ACTIVAL Two-way Ball Valve with Threaded-end Connection

Similar documents
ACTIVAL Three-Way Ball Valve with Threaded-End Connection

Motorized Two-Way Ball Valve with Screwed-End Connection

ACTIVAL Motorized Three-Way Valve with Flanged-End Connection (JIS 10K / FC200)

ACTIVAL Electro-Mechanical Actuator for Control Ball Valve

ACTIVAL Motorized Two-Way Valve with Flanged-End Connection (Spring Return Type Actuator) (JIS 10K-FC200, -SCS13A)

ACTIVAL Electro-Mechanical Actuator for Control Ball Valve Model MY53X0AX000

ACTIVAL Motorized Two-Way Valve with Flanged-End Connection for High Differential Pressure Application (JIS 10K-FC200, -SCS13A)

ACTIVAL Motorized Two-Way Valve with Flanged-End Connection <4-20 ma DC Input with 4-20 ma DC Feedback Output> (JIS 10K-FC200, -SCS13A)

ACTIVAL Electro-Mechanical Actuator for Control Ball Valve

Differential Pressure Transmitter

Intelligent Component Series ACTIVAL Motorized Two-Way Valve with Flanged-End Connection (JIS 10K / FC200, SCS13A)

Intelligent Component Series ACTIVAL Motorized Three-Way Valve with Flanged-End Connection (JIS 10K / FC200)

Intelligent Component Series ACTIVAL Motorized Two-Way Valve with Flanged-End Connection (PN16 / GG-20) (Spring Return Type Actuator)

Intelligent Component Series ACTIVAL Motorized Two-Way Valve with Flanged-End Connection (JIS 10K / FC200, SCS13A) (Spring Return Type Actuator)

Intelligent Component Series ACTIVAL Flow Measurement and Control Valve (JIS 10K / FC200)

Pressure Transmitter

Direct Coupled Damper Actuator Model MY9050A1001

Intelligent Component Series ACTIVAL Electro-Mechanical Actuator for Model VY530X Control Ball Valve Model MY5390A

Direct Coupled Damper Actuator Model MY6050A1001

ACTIVAL Flow Measurement and Control Valve Standalone Model (PN10 / GG-20)

Air Operated Valve Control Valve

ACTIVAL Motorized Two-way Valve with Flanged-end Connection (JIS 10K / FC200, SCS13A)

Insertion Thermostat

Valve Linkages Models Q455C, Q455D, Q455F

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil

NEOTECHA NTB-NTC BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Mounting and Operating Instructions EB 8111/8112 EN. Valve Series V2001 Globe Valve Type 3321

These installation and maintenance instructions must be read in full and completely understood before the installation!

Operation Manual. Document No.: KE KITZ EKSR Series Spring Return Type Electric Actuators. For KITZ Ball Valves

Powers Controls Powertop Two-Way Valves Normally Open

ACTIVAL Motorized Three-Way Valve with Flanged-End Connection (JIS 10K / FC200)

Installation, Operation, and Maintenance Manual

Air Release Valve (PDCPD) Air Release Valve for Water (PDCPD + Epoxy Resin Coating) User s manual. Air Release Valve. Air Release Valve for Water

Two-port seat valves with male thread, PN16

Mounting and Operating Instructions EB 8111/8112 EN. Series V2001 Valves Type 3321 Globe Valve

Pipe Temperature Sensor

Air Trap TATSU2. Copyright 2013 by TLV CO., LTD. All rights reserved ISO 9001/ ISO M-02 (TATSU2) 7 August 2013.

INSTALLATION, OPERATION & MAINTENANCE MANUAL Description Handling Installation Actuators...

V4043 and V4044 Motorized Valves

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

WARNING Warnings are indicated when mishandling this product might result in death or serious injury to the user.

