Type 3271 Pneumatic Actuator. Actuator area: cm². Mounting and Operating Instructions EB EN

Similar documents
Type 3271 and Type 3277 Pneumatic Actuators. Actuator areas: 175 and 750 cm². Type 3271 Type Mounting and Operating Instructions EB EN

Mounting and Operating Instructions EB 8053 EN. Series 250 Type and Type Pneumatic Control Valves

Mounting and Operating Instructions EB 8048 EN. Type and Type Pneumatic Control Valves Type 3249 Aseptic Angle Valve

Type 3379 Pneumatic Actuator. Mounting and Operating Instructions EB 8315 EN

Type 3571 Pneumatic Actuator. Actuator areas: 27 in² 54 in² 116 in². Original instructions. Mounting and Operating Instructions EB 8820 EN

Mounting and Operating Instructions EB 8097 EN. Type and Type Pneumatic Control Valves

Series 250 Pneumatic Control Valves Type and

Mounting and Operating Instructions EB EN. Type 3372 Electropneumatic Actuator. Actuator area: 120 and 350 cm² With Type 3725 Positioner

EB EN. Type 3372 Electropneumatic Actuator. Translation of original instructions

Mounting and Operating Instructions

Mounting and operating instructions EB 8093 EN. Series 240 Pneumatic Control Valve for Cryogenic Temperatures. Type and

Mounting and Operating Instructions EB EN. Type 3271 Pneumatic Actuator. Actuator area: 1000 cm². Translation of original instructions

Mounting and Operating Instructions EB 8392 EN. Series 3710 Type 3710 Reversing Amplifier

Mounting and Operating Instructions EB 8091 EN. Pneumatic Control Valve Type and Type Type with 120 cm 2 actuator

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil

Mounting and Operating Instructions EB 8039 EN. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve

Mounting and Operating Instructions EB 5863 EN. Electric Control Valves. Pneumatic Control Valve

Mounting and Operating Instructions EB EN. Type 3271 and Type 3277 Pneumatic Actuators. Actuator areas: 175v2, 350v2, and 750v2 cm²

Mounting and operating instructions EB Pneumatic Control Valve Type and Type Globe Valve Type 3522 ANSI Class 300

Mounting and Operating Instructions EB 8111/8112 EN. Series V2001 Valves Type 3321 Globe Valve

Mounting and Operating Instructions EB 8097 EN. Pneumatic Control Valves Type and Type

Strainers with flanged connections Type 2 N Type 2 NI. Type 2 N/2 NI Strainers. Mounting and Operating Instructions EB 1015 EN

Mounting and operating instructions EB 8220 EN. Pneumatic Butterfly Valve Type 3335/AT and Type 3335/3278. Fig. 2 Type 3335/AT

Pneumatic Controller for Temperature. Type Pneumatic Controller for Temperature. Type Mounting and Operating Instructions EB 7065 EN

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

Mounting and Operating Instructions EB 5894 EN. Electric control valves with jet pump. Flanged version of valve with jet pump

Series 240 Pneumatic Control Valve Type and Type Three-way Valve Type 3244

Series 240 Type and Type Pneumatic Control Valves Type 3248 Cryogenic Valve

Series W&T Pneumatic Control Valve Type RVG Globe valve and angle valve

Mounting and operating instructions EB EN. Differential Pressure and Temperature Regulator with Flow Limiter Type 2479/2430 K

Series 240 Type and Type Pneumatic Control Valves Type 3248 Cryogenic Valve

Mounting and operating instructions EB 5801 EN. Electric Actuators Type 5801 (Rotary Actuator) Type 5802 (Linear Actuator)

Mounting and Operating Instructions EB 8227 EN. Pneumatic Control Valve Type 3331/BR 31a Special version Type 3331/3278. Type 3331 Butterfly Valve

T 8321 EN Type 3278 Pneumatic Rotary Actuator

Mounting and Operating Instructions EB 5868/5869 EN

Pneumatic Control Valve Type and Type Micro-flow Valve Type 3510

Type and Type Pneumatic Control Valves Type 3510 Micro-flow Valve

Globe Valve Type Fig. 1 Type 3241 Globe Valve. Mounting and Operating Instructions EB EN

