Series 71, 72, and 76 Modutrol IV Motors

Similar documents
Series 41 and 81 Modutrol IV Motors

BCS Modutrol Motor M7484A

Q7130A, Q7230A, Q7330A Modutrol IV Interface Modules

Series 61 and Series 62 Modutrol IV Motors

MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 Fast-Acting, Two-Position Actuators

M436A/M836A,B Damper Motors

ML6420, ML7420 Non-Spring Return Electric Linear Valve Actuators

The ES /118 Explosion-Proof Housings

ML6425, ML7425 Spring Return Electric Linear Valve Actuators

35 and 70 lb-in. Non-Spring Return Direct Coupled Actuators ML6161, ML7161, ML6174, ML7174

ML6420, ML7420 Non-Spring Return Electric Linear Valve Actuators

V5011N Two-Way Threaded Globe Valve

V51E Butterfly Valve. The valve mechanism is equipped with strain release springs.

D690 Round Damper LOW-LEAKAGE, SINGLE-BLADE FEATURES APPLICATION PRODUCT DATA. Contents

V9055A,D Modulating Fluid Power Gas Valve Actuator

Series 61 and Series 62 Modutrol IV Motors

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

ML7421A,B Electric Linear Valve Actuator

Powers TM Controls EA 338 Electronic Actuator

L404F,T,V PressureTrol Controllers

Q5024A,B Globe Valve Linkages FOR DIRECT COUPLED ACTUATORS

MODUTROL IV OEM CROSS REFERENCE

C7046A,B,C,D Air Temperature Sensors

AT120A-E; AT140A-E; AT150A,B,D-F; AT160B; AT175A-D,F Transformers

CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

Q5020A-D Globe Valve Linkages FOR DIRECT COUPLED ACTUATORS

MS4120F, MS4620F, MS8120F, S2024-F, S20230-F Fast-Acting, Two-Position Actuators

V5197A Firing Rate Gas Valve

Q345A, Q3451, Q3481, Q348A, Q348B, Q362A, Q373A, Q381A and Q3452 Intermittent Pilot Burner/Igniter-Sensors

MP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning Hydraulic Actuator General Instructions

CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions

V4043 and V4044 Motorized Valves

MA-5200 Series MA-5300 Series

MP-5200 Series. Application. Features. Applicable Literature. Electronic Hydraulic Actuator General Instructions

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

LF Series Spring Return Direct Coupled Actuator

M9116, M9124, and M9132 Series Electric Non-spring Return Actuators

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m)

M9216 Series Electric Spring Return Actuators

SAX Electronic Valve Actuator

MX4X-6XXX Series MX4X-7XXX Series. Selection Guide. Applications. DuraDrive Series Actuators and Accessories

VA-4233-GGx Series Electric Valve Actuators

MF4E MF4E

Damper Actuator Installation

SAX Electronic Valve Actuator

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

Q7800C Integrated Burner Control Subpanel

M100F Incremental Motor Actuator R81F Interface Board

V5011N Two-Way Threaded Globe Valve

DA-053 Series. Overview. Applications. Features & Benefits. Datasheet. 53lb-in (6 Nm), Non-Spring Return Damper Actuators

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

MS Application. Features. Proportional Valve Actuator General Instructions

M9220-xxx-3 Electric Spring Return Actuators

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

GMX On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 100 to 240 VAC

Technical Instructions Flowrite 599 Series SKD6xU Electronic Valve Actuators 24 Vac Proportional Control Description Features Application

VA-7150 Electric Valve Actuator. Features and Benefits. G 500N force output in a compact unit G Magnetic clutch. G Unique Yoke Design

M9210-xxx-3 Electric Spring Return Actuators

MC-351, 421, 431, MC-4311

LMX120-SR. Proportional Control, Non-Spring Return, Direct Coupled,100 to 240 VAC, for 2 to 10 VDC and 4 to 20 ma

MS Series MS Series MS Series

C7170A,B Encapsulated Temperature Sensor

Immersion Wells and Compression Fittings FOR TEMPERATURE CONTROLLERS

VA-715x Electric Valve Actuator

System 350 S350P Proportional Plus Integral Temperature Stage Module

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

LMCB24-SR LMCB24-SR-T. applications. Dimensions (All numbers in brackets are in millimeters.) 1/4 to 3/4 [6 to 20] 5/16 to 3/4 [8 to 26] 1.

