CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/18 GB. replaces 01260/14 GB

Similar documents
CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/14 GB

CALEFFI. Composite manifolds specifically designed for radiant panel systems. 670 series 01126/18 GB. replaces dp 01126/11 GB.

CALEFFI. Pre-assembled distribution manifolds for. heating and air-conditioning systems. 663 series 01065/18 GB. replaces dp 01065/06 GB.

CALEFFI. Pre-assembled distribution manifold for radiant panel systems S1 series 01144/11 GB. Replaces 01144/07 GB.

CALEFFI. Manifolds in composite specifically designed for radiant panel systems. 670 series 01126/05 GB. Function

Pre-assembled distribution manifolds for radiant panel systems

CALEFFI. Pre-assembled distribution manifolds for radiant panel systems. series 663 & /05 NA. Function

CALEFFI. Modulating temperature regulating unit with distribution kit for primary circuit. 171 series 01153/15 GB. replaces 01153/07 GB

COMPONENTS FOR SOLAR THERMAL SYSTEMS

COMPONENTS FOR SOLAR THERMAL SYSTEMS

CALEFFI. Direct supply unit for heating systems. 165 series 01237/17 GB. replaces dp 01237/15 GB. Function

CALEFFI. Ball shut-off valve fitted for integrated flow rate measuring sensor. 111 series 01234/13 GB. (kpa) (mm w.g.) G (m 3 /h)

CALEFFI. Pressure independent control valve (PICV) 145 series 01262/14 GB B 51

CALEFFI. Motorised ball zone valves with 3-contact control BY series 01131/18 GB. replaces 01131/11 GB

FLOW RATE STATIC BALANCING Valves for radiators

CALEFFI. Motorised temperature regulating unit for heating and air conditioning systems WYP UPM series 01254/17 GB

SINGLE MANIFOLDS TECHNICAL DATA SHEET10/ ENG

CT3202.0_01 EN February 2018

ACCREDITED. brass EN CW617N brass EN CW614N brass EN CW614N, chrome plated PTFE PSU EPDM

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Important Product range Technical specifications

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Product range. Technical specifications. Characteristic components

Art.918C Pre-assembled manifold with flow meters, air

Connection and regulation kit for HVAC terminal units

THERMOSETTER Recirculation thermal balancing valve

PRE-ASSEMBLED MANIFOLD KIT 1 TECHNICAL DATA SHEET 10/ ENG

MANIFOLDS AND DISTRIBUTION EQUIPMENT

PRE-ASSEMBLED MANIFOLD KIT 1 TECHNICAL DATA SHEET 09/ ENG

Pressure Independent Control Valve

CALEFFI. Motorised ball valve for central heating systems. 638 series 01196/18 GB. replaces dp 01196/12 GB

80% Max working pressure: Max working temperature: 70 C. Flow-meter regulation range: Flow meter-regulation range: ± 10%

Components for central heating

WAY MOTORISED COMPACT ZONE VALVES

TECHNICAL CATALOGUE DISTRIBUTION MANIFOLDS

Preassembled manifolds with flow meter, series CPRFL

FO-BV Series. Fixed-orifice balancing and control valves. Technical Data Sheet. WattsIndustries.com

CALEFFI. Solar pump stations 01166/14 NA. 278 and 279 series 01264/16 NA

Dynacon. Floor Heating Manifolds Floor heating manifold with automatic flow control

T2 Wall Hung Radiator & UFH Manifolds

Product Information. Brass Manifolds. Version A

CALEFFI. Mixing valves and actuators series 01169/17 GB. replaces dp 01169/09. Function

CALEFFI. FLOWCAL Automatic flow balancing valve with polymer cartridge. 121 series 01141/11 NA. Function

CALEFFI. QuickSetter Balancing Valve with flow meter. Installation Tip

savings flexibility recyclable LIGHTNESS FULL FLOW MECHANICAL STRENGTH IMPROVE CONTROL TECHNICAL BROCHURE aesthetic performance CHANGE

485 - NC NO/DA DN

PNEUMATICALLY ACTUATED 2-WAY

CATALOG. Actuated Diaphragm Valve DN PVC-U / PVC-C / PP-H / PVDF / ABS SMART IN FLOW CONTROL.

