AI352 ATEX INLINE CONNECTOR TERMINATION PROCEDURE (Rev 6 02May07)

Similar documents
AI352 ATEX INLINE CONNECTOR TERMINATION PROCEDURE

POWER CONNECTOR TERMINATION / HOOK UP PROCEDURE

LIVE DEMATEABLE CONNECTOR TERMINATION / HOOK UP PROCEDURE

11mm Slot Label S1 = 162, S2 = 170, S3 = 250, S4 = 305, S5 = 330, S6 = 410, S7 = 490, S8 = 570, S9 = 650. Maximum Power Dissipation (Watts) T** T**

INSTALLATION &SAFETY DATA SHEET

Dimensions shown apply to both Stainless Steel and Mild Steel S1, SF*1 = 162, S2, SF*2, S2L, SF*2L = 170, S3, SF*3 = 250,

IECEx Certificate of Conformity

ABG Cable Glands Installation Procedure

INSTRUCTION MANUAL (ATEX / IECEx)

INSTRUCTION MANUAL (ATEX / IECEx)

Cable Glands - American Series - NEC/IEC

E A E xe ENCLOSURES. For Harsh & Hazardous Environments.

Fuseholders. Introduction

SEALSAFE PRODUCTS CONDUIT AND CABLE PRODUCTS. for HARSH AND HAZARDOUS ENVIRONMENTS. Certificate ANZEx

7 Lighting Technology

FUSEHOLDERS. Type Fuse Size (mm) Page. Type Fuse Size (mm) Page

FUSEHOLDERS. Type Fuse Size (mm) Page. Type Fuse Size (mm) Page

WORK INSTRUCTION READ FIRST. IF IN DOUBT

INSTALLATION I N S T R U C T I O N S

Installation Instructions (Translation) Marking. Description. Danger, warning and note symbols. Technical data. ANTARES ExtSet.

Load disconnect switch Series 8146/5-V11

PIL0478 ISSUE 01/ 07/16

I 16A 2-pole up to 50 V I I 16A 3-pole up to 50 V I

Junction Boxes & Enclosures JBES and ECES Series: 316L Stainless Steel Enclosures Increased Safety

Amphenol Star-line Ex Assembly Instructions (applies to ATEX and IECEx product)

CABINETS AND ENCLOSURES. XL³ 400 and XL³ 800 GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Whitecroft Lighting Limited

Armoured / Un-armoured Cable Gland

Mineral Insulated Resistance Thermometers (RTD)

LMV RANGE CONTENTS. General information

Installation Instructions

SBD FUEL INJECTION ASSEMBLY AND SET UP INSTRUCTIONS 2.0L DURATEC TAPER THROTTLE KIT

Amphenol Cable Glands and Cord Grips Amphenol

Installation, Operating & Maintenance Instructions. Norbro J-Switch FM 00707

D Series Ex d Stainless Steel

Powerline QC. Single Power Connectors. Ten 47 Limited

Cable resistance thermometer Model TR40

Explosion Protected Group IIB Zone 1 Ex d Ring Enclosure Ex e Terminal Boxes Hollow Shaft Option OPERATING SPECIFICATION TECHNICAL DETAILS

Linear Luminaire for Fluorescent Lamps Series EXLUX 6401

Han-Power Energy Bus Components

Powerline. Single Power Connectors. Ten 47 Limited

IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

Cable thermocouple Model TC40

TRaC Global Limited, Unit 1, Pendle Place, Skelmersdale, West Lancashire, WN8 9PN, United Kingdom

IIC wellglass luminaires for low energy, halogen and incandescent lamps flameproof

MM Tubular K-Member, (Mm5KM-7)

Introduction Fuseholders. Electroustic Ltd (0)

Underfloor to desk 231

Installation Guidelines For BW Gland

American Standard ProAx Triaxial Camera Connectors Installation Instructions

MAIN PRICE LIST. - B 487 Perforated Strip 2 1/2" B 488 Perforated Strip 3 1/2" B 482 Perforated Strip 4 1/2" 9 1.

Light Fitting for Fluorescent Lamps Series ECOLUX 6600

1 GENERAL INFORMATION

3 Pin Schuko Converter Plug Technical Data & Fitting Instructions

It s time to get connected with

Short Shifter Installation Instructions For Miata, 6-speed Manual Transmission

Flameproof Level Sensor (Flameproof F/S FP)

(K),(M),(P)489TB/G Up to 42 kv

Power (W) Tamb 40 o C LX1GAM4LB57 5,700 10, T3 T100 o C T4 T85 o C 13

Powerline. Single Power Connectors. + Ten 47. Ten 47 Limited

EXPLOSION PROOF DIRECTIONAL CONTROL VALVE TYPE ED6 SERIE 5X CENELEC STANDARD & ATEX DIRECTIVE

Linear Luminaire for Fluorescent Lamps Series ECOLUX 6600

CR48 Handle Assembly Drawing Number:

APPLICATION MANUAL. Universal Explosionproof Two-Compartments Instrument Housing Type: XD-ID100, XD-ID100win, XD-ID100H, XD-ID100Hwin

920 Remote Control Switches

Installation Instructions

Valves For Process Industry. Engineered Pneumatic Solutions.

