Report of the investigation into the engine room fire onboard the MV. Laurentian at sea on 11 October M.V. Laurentian

Similar documents
(Chapter II-1, Regulations 29.1, , 29.3, 29.4, , 29.14, 28.2 and 28.3 and 30.2)

REDUNDANT PROPULSION SHIPS RULES FOR CLASSIFICATION OF NEWBUILDINGS DET NORSKE VERITAS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2

(Chapter II-1, Regulations 29.1, , 29.3, 29.4, , 29.14, 28.3 and 30.2)

CHAPTER II-1 C. Construction subdivision and stability, machinery and electrical installations

(Chapter II-1, Regulations 29.1, , 29.3, 29.4, , 29.14, 28.2 and 28.3)

OPERATIONS SEAFARER CERTIFICATION GUIDANCE NOTE. Level 3 Assessment Chief and Second Engineer <3000kW

(Chapter II-1, Regulations 29.1, , 29.3, 29.4, , 29.14, 28.2 and 28.3)

REDUNDANT PROPULSION SHIPS RULES FOR CLASSIFICATION OF NEWBUILDINGS DET NORSKE VERITAS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES. Comments on document FP 46/5/8. Submitted by Japan

CHAPTER II-1 D. Construction subdivision and stability, machinery and electrical installations

The Benefits of Podded Propulsion in the Offshore Market

RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF SHIPS IDENTIFIED BY THEIR MISSIONS CHAPTERS APPROACH

HSS Stena Explorer. Report on the investigation of the fire on board. entering Holyhead. 20 September 2001

Marine Transportation Safety Investigation Report M17C0220

BSS Examination Record Form for Privately Owned and Managed Vessels

GUIDELINES FOR THE MAINTENANCE AND INSPECTIONS OF FIXED CARBON DIOXIDE FIRE-EXTINGUISHING SYSTEMS

Feasibility of Electric Propulsion for Semi-submersible Heavy Lift Vessels

T24 T m3 Chemical and Oil Product Tanker

Report on the investigation. of the engine room fire on. RMS St Helena. 25 August 2000

M A R I T I M E E N G I N E E R S P T Y L TD A Member of James Fisher and Sons plc

ALPHA MARINE CONSULTING LTD. 26, SKOUZE STR PIRAEUS GREECE

SPECIFICATION OFFICIAL NO BREADTH 15.1 GROSS TONNAGE 33 PASSENGERS US GALLONS

Accident Report. Fire Howick Rescue April 2005 Class B

MARINE INVESTIGATION REPORT M01M0005 FIRE - STARBOARD ENGINE ROOM

AIR LUBRICATION SYSTEM INSTALLATION

Gearless / full scantling cellular container vsl with poop, forecastle and open top cargo hold

Title: Lifting Operations Involving Crane or Gantry Offshore

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2, THE FSS CODE AND RELATED FIRE TEST PROCEDURES

VESSEL CHARACTERISTIC FIELDS

National Transportation Safety Board

HAZARDOUS AREA CLASSIFICATION (APPLICATION OF SOLAS REGULATION II-1/45.11)

United Stales COMDPTPUB P Coast Guard NVIC Mar 191

Dropped Object Incidents on Chevron operated assets

DECEMBER 15-18, 1997 ADELAIDE, SOUTH AUSTRALIA. Y. K. Tso and R. G. Juniper

UNIFIED INTERPRETATION OF PROVISIONS OF IMO SAFETY, SECURITY, AND ENVIRONMENT RELATED CONVENTIONS

PART 8 MACHINERY INSTALLATIONS

OPERATIONS SEAFARER CERTIFICATION GUIDANCE NOTE. Level 3 assessment Marine Motorman Higher Grade

CATERPILLAR 3516B DP2 System

Outline Specification 60M -1500m 3 Live Fish Carrier

SCENARIO 8. Propane Fueled Delivery Truck Fire INCIDENT OVERVIEW

NVC-Design TM. NVC m Purse Seiner/Pelagic Trawler. Fact sheet DESIGN & INTEGRATED SHIP SYSTEM GENERAL INFORMATION.

