3 RV 8, 20 0888523 RK 009M3 RV 20 0887181 RK 009 RV 20, 25 0887529 RK SS009 RV 25 0887786 RK 009M2 RV 25 Kit consists of: Diaphragm, Disc assembly, Stem O-rings, O-ring and Cover O-ring. Total Rubber Parts Kits: 0887297 RK 009 RT 8, 10, 15 0887511 RK SS009 RT 15 0886999 RK 009M2 RT 20 0887521 RK SS009M2 RT 20 0888526 RK 009M3 RT 20 0888597 RK SS009M3 RT 8, 20 0887182 RK 009 RT 20, 25 0887530 RK SS009 RT 25 0887787 RK 009M2 RT 25 Kit consists of: Diaphragm, Two discs, Two disc assemblies, Stem O-rings, Cover O- ring, Two seat O-rings and RV seat O-ring. Cover Kits: 0887296 RK 009 C 8, 10, 15 0887500 RK SS009 C 15 0887004 RK 009M2 C 20 0887501 RK SS009M2/M3 C 8 20 0888525 RK 009M3 C 20 0887013 RK 009 C 20 25 0887502 RK SS009 C 25 0887788 RK 009M2 C 25 Kit consists of: Cover and Cover O-ring. 32 50mm Total Kit: 0887307 RK 009M2 VT 32 40 0887277 RK 009M1 VT 32 50 0887016 RK 009 VT 32 50 0887545 RK 009M2 VT 50 Kit consists of: RV assembly,, O-ring, Cover O-ring, Sensing passage O-ring and Upper stem O-ring. Rubber Parts Kit: 0887306 RK 009M2 RV 32 40 0887276 RK 009M1 RV 32 50 0887184 RK 009 RV 32 50 0887544 RK 009M2 RV 50 Kit consists of: Diaphragm, O-ring, Cover O-ring and Sensing passage O-ring. Complete Rubber Parts Kit: 0887309 RK 009M2 RT 32 40 0887280 RK 009M1 RT 32 50 0887185 RK 009 RT 32 50 0887547 RK 009M2 RT 50 Kit consists of: Two check assembly O-rings, Two disc assemblies, One cover O-ring, One RV diaphragm, One RV seat O-ring, One sensing passage O-ring, One diaphragm plate O-ring, One RV lower stem O-ring, One RV upper stem O-ring, One RV disc assembly and One bleed screw O-ring. Cover Kit: 0887308 RK 009M2 C 32 40 0887278 RK 009M1 C 32 50 0887014 RK 009 C 32 50 0887546 RK 009M2 C 50 Kit consists of: Cover, Cover O-ring, Sensing passage O-ring, Bleed screw O-ring, Vent hood and Bleed screw. For additional information, contact your local technical sales representative, see back page.