Pneumatic or Electropneumatic Positioner for Rotary Actuators Type Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Pressure Reducing Valve Type 2114/2415

Valve Series V2001 Three-way Valve Type 3323

Series 240 Pneumatic Control Valves Type and Type Three-way Valve Type 3244

Series 240 Type and Type Pneumatic Control Valves Type 3244 Three-way Valve

Series 240 Type 3351 Pneumatic On/off Valve

Series 240 Pneumatic Control Valve Type DWA, -7 DWA, -9 DWA Globe Valve Type 3241 DWA

Pneumatic Rotary Actuator Type 3278

Series 250 Pneumatic Control Valve Type and Type High Pressure Valve Type 3252

Type 3761 Pneumatic or Electropneumatic Positioner for Rotary Actuators. Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Type 3273 Hand-operated Actuator Type 3273 Side-mounted Handwheel

Series 240 Pneumatic On-off Valve Type 3351

Series 42 Self-operated Regulators. Type RS Check Valve (backflow protection)

Mounting and Operating Instructions EB 8111/8112 EN. Valve Series V2001 Globe Valve Type 3321

Series V2001 Valves Clean Tech Type 3321CT Globe Valve with pneumatic actuator

Valve Series V2001 Globe Valve Type 3321 with Pneumatic or Electric Actuator

Series V2001 Valves Type 3531 Globe Valve for Heat Transfer Oil with pneumatic or electric actuator

Series 240 Types PSA, -7 PSA, -9 PSA Pneumatic Control Valves Type 3241 PSA Globe Valve

Series V2001 Valves Type 3531 Globe Valve for Heat Transfer Oil with pneumatic or electric actuator

Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil with pneumatic or electric actuator

Series 240 Pneumatic Control Valve Type and Type Globe Valve Type 3241

Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil with pneumatic or electric actuator

Series 240 Pneumatic Control Valve Type and Type Globe Valve Type 3241

T 8053 EN Type and Type Pneumatic Control Valves Type 3252 High-pressure Valve

Type 3768 Inductive Limit Switch. Mounting and Operating Instructions EB 8356 EN

Series 240 Type Gas and Type Gas Automatic Shut-off Valves for Gases (valve class D)

Type 3768 Inductive Limit Switch. Mounting and Operating Instructions EB 8356 EN

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

Self-operated Pressure Regulators Type Universal Excess Pressure Valve

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

BR 31a Rack-and-pinion Actuator,

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

Mounting and Operating Instructions EB 3913 EN. Electropneumatic Converters i/p Converter Type

Series 46 Self-operated Regulators Differential Pressure and Flow Limiters Type 46-5 Type 46-6

Series 240 Type and Type Pneumatic Control Valves Type 3347 Hygienic Angle Valve

Pneumatic Control Valve Assembly Type 3331/3278

Pneumatic Shut-off Butterfly Valve Type 3335/BR 31a

Maxifluss Rotary Plug Valves VETEC Types 73.3/M and 73.7/M

Series 240 Type 3349/3379 Pneumatic Control Valve Type 3349 Aseptic Angle Valve

Globe Control Valve Series 1a

Typetested for liquid fuels and liquefied petroleum gas (LPG) in the liquid phase (see Data Sheet T 8022 EN) Version according to ANSI standards

Pneumatic Butterfly Valve Type 3335 / AT

Self-operated Pressure Regulators Universal Pressure Reducing Valve Type 41-23

Self-operated Pressure Regulators Type Universal Excess Pressure Valve

Mounting and Operating Instructions EB 8052 EN. Type 3251 Valve

Mounting and Operating Instructions EB 8252 EN. Type 3281 Steam Conditioning Valve

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

Data Sheet T EN

ANSI version. The valve closes when the differential pressure rises

Mounting and Operating Instructions EB 8256 EN. Type 3286 Steam Conditioning Valve

Series 1b Control Valve

System 6000 Electropneumatic Converter for Direct Current Signals i/p Converter Type 6126