VC2, VC4, VC60, VC8 ON-OFF ACTUATOR FOR VC SERIES BALANCED HYDRONIC VALVES SPECIFICATIONS INSTALLATION INSTRUCTIONS

Installation Instructions

MA/F/S 4D-xxxx-xxx Two Position, Floating and Proportional Series SmartX Actuators Rotary Overshaft Actuators

Installation Instructions

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

System 350 P352AB Electronic Pressure Control Series

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

NV Direct Coupled Globe Valve Actuator

RUS-L24-MOD Electric 24 Volt Modulating Control Damper & Louver Actuator

R182J, R482J, R845A, R847A, R882J, RA89A, RA832A Switching Relays

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

LF Series At A Glance

Torque min. 35 in-lb, for control of air dampers

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

MAx1-720x Two Position Series MFx Floating Series MSx Proportional Series

Excel 15 W7760A BUILDING MANAGER

M9203-xxx-2(Z) Series Electric Spring-Return Actuators

NMB (X) 24-MFT. Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

NFB24, NFB24-S, NFX24, NFX24-S On/Off, Spring Return, 24 V

Non-Spring Return EconoDrive Floating Actuator

1.0 Features and Description

CP (Vdc) CP (Milliamp) CP (Slidewire)

V4062A,B,D HI-LO-OFF Fluid Power Gas Valve Actuator

AF Series Spring Return Direct Coupled Actuator

ATP-2040 Electric Damper Actuator/Transmitter

VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators

M9220-xxx-3 Electric Spring Return Actuators

M9220 Series Electric Spring-Return Actuators

LMB24-3 (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

Installation Instructions

ComfortPoint Programmable Lon, VAV/Unitary Controllers

Transcription:

Series 7, 7, and 76 Modutrol IV Motors PRODUCT DATA FEATURES APPLICATION The Series 7, 7 and 76 Modutrol IV Motors are spring return and nonspring return motors used to control dampers and valves. The motors accept a current or voltage signal from an electronic controller to position a damper or valve at any point between open and closed. Replaces M734H,J,; M744S,T,Y; and M745L,S,T,Y Motors. M764, M76, M784, and M794 are nonspring return motors; M78, M785, M786 and M7685 are spring return motors. Integral spring return returns motor to normal position when power is interrupted. Integral junction box provides NEMA 3 weather protection. Motor and circuitry operate from 4 Vac. Models available with factory installed transformer, or a field added internal transformer. Quickconnect terminals are standard screw terminal adapter is available. Adapter bracket for matching shaft height of older motors is available. Most motors have field adjustable stroke (90 to 60 ). Diecast aluminum housing. Integral auxiliary switches are available factory mounted, or can be field added. Nominal timing standard of 30 seconds (90 stroke), and 60 seconds (60 stroke). Other timings available. Spring return motors can operate valve linkages from power end or auxiliary end shafts for normally closed or normally open valve applications. All models have dual shafts (slotted and tapped on both ends). All models have auxiliary switch cams. Fixed torque throughout the entire voltage range. Motors are designed for either normally open or normally closed valves and dampers. Models available with adjustable start (zero) and span. Models available with 4 to 0 ma input signal. Models available with to 0 Vdc input signal. Contents Application... Features... Specifications... Ordering Information... Installation... 5 Settings and Adjustments... 8 Operation and Checkout... 6364008

