ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split System Air Conditioners HB 180/240, HF -15,-20 Models Only

Similar documents
ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS

LOW AMBIENT ACCESSORY INSTALLATION INSTRUCTION

ELECTRIC HEAT ACCESSORY INSTALLATION INSTRUCTION. 20, 30 & 40 kw for 15 Ton Split System Air Conditioners Models: LB180 & LL A-0102

INSTALLATION INSTRUCTIONS DNLOWAMB015A00, DNLOWAMB016A00

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

Installation Instructions Part Numbers: CRLOWAMB018A00 THROUGH CRLOWAMB026A00

INSTALLATION INSTRUCTION

Installation Instructions

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

INSTALLATION INSTRUCTIONS CMH-7A LOW AMBIENT CONTROL

ACCESSORY KIT INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS CMH-21 Low Ambient 460V Fan Speed Control

ACCESSORY KIT INSTALLATION INSTRUCTIONS

DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS

Installation Instructions

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING

Installation and Start-Up Instructions

Installation Instructions

INSTALLATION INSTRUCTIONS FOR EGA AND EGH SERIES ELECTRIC HEATERS IN V OR H SERIES UNITS

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

OIL PRESSURE SAFETY CONTROLS

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS

PEAKTRONICS DMC-101 ADDITIONAL FEATURES. DC Motor Controller, 5A DMC-101

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS FEATURES DESCRIPTION. H5CE090 & H3CE AND 10 NOMINAL TONS (World 50HZ)

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

E4FH, E5FH SERIES 12 SEER HEAT PUMP

TECHNICAL GUIDE DESCRIPTION MODELS: D4HH 024 THRU 180 HORIZONTAL FEATURES SINGLE PACKAGE AIR CONDITIONERS HORIZONTAL INDOOR & CONDENSER AIR FLOW

System 350 P352AB Electronic Pressure Control Series

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2014 Supersedes 8/2012

534HS Pressure Transmitter

Predator Model Number Nomenclature

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS

NL SERIES - 13 SEER SINGLE PACKAGED AIR CONDITIONER (R-410A, STYLE B)

INSTALLATION INSTRUCTION

Installation Instructions

Application Engineering

M5200 Industrial Pressure Transducer

30A SMART ENERGY MANAGEMENT SYSTEM TM

Supersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO:

SAVE THESE INSTRUCTIONS

TECHNICAL GUIDE GENERAL HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AND WATER COOLED AIR CONDITIONERS


ACCESSORY KIT INSTALLATION INSTRUCTIONS

12 Series Linear Actuators. Operation & Maintenance Manual, Analog Positioner Installation

PREMIUM SERIES 22 SEER SINGLE SPLIT DUCTLESS, COOLING SYSTEMS (CONTAINS INDOOR AND OUTDOOR MODELS)

P70, P72, and P170 Series Controls for High Pressure Applications

P445 Series Electronic Lube Oil Control

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

SUBMITTAL DATA SHEET FEATURES. SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15, 20 & 25 TONS MODELS: J07 thru 25NC, 2-PIPE J10 thru 20ND, 4-PIPE

SAVE THESE INSTRUCTIONS

GE Sensing & Inspection Technologies

Copeland Screw TM Compressors

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS

RP-4000 Reserve Power Control

ECCII to ECCIII Upgrade Kit

ACCESSORY KIT INSTALLATION INSTRUCTIONS

PBA Series Prelube Controls

CHILLER MODEL NO. YS SOLID STATE STARTER, MODEL NO. SSS, L B OPTIONAL FACTORY INSTALLED DISCONNECT SWITCH AMPS OR

Application Engineering

P66 Series Electronic Fan Speed Controls

RVS-DN Digital Reduced Voltage Motor Starter

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

ELECTRICAL SYSTEM RP-7

5001TCP SPEED CONTROLLER

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD

BAS Construction Checklist

Installation Instructions 300 A Current Sensor Kit for D1h/D3h/D5h/D6h Enclosure Sizes VLT Series FC 102, FC 103, FC 202, and FC 302