Servicing First & Second Check Valves 8 50mm 8 25mm First Check Kits: 0887291 RK 009 CK1 8, 10, 15 1. Remove the retainer from the body bore. The check valve 0887505 RK SS009 CK1 15 modules can now be removed from the valve by hand or 0887000 RK 009M2 CK1 20 with a screwdriver. Note: The seats and springs of the first 0887515 RK SS009M2/M3 CK1 8 20 0888520 RK 009M3 CK1 20 and second check modules are not interchangeable. The 0887005 RK 009 CK1 20 25 heavier spring and smaller diameter seat belong with the first 0887009 RK 009 CK1SS 20 25 check module. 0887525 RK SS009 CK1 25 0887789 RK 009M2 CK1 25 2. The check seats are attached to the cage with a bayonet Kit consists of: Check assembly and Cover O-ring. type locking arrangement. Holding the cage in one hand, Second Check Kits: push the seat inward and rotate clockwise against the cage. 0887292 RK 009 CK2 8, 10, 15 The seat, spring cage, spring and disc assembly are now individual components. 0887516 RK SS009M2/M3 CK2 8 20 0887506 RK SS009 CK2 15 0887001 RK 009M2 CK2 20 Note: 20mm M2 modules snap apart. 0888521 0887007 RK 009M3 CK2 RK 009 CK2 20 20 25 3. The disc assembly may now be cleaned and re-assembled 0887011 RK 009 CK2SS 20 25 0887526 RK SS009 CK2 25 or, depending on its condition, may be discarded and 0887790 RK 009M2 CK2 25 replaced with a new assembly from the repair kit. O-rings Kit consists of: Check assembly and Cover O-ring. should be cleaned or replaced as necessary and lightly Check Rubber Parts: greased with the FDA approved grease. Refer to parts price 0887293 RK 009 RC3 8, 10, 15 list, PL-RP-BPD for more information. 0887003 RK 009M2 RC3 15 0888522 RK 009M3 RC3 20 4. Re-assemble the check valve modules. Check modules are 0887507 RK SS009 RC1 15 installed in the valve body with the seat facing the valve inlet. 0887517 RK SS009M2 RC1 20 0888595 RK SS009M3 RC1 8 20 The modules must be securely in place before the retainer 0887017 RK 009 RC1 20 25 can be replaced. On the 20mm size retainer may have to be 0887527 RK SS009 RC1 25 tilted slightly into place. Replace relief valve assembly. 0887791 RK 009M2 RC1 25 0887508 RK SS009 RC2 15 CHECK ASSEMBLY CHECK ASSEMBLY 0887518 RK SS009M2 RC2 20 20mm M3 8 20mm 0888596 RK SS009M3 RC2 8 20 0887180 RK 009 RC2 20 25 O-ring Check Injection Molded Stainless Steel 0887528 RK SS009 RC2 25 Seal Cage Acetyl Resin Spring 0887792 RK 009M2 RC2 25 Kit consists of: Disc, Cover O-ring and O-ring. Retainers: 1047053 99AB47 8, 10, 15 1047394 99BA47 M2-M3 15 Disc Spring O-ring Seal 1047001 99FA47 32 50 1st Check Silicone Seal 1047001 99FA47 M1 32 50 Module M2 50 1047401 99EA47 M2 32 50 CHECK ASSEMBLY 25-50mm 32 50mm Check Cage First Check Kit: O-ring Spring 0887300 RK 009M2 CK1 32 40 Disc 0887270 RK 009M1 CK1 32 50 0887006 RK 009 CK1 32 50 0887010 RK 009 CK1SS 32 50 0887272 RK 009MI CK1SS 32 50 Cover O-ring 0887540 RK 009M2 CK1 50 Kit consists of: First check assembly, Cover O-ring and Sensing passage O-ring. Second Check Kit: 0887301 RK 009M2 CK2 32 40 0887271 RK 009M1 CK2 32 50 Relief 0887008 RK 009 CK2 32 50 Valve 0887012 RK 009 CK2SS 32 50 Module 0887273 RK 009 M1 CK2SS 32 50 0887541 RK 009M2 CK2 50 Kit consists of: Second check assembly, Cover O-ring and Sensing passage O-ring. First Check Rubber Parts Kit: Retainer 0887304 0887274 RK 009M2 RC1 RK 009M1 RC1 32 40 32 50 0887018 RK 009 RC1 32 50 0887542 RK 009M2 RC1 50 Kit consists of: First check assembly O-ring, Disc holder assembly, Cover O-ring and Sensing passage O-ring. Second Check Rubber Parts Kit: 0887305 RK 009M2 RC2 32 40 Watts reserves the right to change or modify product design, construction, 0887275 RK 009M1 RC2 32 50 specifications, or materials without prior notice and without incur- 0887183 RK 009 RC2 32 50 ring any obligation to make such changes and modifications on Watts 0887543 RK 009M2 RC2 50 products previously or subsequently sold. Kit consists of: Second check assembly O-ring, Disc holder assembly, Cover O-ring and Sensing passage O-ring. For additional information, contact your local technical sales representative, see back page. 5 First Check Second Check Repair Kit 8 50mm When ordering, specify Ordering Code, Kit number and Valve Size.

