Why arc-resistant drives need to be considered

Similar documents
A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

Understanding Arc Flash Hazards. White Paper

Electrical Safety and Overcurrent Protection

GE Arc Vault TM Protection System. By Mark Clapper GE Specification Engineer. Introduction. What Variables Contribute To An Arcing fault?

3.2. Current Limiting Fuses. Contents

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy

Not all Low Voltage Switchgear is created equal

Advanced Protective Relay Training

Not all Low Voltage Switchgear is created equal

Future Proof Your Arc Flash Assessment

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

Ampgard The name motor applications rely on

Arc-Flash Mitigation Technologies. Dennis Balickie

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

4-Day Power System Analysis, Coordination, System Studies

Chapter 6 Generator-Voltage System

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

Zone Selective Interlocking

Arc flash solutions catalogue Australia. Safety solutions - Protecting employees and the enterprise

ELECTRICAL POWER and POWER ELECTRONICS

Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear

Cost Benefit Analysis of Faster Transmission System Protection Systems

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

ACHIEVING MAXIMUM BENEFITS WITH A FUSE PROTECTED MOTOR CONTROL CENTER

MITIGATE ARC EFFECTS WITHIN AN E-HOUSE

Small Generator Interconnection Program Interconnection Technical Requirements

FUSES. Safety through quality

Transformer Protection

Shippensburg University

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Variable Frequency Drive Basics

This small footprint makes a BIG impact

SWITCHGEAR OPERATING PERSONNEL SAFETY UPGRADE SOLUTIONS FOR AGED INSTALLED BASE

SIMOVAC and SIMOVAC-AR. Medium-voltage controllers 2.3 kv kv. usa.siemens.com/simovac

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

ECET Distribution System Protection. Overcurrent Protection

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

The safest, most reliable Switchgear in the market today

Electrical Safety CSA Z462 & NB Regulations

Arc Flash Detection and Mitigation

Metal-enclosed medium-voltage power factor correction system

Miniature circuit breaker Application guide

X-Limiter full-range current-limiting fuse

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Arc flash hazard mitigation

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

ARC FLASH MANAGEMENT REVIEW. October 2017

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

White Paper. Application of Resistive/Reactive Load Banks for kva Testing

SafeGear TM Motor Control Center Arc resistant metal-clad construction

Standby Power Systems

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

Custom Medium and LV Switchgear 5-38kV Switchgear Power Systems

TERMS AND DEFINITIONS

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

Overview Brochure Integrated Power Distribution. Medium Voltage Assembly Solutions

C1000 Series Automatic Cap Bank

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008

K-Limiter high ampere Companion II fuse

IEEE Northern Canada & Southern Alberta Sections, PES/IAS Joint Chapter Technical Seminar Series

How to Use Coordinaide to Protect Transformers Against Secondary-Side Arcing Faults.

Small Electrical Systems (Microgrids)

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

Common Bus and Line Regeneration

VFD Best Practices: Getting the Most from Your VFD Investment

IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

Mark Lyvers LLC / Cooper Bussmann Arc Flash Script Script to accompany PowerPoint on New 2002 NEC Arc Flash Hazard Marking Requirement

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

Selective Coordination

Two Recent Case Studies in the Mining Industry

3.0 Radial Distribution Systems

Interconnection System Impact Study Report Request # GI

Medium Voltage Metal-Enclosed Switches

Integrating Roles Within Electric Utilities to Achieve Arc Flash Safety. MIPSYCON Presenters Neil Stiller & Bob Cooke

Medium Voltage Metal-Enclosed Switches

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

HIGH VOLTAGE vs. LOW VOLTAGE: POTENTIAL IN MILITARY SYSTEMS

CONSIDERATIONS FOR THE APPLICATION OF A MV HIGH SPEED GROUNDING SWITCH FOR ARC FLASH MITIGATION OF LV EQUIPMENT

CMU medium voltage power fuses

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers

ABB AG - EPDS. Ultra-Fast Earthing Switch UFES active internal arc protection

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Medium Voltage Adjustable Frequency Drive

Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting

The Case for Hybrid Generator Grounding

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

EE 741 Over-voltage and Overcurrent. Spring 2014

26.3. Power Breakers, Contactors and Fuses. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents.

Transcription:

White Paper WP020003EN Why arc-resistant drives need to be considered Aaron H. Vandereulen Application Engineer Stan R. Simms Design Engineer Reports have shown fatal injuries related to electrical incidents from 2004 through 2010 resulted in 1,494 fatalities, 29% of which were attributed to contact with wiring, transformers and electrical components. From 2011 to 2013, 43% of fatalities were attributed to indirect contact and 54% attributed to direct contact. 1 There is a systematic approach to minimizing or mitigating the risk to electrical injury. It is best to select the highest level of control possible. As outlined by the Occupational Safety and Health Administration (OSHA) Hierarchy of Controls & ANSI Z10 (2012): Elimination or substitution, engineering controls, warnings, administrative controls, personal protective equipment (PPE). BEST IPROVED INIU OSHA/ANSI, Hierarchy of Controls Safe work practice policy ELIINATION SUBSTITUTION Engineering controls Administrative controls PPE Figure 1. OSHA hierarchy of controls Arc flash mitigation any companies are adopting administrative controls such as workplace practices and rules adopting routine training, communication and standard work practices, but this does not eliminate the hazards. PPE is allowed to be used when engineering controls are not feasible or do not completely eliminate the hazard under the OSHA guidance. Over reliance on PPE as a measure is not the correct approach. This paper will focus on understanding why arc-resistant equipment needs to be considered when evaluating the risk of arc flash and arc blasts associated with internal arcing faults in mediumvoltage adjustable frequency drives. The three criteria evaluated in this paper include: 1. System architecture 2. System impedance 3. Failure mode and analysis Ideally, with any electrical equipment, to reduce the risk of injury, the hazard needs to be eliminated. Operating mechanism to disconnect or make power in order to de-energize equipment is in itself a hazard and it is difficult to completely eliminate the hazard. Substitution allows different equipment to be utilized that reduces the risk of injury. In this case, to reduce the risk of injury, the equipment could be upgraded to arc resistant to protect from arc flash and arc blast injury. Engineering controls include isolation devices, guards, etc. or administrative controls such as limiting the time of hazard exposure. Engineered controls will be discussed further in this paper. Training and communication are effective tools for awareness. System architecture any different manufacturers build arc-resistant equipment. This equipment includes, but is not limited to, low-voltage metal-enclosed switchgear, motor control centers, medium-voltage motor starters and metal-clad switchgear. Product safety has evolved to incorporate the standard IEEET C37.20.7-2007, IEEE Guide for Testing etal-enclosed Switchgear Rated Up to 38 kv for Internal Arcing Faults. This standard is widely adopted and builds harmony amongst vendors, end users, third-party certifiers and power test labs. Switchgear and motor starter equipment built and certified to this standard are prevalent in facilities worldwide. edium-voltage adjustable frequency drives (V AFDs) are common in large industrial facilities and are often overlooked regarding the hazards associated with operating and maintaining such complex equipment. edium-voltage drives comprise many interconnect power components operating in tandem. A medium-voltage drive should not be considered a simple add-on piece of equipment or switchgear. A detailed failure mode analysis is presented in several scenarios to illustrate the need for a system evaluation with regards to internal arcing faults. 1 Occupational Injuries from Electrical Shock and Arc Flash Events

White Paper WP020003EN anufacturers may provide a fully integrated or non-integrated solution. Non-integrated solutions require the end user to select additional equipment such as feeders, power transformers, reactors or filters. Specific coordination is needed between components to ensure adequate functionality and protection. Feeder options include load-break switches, fused contactors and power circuit breakers. ain disconnect or feeder Feeder Feeder SGCT or SCR based curent source drive (CSI) Figure 2. Drive topologies ulti-pulse diode front end drive (VSI) IGBT active front end drive (VSI) V AFD designs utilize different converter topologies, inverter topologies and semiconductor devices (diode, SCR, IGBT, SGCT, etc.). Unlike medium-voltage starters or switchgear, V AFD power conversion technology is different based on each manufacturer s approach. Why arc-resistant drives need Two drive architectures will be evaluated. Figure 3 shows a fully integrated drive with a fused, non-load-break disconnect, isolation transformer, converter and inverter with optional output filter. Figure 4 shows a non-integrated drive with similar components as Figure 3. The spacing between zones suggests separate items that could be selected based on end user discretion from manufacturer specification. Each zone represents a power stage typically found in V AFDs. The red x signifies potential internal arc fault locations of interest. Each has its own associated hazard concerns. System impedance Short-circuit currents With V AFDs installed in industrial areas with weak or soft utility power systems, it is important to understand how this affects the arcing current magnitude and duration. Equipment is type tested and rated at a specific short-circuit current magnitude and duration. In many installations, the actual available short-circuit is a fraction of the equipment rating. Also, arc-resistant equipment is given a third rating based on the arc-fault duration tested. As an example, a natural gas compression station with a 20 VA unit substation 13.8 kv / 4160 V DY of 8.5% impedance has a rated secondary current of 2779 A and a maximum short circuit of 32.7 ka (235 VA). However, if the utility available short circuit is only 10 ka (238 VA), the transformer secondary short-circuit current is reduced to 16.4 ka (118 VA); the utility impedance has limited the overall short-circuit current. UTILITY: Isc = 10 ka 13.8 kv/4.16 kv Delta/wye Z = 8.5% 20 VA Filter 52 Zone 1 Zone 2/3 Zone 4 Zone 5 50/51 Figure 3. Fully integrated drive Isc Figure 5. System one-line diagram Filter Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Figure 4. Non-integrated drive 2