Safety cap. Measuring probe. Seal. Operating principle. Advantages of balanced circuits. Balanced circuits have the following principal benefits:

RTL. Floor Heating Controller Return temperature limiter with and without presetting

DKD/CP DN PVC-U. Direct action pneumatically actuated 2-way diaphragm valve

underfloor heating PRODUCTS FOR UNDERFLOOR HEATING

Fan-coil valves Series

CHOOSING YOUR MANIFOLD & LOCATION

Solar Thermal. Grant Solar Pump Station Installation & Servicing Instructions

Floor heating manifold with automatic flow control

STAINLESS STEEL MANIFOLDS FOR RADIANT SYSTEMS CREATION AND DIFFUSION OF THE STAINLESS STEEL MANIFOLD USE DIAGRAMS OF STAINLESS STEEL MANIFOLDS

TA-6-way valve. Standard control valves 6-way valve for change-over systems

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Operating principle Application diagram. Regulator-actuator Wiring diagrams

CALEFFI. Hydraulic separator-manifold SEPCOLL. 559 series 01084/16 GB. replaces dp 01084/13 GB

K35 HeatBloC with 3-temperature mixing valve

dynacon floor heating manifold with automatic flow control

HERZ 7217 V. Integral Fixed Orifice Control Valve HERZ 7217 V. Data sheet 7217 V, Issue Size in mm. STRÖMAX Fig No DN L Lm Rp H SW kv kvs

TECHNICAL CATALOGUE BALL VALVES: PARIS

SELF-CLEANING FILTER

MOTORISED BALL VALVE. Uni/Bi-directional. patented. 3 points 2 points Price list root SR... SS... SY... Connection with ball valve.

CALEFFI. Diverter and isolation valves for panel radiators. 3010, 3011, 3012, 3013 series 01036/12 NA. Function. Product range

HERZ-Motorised flow controler

132 Series. QuickSetter Balancing Valve with flow meter NA Function

Products for underfloor heating

TECHNICAL CATALOGUE GAS BALL VALVES: BERLIN

Section 20. HVAC Valves & Products

FCU Floor Control Unit

TECHNICAL CATALOGUE BALL VALVES: IDEAL

DK/CP DN PVC-U / PVC-C / PP-H / PVDF. Pneumatically actuated 2-way diaphragm valve

TRF.. series spring return rotary actuators for CCV

HYDRAULIC SEPARATOR PRODUCTION RANGE. Code Size Max. flow rate (l/h) " "1/ "1/ " 8.

CALEFFI. Differential pressure by-pass valve. 519 series 01007/14 NA. Replaces 01007/12 NA

MrPEX 1 ¼ Stainless Steel Manifold. Installation Guide

548 hydraulic separator

DESCRIPTION 9.4 G 3/4"M

DN [ ] DN [ ] Functional data Media Cold and hot water, water with glycol up to max. 50% vol.

TECHNICAL SPECIFICATIONS 63/2E DN15 Kvmax /4"E. ( 3 4"x18) 3/4"E

LK Manifold Shunt VS2

Technote. Frese OPTIMA - Pressure independent control & balancing valve. Application. Features. Benefits.

PRESSURE CONTROL VALVES SABS 198

3-Port Seat Valves with Male Thread, PN 16

MrPEX 1 ½ " Brass Manifold Installation Guide

VE-S_15-32 Pressure Independent Balancing & Control Valves

DISTRIBUTION GROUP WITH THERMOSTATIC REGULATION. Upper connections G1 F Without fittings Fittings with running connection* Without pump

Product and installation manual. Underfloor Heating Composite Manifold

Process Multi-Rheo Filter PMRF

M-8100EP. Installation Guide ENGINEERED PLASTIC MANIFOLD SERIES. Introduction. A. Assemble Manifold Components

Combined automatic balancing valve AB-PM valve DN 10-32, PN 16

DK AND DK/CP DN 15 65

AUTOMATIC CONTROL VALVES. TIS asia

Application technology, 5th edition. Volume III: Fonterra radiant heating and cooling

AVQMT. AVQT controller can be combined with AVT or STM thermostatic actuators.

Produkt informatie COSTER T.E.