Servicing the 1. Remove the four or six relief valve cover bolts while holding the cover down. 2. Lift the cover straight off. The stem and diaphragm assembly will normally remain with the cover as it is removed. The relief valve spring will be free inside the body at this point. 3. The relief valve seat is located at the bottom of the body bore, and can be removed, if necessary, for cleaning. The disc can be cleaned without disassembly of the relief valve module. If it is determined that the relief valve diaphragm and/or disc should be replaced, the relief valve module can be readily disassembled without the use of special tools. Note: The disc rubber is molded into the disc holder and is supplied as a disc holder assembly. 4. To reassemble the relief valve, press the seat firmly into place in the body, center the spring on the seat, and insert the cover and relief valve module as a unit straight into the bore. Press down on the cover to assure proper alignment. Insert and tighten bolts. Caution: If cover will not press flat against body, stem assembly is crooked and damage can result. Realign stem and cover before bolts are inserted. NOTE: No special tools required to service Series 009 Ball Type Test Cocks Test Cock No. 1 First Check Module Test Cock No. 2 Second Check Module Test Cock No. 3 R.P. Zone Water Outlet Flow Tube O-ring Replacement Parts When ordering, specify Ordering Code, Kit number and Valve Size. Cover O-ring Total Kit: 0887021 RK 009 VT Kit consists of:, Stem assembly, Spring, Two piston o-rings, Flow tube O-rings and Cover O-ring. Rubber Parts Kit: 0887206 RK 009 RV Kit consists of: Diaphragm, Disc, Molded disc assembly, Piston O-rings, Stem O-ring and Cover O-ring. Service Parts Kit Spring Diaphragm Stem Retainer O-ring 6 For additional information, contact your local technical sales representative, see back page.

Servicing First & Second Check Valves 1. Remove the relief valve assembly as outlined on page 5. 2. Remove the retainer from the body bore. The check valve modules can now be removed from the valve by hand or with a screwdriver. Note: The seats and springs of the first and second check modules are not interchangeable. The heavier spring and smaller diameter seat belong with the first check module. 3. The check seats are attached to the cage with a bayonet type locking arrangement. Holding the cage in one hand, push the seat inward and rotate counterclockwise against the cage. The seat, spring cage, spring and disc assembly are now individual components. 4. The disc assembly may now be cleaned and reassembled or, depending on its condition, may be discarded and replaced with a new assembly from the repair kit. O-rings should be cleaned or replaced as necessary and lightly greased with the FDA approved silicon grease. For more information refer to repair parts price list PL-RP-BPD. 5. Reassemble the check valve modules. Check modules are installed in the valve body with the seat facing the valve inlet. The modules must be securely in place before the retainer can be replaced. Replace relief valve assembly. NOTE: No special tools required to service Series 009 65 80mm O-ring Flow Tube Cover O-ring Check Assemblies Disc Spring Retainer Cage Cover Relief Valve Second Check Service Parts Kit Replacement Parts When ordering, specify Ordering Code, Kit number and Valve Size. First Check Kit: 0887019 RK 009 CK1 65 80 First Check Service Parts Kit Retainer Body Second Check Kit: 0887020 RK 009 CK2 65 80 Kit consists of: Check assembly, Cover O-ring and Flow tube O-ring. First Check Rubber Parts Kit 0887281 RK 009 RC1 65 80 Second Check Rubber Parts Kit 0887205 RK 009 RC2 65 80 Kit consists of: Disc, O-ring and Flow tube O-ring. Total Rubber Parts: 0887207 RK 009 RT 65 80 Kit consists of: Diaphragm, Two discs, Two molded disc assemblies, Two seat O-rings, RV O-ring, Two piston O-rings, RV stem O-ring, Flow tube O- rings and Cover O-ring. Cover Kit: 0887282 RK 009 C 65 80 Kit consists of: Cover, Cover O-ring and Flow tube O-ring. Kit: 0887208 RK 009 S 65 80 Kit consists of: Check seat, O-ring and Cover O-ring. Represented by: Fluidflo Pty Ltd. 107-109 Woodlands Drive Braeside, Victoria 3195 Phone: 1300-662-155 Fax: 1300-799-356 Web: www.fluidflo.com.au For additional information, contact your local technical sales representative, see back page. 7