Mounting and Operating Instructions EB 5868/5869 EN

Valve Series V2001 Three-way Valve Type 3323

Installation, Operation, and Maintenance Manual

Mounting and Operating Instructions EB 5863 EN. Electric Control Valves. Pneumatic Control Valve

NEOTECHA NEOSEAL BUTTERFLY VALVE INSTALLATION AND MAINTENANCE INSTRUCTIONS

Powers Controls Powermite Two-Way Flared Valves Normally Open/Normally Closed

Swing Check Valve ASAHI AV VALVES. Contents. User s Manual. (1) Be sure to read the following warranty clauses of our product 1

3M TM Filter Housing 1BS-T/1BS-TW Series

Manufacturer Kakogawa, Japan DC5S

VG7000 Series Bronze Control Valves

Butterfly valves PN6, PN10, PN16

Compact Direct Operated 2/3 Port Solenoid Valve for Water and Air

Mounting and Operating Instructions EB 8097 EN. Type and Type Pneumatic Control Valves

Installation, Operation, and Maintenance Manual

GATE VALVES. Type P (Standard: Plug) Type S (Soft Seal) Contents. (1) Be sure to read the following warranty clauses of our product 1

Elektric actuator MC50/24-C

Keystone Butterfly valves ParaSeal Installation and maintenance instructions

INSTALLATION, OPERATION & MAINTENANCE MANUAL MODEL BC.

Labyrinth Trim Angle Control Valves

Bypass Blowdown Steam Trap BT3N / MBT3N / PBT3N

Angle seat valve with piston actuator VZXA-...-K

CV-COSR. Pneumatic Control Valve. Copyright 2013 by TLV CO., LTD. All rights reserved

A. This Section includes general duty valves common to several HVAC piping systems.

OPERATION MANUAL. Diaphragm Pump. TD/TD2 Series TD-08, 15, 20/TD2-25. Introduction

3-Port Seat Valves with Male Thread, PN 16

Baumann Way Control Valve

WARNING WARNING. ECM3000 Control Motor User's Manual CAUTION NOTICE SAFETY PRECAUTIONS

I & M Mark 708ME. Ideal Installation. Start-Up Procedure. Installation & Maintenance Instructions for Mark 708 & Motor Actuator

Operating manual Separator

Baumann 24000C Carbon Steel Little Scotty Control Valve Instructions

PIN TYPE FORK POSITIONER WITH SHIFTING SF-F MODEL

Float Dynamic Steam Trap J10

B21 Series BASOTROL Gas Valve

INSTRUCTION OIL PUMP. SH-110A5 MODEL No DR-110A5 MODEL No PD-110A5 MODEL No WARNING

VG9000 Flanged Valves

Globe Valve Type Fig. 1 Type 3241 Globe Valve. Mounting and Operating Instructions EB EN

B-RAD Select USER MANUAL TABLE OF CONTENTS

Constant Flow Valves ASAHI AV VALVES H-V019-E-6. Contents. Serial No. User s Manual

3-port seat valves PN16 with flanged connection

New Products COMPACT PILOT OPERATED SOLENOID VALVE FOR WATER. Lightweight and large flow rate, low power consumption Improved corrosion resistance!

INSTRUCTION GREASE PUMP. PD110A50T MODEL No PD110A50T-SL MODEL No PD110A50 MODEL No DR110A50 MODEL No.

3-port seat valves PN16 with flanged connection

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

These installation and maintenance instructions must be read in full and completely understood before the installation!

Pneumatic Control Valve for Steam PN-COSR-16

Surplussing Valve SP-COSR-16

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1-1/2-2 )

Installation, Operating & Maintenance Instructions. UHV gate valve with pneumatic actuator. Series 108 DN mm (I. D. 2½ 8 )

E-200 Module Service Kit

Operating & Maintenance Manual For Steam Conditioning Valve

Operating Guide SBFV (PN16/25) ENGLISH Steel butterfly valve SBFV Page 2. Danfoss VI.IX.A1.02 1

Angle seat valve with piston actuator VZXA-...-K

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1/2-1 )

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

Installation,Operation and Maintenance Manual H-V016-E-10. Serial No. 目次 ( ページ ) 1. Be sure to read the following warranty clauses of our product 1

Free Float Air Trap G8

Butterfly Valve Type 58 (PDCPD)