THERMOSTATIC CONTROL HEADS:

LK Manifold RF. Design. Requirements. Documentation

TA-6-way valve. NPT threads. Standard control valves 6-way valve for change-over systems

Transcription:

Distribution manifold for radiant panel systems 664 series FM 21654 003 CALEFFI 01260/18 GB replaces 01260/14 GB Function The distribution manifold for radiant panel systems is used to optimally distribute the thermal medium in underfloor heating system circuits, in order to improve the control of the panel thermal emission. This series of manifolds is composed of: - flow manifold complete with built-in flow meters and regulating valves, with indicators that can be cleaned and replaced with the system operating; - return manifold complete with shut-off valves fitted for thermoelectric actuator; - end fittings complete with automatic and manual air vent with fill/drain cocks; - LCD thermometers, on the flow and return manifolds. Product range 664 series Distribution manifold for radiant panel systems size 1 Technical specifications Materials Flow manifold Body: brass EN 1982 CB753S Flow rate regulating valve: Stem and obturator: PA Hydraulic seals: EPDM Protective cover: ABS Spring: stainless steel EN 10270-3 (AISI 302) Return manifold Body: brass EN 1982 CB753S Shut-off valve: Headwork: brass EN 12164 CW614N Obturator stem: stainless steel EN 10088-3 (AISI 303) Obturator: EPDM Spring: stainless steel EN 10270-3 (AISI 302) Hydraulic seals: EPDM Cap: ABS Brackets and supports: Steel EN 10027-1 S235JR Performance Medium: water, glycol solutions Max. percentage of glycol: 30% Maximum working pressure: Working temperature range: 6 bar 5 60 C Liquid crystal digital thermometer scale: 24 48 C Flow meter scale: 0 5 l/min Accuracy: ±10% Main connections: 1 F (ISO 228-1) Outlets: M - Ø 18 Centre distance: 50 mm

Dimensions No. of outlets Total L (A) Mass (kg) 6646B1 2 165 2,7 6646C1 3 215 3,1 6646D1 4 265 3,6 6646E1 5 315 4,2 6646F1 6 365 4,8 6646G1 7 425 5,2 6646H1 8 475 5,7 6646I1 9 525 6,3 6646L1 10 575 7,1 6646M1 11 625 7,6 6646N1 12 675 8,1 6646O1 13 735 9 Characteristic components 1 Flow manifold with built-in flow meters and flow rate regulating valves 2) Return manifold complete with shut-off valves fitted for thermoelectric actuator 3) End fittings complete with manual and automatic air vents, double radial end fitting and drain cocks with plugs 4) Pair of mounting brackets for box or wall installation 4 2 1 4 3 Construction details Flow manifold The flow manifold is equipped with built-in flow meters and flow rate regulating valves (1). Using the regulating valve the flow rate to the individual circuits can be adjusted accurately as required, with the setting being read directly from the single flow meter with a scale of 0 5 l/min. This simplifies and speeds up the circuit setting process, with no need for reference graphs. After regulating, the valve can be locked in its open position by means of its protective cover. The valve itself makes it possible to shut-off each individual circuit, if necessary. 1

Flow meters cleaning or replacement with circuit in operation The flow meter indicators, supplied with the flow manifold, are easily removed for cleaning or replacement purposes without having to empty the system (spare part code R69913). The setting position indicator makes it possible to rebalance the circuit correctly at the design flow rate after maintenance operations. Return manifold end fitting The automatic air vent automatically expels the air accumulating in the circuits of the air conditioning system. It is equipped with a hygroscopic safety cap (1) that prevents water from getting out in order to protect the installation. 1 Return manifold The return manifold is equipped with manual shut-off valves (1), in order to cut off the flow to the individual circuits. They can also be fitted with a thermo-electric actuator (2) that, when used with a room thermostat, maintains the ambient temperature at the set values in spite of thermal load variations. The obturator stem (3) consists of a single piece of ground stainless steel, in order to minimise friction and prevent building up of dangerous limescale deposits. The headwork (4) has a double EPDM O-Ring seal (5) (6) on the sliding stem. The EPDM obturator (7) is shaped so as to optimise the hydraulic characteristics of the valve and minimise the noise caused by the flow of the medium, also during the progressive opening or closing action when operating with thermo-electric actuator. Digital thermometers Both sides of the flow and return manifold body are equipped with LCD thermometers, with 24 48 C temperature range. The LCDs automatically illuminate green in correspondence with the measured temperature value to ensure easy reading even in low light conditions. This thermometer is calibrated to display the actual temperature of the medium, which is essential in evaluating the operating conditions and thermal load of the system. 1 5 4 2 Replaceable components The headwork of the regulating valve with flow meter and the shut-off valve can be removed and replaced with spare parts. 6 3 7