Field Testing of Reduced Pressure Zone Assemblies 1. PROCEDURE: The procedure shall be as follows. All measurements shall be taken at ambient air temperature. Clean line strainer before commencing test. (a) With reference to the above illustration, check and, if necessary, open inlet isolating valve (5). (b) In sequence, open and close test cocks (1), (2) and (3) to flush out any impurities. To test the upstream check valve: (c) Close outlet isolating valve (4) and test kit valves (A) and (B). Open test kit valve (C). (d) Connect - (i) the high-pressure hose of the test kit to test cock (1); and (ii) the low-pressure hose of the test kit to test cock (2). (e) Open test cocks (1) and (2). (f) Slowly open test kit valve (A) and bleed water through the vent hose; close test kit valve (A). (g) Slowly open test kit needle valve (B) and bleed water through the vent hose. (This eliminates air from the system.) (h) Slowly close test kit needle valve (B) and record the reading on the differential pressure gauge (see Note 1). (This indicates the pressure drop across the upstream check valve (5).) To test the downstream check valve: (i) Close test kit valve (C). (j) Connect the vent hose to test cock (3). (k) Open test cock (3) and test kit valve (A). (l) Observe the relief port (6). (m) Record whether there is any discharge (see Note 2). (This checks the pressure tightness of the downstream check valve.) To test tightness of downstream isolating valve: (n) Close test cock (2). (o) Observe the differential gauge (see Note 3). (p) Close test kit valve (C). To test relieve valve: (q) Open test cock (2) and slowly open test kit needle valve (B) observing both the differential gauge and the relief port (6). (r) Record the reading on the differential gauge when the relief port (6) commences discharging. NOTES: 1. A reading below 35 kpa at Step (h) indicates that the upstream check valve is faulty. This should be repaired and the test repeated. 2. A discharge from the relief port during Step (m) indicates the downstream check valve is leaking. This should be repaired and the test repeated. 3. If the pressure differential decreases (approaches zero) during Step (o) this indicates the outlet isolating valve is leaking and should be repaired. Leaking invalidates the results of the earlier tests, which must be repeated after the isolating valve is repaired. 4. If the downstream check valve is leaking the test can continue but tightness of the outlet isolating valve cannot be tested. The relief vent can be tested to give an indication of the degree of protection available. However, results are invalid until the check valve has been repaired because it is not known if the downstream isolating valve is tight. 2. PERFORMANCE REQUIREMENTS: The following shall be the criteria for acceptance: (a) The reading in Step (h) shall be not less than 35 kpa. (b) There shall be no discharge from the relief port in Step (m). (c) The reading in Step (r) shall be not less than 14 kpa. 3. TEST REPORT: The following details may be required by your Local Authority: (a) The reading in Step (h). (b) The presence or absence of any discharge in Step (m) (c) The differential pressure gauge reading in Step (r). (d) Whether the downstream isolating valve is tight. (e) Reference to this test method, i.e. AS 2845.3, Appendix E. (5) Ball Type Test Valves (A) High Hose (Yellow) (C) Low Hose (White or Red) Vent Hose (Blue) (3) (B) Needle Valve (4) (1) (2) (6) Caution: To prevent freezing, hold Test Kit vertically to drain differential gauge and hoses prior to placing in case. Backflow Prevention Products USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com Canada: 5435 North Service Rd., Burlington, ONT. L7L 5H7; www.wattscanada.ca RP/IS-009 0630 EDP# 1915953 Watts Regulator Co., 2006