PowerSwitch Enclosed Disconnect Switch with Receptacle (EDSR) Cat. o. EDSR Rated: 30A-600VAC Max. ISTALLATIO ISTRUCTIOS DI-000-0EDSR-00A
EDSR Enclosed Disconnect Switch with Receptacle (Figure 4) OTE: Receptacle sold separately. For use with 20A -30A EMA Locking Receptacles and any mating EMA 20A-30A Locking Plug. The EDSR has an environmental rating of IP66, UL Standard 0 and EMA environmental ratings of 4 and 12K, when used with Leviton ETUARD TM locking plugs. OTE: If other mating plugs are used the environmental rating is IP4 and EMA environmental rating 3R. PARTS LIST: 1. Enclosure Base with Hinged Cover, Receptacle Mounting Bracket and the following DI Rail mounted hardware: A. Rotary Switch 30A, 660V with ormally Open Auxiliary Contact. B. Terminal Blocks, Color Coded. Blue terminal block is eutral. reen/ ellow terminal blocks are ground. 2. Inside Enclosure Base A. rounding Bracket with Screw. B. Four (4) Enclosure Mounting Feet with Screws. ote: all Mounting Hardware not included. 3. Six (6) 12 # A Leads (3 Black, 2 reen, 1 hite) for internal wiring. 4. Adhesive-backed Ratings Label Sheets.. 20A ETUARD TM seal replacement (shown in Figure 6). 30A gaskets are pre-assembled. Figure 1 Enclosure Bottom as Packaged with Enclosure Open Packaged Mounting Feet and Screws rounding Bracket DI Rail # A Leads for Internal iring Receptacle Mounting Bracket Hinge 1
FEATURES Meets the requirements of Outdoor/Indoor installations conforming to IP 4 and EMA 3R with standard EMA plugs and connectors. Meets the requirements of Outdoor/Indoor installations, conforming to IP 66, UL Standard 0, and EMA Environmental Ratings of 4,12K, only when used in conjunction with Leviton etguard TM plugs. For use with 20A - 30A EMA locking plugs. Provides O-OFF switched control for a connected load. This enclosure provides lockout capability in compliance with OSHA Lockout/Tagout Regulation 29 CFR Part 19.147 (in the OFF position) with an acceptable padlock/shackle, thereby assuring the connected equipment cannot be energized. Auxiliary contact open prior to the line contacts for pilot duty switching. OTE: This enclosure must not be used as a junction box for feed-through connections. ISTALLATIO ISTRUCTIOS ARI: For installation only by a qualified electrician in accordance with the ational Electrical Code (EC) or the Canadian Electrical Code (CEC), local codes, and the installation instructions. ARI: Risk of electrical shock. Disconnect all power supplies to enclosure before exposing interior. More than one supply disconnect may be required to de-energize this equipment before servicing. ARI: Receptacle MUST be installed BEFORE connection to a power supply. 30A MAIMUM receptacle rating. refer to ratings tables and wiring diagrams. ARI: Separate overcurrent protection must be provided in accordance with the EC Article 220 or CEC, section B as appropriate. Overcurrent protection must not exceed the ampere rating of the receptacle per EC section 430-42(C) or CEC Part 1, rule 28-602 (3)(C)(I). OTHER CAUTIOS AD OTES: 1. Use this device only with copper or copper clad wire. ith aluminum wire use only devices marked CO/ALR OR CU/AL. 2. Check to see that rating marked on device is correct for the intended installation. 3. THE Lockout feature DOES OT interrupt the power supplied to the switch. 4. Device is suitable for use on a circuit capable of delivering not more than 600 VAC maximum.. Cover cannot be removed when SITCH handle is in the O position. 6. THESE enclosures must always be mounted vertically with receptacle end down. 2