Castellated/Hex Nut. Insert Retaining Ring. Contact Insert

FAKRA-Compliant SMB Gen-4 Connector System

TERMINAL BOXES FOR HARSH & HAZARDOUS ENVIRONMENTS

Flameproof Alternator

CONNECTORS AND FITTINGS

Energy Supply Systems C-RAIL PROGRAM. KAT a-USA

Plugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8581

Light Fitting for Fluorescent Lamps Series ECOLUX 6600

2. Use Extraction Tool (contact extraction tool). Insert releasing tip into the REAR of the. cavity between the spring and center wall of the

PPT 802, Proximity Probe Transducer System

Application Specification Circular Plastic Connector (CPC) Series 45 System 05 AUG 14 Rev D

Compact System NRGS 11-2 NRGS Original Installation Instructions English

Coaxial Snap-Lock Connectors

Cable resistance thermometer Model TR40

The cover screws and all other external metal parts are made of stainless steel (AISI 316L). International approvals

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

TPM Fuse Panel Installation Guide. Document INS-727XXXXXXX This manual covers the following part numbers- Trimm 727XXXXXXX Family

Cable resistance thermometer Model TR40

Flame arresters 4301A/4319A ATEX Approved

Standard Buccaneer IP68 BUCCANEER FOR POWER BUCCANEER POWER

PLASTI-GRIP* Terminals and Splices

Clarius EP PLUS LED FLOODLIGHT Installation Guide

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS SOLAS LED Luminaire ATEX & IECEx

155 CARTRIDGE SINGLE SEAL

22kV 425 AMP KA STYLE COUPLER 224BKA - Range

Terminal Boxes TNCN. Explosion protection Marking

Plugs and Sockets SolConeX & CES Series 7570, 7571, 7575, 7579, 7581

Series T is Ideal for:

Cubo X Stainless Steel Enclosures

besseges Handrail Catalogue VALVES TUBES FITTINGS

A Type Double Acting Actuator Type: PA2911

CR76/EURO Handle Assembly Drawing Number:

Flameproof Alternator

Transcription:

IMPORTANT NOTE Hawke International does not recommend the use of their ControlEx Connectors in applications where rigid PVC / SWA / PVC power cabling (typically to BS 6346 standards) is used in portable / semi-portable applications. In addition, Hawke recommends that barrier type glands are fitted to flexible power and loose filled control cabling entering the connectors to maintain the Exd protection concept and to reduce the potential for core movements within the cable being transferred to the connector s internal components. 1) Remove the CP/CR connector assembly, electrical insert and cable gland (sold separately) from their packaging. 2) Terminate the cable into the cable gland in accordance with the manufacturer s instructions. Conductor Cutback Length's (X mm) Insert Type 16 25 32 40 50 63 Tolerance 1.5 & 2.5mm² Solder / Crimp Y mm 78 105 108 108 105 105 +5 / -0 6mm² Crimp - 90 93 - - - +5 / -0 10 & 16mm² Crimp - - 79 - - - +3 / -0 25 & 35mm² Crimp - - - 79 - - +3 / -0 6mm² Solder - - 108 - - - +5 / -0 10 & 16mm² Solder - - 108 - - - +2 / -0 25 & 35mm² Solder - - - 108 - - +2 / -0 4) Strip back the insulation from the conductor s as shown. Insert Type Length (Y mm) 1.5mm² Solder / Crimp 6 2.5mm² Solder / Crimp 6 6mm² Solder 7 6mm² Crimp 8 10mm² Solder 9 10mm² Crimp 11 16mm² Solder 9 16mm² Crimp 11 25mm² Solder 9 25mm² Crimp 11 35mm² Solder 9 35mm² Crimp 11 5) Unscrew the rear engaging nut from the connector shell. Then remove the rear shell and spacer tube. Rear Shell 3) Cut the conductor s to the length s shown. Spacer Tube X mm Connector Shell Rear Engaging Nut

6) If you purchased a fixed keyway connector, proceed to step 14. 9) Unscrew the grub screw on the rear shell about 2mm. (Do not remove) 11) Unscrew the button head screw about 5mm. 7) Align the electrical insert to the plastic sleeve inside the connector shell and slide down as shown in the sectional view below. Button Head Screw Plastic Sleeve Electrical Insert 8) Push the spacer tube into the plastic sleeve in the connector, aligning it so that the small slot on the rear of the plastic sleeve is not obscured. 10) Push the rear shell into the connector shell, aligning the grub screw to the slot of the plastic sleeve as shown in sectional view. 12) Looking on the face of the connector, rotate the rear shell (knurled section) until the coloured dot on the face of the electrical insert is aligned to the required keying position on the connector shell. Keying position