Installation/ Operation Maintenance. VariTrac Dampers

Micro-Air Corporation Route 526 Allentown, NJ 08501

Wiring Diagrams DIAGRAM INDEX

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS

K10 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual

Installation Instructions 500 A Current Sensor Kit for D2h/D4h/D7h/D8h Enclosure Sizes VLT Series FC 102, FC 103, FC 202, and FC 302

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide

Installation Instructions

In-Duct High Pressure Nozzle Humidification System - HP HVAC Series Submittal Drawings

P70, P72 and P170 Series Controls for High Pressure Applications

5001TCP SPEED CONTROLLER

KE2 FanControl Installation Instructions

LIGHT COMMERCIAL - 3 HP ECM MOTOR / CONTROLLER HIGH STATIC DRIVE KITS

VTZ variable speed Reciprocating compressors

D M S 760 C01 A A 1 1

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS DESCRIPTION FEATURES YTG-A-0806

UARDIAN TECHNICAL GUIDE MODELS: GCGD18 THRU 60

All Greenerd Presses are designed and built to ANSI B (R-2000) compliance. 4-POST HYDRAULIC DEEP DRAW PRESS

Mid-West Instrument. Series 700 "Wet/Wet" Installation and Operating Instructions. Differential Pressure Transmitter

Figure 1: WPR2 Dimensions and Hardware

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages.

COMMUNICATIONS SETUP DBS STARTER PANEL

MM1/MM2 INSTALLATION & MAINTENANCE INSTRUCTIONS

Transcription:

ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split System Air Conditioners HB 180/240, HF -15,-20 Models Only GENERAL These split-system condensing units are designed to operate at ambient temperatures down to 40 F. This accessory will insure safe operation at ambient temperatures down to 0 F. The VLT6000 control monitors both refrigerant systems. It will vary the speed of the condenser fan based on the system with the highest discharge pressure. This instruction provides all the necessary information to properly field-install a low ambient accessory on the condensing units listed in Table 1. Components that are supplied in the respective accessory are listed in Table 2, and pictured in Figure 1. TABLE 1: APPLICATION DATA ACCESSORY MODEL # VOLTAGE UNIT 2LA04702558 575 HB 180, HL -15 2LA04702758 575 HB 240, HL -20 TABLE 2: ACCESSORY COMPONENTS ITEM QTY. PART NO. DESCRIPTION 1 1 ea. 024-34534-000 VLT6000 Condenser Fan Speed Control 2 2 ea. 025-38680-000 Pressure Transducer 3 2 ea. 025-38681-000 Wire Harness Assembly 4 1 ea. 025-37466-000 Power Wire Harness 5 2 ea. 023-20566-000 Tee Connector 6 4 ea. 021-17153-000 Screw HEX ¼-20 X 1.0 7 1 ea. 025-19209-000 3/8 Bushing 8 2 ea. 025-14284-000 1 3/8 Bushing 9 6 ea. 025-09607-000 Wire Tie 10 1 ea. 025-37455-000 0 Degree Switch 11* 2 ea. 025-37399-575 15 Ton Crankcase Heater 025-37425-575 20 Ton Crankcase Heater * Crankcase Heaters supplied are dependent on accessory ordered. FIGURE 1 - ACCESSORY COMPONENTS The 2LA047 series low ambient accessories are intended for use with the 15-20 Ton Split System condensing units only. UPG cannot guarantee proper operation for any application of this VLT 6000 controller for other equipment or applications. Contact your local branch or distributor for any application related questions. Improper installation, adjustment, service or maintenance can cause injury or property damage. Therefore, only a qualified installer or qualified service personnel should perform this conversion. Unitary Products Group