Why arc-resistant drives need Arcing fault currents Given most V AFDs must comply with the IEEE 519 harmonic limits, manufacturers address this need with an isolation transformer or line reactance in the converter. Similar to the example above, which is examined with a power system study, this added converter impedance affects the system; however, its effect is not well known. The available bolted fault current is reduced with every additional impedance as you move from the utility to the drive converter. This perspective fault current is further reduced with arcing impedance, which can lead to increased fault clearing time and increased incident energy. Examples of arcing fault current with respect to bolted fault current are illustrated in Table 1. This table will be referenced in the next sections. Table 1. IEEE 1584 (2002) arcing current ka Ibf (A) log (Ia) Ia (A) % Ia/Ibf 50 50000 4.623 42003.7 84% 40 40000 4.528 33730.7 84% 30 30000 4.405 25422.0 85% 20 20000 4.232 17065.2 85% 10 10000 3.936 8633.8 86% 5 5000 3.640 4368.0 87% 1 1000 2.953 897.8 90% Legend: Ibf = bolted fault (amperes) Ia = arcing fault (amperes) Failure mode and analysis Primary faults (Zone 1, Figure 3 and Figure 4) Primary faults would be localized to the input equipment. The input equipment, ideally, is constructed to the C37.20.7 standard. any papers discuss the construction of arc-resistant medium-voltage motor starters and switchgear, and this paper does not explore this topic in detail. Care should be taken on understanding the perspective arcing current magnitude and upstream clearing times of the protection equipment. A system study is paramount. It is important that proper coordination is achieved while reducing the likelihood that the arcing fault duration does not exceed the equipment rating. Special consideration should be taken with a weak power system or source. Transformer secondary faults (Zone 2) An example was given with a 20 VA substation transformer and evaluated the secondary short-circuit current of 16.4 ka. This is a relatively straight-forward calculation with a two-winding transformer. However, with V AFD isolation transformers, it is not easy to calculate the secondary short-circuit current because of their given variations and complexities. It is not unusual for these types of transformers to have four to twelve secondary circuits or more to address converter harmonics. A complex model is required that is typically outside the capability of traditional power system analysis software. An approach is used in the following example that may help with future drive system studies. White Paper WP020003EN A 4160 V, 6000 hp drive utilizing a five-winding, 5750 kva transformer is used in this example. The primary to secondary impedance is 6% with all secondary circuits shorted. With only one secondary circuit shorted, the secondary impedance is 11%, but 44% is reflected to the primary, based on empirical data. Zpri Zsec1 Zsec2 Zsec3 Zsec4 Figure 6. Transformer impedance model Each secondary circuit has a rated current of 704 A and 1000 V. The estimated secondary bolted fault circuit current is calculated as: I sec Z sec 704 A I bf,sec1 = = = 6400 A 0.11 Equation 1 Assuming the arcing fault current is 85% of the bolted fault current per the IEEE 1584 table: I a,sec1 = 0.85 x 6400 A = 5440 A Equation 2 The arcing current as reflected to the primary: I pri Z pri 704 A I a,pri = x 0.85 = x 0.85 = 1360 A 0.44 Equation 3 Using a 750E primary fuse for transformer protection, the total clearing time, without additional engineering controls, is beyond 600 seconds. The fuse opens in the time overcurrent region. Significant damage due to the arcing fault is possible because the duration exceeds the design rating. If a breaker and protective relay were used in place of the fuse, the breaker would open based on the time overcurrent region, resulting in similar damage. It is critical to coordinate upstream protection to clear faults within the downstream equipment arcing fault duration rating. 3

White Paper WP020003EN Why arc-resistant drives need TCC Figure 7. Fuse time current curve (TCC) 4

