KENCO ENGINEERING COMPANY

Similar documents
T21 Thermal Differential Switch

LTX RF LEVEL SENSOR. Instruction Manual

IOM. LP-100 & LP-200 Pulse Point TM Installation & Operation Manual

RF Point Level Control with Sensor Monitor

DWYER INSTRUMENTS, INC. Phone: 219/ P.O. BOX 373 MICHIGAN CITY, IN 46361, U.S.A. Fax: 219/

Figure 1: WPR2 Dimensions and Hardware

VRF II Series SURPASSING SENSITIVITY FOR THE TOUGHEST APPLICATIONS FEATURES AND BENEFITS STANDARD VS. ADVANCED UNITS

1100 Series Piston Type Differential Pressure Gauges

12 Series Linear Electric Actuator Installation, Operation & Maintenance Manual

Installation and Operating Manual

12 Series Linear Actuators. Operation & Maintenance Manual, Analog Positioner Installation

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

Thermatel Model TD1/TD2

Masoneilan Series

Thermatel. Model TD1/TD2. Thermal Dispersion Flow/Level/Interface Switch. Installation and Operating Manual. with spherical probe

ATP-2040 Electric Damper Actuator/Transmitter

GE Oil & Gas. Becker * and Series V-0 Control Valves

CAPSU-PHOTOHELIC PRESSURE SWITCH/GAGE*

NEO-DYN MODEL 100P ENCLOSURE 7 ADJUSTABLE EXPLOSION-PROOF PRESSURE SWITCH

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

C.E. Niehoff & Co. C505, C527, C531, and C534 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING

Moniteur INSTALLATION & OPERATING INSTRUCTIONS. SERIES 40 Positioners. Installation and Operating Instructions Series 40 Positioners.

Low Profile Insertion Vortex

M9216 Series Electric Spring Return Actuators

Echotel Trident 91S/92S Ultrasonic Level Switches

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m)

Z4-Series DREXELBROOK DATA SHEET. Easy-Installation. Z-tron IV Point Level Switch, a reliable low-cost, on/off level switch.

1000 Series Piston Type Differential Pressure Gauges

LF Series At A Glance

Surepowr Series 100 Installation Manual

Shock/Vibration Control Switches Installation Instructions Models: VS2, VS2C, VS2EX, VS2EXR, VS2EXRB and VS94 GENERAL INFORMATION LISTED*

RP-4000 Reserve Power Control

LF Series Spring Return Direct Coupled Actuator

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

General Information... 2

Mid-West Instrument. Series 700 "Wet/Wet" Installation and Operating Instructions. Differential Pressure Transmitter

Model 116 DPI Switch Installation and Operating Instructions

Shock/Vibration Control Switches

Chapter Page. 1 Introduction Description 1

C.E. Niehoff & Co. C703/C703A and C706 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

System 350 P352AB Electronic Pressure Control Series

Electric Modulating Actuator Installation, Operation & Maintenance Manual

Solstice Electric Fryers SE Series Service Manual

Pressure Controller. Cataloge K Code Characteristics Index. K00-2 Pressure Controller Brief Introduction

Hot Tap Insertion Vortex

DW PADDLE-BELLOWS FLOWMETER & SWITCH

I-BFV.KIT Butterfly Valve Gear Operator Replacement

MODULATING SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION

COUNTER CLOCKWISE FOR CLARITY (SEE MANUAL FOR SPECIFIC WATER & DUST TIGHT AP LOCAL ELEMENT ENCLOSURE ROTA FLAT PARALLEL TO FLOW.