13) Apply thread locker supplied to the thread of the button head screw and tighten into the connector shell. 14) Slide the rear engaging nut over the rear shell as shown and screw this onto the entry thread of the cable gland ensuring there is a sealing washer between the gland and rear shell. Use the flats on the rear shell to further tighten. 16) Slide the internal earth crimp (supplied with CP/CR connector insert) over the earth conductor and fit into the hole in the rear shell. Tighten the grub screw on the face of the rear shell to lock the crimp assembly in place. The stud on the earth crimp should not protrude from the outer diameter of the rear shell. Adjust if necessary. Crimp with suitable tool. Internal Earth crimp 17) a) Solder inserts (1.5 35mm²). Tin the conductors and fill the solder cups on the back of the inserts with solder as required Solder conductors in place and remove any solder spikes/excess from the solder cup. 15) Proceed to step 17 if internal earthing is not required. The insulation on the required earth conductor should be further stripped back level with the face of the rear shell. Additional Cutback Stud must not protrude Grub Crimp here b) Crimp Inserts (1.5 4mm²). i) Crimp the conductors into the contacts using Weidmuller CTX CM 1.6/2.5 crimp tool part number 901849 only. For 0.75 to 1.5mm² conductors use the 1.5 die. For 1.6 to 4mm² use the 2.5 die. If the contacts are to be solder terminated to the conductors, this must be done prior to insertion through the rear contact retainer. ii) Feed the contacts through the required numbered hole on the rear contact retainer and slide the insertion tool over the contacts up to the groove (one end for pin and one for socket). Clip the groove on the contact into position in the rear contact retainer with the tool. iii) Align the flat on the rear contact retainer with the key on the front contact retainer and slide over the contacts into position.

i) iia) iib) iii) c) Crimp Inserts (6 35mm²). Undo the grub screws on the crimp barrels and slide them off the back of the contacts. Slide the conductors into the back of the barrel. Orientate the barrel so that the grub screws are pointing outwards and crimp with a suitable crimp tool. Push the barrels back onto the rear of the contacts and tighten grub screw into the groove on the contact. Back off grub screw half a turn on crimp barrels of 10mm² or larger to allow them to slide up and down the contact slightly. PTO. NOTE: IF INTERNAL EARTHING IS NOT BEING USED, THE INTERNAL EARTH CRIMP MUST NOT BE FITTED AND THE GRUB SCREW IN THE REAR SHELL MUST BE REMOVED. Crimp here Orientate grub screws 18) Clip spacer tube over conductors. Bend conductors slightly so that there is no or minimal gap between the insert/spacer tube and rear shell. On crimp insert of 10mm² or larger, slide the crimp barrels up and down the contacts to achieve this and then lock them in place by tightening the grub screw s on the crimp barrels. 19) Slide insert into the rear of the connector shell, aligning the key on the insert to the keyway of the plastic sleeve inside the connector. Insert key Keyway

20) Screw the rear engaging nut onto the thread on the connector shell. Tighten grub screws in rear engaging nut. 22) The connector is now ready for use. Please refer to the Hook Up procedure. Grub screws HAWKE / ATEX SIZE-TYPE / Tamb -40 C TO + * C T* MAXIMUM DISSIPATED WATTAGE = *W II2GD EExd IIC T** / IP66/67 / HAWKE OL7 ONA UK 1180 CERTIFICATE NUMBER: Baseefa03ATEX0355X WARNING: DO NOT SEPARATE WHILE ENERGISED. DO NOT OPEN EVEN WHEN ISOLATED WHEN FLAMMABLE ATMOSPHERE PRESENT. *FILL IN AS APPROPRIATE FROM TABLE BELOW CONNECTOR SIZE UPPER AMBIENT = 40 C UPPER AMBIENT = 50 C UPPER AMBIENT = 65 C TEMP CLASS TEMP CLASS TEMP CLASS T6 T5 T6 T5 T6 T5 21) Terminate the external earth to the ring terminal crimp provided with the insert. Remove the button head screw and spring washer from the rear engaging nut. Attach the crimp to the rear engaging nut as shown. 16 5W 7W 4W 6W 2W 4W 25 8W 11W 6W 10W 3W 6W 32 10.5W 14.5W 8W 12W 4W 8W 40 12W 17W 9W 14W 4W 9W 50 13W 20W 10W 17W 5W 10W 63 17W 29W 13W 24W 6.5W 13W **T5 = 95 AND T6 = 80 No maintenance or servicing is required on this product. Do not exceed maximum dissipated wattage stated in above table. Hawke International Sales: UK 0870 60 60 105 UK Office, Sales: +44 (0) 161 830 6698 Oxford Street West, Technical UK: 0870 458 9358 Ashton-under-Lyne, Technical: +44 (0) 161 830 6697 Lancashire. Fax: +44 (0) 161 830 6648 OL7 0NA. UK E-mail: sales@ehawke.com Safety First www.ehawke.com