Maxifluss Rotary Plug Valves VETEC Types 72.3/R and 72.4/R

Series 3730 Type Electropneumatic Positioner. Fig. 1 Type Mounting and Operating Instructions EB EN ( )

System 6000 Electropneumatic Converters for DC ranges I/P Converter Type 6102 Type 5288

Limit Switch Type 3776

BR 01b Control valve

Pfeiffer. Maintenance instructions 3-way control valve Series 1d. 2. Design, operation and dimensions. 3. Installation, start-up and maintenance

Series 3331 Pneumatic Control Butterfly Valve Type 3331/BR 31a

T EN Type 3347/3379 Pneumatic Control Valve Type 3347 Hygienic Angle Valve

Typetested versions With Type 3213 Globe Valve, unbalanced. With Type 3214 Globe Valve, balanced

Transcription:

Type 3271 Pneumatic Actuator Actuator area: 1400-60 cm² Mounting and Operating Instructions EB 8310-3 EN Edition January 2014

Definition of the signal words used in these mounting and operating instructions DANGER! indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING! indicates a hazardous situation which, if not avoided, could result in death or serious injury. NOTICE indicates a property damage message. Note: Supplementary explanations, information and tips 2 EB 8310-3 EN

Contents 1 General safety instructions...5 2 Design and principle of operation...6 2.1 Operating direction...7 2.1.1 Signal pressure routing...7 2.2 Fail-safe action...7 2.2.1 Version with fail-safe action "actuator stem extends" (FA)...7 2.2.2 Version with fail-safe action "actuator stem retracts" (FE)...7 3 Application...8 3.1 Throttling service...8 3.2 On/off service...8 3.3 Versions...8 4 Operation...9 4.1 Travel stop...9 4.1.1 Bottom travel stop (for "actuator stem extends" version)...9 4.1.2 Top travel stop (for "actuator stem retracts" version)...9 5 Maintenance...11 5.1 Releasing the spring preloading...11 5.2 Replacing the diaphragm...12 5.3 Replacing the actuator stem seals...12 6 Reversing the operating direction...13 6.1 Reversal of the operating direction from stem extends to stem retracts...13 6.2 Reversal of the operating direction from stem retracts to stem extends...14 7 Appendix...15 7.1 Nameplate...15 7.2 Dimensions and weights...15 7.3 Customer inquiries...15 EB 8310-3 EN 3

General safety instructions 1 General safety instructions For your own safety, follow these instructions concerning the mounting, start up and operation of the actuator: The actuator is to be mounted, started up or operated only by trained and experienced personnel familiar with the product. According to these mounting and operating instructions, trained personnel refers to individuals who are able to judge the work they are assigned to and recognize possible dangers due to their specialized training, their knowledge and experience as well as their knowledge of the applicable standards. Any hazards that could be caused by the signal pressure or moving parts of the actuator are to be prevented by taking appropriate precautions. To avoid damage to any equipment, the following also applies: Proper shipping and storage are assumed. WARNING! The lifting ring on the top diaphragm case is only intended for assembling and dismantling the pneumatic actuator. Do not use it to lift the entire control valve assembly. EB 8310-3 EN 5

Design and principle of operation 2 Design and principle of operation The Type 3271 Pneumatic Actuator with 1400-60 cm² diaphragm area contains a rolling diaphragm and internal springs. It is mounted on SAMSON Series 240, 250, 280 and 290 Valves. The signal pressure p st generates a force F = p st x A on the diaphragm area A. This force is balanced by the actuator springs (10). Taking into account the rated travel, the number of springs and their compression determine the bench range. The travel is proportional to the signal pressure p st. The operating direction of the actuator stem (7) depends on how the springs are installed in the actuator. The stem connector (51) connects the actuator stem (7) with the plug stem of the valve. Actuator stem retracts (FE) S Actuator stem extends (FA) 10 4 5 4 Diaphragm 5 Diaphragm plate 7 Actuator stem 10 Springs 51 Stem connector S Loading pressure connection S 7 51 Fig. 1: Sectional drawing of Type 3271, 1400-60 cm² 6 EB 8310-3 EN