SERIES 7, 7, AND 76 MODUTROL IV S SPECIFICATIONS Models: TRADELINE models are selected and packaged to provide ease of stocking, ease of handling and maximum replacement value. TRADELINE model specifications are the same as those of standard models unless specified otherwise. IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances. Therefore, an individual unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed. Modutrol IV Order Number Guide: See Table 4. Dimensions: See Fig.. Lifetime 60,000 Full Stroke Cycles Repositions:.5 Million Controller: These motors can be used with any electronic controller that provides a stable noisefree proportional current output as specified in Electrical Ratings, Input Range below. Electrical Ratings: Power Consumption: See Table. Input Range: Current, Nonadjustable: 4 to 0 ma nominal, 5 ma maximum. Current, Adjustable: 4 to 0 ma adjustable, 50 ma maximum. Zero/Null (Motor Closed): 0.0 to 8 ma. Span:.8 to 0 ma. Voltage, Nonadjustable: to 0 Vdc. Input Impedance: 4 to 0 ma Input: 00 ohms. to 0 Vdc Input: 400K ohms. Auxiliary Switch Ratings (in Amps): See Table. Stroke: Most models available with field adjustable strokes from 90 to 60. Stroke adjusted by means of potentiometers located in the wiring compartment. Timing: Nominal 30 seconds for 90 stroke and 60 seconds for 60 stroke. Dead Weight Load On Shaft: 00 lb (9 kg) on motor power or auxiliary end; maximum combined load of 300 lb (36 kg). Ambient Temperature Ratings: 40 to 50 F (40 to 66 C). Shaft: 3/8 in. (9.5 mm) square. Motor Rotation: Closed: Counterclockwise rotation limit as viewed from motor power end. Mechanically Normally Closed: Spring return. Normally closed motors rotate to closed position on power loss. Electrically Normally Closed: Both spring return and nonspring motors return to closed position on minimum signal. Table. Series 7 Modutrol IV Motor Power Consumption Ratings (at 0 Vac, 50/60 Hz). Power Consumption Model VA Watts M76 5 3 M78 0 8 M784 5 3 M785 0 8 M786 0 8 M794 5 3 Table. Auxiliary Switch Ratings (in Amps). One Contact Rating a 0V 40V Full Load 7. 3.6 Locked Rotor 43..6 a 40 VA pilot duty, 0/40 Vac on opposite contact. Approvals: Underwriters Laboratories Inc. Listed: File No. E4436; Guide No. XAPX for USA and Canada. U.S. Patents: pending Table 3. Primary 500746000 Color Code Lead Color Brown White Blue Black 4 VAC 0 VAC 30 VAC Common Primary Voltage ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE wholesaler or distributor, refer to the TRADELINE Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).. Honeywell Customer Care 885 Douglas Drive North Minneapolis, Minnesota 5544386 3. http://customer.honeywell.com or http://customer.honeywell.ca International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States. 63640 08

SERIES 7, 7, AND 76 MODUTROL IV S Fig.. Stroke ASYMMETRICAL S SYMMETRICAL S VERTICAL REFERENCE VERTICAL REFERENCE VERTICAL REFERENCE VERTICAL REFERENCE 0 FULLY CLOSED 90 0 FULLY CLOSED 45 FULLY CLOSED 0 FULLY CLOSED 60 60 FULLY OPEN 90 FULLY OPEN FULLY OPEN 90 DEGREE STROKE 60 DEGREE STROKE SPRING RETURN S AND NONSPRING RETURN S FULLY OPEN 90 DEGREE STROKE 60 DEGREE STROKE NONSPRING RETURN S M3079 M Table 4. Modutrol IV Motors Series and 3 Model Number Guide. Motor 7 0.5 3.5 Vdc voltage input 7 40 ma or 0 Vdc Control 76 47 dc voltage control with minimum position capability 6 35 lbin. NonSpring Return 7 75 lbin. NonSpring Return 8 60 lbin. Spring Return 50 lbin. NonSpring Return 9 300 lbin. NonSpring Return Dualended shaft Normally Closed Spring Return 4 NonSpring Return 5 Normally Closed Spring Return A 0 Auxiliary Switches Adjustable Stroke * Normally Closed B Auxiliary Switch C Auxiliary Switches D 0 Auxiliary Switch Q a Auxiliary Switches M 7 8 4 A XXXX See Tradeline Catalog for Complete Model Number a Adjustable zero and span. * Fixed stroke on M784C083, M784C09, M784Q08, and M784Q090 3 63640 08