TO ISTALL: OTE: Leviton EDSR Switches may be mounted for Top or Bottom feed of supply wires (refer to Figures 2 and 3). Mounting: arning: To avoid fire, shock, or death; turn off power at the circuit breaker or fuse, and test that the power is off before attempting to install enclosure. CAUTIO: ThESE enclosures must always be mounted vertically with receptacle end down. ote: Hinged cover will open only when the rotary switch knob is turned to the OFF position. 1. Remove the six (6) #-32 x 1-1/4" cover mounting screws, and rotate the hinged cover open (refer to Figure 1). 2. Determine if the installation is top or bottom feed. 3. Drill appropriate hole size for conduit hub (not included) as indicated below in one of the four drill points indicated on the top and bottom of enclosure base. Drill points provided for top left, top right, bottom left and bottom right conduit entry (see Conduit Hub Mounting). Enclosure Mounting Using Mounting Feet: 1. Orient mounting feet as desired (refer to Figures 2, 3) and secure to the enclosure base with the provided mounting screws #-32 x 1-1/4". Torque to - 12 in.-lbs (1.2 -m). Conduit Hub Mounting (Conduit Hub not included): 1. Route wires. Install 3/4" or 1" hub (not included) to conduit and enclosure. For 3/4" hub, drill a 1-1/16" mounting hole. For a 1" hub, drill a 1-/16" mounting hole. Ensure that the "O" ring seats on the enclosure base outside wall. Install grounding bracket and secure tightly with hub nut. 2. Secure enclosure to the desired surface. Mounting hardware accept up to a 1/4" diameter screw (not included). 3. Make connections as per wiring instructions. Figure 2 Top Conduit Connection/ire Entry Figure 3 Bottom Conduit Connection/ire Entry Listed Conduit Hub (not supplied) Type 3R, 4, 12K Rated Mounting Feet (4) Mounting Feet (4) round Bracket eutral Buss Rotary Switch eutral Buss Rotary Switch round Buss Auxiliary Contact round Buss Auxiliary Contact Condensation Drip Loops To Term. of Rcpt. To Term. of Rcpt. Receptacle (not supplied) To Term. of Rcpt. To Term. of Rcpt. Receptacle (not supplied) round Bracket CAUTIO ThESE enclosures must always be mounted vertically with receptacle end down. 3 Listed Conduit Hub (not supplied) Type 3R, 4, 12K Rated
Top or Bottom Feed: OTE: A metal closure plug must be grounded (bonded) back on to an unused ground terminal. Use of a UL Listed atertight conduit fitting (not included) required to maintain Type 4 and Type 12K ratings (refer to Figures 2, 3). 1. hen using Top feed conduit entrance, always form condensation drip loops in wiring as shown in Figure 2. iring: OTE: Use conductors with insulation rated 7 C or higher having sufficient ampacity in accordance with the 60 C column of Table 3-16 of the EC or Table 2 of the Canadian Electrical Code. DO OT tin conductors. 1. ARI: TO AVOID FIRE, SHOCK, OR DEATH; TUR OFF POER AT CIRCUIT BREAKER OR FUSE AD TEST THAT POER IS OFF BEFORE IRI! 2. From conduit, route round wire and eutral wire to DI mounted color coded round and eutral terminals. Connect Hot wire(s) to terminal(s) L1, L2, L3 on DI mounted Rotary Switch, as per wiring Diagrams shown on pages 8 to 9 (loop wires as necessary). Route provided leads through receptacle mounting bracket and connect load side of switch T1, T2, T3 to appropriate receptacle terminals as per iring Diagrams. Connect round and eutral Terminal (if applicable) of Receptacle to corresponding terminals on DI mounted Terminal Blocks. Blue color terminal block is eutral. reen/ellow terminal block is ground. Tighten all screws to specified torques. Make sure that there are no loose strands. ote: The Conduit Hub steel bracket must be grounded (bonded) to the DI rail mounted color coded round Terminal (refer to Figures 2, 3). 3. Strip ages and Torques for LIE and LOAD terminals: For eutral and round terminals, use #14-#8 A conductors, strip to 1/32" (12.0 mm) Torque 7.1-8.9 in-lbs (0.8-1 -m). For Rotary Switch terminals, use #14-#8 A conductors, strip to 11/16" (17. mm) Torque 7 in-lbs (0.8 -m). For Auxiliary terminals, use #18-#14 A conductors, strip to /16" (8.0 mm) Torque 7.1-8.9 in-lbs (0.8-1 -m). For Receptacle, refer to wiring instruction sheet supplied with device. 