Hydraulic characteristics In order to determine the hydraulic characteristics of the circuit, it is necessary to calculate the total head loss suffered by the flow rate of medium on passing through the devices forming the manifold assembly and the radiant panel circuits. From a hydraulic point of view, the system consisting of the manifold assembly and the circuits can be represented as a set of hydraulic elements arranged in series and in parallel. Δp Tot. DpTot. = Total head loss across the manifold (Flow + Return + Loop) RV LOOP SV DpRV = Localized loss at loop balancing valve (loop flow rate) DpLoop = Loop head loss (loop flow rate) Δp Manif. F Δp Manif. F DpSV = Localized loss at panel circuit shut-off valve (loop flow rate) G Tot. G Tot. DpManif. F = Distributed loss of the flow manifold (total flow rate) DpManif. R = Distributed loss of the return manifold (total flow rate) DpTot. = DpRV +DpLoop + DpSV + DpManif. F + DpManif. R (1.1) When the hydraulic characteristics of each component and the design flow rates are known, the total loss can be calculated as the sum of the partial head losses for each specific component in the system, as indicated by the formula (1.1).

Hydraulic characteristics Δp (mm w.g.) RV SV Δp (kpa) Flow rate (l/min) (m 3 /h) Flow rate Flow rate regulating valve fully open (BV) Panel circuit shut-off valve (SV) - Kv = flow rate in m 3 /h for a head loss of 1 bar - Kv0,01 = flow rate in l/h for a head loss of 1 kpa Flow manifold 2 7 outlets Return manifold 2 7 outlets Flow manifold 8 13 outlets Return manifold 8 13 outlets *Average value Example of total head loss calculation Supposing we need to calculate the head loss of a manifold with three circuits with the following characteristics: Total manifold flow rate: 450 l/h The flow rate and head loss of the three loops are as follows: Circuit 1 Circuit 2 Circuit 3 Dp 1 = 10 kpa Dp 2 = 10 kpa Dp 3 = 7 kpa (1.2) G 1 = 120 l/h G 2 = 150 l/h G 3 = 80 l/h Each segment of the formula (1.1) is calculated using the following relationship: Dp = G 2 2 /Kv 0,01 G = flow rate in l/h Dp = head loss in kpa (1 kpa = 100 mm w.g.) Kv 0,01 = flow rate in l/h through the device, which corresponds to a head loss of 1 kpa It should be stressed that the calculation of DpTot. must be carried out taking account of the circuit in which there are the greatest head losses distributed along the entire panel pipe loop. In the case we are examining, the relevant circuit is No. 2. It follows that: Dp BV2 = 150 2 /110 2 = 1,86 kpa Dp Loop2 = 15 kpa Dp SV2 = 150 2 /410 2 = 0,13 kpa Dp Manif. F = 350 2 /1110 2 = 0,1 kpa Dp Manif. R = 350 2 /1670 2 = 0,04 kpa } Values obtained by neglecting the changes due to the flow rate sent to each branch circuit Using formula (1.1), adding up all the calculated terms, we obtain: Dp Tot.= 1,86 + 15 + 0,13 + 0,1 + 0,04 17 kpa Note: Because of the low head losses associated with the manifolds, the two terms relating to them can be disregarded. In general, the total head loss is fairly close to the branched panel circuit head loss.