SERIES 7, 7, AND 76 MODUTROL IV S TOP VIEW TOP VIEW OF BRACKET 47/8 (4) 4/4 (07) 5/ (40) 45/8 (6) 5/6 (58) 53/6 (48) /6 (7) /4 (7) 3 5/ (40) 4/6 (03) 3/6 (0) 3/6 (0) / (37) POWER END /4 (7) 47/8 (4) 59/6 (4) / (37) JUNCTION BOX 3/4 (9) END POWER END 9/6 (66) 53/8 (37) 67/6 (64) SPRING RETURN MODEL SHOWN FOR 60 LBIN. SPRING RETURN MODELS 83/4 (). FOR NONSPRING RETURN MODELS 75/6 (85). FOR 60 LBIN. SPRING RETURN MODELS (SHOWN). 3 FOR NONSPRING RETURN MODELS. 9/6 (5) ADAPTER BRACKET 3/4 (9) M8998D Fig.. Series 7 Modutrol IV Motor dimensions in inches (mm). 63640 08 4

SERIES 7, 7, AND 76 MODUTROL IV S Accessories: 0736A Internal Auxiliary Switch Kit; one switch. Can be fieldinstalled. 0736B Internal Auxiliary Switch Kit; two switches, can be fieldinstalled on TRADELINE models. 0738A Adapter Bracket raises motor shaft height by 3/4 in (9 mm) to match that of previous Modutrol Motor models. 074A Screw Terminal Adapter converts the standard quickconnect terminals to screw terminals. 455A Infinitely Adjustable Crank Arm, can rotate through downward position and clear motor base without requiring an adapter bracket. 4074ERU Weatherproofing Kit provides NEMA 3 rating for Modutrol IV Motors mounted in position other than upright. 500746000 Internal Transformer; 4/0/30 Vac 50/60 Hz primary, 4 Vac secondary, quick connect terminals. 5007460003 Internal Transformer; 0 Vac 50/60 Hz primary, 4 Vac secondary, quick connect terminals. 767ADW Crank Arm, can rotate through downward position and clear motor base without requiring an adapter bracket. Q00 Linkage connects Modutrol Motor to V5 Butterfly Valve. Requires the 0738A Adapter Bracket. Q8 Auxiliary Potentiometer for sequence or unison control of to 4 additional modulating (Series 90) motors. Q09E,F Manual Potentiometer for Modutrol Motors Q500 Bracket and Linkage Assembly connects Modutrol IV Motor to water or steam valve. Q605 Damper Linkage connects motor to damper. Includes motor crank arm. Q607 External Auxiliary Switch controls auxiliary equipment as a function of motor position. ES6507 ExplosionProof Housing encloses motor for use in explosive atmospheres. Also required, a 767DM coupling assembly from Honeywell to use with the cover. Not for use with Q500 (or any other valve linkages). To order ES650 7, contact EGS Enclosures at (8) 44967, ask for the sales department and for distribution in your area. INSTALLATION When Installing this Product.... Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. Installer must be a trained, experienced service technician. 4. After installation is complete, check out product operation as provided in these instructions. Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect all power supplies before installation. Motors with auxiliary switches can have more than one disconnect. Equipment Damage Hazard. Can damage the motor beyond repair. Never turn the motor shaft by hand or with a wrench. Forcibly turning the motor shaft damages the gear train and stroke limit contacts. IMPORTANT Always conduct a thorough checkout when installation is complete. Location Allow enough clearance for accessory installation and motor servicing when selecting a location (see Fig. ). If located outdoors, use liquidtight conduit connectors with the junction box to provide NEMA 3 weather protection. If mounted outdoors in a position other than upright, install a 4074ERU Weatherproofing Kit and liquidtight connectors to provide NEMA 3 protection. Motor Damage Hazard. Deteriorating vapors and acid fumes can damage metal parts. Install motor in areas free of acid fumes and other deteriorating vapors. In excessive salt environments, mounting base and screws should be zinc or cadmium plated, not stainless steel or brass. Use the 0738A Adapter Bracket for mounting on these surfaces. Mounting Use the following guidelines for proper motor mounting: Always install motors with the crankshaft horizontal. Mounting flanges extending from motor housing base are drilled for /4 inch (6.4 mm) machine screws or bolts. NonSpring Return Motors are shipped from the factory in the closed position (at the counterclockwise rotation limit, as viewed from the motor power end). Spring Return Motors are shipped from the factory in their normal position. Normally closed models are shipped at the counterclockwise rotation limit, as viewed from the motor power end. Adapter Bracket The 0738A Adapter Bracket, positioned between the motor and the equipment, raises motor shaft height by 0.75 in. (9 mm) to match that of previous Modutrol Motor models. The following applications require this bracket: Q607 External Auxiliary Switch. Damper linkage applications requiring added clearance to allow: Crank arm rotation through the downward position. Sufficient damper linkage to reach the motor shaft. All valve linkages except the Q500. NOTE: When the bracket is not used in a replacement application, the damper linkage requires adjustment for the new shaft position. To mount the motor with the bracket:. Mount the bracket to the equipment with existing or standard bolts.. Using the provided bolts, mount the motor to the bracket threaded holes. See Fig. 3. For valve linkage applications (other than the Q500):. Mount the bracket to the linkage.. Position the motor on the bracket to align the motor shaft with the linkage. 5 63640 08