4. To wire the Locking Receptacle, feed the enclosed wires from Load side of switch, round terminal, and eutral terminal up through the Receptacle Mounting Bracket (refer to Figures 2, 3).. Make sure there are no stray conductor strands. 6. Mount the Locking Receptacle to the Mounting Bracket. Use the two (2) mounting screws provided with the Receptacle. 7. Make sure there are no stray conductor strands. 8. Looping of wires as shown in Figure 2 is mostly necessary for top feed installations to prevent possible condensation from dripping on to terminals. 9. Ensure that the enclosure cover s gasket is in the groove. Close cover and tighten cover screws alternately to in.-lbs. (1.2 -m) of torque. OTE: For EDSR, switch knob must be in the OFF position to close cover.. Select Receptacle Voltage Label from label sheet provided. Affix Receptacle Voltage Label to cover (refer to Figure 4). 11. hen mating Receptacle with a ETUARD TM Plug, affix IP66 ratings label below Receptacle label as shown in Figure 4. ote: hen using a 20A Receptacle, the appropriate asket and asket Clamp must be used as per following installation instructions. If using a 30A Receptacle, your installation is complete. 4
Figure 4 EDSR Front View Affix Receptacle Voltage Label Here Affix IP66 Ratings Label Here Switch Handle Receptacle Cover 20A RECEPTACLE SEAL ISTALLATIO (Figure ) OTE: 20A Receptacle seal components are only to be used when a 20A Receptacle is installed. If installing a 30A Receptacle no components are required to be replaced. Leviton EDSR is pre-assembled with askets for a 30A Receptacle. hen using with a 20A Receptacle, the 20A asket and asket Clamp (included) must be used along with a ETUARD TM Plug to maintain an environmental rating of IP66, UL Standard 0 and a EMA environmental rating of 3R 4 and 12K. All parts are self aligning to mating parts (refer to Figure ). OTE: The asket, and the asket Clamp are a mated pair. The parts are identified with a visible mark ( 20A or 30A ) to be used either for 20A or 30A installation. EDSR is shipped with a 30A asket Clamp. For 30A applications, mate with 30A asket. For 20A applications use 20A asket and 20A asket Clamp. OTE: DO OT MI ASSEMBL COFIURATIOS. To Install SEAL COMPOETS FOR A 20A RECEPTACLE: FOR SAFET, MAKE SURE SITCH IS I THE "OFF" POSITIO. 1. Lift Receptacle Cover. Unscrew pre-assembled asket Clamp assembly and remove from box. Set mounting screws aside. 2. 20A asket and asket Clamp are indentified with a "20A" visible mark (30A asket and asket Clamp are marked "30A"). 3. ith Receptacle Cover open, align asket Clamp with rubber asket and place this loose assembly over the Receptacle Opening. Make sure that the circular V ribs of the asket are within the V grooves of the Receptacle Opening and secure with (4) screws previously removed to 8- in. lbs. of torque. OTE: ew environmental ratings label for 4, 12K & IP66, are included for device cover when using a mating Leviton ETUARD TM Plug.
Figure etguard Accessory Seal Replacement Environmental Rating Label EDSR Rubber asket (20A) V Ribs asket Clamp (20A) asket-clamp Assembly Mounting Screws (4) 30A Rubber asket and asket Clamp are pre-installed with EDSR. EDSR DEVICE OPERATIO To use, turn EDSR switch to the OFF position. Raise Receptacle Cover and insert mating plug. Refer to Ratings chart (page 7) for the list of mating configurations. The EDSR will work with all 20A and 30A EMA Configurations. For an environmental rating of IP66 "while-in-use", a Leviton etguard TM plug must be used. 6