DIAMOND POINT VIBRATING PROBES

SUREPOWR TM SERIES -SURE 24/25 FIELD INSTALLATION INSTRUCTIONS

Flow Computer Installation

UNIVERSAL Flow Meters

Mobrey MLT100. Displacer Level Transmitter. Product Data Sheet February 2015 IP119, Rev CA. Level, contents or interface measurement transmitter

Control. Part B, Section 2. This section covers the following unit configurations. 3400V 3500V. Voltage 4. Pump Piston (E, F, G)

KDM ARMORED FLOW METER & SWITCH

331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH

Installation and Operating Instructions Electro-Pneumatic Rotary Positioner SP-21. Description of Device. Part Number System

DMC mA Positioner

Quarter Master Series 94 Actuator

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

ELECTRIC ACTUATOR HVAC/BAC ELECTRIC IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

DW PADDLE-BELLOWS FLOWMETER & SWITCH

For additional information, please visit our website at SENSOR SPECIFICATIONS

BULLETIN NO.ELEC IM121/10A Replaces IM121/09A

SIGNET 7002 Vortex Flow Sensor ENGLISH

CAP ANALOG 4100 INSTALLATION & OPERATION MANAUL

Valtek Position Pac GENERAL INFORMATION INSTALLATION INSTRUCTIONS OPERATION. Valtek Linear Actuators

Model 124 Filter Minder & Model 124

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

Type E-10, E-11 Hazardous Area Explosion-proof Transmitters

Surepowr Series Sure 150

SM-1000 SERIES ROTARY ACTUATORS

Rosemount 8750WA Magnetic Flowmeter System For Water and Wastewater Industries

CAPTROL MODEL 500 MANUAL # R.F. Capacitance Point Level Switch

AQUASWITCH AQUASWITCH & 760-A AQUASWITCH

Flow meters, Flow switches and Flow transmitters

tekson TS Series Low Cost Ultrasonic Water Energy Flow Measurement

RESISTIVITY MONITOR/CONTROLLERS

Remote Temperature Controller for Heated Mold Shoes, using a RTD/Digital Display, # C (version pre-2009).

MAGNETIC LEVEL GAUGES

ANDCO Eagle Actuator Instruction Manual

OPERATIONS & INSTALLATION MANUAL

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017

( )

(770)

7330 Pro-Stik II Magnetostrictive Level System

OPERATING & SERVICE PARTS MANUAL SM20ES ENERGY SMART WRAPPER

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages.

ComfortPoint Programmable Lon, VAV/Unitary Controllers

Electric Actuator Instructions

8460SRC Replacement Chassis for Scully ST-6 and Biclops Monitors

Radius, LLC Electric quarter turn actuator EW series Installation, Maintenance and Operating Manual

Safe & Secure Series Electric Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual

ONYX VALVE CO MODEL DAO-PFO Installation & Maintenance

INTRODUCTION / TABLE OF CONTENTS

Transcription:

KENCO ENGINEERING COMPANY P.O. BOX 470426 TULSA, OK 74147-0426 PHONE: (918) 663-4406 FAX: (918) 663-4480 www.kenco-eng.com e-mail: info@kenco-eng.com SERIES KTD THERMAL DIFFERENTIAL FLOW/LEVEL SWITCH INSTALLATION / OPERATION INSTRUCTIONS TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 2 2. PRINCIPLE OF OPERATION... 2 3. MODEL DESCRIPTION... 2 4. INSTALLATION... 3 5. WIRING CONNECTIONS... 4 6. OPERATIONAL CHECK... 5 7. PRE-CALIBRATION... 5 8. CALIBRATION (Level Switch)... 6 9. CALIBRATION (Flow Switch)... 7 10. MAINTENANCE & TROUBLESHOOTING... 8 11. SPECIFICATIONS... 8 Page 1