SERIES 7, 7, AND 76 MODUTROL IV S 3. Attach the motor to the bracket with the four bolts provided. See Fig. 4. STANDARD BOLTS (4) BOLTS PROVIDED (4) WIRING BOX POWER END ADAPTER BRACKET EQUIPMENT BASE POWER END POWER END # OR /4" ZINC PLATED MACHINE SCREWS OR BOLTS M8999 NONSPRING RETURN SPRING RETURN Fig. 3. Mounting the motor with an adapter bracket. Damper Linkages The motor does not include a crank arm. Order the crank arm separately (see Accessories in the Specifications section). For detailed instructions on the assembly of specific linkages, refer to the Installation Instructions packed with the linkage. Equipment Damage Hazard. Stalling a motor can damage the drive shaft. Ensure installation of motors and linkages allows the motor to drive through full stroke without obstruction. Valve Linkages The Q00 Linkage requires a 0738A Adapter Bracket for all valve applications. Applications with the Q500 Valve Linkage do not require the 0738A Adapter Bracket (see Fig. 4). For detailed instructions on specific linkage assemblies, refer to the instruction sheet packed with the linkage. In general, check the following points when installing a motor and linkage: Adjust valve and louvertype damper linkages so the damper or valve moves through only the maximum required distance while the motor moves through its full stroke. With modulating control, maximum damper opening should be no more than 60 degrees. Little additional airflow is provided beyond this point. Do not exceed load and torque ratings in any application. Junction Box When used with liquidtight conduit connectors, the junction box provides NEMA 3 weather protection for the motor. The junction box, standard with replacement motors, encloses the terminals and provides knockouts for wiring conduits. Housing an internal transformer or internal auxiliary switches requires using a junction box. 63640 08 6

SERIES 7, 7, AND 76 MODUTROL IV S 3. Replace wiring box cover. Q500 VALVE LINKAGE POWER END OF JUNCTION BOX CONTROLLER T T 4V F L (HOT) L POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQURED. CONNECTING F TO WILL DRIVE TO FULLY OPEN. VALVE /40 UNC in. LONG MOUNTING BOLTS M8994 Fig. 4. Mounting the motor on a Q500 Valve Linkage. L (HOT) L Fig. 5. Typical system wiring. DAMPER L L C R F M5778 MODULATING DC VOLTAGE SOURCE Wiring Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect all power supplies before installation. Motors with auxiliary switches can have more than one disconnect. IMPORTANT All wiring must agree with applicable codes, ordinances and regulations.. Ensure that the voltage and frequency stamped on the motor correspond with the power supply characteristics.. When connecting several motors in parallel, ensure that the power supply VA rating is large enough to provide power to all motors used without overloading. 3. Fig. 0 shows that motor terminals are quickconnects located on top of the printed circuit board. 4. To access the wiring compartment: a. Remove the four screws from the junction box top. b. Lift off the cover. 5. Refer to Fig. 5 through 8 for wiring. Wire the motor as follows:. Remove the wiring box cover by removing the four screws holding the cover to the motor.. Wire motor to system using quickconnect terminals in wiring box. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M376 Fig. 6. Series 7 optional override switches to drive motor open or closed. L (H OT ) L 3 3 EXTERNAL CONTROL DAMPER S T T C R 3 4 WHITE RED MINIMUM POSITION POTENTIOMETER MODULATING dc VOLTAGE SOURCE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. IF MINIMUM POSITION POTENTIOMENTER IS NOT USED, JUMPER TERMIALS 3 AND 4. TRANSFORMER MAY BE INTERNAL OR EXTERNAL. Fig. 7. M7685 Typical application wiring. M377A 7 63640 08