Free Float Air Trap JA3 JAF3 / JA5 JAF5 JA7 / JA7.2 / JA7.5 / JA8

Storage, operating and maintenance instructions for AZ plug valves and Standard valves

Transcription:

Specifications/Instructions ACTIVAL Two-way Ball Valve with Threaded-end Connection General ACTIVAL Model VY5302A is a two-way ball valve with threaded-end connection (ISO 7-1: 1994). It proportionally controls chilled/hot water for HVAC applications. Model VY5302A has bronze valve body, stainless-steel ball and stem, and the components exposed to process fluid are made of other corrosion resistant materials. Cv value and size variation of Model VY5302A are best suited to HVAC control. Model VY5302A is used in combination with the actuator Model MY53X0A. Regarding the detailed information on the actuator, refer to: Specifications/Instructions of ACTIVAL Model MY53X0A HVAC: Heating, ventilation, and air conditioning ISO: International Organization for Standardization Features Compact and lightweight: Valve can be installed in a restricted space such as inside of a compact AHU. Bronze valve body applicable to PN16. Easy assembly with Model MY53X0A actuator using no tool, and no adjustment required. Equal percentage flow characteristic. AHU: Air handling unit Dimensions and Maintenance Clearance min.400 H min.120 (MY53) DN min.120 100 80 Rc 91 IMPORTANT: To control ACTIVAL with a third-party controller, please consult with our sales person. L 120 E Model Numbers Base model Material number VY53 Size/ Cv Description Two-way valve with threaded-end connection 0 Bronze 2A00 Fixed 11 DN15 (1/2 ) / 2.5 in Cv 12 DN15 (1/2 ) / 4 in Cv 22 DN20 (3/4 ) / 6.3 in Cv 23 DN25 (1 ) / 10 in Cv 31 DN32 (1 1 / 4 ) / 16 in Cv 41 DN40 (1 1 / 2 ) / 25 in Cv 42 DN40 (1 1 / 2 ) / 40 in Cv 51 DN50 (2 ) / 40 in Cv Model number Valve size Dimensions L Rc* (mm) H (mm) E (mm) VY5302A0011 DN15 Rc 1/2 63 47.5 27 VY5302A0012 DN15 Rc 1/2 63 47.5 27 VY5302A0022 DN20 Rc 3/4 72 50 33 VY5302A0023 DN25 Rc 1 85 53.5 41 VY5302A0031 DN32 Rc 1 1 / 4 98.5 68.5 50 VY5302A0041 DN40 Rc 1 1 / 2 108.5 72 56 VY5302A0042 DN40 Rc 1 1 / 2 108.5 72 56 VY5302A0051 DN50 Rc 2 109 73 69 Note: * Rc: Internal tapered pipe thread complying with ISO 7-1: 1994. Figure 1. Dimensions and maintenance clearance (mm) 1

Safety Instructions Please read instructions carefully and use the product as specified in this manual. Be sure to keep this manual near by for ready reference. Usage Restrictions This product is targeted for general air conditioning. Do not use this product in a situation where human life may be affected. If this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact our sales representative. Azbil Corporation will not bear any responsibility for the results produced by the operators. Warnings and Cautions WARNING CAUTION Alerts users that improper handling may cause death or serious injury. Alerts users that improper handling may cause minor injury or material loss. Signs Alerts users possible hazardous conditions caused by erroneous operation or erroneous use. The symbol inside I indicates the specific type of danger. (For example, the sign on the left warns of the risk of electric shock.) Notifies users that specific actions are prohibited to prevent possible danger. The symbol inside Q graphically indicates the prohibited action. (For example, the sign on the left notifies that disassembly is prohibited.) Instructs users to carry out a specific obligatory action to prevent possible danger. The symbol inside d graphically indicates the actual action to be carried out. (For example, the sign on the left indicates general instructions.) CAUTION Install and use the product under the operating conditions requirement (temperature, humidity, power, vibration, shock, mounting direction, atmospheric condition, etc.) as listed in the specifications. Failure to do so might cause fire or device failure. Use the product within its lifespan and avoid instrumentations that keep the product to operate excessively. Continued use beyond the lifespan might cause fire or device failure. Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards. Install the product in the proper position as specified in this manual. Excessively tight connection to a pipe or improper installation position might damage the product. After installation, make sure no fluid leaks from the valve-pipe connections. Incorrect installation might cause fluid leakage. Install the product so that no foreign objects remains inside the pipes. Be sure to provide a strainer (suitable for the process fluid) on the inflow side of the piping. Flush the piping to remove the foreign objects after installation. Foreign objects inside the piping might damage the product. Do not excessively screw the valve into a pipe. Doing so might damage or deform the inside of the valve causing leakage and malfunction. Do not allow process fluid to freeze. Doing so might damage the valve body causing leakage. Do not install the product nearby a steam coil or a hot-water coil. High temperature radiation might cause malfunction of the actuator assembled with the valve. Do not use the product in an atmosphere corrosive to the product, its actuator, and their components. Doing so might damage the product. Do not disassemble the product. Doing so might cause device failure. Do not carelessly touch the product when being used to control hot water. The product temperature goes high, and you might get burned. Dispose of the product as industrial waste in accordance with your local regulations. Do not reuse all or part of this product. 2