GENERAL DESCRIPTION The Series KTD Thermal Differential Switch is the state-of-the-art in gaseous and liquid flow switching or liquid level / interface control. Flow or level detection is accomplished by using a high resolution thermal differential technique. The standard sensor wetted parts are of durable 316L series stainless steel, all welded construction with no moving parts. The switch is easy to install and adjust, giving reliable, low maintenance performance in the most demanding applications. PRINCIPLE OF OPERATION The Series KTD Thermal Differential Switch uses a thermal differential technique to measure liquid level or interface by sensing changes in the thermal heat transfer characteristics of the media where it is located. The sensor consists of a pair of matched Resistance Temperature Detectors (RTD s) encased in twin 316 series, stainless steel tubes. One RTD is self-heated using a constant DC current. The other sensor is unheated and provides an accurate ambient process temperature reference. The thermal differential created between the heated and reference RTD pair is a function only of the media with which the sensor is in contact. The differential is greatest when no liquid is present (dry condition) and decreases as liquid quenches the switch sensors (wet condition). Hydrocarbons generally have lower heat-transfer characteristics than aqueous-based materials so liquid-liquid interface detection is possible. In general, any two media will exhibit some difference in heat-transfer characteristics. Thus, the switch can be calibrated to detect the interface between two immiscible liquids. This switch can also be used as a no-flow or a low flow switch. In this case the actual flow of the liquid or gas provides the cooling effect. In other words, the lower the flow rate the greater the temperature differential between the (2) RTD s. Solid-state electronics transform the temperature differential into a voltage that is compared to a control voltage to actuate a relay and indicate a change in state (wet vs. dry). The instrument head at the top of the unit contains the Switch electronics board which is easily removable from the instrument head so that field wiring can be connected to the field terminal block. MODEL DESCRIPTION - - - - - - Model Process Connection Sensor Material Insertion Length (Inches) Input Power Configuration Options Model Sensor Material Description Code Description Code Level Switch KTDL 316L SS S6 Flow Switch KTDF 304 SS S4 304L SS SL Process Connection Hastelloy-B HB Description Code Hastelloy-C HC ½ NPT 050 Inconel 600 IO ¾ NPT 075 Monel MN 1 NPT 100 Alloy-20 A2 1½ Sanitary 3A1 Special Material SM 1 150# ANSI Flange RA1 2 150# ANSI Flange RA2 Input Power 1 300# ANSI Flange RB1 Description Code 2 300# ANSI Flange RB2 110 Vac 110 Low Flow Sensor LFS 220 Vac 220 Special Connection SPL 24 Vdc 24D 24 Vac 24A Configuration Description Code Insertion Length Integral Mounting LE 002.00 (standard) Remote Mounting RE 000.50 120.00 (optional) Options Options (cont.) Options (cont.) Options (cont.) Description Code Description Code Description Code Description Code No Options 00 Extended Neck EN Additional Cable CA SS Tag TG RTD Output RT *High Temp (850ºF) HT Variable Insertion VI Sensor Live Tap LT *Medium Temp (572ºF) MT Factory Calibration CB CE Approved CE Explosion-proof Window XW Thermocouple Output TO * Remote Mounting Required Installed in Tee TE Page 2

INSTALLATION Unpack the switch carefully. Inspect all units for damage. Report any damage to carrier immediately. Check the contents against the packing slip and purchase order. Kenco s Thermal Differential Flow / Level Switches are manufactured to the highest quality standards. These instruments use electronic components that can be damaged by static electricity. Make sure that you are properly grounded before starting installation. Insure that all electrical connections are properly made, and that there are no floating connections. Mechanical Installation The Series KTD Switches have a ¾ NPT (standard) process connection. When used as a level / interface switch, and horizontally mounted, the sensor must be oriented so that the RTD s are parallel with the liquid surface. When used as a flow switch the sensor must be oriented so that the RTD s are perpendicular with the flow direction. Use a 1-1/8 open end wrench to tighten the sensor in the process connection. Use the hex flats on the sensor for tightening. DO NOT use the instrument housing for tightening. Rotation of the instrument housing in respect to the sensor can cause internal wiring damage, and will void the warranty. Page 3

Electrical Installation It is recommended that conduit be installed onto the ¾ NPT connection on the electronics housing. A seal drain fitting should be used to prevent moisture from entering the switch. In high humidity areas, use a breather drain to minimize moisture intrusion All wiring, conduit, and fittings must conform to local electrical codes for the location selected. If the transmitter is to be used in a Hazardous Area, the applicable sections of the National Electric Code must be followed as well. WIRING CONNECTIONS Before starting installation procedures in hazardous areas, insure that all power sources have been turned off and locked out. Live electrical circuits can ignite flammable gasses and dusts. 1. Remove the cover from the instrument enclosure. 2. Loosen the (2) screws holding the electronics module in place. These are spring-loaded captive screws. They will pop-up when loosened sufficiently. Remove the electronics module from the instrument enclosure. 3. Hold the module firmly around the transformer and pull it out of the enclosure. No tools are necessary to remove the module. Field Wiring (TBB) Sensor Wiring (TBA) Page 4