Design and principle of operation 2.1 Operating direction The operating direction is determined by how the springs and diaphragm plate are arranged in the actuator. With operating direction "actuator stem retracts", the compressed air is applied to the loading pressure connection on the top diaphragm case. With operating direction "actuator stem extends", the compressed air is applied to the loading pressure connection on the bottom diaphragm case. The operating direction of the actuator is reversible. The actuator must be removed from the valve before reversing the operating direction (see section 6 on page 13). 2.1.1 Signal pressure routing In the actuator stem extends version of Type 3271 Actuator (1400-60 cm²) (Fig. 1, right), the signal pressure is routed through the bottom loading pressure connection (S) to the bottom diaphram chamber and moves the actuator stem (7) upward opposing the spring force. In "actuator stem retracts" verion (Fig. 1, left), the signal pressure is routed through the top loading pressure connection (S) to the top diaphram chamber and moves the actuator stem (7) downward opposing the spring force. 2.2.1 Version with fail-safe action "actuator stem extends" (FA) When the signal pressure is reduced or the air supply fails, the springs move the actuator stem downward and close a mounted globe valve. The valve opens when the signal pressure is increased enough to overcome the force exerted by the springs. 2.2.2 Version with fail-safe action "actuator stem retracts" (FE) When the signal pressure is reduced or the air supply fails, the springs move the actuator stem upward and open a mounted globe valve. The valve closes when the signal pressure is increased enough to overcome the force exerted by the springs. 2.2 Fail-safe action When the signal pressure fails, the fail-safe action of the actuator depends on whether the springs are installed in the top or bottom diaphragm chamber. EB 8310-3 EN 7

Application 3 Application NOTICE To mount the actuator on the valve or to remove it from the valve, follow the instructions written in the mounting and operating instructions of the corresponding valve. 3.1 Throttling service The Type 3371 Pneumatic Actuator (1400-60 cm²) is designed for a maximum supply pressure of 6 bar when used for throttling service. 3.2 On/off service To prevent the actuator from being damaged, the supply pressure must not exceed the upper spring range value by more than 3 bar at the maximum when the actuator with fail-safe action "actuator stem retracts" is used for on/ off service. Example: Bench range Fail-safe action Max. supply pressure 0.2 to 1.0 bar 4 bar 0.4 to 2.0 bar Actuator stem retracts 5 bar 0.6 to 3.0 bar 6 bar With fail-safe action "actuator stem extends" and travel stop, the supply pressure must not exceed the upper bench range value by more than 1.5 bar. 3.3 Versions Standard version The Type 3271 Pneumatic Actuator (1400-60 cm²) has a diaphragm area of 1400 cm². The diaphragm cases are made of plastic-coated sheet steel. Travel stop The actuator as a special version can be fitted with a mechanically adjustable travel stop. The actuator travel can be limited by up to 50 %. Pneumatic actuator with Type 3273 Side-mounted Handwheel for travels up to 80 mm Versions for other control media (e.g. water) NOTICE Label actuators with reduced supply pressure with a sticker ("Max. supply pressure limited to... bar"). 8 EB 8310-3 EN

Operation 4 Operation WARNING! The lifting ring on the top diaphragm case is only intended for assembling and dismantling the pneumatic actuator. Do not use it to lift the entire control valve assembly. NOTICE Only apply the signal pressure to the loading pressure connection (S) on the diaphragm chamber of the actuator which does not contain any springs. The applicable bench or operating range which the actuator can move through is written on the nameplate. It is essential that the vent plug (16, Fig. 3 on page 11) lets air through it to allow the actuator to work properly. Note: Actuators with preloaded springs are labeled correspondingly and can also be identified by the long nuts and bolts used to fasten the diaphragm cases together. 4.1 Travel stop In the special version of Type 3271 (1400-60 cm²), the actuator travel can be adjusted by up to 50 % upward or downward. 4.1.1 Bottom travel stop (for "actuator stem extends" version) 1. Undo lock nut (70) and remove cover (73). 2. Unscrew lock nut (74) and turn the adjustment nut (72) to adjust the travel stop. 3. Tighten lock nut (74). 4. Attach the cover (73) and retighten the lock nut (70). 4.1.2 Top travel stop (for "actuator stem retracts" version) 1. Undo the lock nut (70). 2. Adjust the cover (73) to the required travel stop. 3. Retighten lock nut (70). EB 8310-3 EN 9