If the unit is connected to power sources, make sure that all electrical power to the unit has been disconnected prior to servicing. Hand thread the tee to the discharge line port. Tighten and secure the connection, making sure the transducer is mounted vertically. See Figure 3. Perform a leak test on fittings and connections before putting the system into operation. Before installing accessory, read all of this installation instruction. 1. Remove the condensing unit control box access panel. MOUNT TRANSDUCER VERTICALLY MOUNT TRANSDUCER VERTICALLY INSERT WIRING HARNESS PLUG ¼ In. SAE FEMALE FITTING WITH SCHRADER VALVE DEPRESSOR TEE TO DISCHARGE LINE PORT TO DISCHARGE LINE PORT FIGURE 3 - PRESSURE TRANSDUCER MOUNTING FIGURE 2 - PRESSURE TRANSDUCER Do not remove the plastic plugs from the transducers until they are ready to be installed. 2. Attach the pressure transducers to the connection tee (provided in accessory). The pressure transducer has a ¼ In. SAE female flare with Schrader valve depressor for mounting to the tee. See Figure 2. NOTE: This procedure must be repeated for each system. 3. Attach wiring harness plug to transducer. Route sensor wires with the discharge pressure switch wires back to control box. Run wires through the bushing (provided), using knock out located near the control in the bottom of the unit control box. See Figure 4. RED WIRE = 10.0 VDC SUPPLY BLACK WIRE = COMMON WHITE WIRE = OUTPUT NOTE: Two tees are provided to insure the transducers are mounted vertically. Hand thread the transducer to the tee. Tighten and secure the connection. Remove the Schrader valve cap from the discharge line port (provided). FIGURE 4 - WIRE HARNESS ASSEMBLY 4. Access the VLT6000 control terminal blocks. See Figure 5. Remove the terminal access cover. 2 Unitary Products Group

FIGURE 5 - VLT6000 CONTROL TERMINAL BLOCK LOCATION Connect Red Wire from Transducer #1 to terminal (50) on the VLT6000. Connect Black Wire from Transducer #1 to terminal (55). Connect White Wire from Transducer #1 to terminal (53). Connect Bare (shield) Wire from Transducer #1 to the grounding terminal. Connect Red Wire from Transducer #2 to terminal (50). Connect Black Wire from Transducer #2 to terminal (55). Connect White Wire from Transducer #2 to terminal (54). Connect Bare Wire (shield) from Transducer #2 to the grounding terminal on VLT6000 control. 5. Wire transducers to the VLT6000 control. See Figure 6. OUTPUT POWER (MOTOR) TERMINAL BLOCK INPUT POWER (MAINS) TERMINAL BLOCK FAN MOTOR # 2 FAN MOTOR # 1 VLT 6000 ENCLOSURE FIGURE 7 - FAN MOTOR #1 LOCATION CONTROL TERMINAL BLOCK FIGURE 6 - POWER AND CONTROL TERMINAL BLOCKS Route power wires, motor leads, and transfer signal wires through separate knockouts. See Figure 6. 6. Cut two lengths of flexible conduit (Field Supplied) to connect from the VLT6000 Control to the condensing unit control box. Conduit #1 should run from the bottom of the VLT6000 enclosure to the condensing unit control box, using knock outs provided. In conduit #1 insert three # 14 Gage wires marked on both ends (field supplied). Conduit #2 should run from the bottom of the VLT6000 enclosure to the condensing unit control box, using knock outs provided. In conduit #2 insert shielded power cable supplied in accessory. Allow additional conduit length to remove the VLT Control enclosure from the top rail and place on side for servicing. Unitary Products Group 3