4. Pull the power/signal wires through the conduit opening. 5. Connect Power and relay wiring to Terminal Block (TBB) see figure on previous page. 6. Reinstall the Electronic Module and tighten the (2) captive screws. 7. Reinstall the Instrument Enclosure cover. OPERATIONAL CHECK After the switch is installed, and the level is below the sensor or there is no flow, perform the following test procedure to insure proper function. 1. Remove the Instrument Enclosure Cover. 2. Apply power. 3. Verify that either the Red or Green LED is illuminated. 4. If neither LED is on, refer to the Troubleshooting section. PRE-CALIBRATION LED States The Red and Green LED s indicate the status of the sensor, and are independent of the relay status. When the Red LED is illuminated, this indicates a Dry (Level) or No/Low (Flow) condition. When the Green LED is illuminated, a Wet (Level) or High (Flow) condition is indicated. Jumper Settings There are (2) jumpers that must be set prior to calibration: J1 Model KTDL There is no J1 Jumper or Pins Model KTDF Leave the Jumper in place for Flow Applications; Remove the Jumper if you decide to use this model for a Level / Interface Application Page 5

J2 This sets the Failsafe condition of the switch. The jumper should cover the (2) left-most pins for High Level Failsafe (HLFS) condition, or the (2) right-most pins for Low Level Failsafe (LLFS) condition. See the table below for the comparison of the two conditions, as well as the condition of the Red and Green LED s. J2 J2 HLFS LLFS Sensor Status Wet (Level) or High Flow Dry (Level) or Low/No Flow Red LED Off On Green LED On Off Fail Safe Relay Relay Terminals Setting Condition NC to C NO to C HLFS De-Energized Closed Open LLFS Energized Open Closed HLFS Energized Open Closed LLFS De-Energized Closed Open CALIBRATION (Level Switch) (Refer to Page #5 for location of controls) NOTE: For optimum performance, the calibration must be done at actual process temperature. 1. Remove the Instrument Enclosure Cover 2. Ensure that the level is below the sensor tips, and that the tips are dry. 3. Apply power. Allow the sensor to warm-up for five minutes. 4. Set the Trip Point Adjust pot to 0 (fully counterclockwise). 5. Set the Zero Adjust pot so that the Red LED just does illuminate. This is a 25-turn pot. If the Green LED is on, turn the pot counterclockwise. If the Red LED is on, turn the pot clockwise. 6. Toggle the Zero Adjust pot back and forth until the trip point is well defined. Leave the Red LED Illuminated. 7. Raise the level of the liquid in the vessel until the sensor tips are covered. 8. Set the Trip Adjust pot to 100 (fully clockwise). 9. Set the Span Adjust pot so that the Green LED just does illuminate. This is a 25-turn pot. If the Green LED is on, turn the pot clockwise. If the Red Led is on, turn the pot counter clockwise. 10. Toggle the Span Adjust pot back and forth until the switching point is well defined. Leave the Green Led illuminated. 11. Set the Trip Point Adjust pot to 80 and the calibration is complete. Setting this pot to 80 gives an approximate equal trip time from wet-to-dry and dry-to-wet. Setting this pot closer to 0 will speed up the dry-to-wet time, and slow down the wet-to-dry time. Setting this pot closer to 100 will slow down the dry-to-wet time, and speed up the wet-to dry time. Page 6