E-15 Uninterruptible Power Systems (UPS)

Tank Truck Explosion Date of Incident: Type of Incident: Double Fatality

INFORMATION BULLETIN No. 84

ALTERNATE COMPLIANCE PROGRAM

O C E A N T O W I N G C O N D I T I O N S C H E C K L I S T T U G : T O W :

ST. VINCENT AND THE GRENADINES

Inspecting Airport Fueling Systems

Efficient and flexible solution

Deck Mounted Electric Rotatable Propeller Drives

Topaz Master. 85T BP M 5700 kw DP2 - AHTS. Vessel Specifications

NaviSafe nv. Emdenweg 11 Haven Antwerpen Belgium T F

OVID Refresher Inspector Course. A Guide to the uniform inspection procedure OVID

Engtek Manoeuvra Systems Pte Ltd

INFORMATION BULLETIN No. 165

Recommendation for petroleum fuel treatment systems for marine diesel engines

AZIMUTH STERN DRIVE 35/105 TERMINAL SUPPORT/ESCORT TUG

Y-fl'. MINISTRY OF TRANSPORT AND COMMUNICATIONS DEPARTMENT OF MARINE ADMINISTRATION

PENNSYLVANIA STATE FIRE ACADEMY PUMPER - DRIVER/OPERATOR (PDO) SKILL STATIONS. Pumper -Driver / Operator (PDO) Skill Stations

M-22 DUAL FUEL ENGINE

Sector Baltimore Small Passenger Vessel Branch Initial Certificate of Inspection (ICOI) Work Instruction

Delta 85 Flushdeck Flybridge MY Feelin' Free

MSC Guidelines for Fuel Oil Systems

MSN 047 June 2014 MANX SHIPPING NOTICE DEPARTMENT OF ECONOMIC DEVELOPMENT

mv ARK FORWARDER IMO MMSI call sign 5BQY3

Emergency Towing Booklet (ETB) According to SOLAS II-1, Reg. 3-4 and MSC.1/Circ. 1255

AVIATION OCCURRENCE REPORT A98P0100 ENGINE FIRE IN FLIGHT

BOURBON LIBERTY 150 SERIES. Platform Supply vessels. DP2-1,701 t DWT

Jersey Harbour Authority Maritime House, St Helier, Jersey, JE1 1HB Tel: +44 (0) Website:

GENERAL SPECIFICATION. FRSQ 700 A 370 HP inboard FAST RESCUE BOAT

Programmable Safety Systems for Burner Management on Gas Turbines.

Prof. Mustafa Insel HİDROTEKNİK Nautical Design Development. A Decision Support System for Energy Efficient Propulsion MARENER WMU

Specifications for New Underground Mobile Mining Equipment Underground Mobile Equipment Major Hazard Standard

PT. Marine Propulsion Solutions. BTM Thruster Series

Machinery Systems, General

PRIDE / EXCELLENCE Vessel Specification

SEA ROYAL. Dimensions Length Overall : 60 m. Registration. Breadth Moulded : 16 m. Depth Moulded : 6 m

OPERATIONS SEAFARER CERTIFICATION GUIDANCE NOTE SA MARITIME QUALIFICATIONS CODE. Deck: Ship s Power Plants

EXPEDITION FIRE- BURNED DOZER

Maintenance Checklist

Mechanical, hydraulic and electrical independency of steering gear control systems

Technical Publication. Guidelines for the development of ship's Data Collection Plan (SEEMP Part II) /

MACHINERY SYSTEMS, GENERAL

KEY FEATURES. DP-3 250T Offshore Crane 1600m 2 Deck Space Moonpool High sea state capability ARIADNE

INFORMATION BULLETIN No. 165

E-15 Uninterruptible Power Systems (UPS)

Ships in Operation Survey Requirements

Berlingo First Electric. Safety procedures to be observed with an accident-damaged vehicle where the traction battery may be damaged

SSC Case Study V Container Ship Recurring Failure of Side Longitudinal Passing through a Web Frame

BOA DEEP C Subsea / IMR / Offshore Construction Vessel

SUBSEA Petroleum service -- Page 1 of 5 Website

Equipment tug collision with BAe , EI-CMS, 24 May 1999 at Dublin Airport, Ireland.

