(598) STELLAR 2000 SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING HEAT PUMP S: F2RP / F2FP018 THRU 060 COOLING S: F2RC / F2FC018 THRU 036 VARIABLE SPEED : F2FV060 DESCRIPTION This fan coil unit provides the flexibility for installation in any upflow or horizontal application. These versatile models may be used for split-system cooling or heat pump operation. Compact cabinets along with return air options in both the upflow and horizontal positions allow this unit to fit into tight spaces such as attics, crawl spaces, and closets. NOTE: For matching condensing units and performance data, refer to condenser technical guides. FEATURES CABINET -The compact and sturdy cabinet is protected with a durable, attractive finish to prevent rust. The cabinet is also insulated to prevent cabinet sweating. F2RP/RC models have 1/2 inch fiber glass insulation and F2FP/FC & F2FV models have 1 inch insulation (R value = 4.2). BLOWERS - Blowers are sized to circulate air both quietly and efficiently. The direct-drive, 3-speed motors provide a selection of air volume to match any application. Motor speeds may be selected via quick connect terminal at the motor. Slide-out blower/motor assemblies provide for easy servicing. COILS - Using the latest in heat transfer technology, the rifled tube coil/aluminum fin coils produce high performance ratings and provide long lasting quality. The coils are capable of bottom return air in the upflow position, and right or left end return air in the horizontal position. ELECTRIC HEATERS - s providing up to 25kw of heat are available. Heaters can be field or factory installed. Electric heaters are available in both single and three phase. EASY INSTALLATION - These fan coil units are designed to provide the lowest total installation cost. Accessible color coded control wiring, top and side power wiring knockouts, easy to install drain connections and electric heaters all combine to minimize installed cost on every job. CONTROL BOARD - The control board is equipped with low voltage terminal strips for easy installation. The control board is also equipped with plug-in receptacles for the auxiliary heaters. ACCESSORIES Refer to Price Manual for specific model numbers. VERTICAL SUSPENSION KIT - The suspension kit is designed to be used with all sizes of blowers whenever the application requires vertical suspension of the unit. ELECTRIC HEATERS - s shown under Electrical Data include sequencers and temperature dual limit switches for safe, efficient operation. Circuit breakers are provided where shown. BOLT-ON THERMAL EXPANSION VALVE - TXV kits are available for enhanced efficiency. HORIZONTAL DRAIN PAN - The drain pan kit is designed for field conversion to Horizontal left or right applications. Also available as factory installed option (horizontal right only). FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DIMENSIONS