7. Wire condenser fan motor #1 to the VLT6000 control. See Figure 6 and SWD Figure 8. The VLT6000 must be wired to operate fan motor #1. Fan motor #2 is already controlled by factory installed pressure switches. Disconnect wire 136/ from terminal (T1) on contactor (M2). Disconnect wire 137/BRN from terminal (T2) on contactor (M2). Disconnect wire 138/PR from terminal (T3) on contactor (M2). Connect wire 136/ to terminal (96 / U) on the VLT6000 control. Connect wire 137/BRN to terminal (97 / V). Connect wire 138/PR to terminal (98 / W). Connect () wire of power harness to terminal (T1) on contactor (M2) and to terminal (91 / L1) on the VLT6000 control. Connect (RED) wire of power harness to terminal (T2) on contactor (M2) and to terminal (92 / L2). Connect (WHT) wire of power harness to terminal (T3) on contactor (M2) and to terminal (93 / L3). Connect bare wire of power harness to the grounding terminal on VLT6000 control. 8. Remove existing low ambient switch (LAS) and replace with new 0 F low ambient switch (provided). See Figure 9. 9. Install additional sump heaters on compressor #1 and compressor #2. Wire each sump heater parallel to the existing heater. Ground the new crankcase heaters with the existing crankcase heater ground. 10. The parameters for proper operation are preset in the VLT6000. Parameter settings are listed on a label in the enclosure and later in this document. The activation pressures are preset at the factory. 11. Secure wiring in the enclosure in a neat workman like manner using wire ties. 12. Install the enclosure front cover and restore power to the unit. 13. Verify proper unit operation. A call for cooling closes the (M2) contactor powering the VLT6000 control. As the discharge pressure rises above 210 PSI. during startup on either system #1 or #2 compressor, the VLT6000 control will increase the speed of condenser fan #1 accordingly. The scroll compressor produces a rapid rise in discharge pressure upon startup and this, depending on the ambient temperature, will result in full speed operation of condenser fan #1. After the discharge pressure has stabilized, the speed of the condenser fan #1 may decrease especially during times when the ambient temperature is below 80 F. After the #1 system has stabilized and compressor #2 is energized, usually the speed on condenser fan #1 will increase, compensating for the discharge pressure rise. As the discharge pressure begins to fall below the 210 PSI. setpoint, the drive will reduce the speed of condenser fan #1. As the ambient temperature drops below 40 F the #1 condenser fan will slow to the minimum speed. The #2 condenser fan will disengage when the discharge pressure drops below 180 PSIG as the ambient temperature falls. The discharge pressure of system #1 and/or #2 will increase when condenser fan #2 is disengaged; condenser fan #1 will then, typically, speed up. 14. Contact York Technical Service for questions regarding installation. NOTE: VLT6000 See Table 3 for the parameter settings in the drive. For specific instructions on the VLT6000, refer to the Danfoss manual shipped with the kit. The VLT6000 accepts one or two input signals from pressure transducers on the compressor discharge lines. The control will respond to the higher voltage signal. It will modulate the speed of fan 1 to hold discharge pressure at 210psi; if fan 1 cannot keep the discharge pressure at 210psi, the fan switch will energize fan 2 at 230psi (and typically fan 1 will slow down). If pressure falls below 180psi, fan 2 will drop out (and typically fan 1 will speed up). 4 Unitary Products Group

VLT 6000 L1 L2 L3 M5-1 T1 M5-2 T2 M5-3 T3 INPUT POWER (MAINS) TB 91, (L1) 92, (L2) 93, (L3) OUTPUT POWER (MOTOR) TB (U), 96 (V), 97 (W), 98 P 15 S 15 136 / BK 137 / BR 138 / PR 1 2 3 BRN PRP T1 T2 T3 FM 1 M GND CONTROL TERMINALS 50 53 54 55 4 GRN Pressure Transducer System 1 WHT RED Pressure Transducer System 2 WHT RED FIGURE 8 - SIMPLIFIED WIRING DIAGRAM Unitary Products Group 5