Driver Fatally Injured by Fall from Truck Date of Incident: March 5, 2007 Type of Incident: Fatality

motralec KRAL Pumps with Magnetic Coupling for Marine Applications.

KEEL MARINE LTD Naval Architects, Marine Engineers and Surveyors

ACCIDENT REPORT. Pride of Canterbury. Report on the investigation of. a main engine room fire on board. while berthing in Calais. on 29 September 2014

Chapter 14:08 Factories and Works (Electrical) Regulations, Chapter 14:08 Factories and Works (Electrical) Regulations, 1976

ANNEX 23. RESOLUTION MEPC.187(59) Adopted on 17 July 2009

JU Operator And Service Provider For Offshore Works

CWS MARITIME SERVICES

Transcription:

Report of the investigation into the engine room fire onboard the MV. Laurentian at sea on 11 October 2001 M.V. Laurentian

The Bahamas Maritime Authority investigates incidents at sea for the sole purpose of discovering any lessons which may be learned with a view to preventing any repetition. It is not the purpose of the investigation to establish liability or to apportion blame, except in so far as emerges as part of the process of investigating that incident. It should be noted that the Bahamas Merchant Shipping Act, Para 170 (2) requires officers of a ship involved in an accident to answer an Inspector s questions fully and truly. If the contents of a report were subsequently submitted as evidence in court proceedings relating to an accident this could offend the principle that a person cannot be required to give evidence against himself. The Bahamas Maritime Authority makes this report available to any interested parties on the strict understanding that it will not be used as evidence in any court proceedings anywhere in the world. Date of Issue : 23 April 2002 Bahamas Maritime Authority Latham House 16 Minories LONDON EC3N 1EH United Kingdom THE BAHAMAS MARITIME AUTHORITY

CONTENTS Page 1. Summary 2 2. Particulars of Vessel 3 3. Configuration 4 4. Narrative of Events 5 5. Conclusions 7 6. Recommendations 8 Annex 1 Arrangement of main engine generators 9 Annex 2 Photographs 11 1 THE BAHAMAS MARITIME AUTHORITY

1. SUMMARY 1.1 At the time of the incident the vessel was at 26 09.1 N, 053 07.1 E and engaged in deploying a streamer prior to the commencement of work. At 0614 the duty engineer informed the bridge of a fire in the engine room. The initial fire on the No.1 engine was extinguished by the engine room staff, but subsequently reignited. The engine room team could not extinguish the secondary fire and the engine room was evacuated at 0620. All personnel on the vessel were mustered at the muster stations and at the same time all external vents were closed. 1.2 At 0621 flames were seen coming from the starboard funnel and starboard access door on main deck which was open at the time. The fuel oil quick closing valves were activated and at 0626 all main engines stopped, rendering the vessel powerless. 1.3 Boundary cooling was applied on funnel casings and the engine room forward water tight bulkhead which were monitored for temperature rise. The vessel was then taken in tow by the accompanying chase boat and at 0700 the tow was underway. Subsequently the engine room was re-entered and the habour generator started allowing lighting and limited power to be restored. 1.4 After starting Nos. 3 & 4 main engine generators the vessel regained propulsive power, and released the tow line to the chase boat. In water seismic equipment was recovered overnight and then the vessel proceeded to Dubai for repairs. 2 THE BAHAMAS MARITIME AUTHORITY

2. PARTICULARS OF VESSEL 2.1 M.V.Laurentian was an offshore supply/ survey vessel registered at Nassau, Bahamas, of welded steel construction with the following principal particulars:- Official Number - 715224 IMO Number - 8112500 Length overall - 84.7 metres Breadth - 16.8 metres Depth - 7.10 metres Gross Tonnage - 3375 tonnes Net Tonnage - 1013 tonnes Call Sign - C6DQ3 Year of build 1983 Class Det Norske Veritas Owner Seismic Exploration International Inc. Manager Techmarine International Ltd. 2.2 Power was produced by 4 Wartsila 8R 22 HE main engine generators that developed a total of 5120 kw operating a diesel electric system powering two 1500 kw azimuthing thrusters. 2.3 The vessel was built in Norway and was formerly named Labrador Horizon. 2.4 At the time the vessel complied with the all statutory and international requirements and certification. 3 THE BAHAMAS MARITIME AUTHORITY