Specifications Item Specification Type Two-way ball valve with threaded-end connection (internal), proportional control Applicable actuator to be combined Model MY53X0A Pressure rating PN16 (Max. working pressure: 1.6 MPa) Valve size, Cv, close-off rating Model number Nominal size Cv Close-off rating VY5302A0011 DN15 (1/2 ) 2.5 1.0 MPa VY5302A0012 DN15 (1/2 ) 4 1.0 MPa VY5302A0022 DN20 (3/4 ) 6.3 1.0 MPa VY5302A0023 DN25 (1 ) 10 1.0 MPa VY5302A0031 DN32 (1 1 / 4 ) 16 0.5 MPa VY5302A0041 DN40 (1 1 / 2 ) 25 0.5 MPa VY5302A0042 DN40 (1 1 / 2 ) 40 0.5 MPa VY5302A0051 DN50 (2 ) 40 0.5 MPa Materials Body Cast bronze (equivalent to: - CuAn5An5Pb5-C (DIN EN1982) for global standard - CAC406 (JIS) for Japanese standard) Ball Cast stainless steel Stem Stainless steel Seat ring PTFE O-ring EPDM End connection Internal threaded-end (equivalent to ISO 7-1: 1994) Applicable fluid Chilled/hot water, brine (ethylene glycol solutions, 50 wt.% max.) Allowable fluid temperature 0 C to 100 C (non-freezing) Flow characteristic Equal percentage Rangeability 100 : 1 Seat leakage in fully closed position 0.01 % of rated Cv value (0.0006 Cv or less for DN15 models) Mounting position On vertical / horizontal pipe Weight VY5302A0011 0.4 kg (Actuator in combination is NOT VY5302A0012 0.4 kg included.) VY5302A0022 0.6 kg VY5302A0023 0.8 kg VY5302A0031 1.2 kg VY5302A0041 1.5 kg VY5302A0042 1.5 kg VY5302A0051 1.8 kg DIN: Deutsche Industrie Normen EPDM: Ethylene-propylene-diene copolymer JIS: Japanese Industrial Standards PTFE: Polythetrafluoroethylene 3

Parts Identification and Materials Valve size: DN15 to DN40 Valve size: DN50 5. Stem 5. Stem 6. O-rings 1. Body 6. O-rings 2. Seat retainer 2. Cap 1. Body 4. Ball 4. Ball 3. Seat rings 3. Seat rings 3. Seat rings 3. Seat rings No. Part name Material No. Part name Material 1 Body Cast bronze (equivalent to: - CuAn5An5Pb5-C (DIN EN1982) - CAC406 (JIS)) Cast bronze (equivalent to CuAn5An5Pb5-C (DIN EN1982)) 1 Body 2 Cap 2 Seat retainer Copper alloy 3 Seat ring PTFE 3 Seat ring PTFE 4 Ball Stainless steel 4 Ball Stainless steel 5 Stem Stainless steel 5 Stem Stainless steel 6 O-ring EPDM 6 O-ring EPDM Figure 2. Parts identification and materials: DN15 to DN40 valve Cast bronze (equivalent to: - CuAn5An5Pb5-C (DIN EN1982) - CAC406 (JIS)) Figure 3. Parts identification and materials: DN50 valve Flow Characteristic 100 75 Cv (%) 50 25 0 25 50 75 100 Valve position (%) Figure 4. Flow characteristic diagram 4