All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. Dimensions F2RP / F2RC Wiring K.O. s* Refrigerant Connections Line Size A B C J K D E F Height Width Depth Power Control Liquid Vapor 018 40 18 14-7/8 16-1/2 5/8 024 40 18 14-7/8 16-1/2 5/8 030 40 18 14-7/8 16-1/2 3/4 7/8 (1/2) 036(RC) 40 18 12-1/8 14-7/8 16-1/2 3/4 1-3/8 (1) 036(RP) 40 21-1/2 18-3/8 20 3/4 22 7/8 (1/2) 3/8 040 ** 40 21-1/2 18-3/8 20 7/8 042 40 21-1/2 18-3/8 20 7/8 045 ** 50 24 20-7/8 22-1/2 7/8 (1/2) 7/8 F2FP048 50 24 17-3/8 20-7/8 22-1/2 1-3/8 (1), 7/8 F2FV060** 50 24 20-7/8 22-1/2 1-23/32 (1-1/4) 7/8 *NOTE: Actual conduit size is shown in brackets. COIL DATA AIR REFRIG. STD. FACE FINS COIL APPLICA- ROWS HANDLER CONN. ORIFICE AREA PER SLAB SIZE TION DEEP TYPE SIZE (SQ. FT.) INCH H W F2RC/FC018 A/C 53 2.43 2 14 10 17.5 F2RP/FP018 A/C & HP 53 2.43 2 14 10 17.5 F2RC/FC024 A/C 61 2.92 2 14 12 17.5 F2RP/FP024 A/C & HP 61 3.40 2 14 14 17.5 F2RC/FC030 A/C 65 2.92 2 14 12 17.5 F2RP/FP030 A/C & HP 65 3.89 2 14 16 17.5 F2RC/FC036 A/C Sweat 73 3.89 2 14 16 17.5 F2RP/FP036 A/C & HP 75 3.40 3 12 14 17.5 F2FP040** A/C & HP 63 3.89 3 11 16 17.5 F2RP/FP042 A/C & HP 78 3.89 3 11 16 17.5 F2FP045** A/C & HP 78 5.83 3 12 24 17.5 F2FP048 A/C & HP 84 5.35 3 12 22 17.5 F2FP060 A/C & HP 90 5.83 3 12 24 17.5 F2FV060** A/C & HP 90 5.83 3 12 24 17.5 ** s only available with factory installed horizontal drain pan. TUBE GEOM- ETRY TUBE DIA. 1 x.886 3/8 FIN TYPE Enhanced EXPAN- SION DEVICE Orifice 2 Unitary Products Group
COOLING CAPACITY ENTERING BLOWER RATED AIR F CFM (Dry / Wet Bulb) UPFLOW / HORIZONTAL POSITIONS ONLY F2RP/RC018 650 F2RC024 800 F2RP024 830 F2RC030 1050 F2RP030 1050 F2RC036 1200 F2RP036 1250 F2FP040** 1050 F2RP042 1400 F2FP045** 1400 F2FP048 1600 F2FP060 1850 F2FV060** 1980 ** s only available with factory installed horizontal drain pan. MBH @ Evaporator Temperature and Corresponding Pressure F / PSIG 35 / 61.5 40 / 68.5 45 / 76.0 50 / 84.0 27.2 25.1 20.6 16.7 31.1 28.6 23.5 19.1 36.3 33.4 27.4 22.2 31.1 27.1 21.8 18.1 41.5 36.2 29.1 24.1 41.6 33.3 26.0 22.3 53.4 42.8 33.4 28.7 55.3 44.2 34.5 29.6 88.4 70.8 55.2 47.4 92.7 74.2 57.8 49.7 100.5 80.4 62.7 53.9 119.9 96.0 74.8 64.3 122.0 98.1 76.9 66.4 24.8 22.6 18.2 14.5 28.3 25.9 20.8 16.5 33.0 30.2 24.3 19.3 28.3 24.3 19.0 16.1 37.8 32.4 25.3 21.5 37.8 29.4 21.9 20.6 48.6 37.8 28.1 26.5 47.5 37.1 27.5 26.0 76.0 59.4 43.9 41.5 78.1 61.3 45.3 42.8 86.4 67.5 49.9 47.2 101.0 79.2 58.6 55.4 103.1 81.3 60.7 57.5 22.1 20.0 15.8 12.1 25.2 22.9 18.0 13.8 29.5 26.7 21.0 16.2 25.3 21.4 18.0 14.0 33.7 28.6 24.0 18.7 33.8 25.8 23.9 19.0 43.4 33.1 30.6 24.5 39.6 30.2 22.4 22.4 63.3 48.4 35.8 35.8 63.4 48.4 35.7 35.7 72.0 55.0 40.7 40.7 82.0 62.6 46.2 46.2 84.1 64.7 50.3 48.3 19.2 17.3 13.3 9.4 21.9 19.8 15.1 10.8 25.6 23.1 17.7 12.6 22.1 18.4 14.4 11.8 29.5 24.5 19.2 15.8 29.8 21.9 17.8 17.8 38.3 28.2 22.8 22.8 31.2 23.1 18.7 18.7 50.0 37.0 29.9 29.9 48.1 35.4 28.6 28.6 56.8 42.1 34.0 34.0 62.2 45.8 37.0 37.0 64.3 47.9 39.1 39.1 Unitary Products Group 3