3. CONFIGUATION OF MACHINERY The vessel power configuration is as follows:- 3.1 The 4 main engine generators supply 600 volts to the main switchboard. The main switchboard supplies the following equipment at 600 volts:- Main azimuthing thruster motors which operate at 1200 or 1800 revs/min. Bow thrusters Windlass power packs Auxiliary switchboard distribution panel 3.2 All auxiliary services are supplied from 440 volt system fed from two transformers located in the after end of the engine room 220 volt supplies for lighting etc. are fed from the 220 volt switchboard 3.3 Main propulsion is from two animating thrusters, however, an independent diesel driven aqua master (retractable thruster) unit is located forward of the engine room to provide back up forward propulsion in the event of main propulsion breakdown. 3.4 At the time of the incident nos. 1.2 &4 generators were supplying the main switchboard. Both animating thrusters were running at 1800 revs /min. The aqua master was also deployed and running at the time of the incident. 3.5 The main engine fuel is drawn from the daily service tank and fed to the fuel oil booster pump. The booster pump supplies the generator fuel rails from a common piping system at a pressure of 5 bar. Fuel isolating vales for maintenance purposes are fitted at the forward end of each engine located under the floor plates just forward of the turbocharger. 3.6 Fuel at 5 bar is fed to the engine driven booster pump which increases the pressure to 8 bar feeding it to the main supply rail which is connected to each individual high pressure fuel pump suction by an individual line. This line is flanged at both the rail and fuel pump suction, the flanges being secured at both ends by two Allen screws. 4 THE BAHAMAS MARITIME AUTHORITY

4. NARRATIVE OF EVENTS 4.1 All times noted in this narrative are given in the style of the standard 24 hour clock and as local time which was GMT +4. 4.2 The weather at the time of the incident was, wind NW Force 4, sea slight and visibility good 4.3 At the time of the incident the vessel was in position 26 09.1 N 053 07.1 E and was engaged in deploying a streamer at 3.2 knots, course 305 prior to the commencement of work. 4.4 At 0614 the duty engineer informed the bridge of a fire in the engine room. The officer of the watch sounded the fire alarm whereupon the chief engineer entered the engine room to find the forward end of the starboard outboard, No.1, main engine engulfed in flames. The 3 rd engineer was fighting the fire with a CO2 fire extinguisher. 4.5 The chief engineer went to the control room and informed the bridge of the fire and its location. He then disconnected No.1 main engine from the main switch board and shut the machine down. 4.6 He then proceeded to the forward compartment and returned with a wheeled foam fire extinguisher and began to douse the fire. With this unit and other portable units brought to bear by the engine room staff who were on the scene the flames were knocked down. The bridge was then informed that the fire was extinguished. 4.7 However, the engine room staff were unable to shut off the fuel supply to the engine due to the high heat concentration in way of the forward end of the engine where the fuel shut off valve was sited. The fuel re-ignited and attempts to extinguish the fire were successful in only keeping the fire confined to the starboard forward corned of the engine room. At this point the chief engineer instructed the 3 rd engineer to activate the fuel quick closing valve to the main engines starving the fire of fuel and blacking the vessel out. 4.8 Further attempts to extinguish the fire using portable apparatus failed and the chief engineer gave instructions for the engine room staff to muster in the engine control room, while informing the bridge of this decision. The master instructed all engine room staff to evacuate the engine room and the ventilation flaps and watertight doors to be closed. 4.9 Whilst all engine room personnel were assembled in the control room a high pressure release was heard in the engine room and this was assumed to be a bursting disc on a Halon cylinder releasing due to the heat in the area. At the same time as the pressure release was noted, a large fire ball was observed over the top of No. 1 engine travelling forward towards the forward casing. At this time the engine control room 5 THE BAHAMAS MARITIME AUTHORITY