SERIES 7, 7, AND 76 MODUTROL IV S 40 ma CONTROLLER F F F T T L L (HOT) POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQURED. CONNECTING F TO WILL DRIVE TO FULLY OPEN. S FUNCTION INDEPENDENTLY. M309 Fig. 8. Driving up to six motors from one 4 to 0 ma controller. T T T T SETTINGS AND ADJUSTMENTS Before Setting Stroke. Remove the top cover from the motor.. Disconnect the controller from the motor. 3. For models with an internal transformer (line voltage motors), ensure that power (and nothing else) remains connected to the motor. IMPORTANT Detach linkage from motor before adjusting stroke. Careless Installation Hazard. Use of excessive force while adjusting cams damages the motor. To avoid damaging motor end switches, set cams by moving only the screwdriver top. Equipment Damage Hazard. Can damage the motor beyond repair. Never turn the motor shaft by hand or with a wrench. Forcibly turning the motor shaft damages the gear train and stroke limit contacts. Adjustable Stroke All models except for M784C083, M784C09, M784Q08, and M784Q090. When viewing from the power end of the motor, the stroke potentiometer is to the far left. To set the stroke to 60 (maximum position) turn the potentiometer fully clockwise, using a /8 in. straightblade screwdriver. To set the stroke at 90 (minimum position) turn the potentiometer fully counterclockwise. Setting the potentiometer anywhere between fully clockwise and fully counterclockwise will set the stroke between 60 and 90. ADJUSTABLE STROKE POTENTIOMETER POWER END OF SWITCH CAMS M3699 Fig. 9. Stroke adjustment setup 63640 08 8

SERIES 7, 7, AND 76 MODUTROL IV S Zero and Span Adjustment for M784Q, M785Q, and M794Q M784Q, M785Q, and M794Q actuators have the capability of adjustable zero and span. Fig. 0 shows the module with the zero and span potentiometers. Zero: Sets input voltage to define the 0% angle of rotation. It is factory set to minimum position and can be adjusted to the maximum position of 0mA or 0V. Span: Adjusts motor response to travel a full stroke through the selected input span. It is factory set to maximum position, and is adjustable from 40mA or 0Vdc.. Adjust the start potentiometer fully clockwise (maximum zero) and the span potentiometer fully counterclockwise (minimum span). See Fig. 0.. Set the controller current to the value required to drive the motor to the closed position. A 3. Turn the start potentiometer slowly counterclockwise until the motor begins to open. This is defined as the start or zero setting. 4. Set the controller current to the value required to drive the motor to the fully open position. The motor will open. 5. Turn the span potentiometer clockwise until the motor starts to close. The difference between the fully open span position current and the zero position current is defined as the operating span. 6. Recheck the start and readjust the span potentiometer if necessary. Turn the start potentiometer clockwise to increase the zero position. 7. Recheck the span and readjust the span potentiometer if necessary. Turn it clockwise to increase the full span position. 8. For sequential operation, as shown in Fig., repeat the above steps for each motor. B RIGHT/INNER SWITCH () RIGHT/INNER SWITCH F (TEST) INNER SWITCH CAM (BLUE) F INNER SWITCH CAM (BLUE) V() Y() POWER END POWER END T OUTER SWITCH CAM (RED) () T OUTER SWITCH CAM (RED) T LEFT/OUTER SWITCH T LEFT/OUTER SWITCH NOTE: FEATURES AVAILABLE ON SOME MODELS ONLY. NOTE: FEATURES AVAILABLE ON SOME MODELS ONLY. TO 0 VDC INPUT S 4 TO 0 ma NONADJUSTABLE INPUT S RESOLUTION POTENTIOMETER, 60 ON M784C083, M784C09, M784Q08, AND M784Q090 C SPAN ADJUST POTENTIOMETER RIGHT/INNER SWITCH () F SPAN ADJUST MIN MAX INNER SWITCH CAM (BLUE) POWER END ( ) T T START ADJUST MIN MAX OUTER SWITCH CAM (RED) LEFT/OUTER SWITCH START ADJUST POTENTIOMETER NOTE: FEATURES AVAILABLE ON SOME MODELS ONLY. 4 TO 0 ma ADJUSTABLE INPUT S M3648A Fig. 0. Terminals and adjustments. 9 63640 08