Operation 73 74 72 70 1 1 Top diaphragm case 5 Diaphragm plate 7 Actuator stem 70 Lock nut 72 Adjustment nut 73 Cover 74 Lock nut Left: Right: 5 7 Actuator stem retracts (FE) Actuator stem extends (FA) Fig. 2: Travel stop 10 EB 8310-3 EN

Maintenance 5 Maintenance WARNING! Special care needs to be taken on dismantling actuators with preloaded springs (labeled accordingly and identifiable by three long bolts protruding from the bottom of the actuator). If the actuator fails to work, the spring compression must be released before removing the actuator from the valve! 5.1 Releasing the spring preloading Note Before performing the following maintenance work, remove the pneumatic actuator from the valve. 1. Unscrew and remove the nuts (21) on the short bolts (20) on the diaphragm casing. 2. Unthread the nuts on the long bolts a few turns, alternating between them to gradually release the spring preloading. S M 16 1 M.1 10 4 20 a x 21 1 Top diaphragm case 2 Bottom diaphragm case 4 Diaphragm 5 Diaphragm plate 6 Adjustable clamp 7 Actuator stem 8 Nut 10 Spring 16 40 16 Vent plug 20 Bolt 21 Nut 40 Radial shaft seal 41 Wiper ring 42 Plain bearing S Loading pressure connection 42 8 41 7 5 6 2 S Fig. 3: Opening Type 3271 Pneumatic Actuator (1400-60 cm²) EB 8310-3 EN 11

Maintenance 5.2 Replacing the diaphragm If the diaphragm does not work reliably and must be renewed, we recommend renewing the plain bearing and seal as well. 1. Undo the nuts (21) and remove the bolts (20) from the diaphragm casing. 2. Lift off the top diaphragm case (1) and remove springs (10). 3. Take the diaphragm plate (5) together with the diaphragm (4) and actuator stem (7) out of the bottom diaphragm case (2). 4. Undo the adjustable clamp (6) and pull the diaphragm off the diaphragm plate. 5. Pull the new diaphragm onto the diaphragm plate. Insert the adjustable clamp (6) evenly into the intended groove and tighten screw with 6 to 7 Nm at the maximum. Make sure that the part to protect the diaphragm is inserted where the clamping screw is located. 6. Reassemble actuator. 9. Fasten the top and bottom diaphragm cases together with the nuts and bolts. Mount the actuator onto the valve following the instructions in the mounting and operating instructions of the valve. 5.3 Replacing the actuator stem seals 1. Take the diaphragm plate (5) together with the actuator stem (7) out of the bottom diaphragm case (2) as described in section 5.2. 2. Apply sealant/lubricant (8152-0043) to the new radial shaft seal (40) and carefully install it. 3. Replace the plain bearing (42) and wiper ring (41) as well, if necessary. 4. Reassemble actuator as described in section 5.2. NOTICE Make sure that the actuator stem in the area where the plain bearing (42) and seals (40, 41) are located does not get damaged. 7. Apply sealant/lubricant (order no. 8152-0043) to the actuator stem. Insert it together with the diaphragm plate and diaphragm into the bottom diaphragm case (2). 8. Insert springs (10) and place on the top diaphragm case (1). Fig. 4: Actuator stem seals 40 42 7 41 12 EB 8310-3 EN