Installation CAUTION Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards. Install the product in the proper position as specified in this manual. Excessively tight connection to a pipe or improper installation position might damage the product. After installation, make sure no fluid leaks from the valve-pipe connections. Incorrect installation might cause fluid leakage. Install the product so that no foreign objects remains inside the pipes. Be sure to provide a strainer (suitable for the process fluid) on the inflow side of the piping. Flush the piping to remove the foreign objects after installation. Foreign objects inside the piping might damage the product. To remove foreign substances inside the pipes, install a strainer on the inflow side of each valve. In case that the strainers cannot be installed on the inflow side of each valve, install it on the pipe diverting sections (sections diverting from main piping system to sub piping system). Install the valve so that the flow direction of process fluid agrees with the arrow indicated on the valve body. Installation location CAUTION Do not install the product nearby a steam coil or a hot-water coil. High temperature radiation might cause malfunction of the actuator assembled with the valve. Do not use the product in an atmosphere corrosive to the product, its actuator, and their components. Doing so might damage the product. Install the valve assembled with the actuator in a position allowing easy access for maintenance and inspection. Fig. 1 shows the minimum clearance for maintenance and inspection. When installing the valve and actuator in a ceiling space, provide an access panel within the 50 cm radius of the valve and actuator. And, place a drain pan under the valve. Do not mount the valve on a pipe where water hammer occurs, or where solid objects including slug may accumulate. Mounting position The valve (assembled with the actuator) can be mounted in any position ranging from upright to sideways (90 tilted). The valve should be installed with its actuator vertically positioned above the valve body. However, the valve must be installed always in upright position outdoors. Correct examples Incorrect examples Figure 5. Mounting positions of the valve 5

Piping Install a bypass pipe and gate valves on the inflow, outflow, and bypass sides. Also, install a strainer (with 40 or more meshes) on the inflow side. When installing the valve to pipes, do not allow any object, such as chips, to get inside a pipe or valve. Valve cannot fully closes, or the valve seat may get damaged causing fluid leakage, due to an foreign object jammed inside the valve. When piping, do not apply too much sealing material, such as solidifying liquid and tape, to the pipe connection sections so that these materials flow into the valve. Valve cannot fully closes, or the valve seat may get damaged causing fluid leakage, due to the sealing material jammed inside the valve. When connecting the valve to pipes, hold the valve body (where a pipe is screwed) with a tool such as a wrench, and screw the pipe into the valve. (See Fig. 6.) Do not apply excessive torque to the pipe. Refer to the table in Fig. 6 for the recommended torque. Incorrect holding position Torque Recommended torque to screw into the pipe Valve size (DN) 15 20 25 32 40 50 Max. torque (Nm) 40 60 100 120 150 200 Correct holding position Figure 6. Valve connection to a pipe Before activating the valve and actuator, flush the pipes (with the valve and actuator installed) at the maximum flow rate to remove all the foreign substances. Fully open (in 100 % position) the valve to flush. (Factory preset position: 100 %) Heat insulation Do not apply heat insulation to the joint surface. Correctly apply heat insulation to the valve as shown in Fig. 7. Joint surface Joint surface Heat insulation material Heat insulation material Correct application Incorrect application Figure 7. Heat insulation Factory preset position ACTIVAL is set in fully open (100 %) position before shipment. 6