Using the balancing valves with flow meter The regulating valves in the flow manifold make it possible to balance each individual panel circuit to obtain the design flow rates in each loop. Considering the following data: - medium flow rate across each circuit - head loss generated in each circuit by this flow rate: Dp Circuit = Dp Loop + Dp SV (Dp Shut-off valve ) SYSTEM FLOW RV Δp RV - available head on the panel circuit or predefined head: H Predefined Dp Circuit + = Dp RV + Dp Loop + Dp SV disadvantaged Δp Tot. ΔpCircuit H Predefined ΔpCircuit + disadvantaged Referring to the adjacent diagram, for the loop flow rate the regulating valve must provide an additional head loss equal to the difference Dp BV (Dp Balancing valve ). SYSTEM RETURN SV Flow rate balancing and reading Manually remove the red protective cover from the flow meter. While the system is running, manually adjust the design flow rate using the adjustment nut (1). The flow rate value is indicated by vertical movement of the red indicator disc (2). When the red indicator disc is positioned on the desired flow rate value, set the external indicator (3) in line with the internal indicator disc. 2 3 1 SPECIFICATION SUMMARY 664 series Distribution manifold for radiant panel systems with 2 (from 2 to 13) outlets. Brass body. EPDM seals. Main connections 1 F (ISO 228-1). Outlet connections M - Ø 18 threaded, centre distance 50 mm. Medium water and glycol solutions. Maximum percentage of glycol 30%. Maximum working pressure 6 bar. Working temperature range 5 60 C. Complete with: - Flow manifold with flow rate balancing valves and flow meter with 0 5 l/min graduated scale. Accuracy ±10%. - Return manifold complete with shut-off valves fitted for thermo-electric actuator. - Pair of end fittings complete with automatic air vent with hygroscopic cap on the return manifold and manual air vent and plug on the flow manifold. Complete with fill/drain cock. - Pair of mounting brackets for box or wall installation and mountable manifold supports.

ACCESSORIES CBN6646F1 CBN6646N1 CBN6646O1 By-pass kit Gruppo di testa Air vent Drain cock Insulation for distribution manifolds 664 series. For heating and cooling systems. For use with box code 659..4 (adjustable depth from 110 to 140 mm). for manifolds from 2 to 6 outlets for manifolds from 7 to 12 outlets for manifolds with 13 outlets 662010 Off-centre by-pass kit fixed setting 25 kpa (2500 mm w.g.) Working temperature range: -10 110 C. 599662 End fitting composed of air vent cock, double radial connection and plug. Max. working pressure: 10 bar. Working temperature range: 5 100 C. Main connection: 1 F. Lower connection: M. Upper air vent connection: 3/8 F. Lower plug connection: 1/2 F. 502033 Automatic air vent. In hot-stamped brass. With hygroscopic safety cap. Max. discharge pressure: 2,5 bar. Max. working temperature: 120 C. Connection: 3/8 M. R59681 AQUASTOP Hygroscopic safety cap. For air vents 5020 series. 337231 Drain cock with metal seal. Adjustable outlet. PTFE seal on. Max. working temperature: 100 C. Connection: 3/8 M. 538400 Drain cock with hose connection and cap. Max. working temperature: 110 C. Connection: 1/2 M. Valvole di intercettazzione 391066 Pair of ball shut-off valves with female-male connections and union with O-ring seal. Working temperature range: 5 100 C. Connection: 1. Brackets Fittings Ø inner Ø outer 680507 680502 680503 680500 680501 680506 680515 680517 680524 680526 680535 680537 680544 680546 680555 680556 680564 680505 347510 347512 347514 347515 347516 347518 17,5-18,0 17,5-18,0 8,5 19, 19,0 19,5 19,5 10,0 19,5 10,0 10,5 11,0 10,5 11,0 11,5 12,0 11,5 12,0 12,5-13,0 12,5-13,0 13,5 14,0 13,5 14,0 14,5 15,0 15,5 15,5 15,5 16 17 - Ø 10 - Ø 12 - Ø 14 - Ø 15 - Ø 16 - Ø 18 R69913 Spare glass with graduated scale for flow meter. 658101 Pair of mounting brackets in steel. For distribution manifolds 664 series. For use with box 659..5 series or directly wall mounted 680 DAR Self-adjustable diameter fitting for single and multi-layer plastic pipes. Working temperature range: 5 80 C (PE-X) 5 75 C (Multi-layer marked 95 C) 10,5 12 12,5 14 12,5 14 14,5 16 12,5 14 14,5 16 14,5 16 16,5 18 14,5 16 16,5 18 16,5 18 18,5 20 16,5 18 18,5 20 18,5 20 18,5 20 18,5 20 22,50 347 Compression fitting for annealed copper, hard copper, brass, mild steel and stainless steel pipes. With O-Ring seal. Temperature range: -25 120 C. 386500 Screw plug with nut, for distribution manifold outlets. Connection:.