CALIBRATION (Flow Switch) (Refer to Page #5 for location of controls) NOTE: For optimum performance, the calibration must be done at actual process temperature and pressure conditions in gasses, or actual process temperature in liquids. NOTE: The sensor tips must be perpendicular to the flow direction (see Page #3 View C-C) 1. Remove the Instrument Enclosure Cover 2. Ensure that the pipeline is filled with fluid and at no or minimum flow. 3. Apply power. Allow the sensor to warm-up for five minutes. 4. Set the Trip Point Adjust pot to 0 (fully counterclockwise). 5. Set the Zero Adjust pot so that the Red LED just does illuminate. This is a 25-turn pot. If the Green LED is on, turn the pot counterclockwise. If the Red LED is on, turn the pot clockwise. 6. Toggle the Zero Adjust pot back and forth until the trip point is well defined. Leave the Red LED Illuminated. 7. Adjust the liquid or gas flow to maximum velocity for the application. Insure that the flow is homogenous, constant, and if a liquid free of bubbles. NOTE: The maximum allowable flow rate for the unit is 2.5ft/sec (aqueous liquid), 5 ft./sec (hydrocarbon liquid) or 500ft./sec (gases). 8. Set the Trip Adjust pot to 100 (fully clockwise). 9. Set the Span Adjust pot so that the Green LED just does illuminate. This is a 25-turn pot. If the Green LED is on, turn the pot clockwise. If the Red Led is on, turn the pot counter clockwise. 10. Toggle the Span Adjust pot back and forth until the switching point is well defined. Leave the Green Led illuminated. 11. If the switch is to be used for flow no flow, set the Trip Adjust pot to 50 and go to Step #14. NOTE: This adjustment can be set for tripping points between 10% and 90% of the span from no flow to maximum flow). 12. A more exact flow rate setting may be made by establishing the flow at the desired rate with a separate flow meter and proceeding to Step #13. 13. Adjust the Trip Adjust pot to obtain a trip point as exhibited by the LED Status Lights. If trip on decreasing flow is desired, set for Red Illumination. If a trip on increasing flow is desired, set for Green Illumination. 14. Verify that the switch will reset by returning the actual product flow to maximum or minimum flow rates. The calibration is complete. Page 7

MAINTENANCE & TROUBLESHOOTING The sensor can be cleaned by soaking, spraying or ultrasonic cleaning. Verify material compatibility before using any strong solvent or acid on the sensor. DO NOT sandblast or scour the sensor with abrasives. The sensor could be damaged by this process. TEST #1 - Power & Continuity Check 1. Remove power. 2. Remove Instrument Enclosure cover. 3. Loosen (2) Captive Screws (see Page #4) 4. Remove Electronic Module by grasping the Transformer, and pulling straight out. 5. Apply power. Verify the correct voltage at pins 7 (+ for DC) & 8 (- for DC) of Terminal Block TBB. 6. If the voltage is correct, remove power and check the fuse (F1 see Page #5). If the fuse is bad, replace it with the appropriate fuse. 7. If the fuse is OK, proceed to the Functionality Check. TEST #2 - Functionality Check (Perform TEST #1 first) 1. Remove power. 2. Allow a 5 minute cool-down period. 3. Measure the resistance of each RTD (Terminal Block TBA). a. Measure the resistance between Pins 1 & 6 (First RTD). b. Measure the resistance between Pins 3 & 5 (Second RTD). 4. The resistance values for Step #3 should be 110Ω ± 10Ω @ 70ºF. Also, they must be within 5% of each other. 5. Measure the resistance between Pin #1 of Terminal Block TBA and the Instrument Enclosure. It should be greater than 20Meg Ohms. 6. If the resistance values are not as specified above, the sensor must be replaced. 7. If the resistance values are correct, the Electronics Module must be replaced. SPECIFICATIONS Description Specification Power Supply AC 110Vac or 220Vac @ 50/60 Hz DC 24Vdc Output 5A DPDT Failsafe is field selectable Temperature Range (Electronics) -40ºF to 140ºF (-40ºC to 60ºC) Standard -100ºF to 390ºF (-70ºC to 200ºC) Temperature Range Medium Temp. -100ºF to 572ºF (-40ºC to 300ºC) (Sensor) High Temp. -100ºF to 850ºF (-40ºC to 458ºC) Pressure Range Atmospheric to 3000psig Aqueous Liquids 0.01 2.5 feet/second Operating Range (Flow) Hydrocarbon Liquids 0.01 5.0 feet/second Gasses 0.1 500 feet/second Response Time 0.5 to 5.0 seconds (media dependent) Stability <0.5% from calibrated setpoint over a range of ±50ºF Repeatability ±1.0% Page 8