System # 1 BOTTOM OF CONTROL BOARD RB1 HPS2 P 9 S 9 - SYS 1 1 21 216 / O HP1 S 11 - SYS 1 P 11 LPS2 3 4 BLU 281 / BL LAS1 2 3 4 5 FS1 FS2 HPS1 LPS1 5 6 7 8 214 / BL 215 / BL 217 / O LP1 283 / BL 284 / BL 6 LOW AMB. 7 9 FAN OVER 10 BLU FIGURE 9 - LAS - LOW AMBIENT SWITCH 6 Unitary Products Group

TABLE 3: PARAMETER SETTING Parameter Condenser Fan 2 Setup #1 Active setup 6 PSI 2 What the readout will show 7 CUSTOM READ [UNITS] Main display will show system pressure 8 Reference (unit) Top Left Display (drive reference: open loop = Hz; closed loop = in WG) 9 Frequency [%] Top Middle Display (closed loop = actual pressure) 10 Motor Current (A) Top Right Display (motor current in Amps) 100 Closed Loop Feedback from transducer controls speed 101 AEO Function Motor torque curve 102 1.1 Motor Power (1.1 kw = 1.5hp) 103 575 Motor Voltage 104 60 Motor Frequency 105 2.3 Motor Current 106 1140 Rated Motor Speed 201 20 Hz Minimum Motor Speed Frequency 202 60 Hz Maximum Motor Speed Frequency 204 0 Minimum allowable setpoint, equal to parameter 413 in closed loop 205 500 Maximum allowable setpoint, equal to parameter 414 in closed loop 206 5 seconds Ramp up time 207 10 seconds Ramp down time 209 --- Frequency to operate upon loss of analog input signal 210 External/preset Reference location (external transducer) 211 0 Preset reference 1 212 0 Preset reference 2 213 0 Preset reference 3 214 0 Preset reference 4 216 1 Frequency bypass bandwidth 217 41 Frequency bypass 1 (skip 41 Hz motor speed) 300 No operation Digital input 16 301 No operation Digital input 17 302 Start Jumper terminal 12 or 13 to terminal 18 to start the drive whenever powered 303 No operation Digital input 19 304 Coast inverse Jumper terminal 12 or 13 to terminal 27 to enable to drive to run 305 No operation Digital input 29 306 No operation Digital input 32 307 No operation Digital input 33 308 Feedback Pressure transmitter 1 is wired to terminal 53 309 0 VDC Transmitter voltage at minimum pressure 310 10 VDC Transmitter voltage at maximum pressure 311 Feedback Pressure transmitter 2 is wired to terminal 54 312 0 VDC Transmitter voltage at minimum pressure 313 10 VDC Transmitter voltage at maximum pressure 314 No operation Assumes terminal 60 is not used 315 0 ma Unitary Products Group 7

TABLE 3: PARAMETER SETTING (CONTINUED) Parameter Condenser Fan 316 20 ma 317 2 seconds Length of time analog input must be gone before the drive reacts 318 No function How the drive reacts on loss of analog input (only works if minimum voltage is greater than 0) 400 Infinite Automatic Reset function 402 Enable Flying start 403 Off Length of time to run at minimum speed before shutting off (part of sleep mode) 404 --- Set about 1 Hertz above 201 (part of sleep mode) 405 --- Frequecy to turn back on (part of sleep mode) 406 --- 413 0 psi Pressure value at minimum transducer signal 414 500 psi Pressure value at maximum transducer signal 415 PSI 2 Text string to display on the keypad 417 MAX Feedback function 418 210 psi Desired pressure to maintain 420 Inverse Control response; "inverse" = motor speed will increase when pressure increases 421 Enable PID antiwindup 422 20 Hz PID Start Frequency 423 2 Proportional gain 424 3 Integral time 425 Off Differential time (leave OFF) 427 0.02 First order filter on feedback signal Subject to change without notice. Printed in U.S.A. Copyright by Unitary Products Group 2004. All rights reserved. Supersedes: Nothing 035-20208-000-A-0904 Unitary 5005 Norman Products York OK Group Drive 73069