Assembling the valve Model VY5302A with the actuator Model MY53X0A IMPORTANT: The actuator can be horizontally rotated every 90 degrees to fit into the valve mounting position (4 mounting positions). Make sure the positions of the actuator and the valve as follows, referring to Fig. 8: - Actuator: Indicator/manual lever points at 100 (fully open position). - Valve: An arrow on the top of the stem points at 100 (fully open position). (Align the hole on the side of the stem with the tip at the joint surface as a in Fig. 8 shows.) Set the ACTIVAL (actuator and valve) in 100 % position when changing the mounting position. If the valve in 0 % position is assembled with the actuator in 100 % position, the actuator put torque on the closed valve, and the gear of the actuator gets damaged. If the valve and the actuator are assembled despite their positions unmatched, they might operate reversely and become unable to control the process fluid. Indicator/ manual lever Lever release button Actuator Model MY53X0A Lock lever 3) Confirm that the arrow on the top of the valve stem points at 100. A hole on the side of the stem faces the same direction at which the tip of the valve joint surface (with the actuator) points when the valve position is fully open. (See a in Fig. 8.) Stem Tip Joint surface Stem a Valve Model VY5302A Figure 11. Valve stem pointing at 100 % (fully open) position 4) Assemble Model MY53X0A actuator with the valve. Engage 4 pins of the actuator with the mating holes on the valve joint surface. Figure 8. Mounting the actuator onto the valve 5) Move the lock lever to left-end to lock. Locked position is indicated with the groove as shown in Fig. 12. Mounting procedure 1) Manually turn the indicator/manual lever of the actuator to 100 with the lever release button pressed. Locked position indication Turn. Press. Figure 9. Indicator/manual lever at 100 % (fully open) position 2) Move the lock lever to right-end to unlock. Unlock. Lock. Figure 12. Locking the lock lever Figure 10. Unlocking the lock lever 7

Inspection and Troubleshooting CAUTION Do not carelessly touch the product when being used to control hot water. The product temperature goes high, and you might get burned. Manually open/close the product at least once a month if it is left in inactive state for a long period after installation. Inspect the product according to Table 1. Visually inspect the product (e.g., fluid leakage) every six months. If any of the problems described in Table 2 are found, take corresponding actions shown in the table. If your problem is not solved by the corresponding action, please contact us. Table 1. Inspection items and details Inspection item Inspection interval Inspection detail Visual inspection Semiannual Loosened lock lever Valve and actuator damages Fluid leakage from the gland/pipe connecting part Operating status Semiannual Unstable open/close operation Abnormal noise and vibration Routine inspection Any time Abnormal noise and vibration Unstable open/close operation Valve hunting Table 2. Troubleshooting Problem Part to check Action Valve does not operate smoothly / valve stops halfway / valve does not operate at all. Fluid leaks to the outside of the valve when the assembled actuator fully closes the valve. Valve hunting occurs. Conditions of the power applied and of the input signal applied to the actuator. Wiring condition/disconnected wires of the actuator. Foreign substance jammed. Confirm the mounting procedure referring to the section Assembling the valve Model VY5302A with the actuator Model MY53X0A. Secondary pressure condition. Differential pressure condition. Control stability. Check the power supply and the controller connected to. Check the wiring. Remove foreign substance by manually opening the valve. Dismount and remount the actuator according to the correct mounting procedure. Reset and adjust the valve inlet/outlet pressure. Modify control parameter/pid setting of the controller in connection to the assembled actuator. Redo the cam switch setting. Check the wiring. Lock the lock lever. Consult with our sales/service personnel. The auxiliary switch of the assembled actuator does not operate. Auxiliary switch (cam switch) condition. Wiring condition/disconnected wires of the actuator. Connecting part between the valve Lock lever condition of the actuator. and the actuator vibrates or produces Yoke damages. an abnormal noise. Water flowing sound level is too high. Consult with our sales/service personnel. The assembled actuator in operation Consult with our sales/service personnel. produces an abnormal noise. Voltage/current input signal of the To completely shut off the valve, valve open and close (0-100% position) operation is controlled by assembled actuator disagrees with the 10-90 % range of the actuator voltage/current input signal. Voltage/current input signal therefore feedback output signal. disagrees with the feedback signal, and this is not an error. ACTIVAL is a trademark of Azbil Corporation in Japan or in other countries. Specifications are subject to change without notice. Building Systems Company http://www.azbil.com/ Rev. 3.0 Sep. 2014 AB-6594 8