SERIES 7, 7, AND 76 MODUTROL IV S CONTROL OUTPUT ma CURRENT (OR VOLTS DC) 0 (0) 6 (8) (6) 8 (4) 4 () 0 CLOSED OPEN CLOSED OPEN CLOSED OPEN 3 3 3 3 PROPORTIONS BETWEEN 4 AND ma; FULLY CLOSED AT 4 ma, FULLY OPENED AT ma. 3 SEQUENTIAL OPERATION FOR ADJUSTABLE ZERO AND SPAN MODELS PROPORTIONS BETWEEN 8 AND 6 ma; FULLY CLOSED AT 8 ma, FULLY OPENED AT 6 ma. 3 PROPORTIONS BETWEEN AND 0 ma SIGNAL; FULLY CLOSED AT ma, FULLY OPENED AT 0 ma. UP TO 6 S CAN BE DRIVEN SEQUENTIALY OR IN UNISON FROM ONE CONTROLLER. ADJUST ZERO ADJUST AND SPAN ADJUST POTENTIOMETERS TO ACHIEVE DESIRED SEQUENCE. M893A Fig.. Sequential operation of motors. Enhanced Resolution M784C083, M784C09, M784Q08, and M784Q090 These four motors have enhanced resolution with 60 repositions (steps) from 90 degrees to 60 degrees stroke. Auxiliary Switches Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect all power supplies before installation. Motors with auxiliary switches can have more than one disconnect. Equipment Damage Hazard. Can damage the motor beyond repair. Never turn the motor shaft by hand or with a wrench. Forcibly turning the motor shaft damages the gear train and stroke limit contacts. Adjustable cams actuate the auxiliary switches. These cams can be set to actuate the switches at any angle within the motor stroke. Select switch differential of or 0. Motors with factory added auxiliary switches are shipped in the closed position (fully counterclockwise, as viewed from the motor power end) with auxiliary cams set to actuate switches 30 from the closed position and to provide degree differential. With the motor in the closed (fully counterclockwise) position, the auxiliary switch breaks contacts RB. See Fig. for auxiliary switch wiring. Series Motors are shipped with auxiliary switch cams that permit acceptance of 0736A,B Internal Auxiliary Switch Kits. Refer to form 638 for 0736A,B Installation Instructions. Auxiliary Switch Adjustment IMPORTANT When adjusting the auxiliary switch cams use the following procedure:. Insert /8 in. screwdriver blade into a slot on cam and move the screwdriver top as far as possible in the required direction. See Fig... Repeat step in successive cam slots until the cam is in the required position. NOTE: Series Motors are shipped with auxiliary switch cams that permit acceptance of 0736A,B Internal Auxiliary Switch Kits. Refer to Form no. 63 8 for 0736A,B Installation Instructions. Use the following procedure to obtain the desired auxiliary switch settings:. Remove the top cover from the motor to gain access to the motor terminals and auxiliary cams.. Disconnect the controller from the motor. 3. Connect a current source to the positive and negative terminals. 4. Drive the motor to the position where the auxiliary equipment is to be switched by increasing or decreasing the current. 5. For a switch differential of, check continuity of auxiliary switch contacts RB and rotate the cam as follows: a. If the contacts are open, rotate the cam clockwise until the RB contacts close. b. If the contacts are closed, rotate the cam counterclockwise until the RB contacts open. 6. For a switch differential of 0 rotate the cam approximately 80 so the slowrise portion of the cam actuates the switch. 7. Check continuity of the auxiliary switch contacts RB. 8. Rotate the cam as follows: a. If the contacts are open, rotate the cam counterclockwise until the RB contacts close. b. If the contacts are closed, rotate the cam clockwise until the RB contacts open. c. Make final adjustment in the proper direction to obtain contact make or break at the desired position. 9. Check for the proper differential and switching of the auxiliary equipment by driving the motor though the full stroke in both directions. 0. Disconnect power, remove current source, reconnect the controller, and replace the top cover on the motor. NOTE: Changing the differential from to 0 reverses the switching action. For example, with a 0 differential, switch contacts RB make and RW break on a counterclockwise (closed) rotation. With a differential, switch contacts RW make and RB break on a counterclockwise (closed) rotation. 63640 08 0