Why arc-resistant drives need White Paper WP020003EN I 2 t = 1,400,000 A 2 s = 1,400,000 (5440 A) 2 = 0.0473 sec Equation 7 (Arcing fault clearing time) 52 50/51 52 50/51 With the addition of this engineering control, the theoretical available incident energy has been significantly reduced. Note the outcome is still a cause for concern. The hazard is not yet completely eliminated. ( ) 0.047 s E = 5.12 x 10 5 (1.0)(6400 A) = 185 914 2 cal cm 2 52 Equation 8 Drive system 50/51 Drive system It should be noted that this single winding fault scenario does not include arcing faults that dynamically propagate to multiple secondary circuits. Arc back failure VFD VFD One failure mode of power converters is the diode arc back failure mode outlined in IEEE 551 Violet Book, section 8.7. When a diode (valve) loses its semiconducting properties (diode short), the current magnitude exceeds that of typical three-phase bolted faults by up to 2.73 times. This short-circuit peak current, if not accounted for in the design of the drive, can result in catastrophic transformer failure and arcing faults with significant enclosure damage. In some cases, enclosure doors have bowed or blown off. There is a need for semiconductor fuses as an engineering control. Figure 8. V AFD feeder Based on the Lee method 2, the unaddressed theoretical available incident energy is well above 40 cal/cm 2 at a working distance of 36 inches even if the clearing time is limited to 1 second, posing a problem. t E = 5.12 x 10 5 VI bf ( D ) 2 Equation 4 1.0 s E = 5.12 x 10 5 (1.0)(6400 A) = 3919 ((914 mm) ) 2 Equation 5 cal cm 2 Rectifier faults (Zone 3) Designs in which some manufacturers do not incorporate semiconductor fuses into the converter are known as fuse-less designs. When semiconductor fuses are provided and properly coordinated, these engineering controls have the potential to reduce the available incident energy, as compared to the previous example. For a secondary bolted fault from the working example above, the semiconductor fuses open in approximately 34.2 milliseconds. 3 Arcing fault current of 85% of bolted fault magnitude results in a clearing time of approximately 47.3 milliseconds. 2 IEEE 1584-2002 I 2 t = 1,400,000 A 2 s = 1,400,000 (6400 A) 2 = 0.0342 sec Equation 6 (Bolted fault clearing time) 3 SIBA SBQ3 semiconductor fuse, 1100 A DC bus faults (Zone 4) An arcing fault on the DC bus is difficult to model but can be estimated as a three-phase bolted fault on the secondary with an 85% factor from Table 1. In a distributed multi-pulse rectifier design, a fault may begin at a single module, but then dynamically propagate to subsequent locations. Figure 9 shows a vertical or horizontal module arrangement for rectifiers or inverters. Cell 1 Cell 2 Cell 3 Cell 4 Figure 9. odule layout I I bf,pri = pri 704 A = = 11,733 A x 0.85 = 9973 A Z 0.06 Equation 9 Cell 4 Cell 3 Cell 2 Cell 1 The transformer primary current of 10 ka would open the primary fuse in approximately 0.55 seconds (Figure 7). The semiconductor fuses would open in approximately 0.0141 seconds. This results in an incident energy of 101.3 cal/cm 2 at a working distance of 36 inches. E = 5.12 x 10 5 (1.0)(11,733 A) 0.0141 = 101.3 ( 914 ) 2 Equation 10 cal cm 2 5

White Paper WP020003EN Ionized gasses Ionized gas from an arc fault is the source for dynamic propagation. With medium-voltage motor starters or switches, segregation barriers are implemented as engineering controls to reduce propagation and allow fuses to clear the fault as intended. This is especially important to consider in medium-voltage drive design. Some designs incorporate stacked converter and inverter cells/ modules. As mentioned previously, an arcing fault in the module can easily propagate to an adjacent cell without barriers. In Figure 10, diode and semiconductor fuse barriers are implemented. Why arc-resistant drives need An arcing fault heats and expands copper metal rapidly, producing a pressure wave that has to be contained and directed away from personnel. The peak pressure wave occurs between 8 and 10 milliseconds after arc initiation. With drive configurations using forced air-cooling, a deflection means is necessary to prevent pressurized gases from exiting the intake vents, possibly toward a user. An additional engineering control (shown in Figure 12) closes a louver upon internal high pressure. In this approach, the pressure wave is engineered to redirect away from the user. Figure 10. Phase segregation barriers External view Figure 12. Louver Internal view Pressure wave Pressure Pressure relief opens / louvers close The heated and expanded gasses can reach temperatures of 35,000 degrees F. The type test as required by IEEE C37.20.7 has measures that detect non-complying internal arc fault containment. Figure 14 is an example of an additional engineering control that quenches exhaust arc flames in air-cooled enclosures. Figure 13 represents a type test setup with cotton indicators to observe the effects of possible escaping arc gasses. Expansion Emission Thermal Compression Time Figure 11. Pressure wave Figure 13. Cotton indicators 6