Thermo-electric actuators Technical specifications 656102 656104 656112 656114 Voltage (V) 6561 tech. broch. 01042 Thermo-electric actuator for manifolds 662 and 664 series. Normally closed. Materials Protective shell: self-extinguishing polycarbonate Colour: (code 656102/04) white RAL 9010 (code 656112/14) grey RAL 9002 Performance Normally closed Electric supply: V (ac) - 24 V (ac) - 24 V (dc) Starting current: 1 A Running current: V (ac) = 13 ma 24 V (ac) - 24 V (dc) = 140 ma Running power consumption: 3 W Auxiliary microswitch contact rating (code 656112/114): 0,8 A ( V) Protection class: IP 44 (in vertical position) Double insulation construction: CE Max. ambient temperature: 50 C Operating time: opening and closing from 120 s to 180 s Length of supply cable: 80 cm Thermo-electric actuators with manual opening knob and position indicator 656302 656304 656312 656314 Voltage (V) 6563 tech. broch. 01142 Thermo-electric actuator for manifolds 662 and 664 series. Normally closed. Technical specifications Materials Protective shell: self-extinguishing polycarbonate Colour: (code 656302/04) white RAL 9010 (code 656312/14) grey RAL 9002 Performance Normally closed Electric supply: V (ac) - 24 V (ac) - 24 V (dc) Starting current: 1 A Running current: V (ac) = 13 ma 24 V (ac) - 24 V (dc) = 140 ma Running power consumption: 3 W Auxiliary microswitch contact rating (code 656312/14): 0,8 A ( V) Protection class: IP 40 Double insulation construction: CE Max. ambient temperature: 50 C Operating time: opening and closing from 120 s to 180 s Length of supply cable: 80 cm Thermo-electric actuator, quick-coupling installation with clip adaptor 656202 656204 656212 656214 656402 656404 656412 656414 Voltage (V) Low power consumption version Voltage (V) 6562/4 tech. broch. 01198 Thermo-electric actuator for manifolds 662 and 664 series. Normally closed. Technical specifications Materials Protective shell: self-extinguishing polycarbonate Colour: (code 656.02/04) white RAL 9010 (code 656.12/14) grey RAL 9002 Performance Normally closed Electric supply: V (ac) - 24 V (ac) - 24 V (dc) Starting current: (6562) 1 A (6564) 250 ma ( V) Running current: -6562 series: V (ac) = 13 ma; 24 V (ac) - 24 V (dc) = 140 ma -6564 series: V (ac) = 15 ma; 24 V (ac) - 24 V (dc) = 125 ma Running power consumption: 3 W Auxiliary microswitch contact rating (code 656.12/14): 0,8 A ( V) Protection class (fitted in all positions): IP 54 Double insulation construction: CE Operating time 6562 series Operating time: opening and closing from 120 s to 180 s Aux. microswitch closing time: from 120 s to 180 s Operating time 6564 series Opening time: (80%): 300 s; (100%): 600 s Closing time: 240 s Aux. microswitch closing time: 300 s Length of supply cable: 80 cm

Choice of box size, 659..5 series, according to the number of outlets L total No. of outlets Manifold total length (mm) Box length (mm) Box code, 659 series 6646B1 2 180 400 659045 6646C1 3 400 659045 6646D1 4 280 400 659045 6646E1 5 330 600 659065 6646F1 6 380 600 659065 6646G1 7 440 600 659065 6646H1 8 490 600 659065 6646I1 9 540 800 659085 6646L1 10 590 800 659085 6646M1 11 640 800 659085 6626N1 12 690 800 659085 6646O1 13 750 1000 659105 Boxes 659 tech. broch. 01180 Inspection wall box for distribution manifolds 664 series. Complete with specific support for manifold brackets. Closure with a pish-fit clamp. In painted sheet steel. Adjustable depth from 80 to 120 mm. (h x w x d) 659045 659065 659085 659105 500 x 1400 x 80 120 500 x 1600 x 80 120 500 x 1800 x 80 120 500 x 1000 x 80 120

CALEFFI CALEFFI Application diagrams Pump Thermostatic valve Shut-off valve Clock Lockshield valve

We reserve the right to make changes and improvements to the products and related data in this publication, at any time and without prior notice. Caleffi S.p.A. S.R. 229 n. 25 28010 Fontaneto d Agogna (NO) Italy Tel. +39 0322 8491 Fax +39 0322 863723 info@caleffi.com www.caleffi.com Copyright 2018 Caleffi