SERIES 7, 7, AND 76 MODUTROL IV S /8 INCH STRAIGHTBLADE SCREWDRIVER MOVE SCREWDRIVER AT TOP ONLY TO ADJUST CAM. NOTE: CAMS ARE OFFSET VERTICALLY TO PROVIDE BETTER VIEW OF BACK CAM. SLOW RISE PORTION (APPROX. 0 DIFF.) INNER CAM (BLUE) RIGHT/INNER SWITCH FAST RISE PORTION (APPROX. DIFF.) LEFT/OUTER SWITCH FAST RISE PORTION (APPROX. DIFF.) OUTER CAM (RED) SLOW RISE PORTION (APPROX. 0 DIFF.) RIGHT/INNER SWITCH INNER CAM (BLUE) OPEN POWER END CLOSE LEFT/OUTER SWITCH POWER END OF OUTER CAM (RED) M70 Fig.. Auxiliary switch adjustment. OPERATION AND CHECKOUT Operation The internal shaft position feedback potentiometer in conjunction with the actuator microprocessor and modulating input circuit form a control loop. When the external controller s output remains at a fixed amplitude the actuator s shaft position is held at a position proportional to that input amplitude. When the value of the external controllers output changes the actuator responds by initiating movement of the motor to proportionately compensate for the change in input amplitude. When the motor reaches the control loop balance point the system is again in a static state and the actuator holds position until the next change of input from the external controller. M7685 motor also have a minimum position feature. An external 30 ohm potentiometer wired to terminals 3 and 4 establishes a position beyond which the control input cannot close the motor. If power to the TT is interrupted the M7685 motor will spring close. Checkout After installation and linkage adjustment, operate the motor through the controller. Make sure that: The motor properly operates the damper or valve. The motor responds properly as the input is varied. The auxiliary switch, if used, operates at the desired point of motor rotation. Inspect the motor, linkage, and valve or damper to see that all mechanical connections are correct and secure. In damper installations, the pushrod should not extend more than a few inches past the ball joints. Check to see that there is adequate clearance for the linkage to move through its stroke without binding or striking other objects. See controller or system instructions for additional checkout procedures. Motor Operation Checkout For motors with F, and terminals: To close the motor, open terminals,, and F. To open the motor connect terminal F to positive () or negative (). NOTE: DO NOT SHORT to M764A07 and M764G030 do not have or terminals, and operate as follows: The motor closes if it does not receive an input to F. To open the motor, short F to C. M7685A05 is a normally open motor, and operates as follows: To close the motor, short 3 to 4 or short 3 to C. The motor opens if it does not have an input to 3. 63640 08

SERIES 7, 7, AND 76 MODUTROL IV S Automation and Control Solutions Honeywell International Inc. 985 Douglas Drive North Golden Valley, MN 554 customer.honeywell.com U.S. Registered Trademark 0 Honeywell International Inc. 63640 08 M.S. Rev. 0 Printed in United States