Amps iring Voltage, AC 20 2P, 3 20 2P, 3 20 2P, 3 20 2P, 3 20 2P, 3 20 2P, 3 20 2P, 3 20 2P, 3 20 3P, 4 20 3P, 4 20 3P, 4 20 3P, 4 20 3P, 4 20 3P, 4 20 4P, 20 4P, 20 4P, 20 4P, 20 4P, 20 4P, 30 2P, 3 30 2P, 3 30 2P, 3 30 2P, 3 30 2P, 3 30 2P, 3 30 2P, 3 30 2P, 3 30 3P, 4 30 3P, 4 30 3P, 4 30 3P, 4 30 3P, 4 30 3P, 4 30 3P, 4 30 3P, 4 30 4P, 30 4P, 30 4P, 30 4P, 30 4P, 12 12 20 20 277 277 480 600 12/20 12/20 3Ø20 3Ø20 3Ø480 3Ø480 3Ø120/208 3Ø120/208 3Ø277/480 3Ø277/480 3Ø347/600 3Ø347/600 12 12 20 20 277 277 480 600 12/20 12/20 3Ø20 3Ø20 3Ø480 3Ø480 3Ø600 3Ø600 3Ø120/208 3Ø120/208 3Ø277/480 3Ø277/480 3Ø347/600 EMA COFI L-20 L-20 L6-20 L6-20 L7-20 L7-20 L8-20 L9-20 L14-20 L14-20 L1-20 L1-20 L16-20 L16-20 L21-20 L21-20 L22-20 L22-20 L23-20 L23-20 L-30 L-30 L6-30 L6-30 L7-30 L7-30 L8-30 L9-30 L14-30 L14-30 L1-30 L1-30 L16-30 L16-30 L17-30 L17-30 L21-30 L21-30 L22-30 L22-30 L23-30 HP Rating 3 3 1 1 20 20 2 2 20 20 2 Ratings Receptacle Type Cat. o. 30 4P, 3Ø347/600 L23-30 2 2830 etguard 2883 23 To maintain an environmental rating of IP4 and EMA 3R, Leviton EDSR enclosures do not require proprietary plugs or receptacles. Any (non-shrouded) EMA mating plug or receptacle can be used. For an environmental rating of IP66, UL Standard 0, and EMA environmental ratings of 4 and 12K, a Leviton etguard TM mating locking plug must be used. 7 23 23CM etguard 2320 23CM20 etguard 2330 23CM30 etguard 2340 230 24 24CM etguard 2420 24CM20 etguard 2430 24CM30 etguard 2 2 220 220 230 230 26 26CM etguard 2620 26CM20 etguard 2630 2630 2640 260 27 27CM etguard 2720 27CM20 etguard 2730 2730 2740 2740 28 28 2820 2820 2830 Type Plug Cat. o. Power Indicator 2311-PLC Power Indicator 2321-PLC Power Indicator 2331-PLC Black&hite 2341 Black&hite 231 Black&hite 2411 Black&hite 2421 Black&hite 2431 Black&hite 211 etguard Black&hite 221 etguard Black&hite 231 etguard Power Indicator 2611-PLC Power Indicator 2621-PLC Power Indicator 2631-PLC etguard Black&hite 2641 Black&hite C261 Black&hite 2711 Black&hite 2721 Black&hite 2731 etguard Black&hite 2741 etguard Black&hite 2811 etguard Black&hite 2821 etguard 2647 2648 2649 2674 267 2676 2681 2682 2683 2847 2848 2849 2874 287 2876 2877 2881 2882 Black&hite 2831 iring Diagram 1 1 2 2 3 3 4 6 6 7 7 8 8 9 9 11 11 12 12 13 13 14 14 1 16 17 17 18 18 19 19 20 20 21 21 22 22 23
iring Diagrams ire Diagram 1 EMA L-20 ire Diagram 2 EMA L6-20 ire Diagram 3 EMA L7-20 ire Diagram 4 EMA L8-20 ire Diagram EMA L9-20 ire Diagram 6 EMA L14-20 ire Diagram 7 EMA L1-20 ire Diagram 8 EMA L16-20 ire Diagram 9 EMA L21-20 ire Diagram EMA L22-20 ire Diagram 11 EMA L23-20 8
iring Diagrams ire Diagram 12 EMA L-30 ire Diagram 13 EMA L6-30 ire Diagram 14 EMA L7-30 ire Diagram 1 EMA L8-30 ire Diagram 16 EMA L9-30 ire Diagram 17 EMA L14-30 ire Diagram 18 EMA L1-30 ire Diagram 19 EMA L16-30 ire Diagram 20 EMA L17-30 ire Diagram 21 EMA L21-30 ire Diagram 22 EMA L22-30 ire Diagram 23 EMA L23-30 9
OTES
LIMITED 2 EAR ARRAT AD ECLUSIOS Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for two years from the purchase date. Leviton s only obligation is to correct such defects by repair or replacement, at its option, if within such two year period the product is returned prepaid, with proof of purchase date, and a description of the problem to Leviton Manufacturing Co., Inc., Att: Quality Assurance Department, 9-2 Little eck Parkway, Little eck, ew ork 11362-291. This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to two years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise. PRODUCT IFORMATIO For technical assistance, contact us at 1-800-824-300 Visit our website at www.leviton.com DI-000-0EDSR-00A
FOLD SCHEME THIS PAE IS OT TO BE PRITED I BOOKLET 11.0"." TM PowerSwitch 8." Saddle Stitch 8." Booklet 2 3 OVERALL SIzE Cat. o. 1 FIAL SIzE LEVITO ISTRUCTIO SHEET/MAUAL SPECIFICATIOS DI-000-0EDSR-00A Black Helvetica 0 Lb. offset Paper size: Overall size:." 8." Booklet Final fold size: DOCUMETATIO /A H2D 3/12/08