Why arc-resistant drives need Figure 14. Arc flame quencher Active engineering controls (preventative) Pre-charge system any drives utilize a DC bus pre-charge system to limit capacitor inrush current. An engineering control to reduce arc flash risk can be in the form of a limited energy pilot circuit that additionally soft magnetizes the transformer. This circuit would include sensors and a detection method to determine if there is a short circuit within Zone 1, 2 and 3 (Figure 3) such as a misplaced tool left after maintenance. This approach detects a short circuit prior to closure of the main contactor and is the highest level of engineering control. Summary White Paper WP020003EN The failure mode analysis in this paper has highlighted the need for arc-resistant engineering controls for the entire drive system, particularly Zone 2. It is suggested that a comparable evaluation be performed on the internal failure modes of other vendors mediumvoltage drives not shown in this paper. The outcome of a thorough system analysis, with regards to V AFD internal arcing faults, results in the both active and passive engineering controls to protect personnel and minimize equipment damage. Although active engineering controls have the potential to reduce arc incident energy, they are likely defeated to type test the passive construction when evaluating to the commonly accepted IEEE standard. The following is a checklist of requirements to include when specifying an arc-resistant medium-voltage adjustable frequency drive: Arc equipment considerations Design Requirement Passive construction 3 Short-circuit protection 3 Arc rating 3 Fully integrated 3 Fused converter 3 Gas segregation barriers 3 System FEA 3 Third-party certification (UL/CSA) 3 Active Engineering controls (reactive) Light detection system Fiber optic light detection sensors have been utilized in switchgear as a means to protect equipment by limiting the arcing fault duration. There is no governing body that has created a set of standards that provides guaranteed integration of the detection circuits and equipment without type testing to evaluate the efficacy of these systems. At best, this active engineering control provides a backup to passive arc-resistant construction. It does not eliminate the localized pressure wave caused by an arcing fault because the relatively slow reaction time of upstream coordination. Differential protection Transformer differential protection schemes, utilized widely in industrial facilities to reduce arcing duration, are difficult to implement with drive isolation transformers. Bus differential schemes could be implemented but would be limited to protection up to the transformer primary. Application on the output of the inverter would cause protection relay misoperation due to the change in line/load kva and base frequency. These last two active engineered controls do not eliminate the hazard nor do they protect against the initial arc blast or pressure wave. The philosophy behind these engineered controls is to decrease the upstream clearing time to limit equipment damage. 7

White Paper WP020003EN Why arc-resistant drives need References. etzdorf, D. BeCraft, R. Bhalla, A. Fabrici, Performance of an Arc Resistant edium Voltage otor Control Center for an In-Service Fault, IEEE Petroleum Chemical Industry Conf., 2017 A. Smith, D. Doan, Sometimes Overlooked Safety Concerns With Large Engineered ASD Systems, IEEE Electrical Safety Workshop, 2017, pp. 100 108 IEEE Guide for Performing Arc-Flash Hazard Calculations, IEEE Standard 1584, 2002 IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems, IEEE Standard 242, 2001 IEEE Guide for AC otor Protection, IEEE Standard C37.96, 2012 IEEE Recommended Practice for Calculating Short-Circuit Currents in Industrial and Commercial Power Systems, IEEE 551, 2006 R. Campbell, D. Dini, Occupational Injuries From Electrical Shock and Arc Flash Events, Fire Protection Research Foundation, arch 2015. Wactor, T. Olsen, C. Ball, D. Lemmerman, R. Puckett, J. Zawadzki, Strategies for itigating the Effects of Internal Arcing Faults in edium-voltage etal Enclosed Switchgear, IEEE Transmission and Distribution Conference and Exposition, 2001 IEEE Guide for Testing etal-enclosed Switchgear Rated up to 38 kv for Internal Arcing Faults, IEEE Standard C37.20.7, 2007 Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com 2017 Eaton All Rights Reserved Printed in USA Publication No. WP020003EN / Z19859 August 2017 Eaton is a registered trademark. All other trademarks are property of their respective owners.