was evacuated through the emergency escape hatch and the machinery space completely sealed off. 4.10 Boundary cooling was applied on funnel casings and the engine room forward water tight bulkhead. After monitoring of the engine room boundary bulkheads and no rise in temperature noted it was decided not to activate the Halon system as it would be better kept in reserve. 4.11 The vessel was then taken in tow by the accompanying chase boat and at 0700 the tow was underway. Subsequently the engine room was re-entered and the harbour generator started allowing lighting and limited power to be restored. After starting Nos. 3 & 4 main engine generators the vessel regained propulsive power, and released the tow line to the chase boat. In water seismic equipment was recovered overnight and then the vessel proceeded to Dubai for repairs. 6 THE BAHAMAS MARITIME AUTHORITY

5. CONCLUSIONS 5.1 Subsequent investigation indicated that the Halon smothering system was intact with all cylinders at the correct operating pressure of 40 Bar. The high pressure release which was heard from the engine control room (4.9) was believed to be the relief valve vent in the main air receiver which was located on the forward bulkhead directly ahead of No. 1 generator. 5.2 The primary fire was caused by the fuel leakage due to the failure of the O ring on No 8 high pressure fuel pump suction flange which allowed fuel at 8 bar pressure to spray out below the fuel pump cover and impinge on the exhaust manifold in way of the turbo charger. The O ring failed due to the top retaining Allan screw vibrating loose which eased the pressure on the flange allowing O ring to blow out. 5.3 Although the fire was knocked down, fuel to the engine could not be isolated due to the intense heat in the location of the shut off valve. This allowed the leakage at No.8 fuel pump to continue. The fuel return line was isolated, but the fuel supply line isolating valve could not be shut. Therefore fuel leakage continued, re-igniting and causing a secondary fire. The secondary fire was fuelled with further oxygen from the main air receiver relief valve which resulted in the fire ball. 5.4 The starboard engine casing access door situated on to Main Deck was open, causing a natural draught up the casing. When the fire ball occurred it was drawn up the casing by the draught and exited partly out of the open door and partly out of the top exhaust vent. This resulted in the main fire damage being localized to the starboard forward end of the engine room. 5.5 The fuel system fitted to the vessel is a conventional fuel booster system with one pump supplying four engines. In the case of a diesel electric system such as this, stopping the fuel booster pumps to isolate a fuel leak will result in the loss of all power supplies. 7 THE BAHAMAS MARITIME AUTHORITY

6. RECOMMENDATIONS The owners of M.V. Laurentian are recommended to :- 6.1 Replace fuel line retaining Allan screws in way of HP fuel pump suctions on all 4 main engines 6.2 Fit fuel pump covers with sealing strips in way of the cylinder head cover landing face. 6.3 Fit independent remote shut off valves to each main engine to allow individual engine remote fuel isolation. 6.4 Investigate the cause of vibration in No.1 main engine fuel system and rectify. 6.5 Review and apply the requirements of SOLAS 2001Chapter II-2 Regualtion 15. 2.7 2.12. 6.6 Fit a sheet steel guard between No. 8 cylinder and the turbo charger of each engine. The owners have attended to each of the above recommendations during the repairs to the vessel after this fire. 8 THE BAHAMAS MARITIME AUTHORITY

ANNEX 1 9 THE BAHAMAS MARITIME AUTHORITY

10 THE BAHAMAS MARITIME AUTHORITY

ANNEX 2 11 THE BAHAMAS MARITIME AUTHORITY

Photo 1 No 8 Cylinder fuel pump Photo 2 Guard retro fitted between No. 8 cylinder and turbo charger on each engine 12 THE BAHAMAS MARITIME AUTHORITY

Photo 3. Quick closing valve operating station in MCR Photo 4. New fuel oil quick closing valves fitted on each main engine 13 THE BAHAMAS MARITIME AUTHORITY