Reversing the operating direction 6 Reversing the operating direction The operating direction and fail-safe action of pneumatic actuators can be changed. Remove the actuator from the valve before proceeding. The fail-safe action is indicated on the nameplate by a symbol: Actuator stem extends (FA) Actuator stem retracts (FE) WARNING! Special care needs to be taken on dismantling actuators with preloaded springs (labeled accordingly and identifiable by three long nuts and bolts protruding from the bottom of the actuator.) If the actuator fails to work, the spring compression must be released before removing the actuator from the valve (see section 5.1). 6.1 Reversal of the operating direction from stem extends to stem retracts ÎÎ See Fig. 3 on page 11 1. Undo the nuts (21) and remove the bolts (20) from the diaphragm casing. 2. Lift off the top diaphragm case (1) and remove springs (10). 3. Pull the actuator stem (7) together with the diaphragm plate (5) and diaphragm (4) out of the bottom diaphragm case (2). 4. Unscrew the nut (M) while holding the nut (M.1) in place. NOTICE Do not undo the nut (M.1) from the actuator stem. It is stuck in place using thread-locking fluid. However, if it does become undone, adjust the dimension a from the top of the nut to the end of the actuator stem to 230 mm as shown in Fig. 3: 5. Lift off the diaphragm plate together with the diaphragm, turn them over and reinsert them. 6. Apply sealant/lubricant (order no. 8152-0043) to the actuator stem. 7. Place the diaphragm plate together with the diaphragm into the top diaphragm case. Insert springs and slide the bottom diaphragm case over the actuator stem. 8. Fasten the top and bottom diaphragm cases together with the nuts and bolts. EB 8310-3 EN 13

Reversing the operating direction 9. Remove the vent plug (16) from the top loading pressure connection (S) and screw it into the bottom connection. ÎÎ The actuator springs, which now push against the diaphragm plate from below, cause the actuator stem to retract. The signal pressure is connected to the connection (S) on the top diaphragm case. As a result, the actuator stem extends opposing the spring force as the signal pressure increases. 10. Write down the changed fail-safe position on the nameplate. 6.2 Reversal of the operating direction from stem retracts to stem extends ÎÎ See Fig. 3 on page 11 1. Undo the nuts (21) and remove the bolts (20). Lift off the top diaphragm case (1). 2. Pull the diaphragm plate (5) and diaphragm (4) together with the actuator stem (7) out of the bottom diaphragm case (2). Remove the springs (10). 3. Unscrew the nut (M) while holding the nut (M.1) in place. 4. Take care not to damage the actuator stem at the locations where the seals are located. 5. Lift off the diaphragm plate together with the diaphragm, turn them over and reinsert them. 6. Apply sealant/lubricant (order no. 8152-0043) to the actuator stem. Insert it together with the diaphragm plate and diaphragm into the bottom diaphragm case. 7. Insert springs and place on the top diaphragm case. 8. Fasten the top and bottom diaphragm cases together with the nuts and bolts. 9. Remove the vent plug (16) from the bottom loading pressure connection (S) and screw it into the top connection. ÎÎ The actuator springs, which now push against the diaphragm plate from above, cause the actuator stem to extend. The signal pressure is connected to the connection (S) on the bottom diaphragm case. As a result, the actuator stem retracts opposing the spring force as the signal pressure increases. 10. Write down the changed fail-safe position on the nameplate. 14 EB 8310-3 EN

Appendix 7 Appendix 7.1 Nameplate The plastic nameplate for the Type 3271 Pneumatic Actuator (1400-60 cm²) is stuck on the diaphragm casing. It includes all details required to identify the actuator: 7.2 Dimensions and weights Refer to Data Sheet u T 8310-3 EN for details on dimensions and weights of the actuator versions. 7.3 Customer inquiries Submit the following details when making inquiries: Type designation and model number Effective area Bench range (spring range) in bar Actuator version and fail-safe action Fig. 5: Nameplate Manufacturer and type number Configuration ID (Var.-ID) as bar code and plain text Serial number Country of origin Diaphragm area in cm² Diaphragm material: NBR or EPDM Symbol indicating fail-safe action: stem extends or retracts (stem extends in this example) Bench range in bar and psi Symbol for operating travel in mm Bench range with preloaded springs Thread for pneumatic connection in G, NPT or Rc Permissible supply pressure p max EB 8310-3 EN 15

SAMSON AG MESS- UND REGELTECHNIK Weismüllerstraße 3 60314 Frankfurt am Main Germany Phone: +49 69 4009-0 Fax: +49 69 4009-1507 Internet: www.samson.de EB 8310-3 EN 2014-07-03