LIMITATIONS These units must be wired and installed in accordance with all national and local safety codes. Voltage limits are as follows: Normal Operating Voltage Range* 187-253 * Utilization range A in accordance with ARI Std. 110. Air flow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units. Entering Air Temperature Limits Wet Bulb Temp. F Dry Bulb Temp. F Min. Max. Min. Max. 57 72 65 95 AIRFLOW DATA* - HEAT PUMP S F2RP/F2FP BLOWER MOTOR SPEED 230 VOLT 208 VOLT CFM @ External Static Pressure - IWG 0.10 0.20 0.30 0.40 0.50 0.10 0.20 0.30 0.40 0.50 High 855 810 765 710 650 770 729 689 639 585 018 Med. 765 730 695 650 590 689 657 626 585 531 Low 645 620 590 555 505 581 558 531 500 455 High 950 910 865 835 775 855 819 779 752 698 024 Med. 845 815 785 745 705 760 733 706 670 634 Low 650 630 605 575 540 585 567 545 518 486 High 1,270 1,210 1,150 1,085 1,015 1,143 1,089 1,035 977 914 030 Med 1,050 1,040 995 930 855 941 936 895 837 770 Low 855 820 780 735 680 770 738 702 662 612 High - 1310 1250 1175 1120 1235 1179 1125 1058 1008 036 Med 1200 1150 1100 1040 985 1080 1035 990 936 887 Low 1060 1015 970 925 860 954 914 873 833 774 High - 1575 1500 1420 1350 1400 1418 1350 1278 1215 040 Med 1460 1295 1330 1260 1190 1314 1166 1197 1135 1071 Low 1250 1200 1155 1100 1050 1125 1080 1040 990 945 High - 1575 1500 1420 1350 1400 1418 1350 1278 1215 042 Med 1460 1295 1330 1260 1190 1314 1166 1197 1135 1071 Low 1250 1200 1155 1100 1050 1125 1080 1040 990 945 High 1575 1535 1475 1390 1310 1418 1382 1328 1251 1179 045 Med-high 1375 1315 1255 1185 1110 1238 1184 1130 1067 999 Med-low 1210 1160 1110 1050 980 1089 1044 999 945 882 Low 1035 990 940 890 825 932 891 846 801 743 High 1,855 1,795 1,730 1,670 1,605 1,670 1,616 1,557 1,503 1,445 048 Med 1,685 1,630 1,575 1,520 1,470 1,517 1,467 1,418 1,368 1,323 Low 1,465 1,435 1,405 1,370 1,335 1,319 1,292 1,265 1,233 1,202 High 2,285 2,195 2,105 2,015 1,920 2,057 1,976 1,895 1,814 1,728 060 Med 2,125 2,020 1,910 1,805 1,705 1,913 1,818 1,719 1,625 1,535 Low 1,655 1,605 1,550 1,500 1,450 1,490 1,445 1,395 1,350 1,305 * Includes Return Air Filter and Largest Electric Heater. AIRFLOW DATA* - COOLING S F2RC/ F2FC BLOWER MOTOR SPEED 230 VOLT 208 VOLT CFM @ External Static Pressure - IWG 0.10 0.20 0.30 0.40 0.50 0.10 0.20 0.30 0.40 0.50 High 810 765 720 670 615 729 689 648 603 554 018 Med. 730 705 670 615 565 657 635 603 554 509 Low 625 605 575 535 490 563 545 516 482 441 High 925 885 850 805 750 833 797 765 725 675 024 Med. 820 800 765 720 680 738 720 688 648 612 Low 645 620 595 570 535 581 558 536 513 482 High 1205 1150 1090 1025 990 1085 1035 981 923 891 030 Med 1020 1010 960 895 825 919 909 864 805 742 Low 840 805 760 715 660 756 725 684 644 594 High 1305 1250 1195 1150 1065 1175 1125 1076 1035 959 036 Med 1225 1175 1125 1070 1000 1103 1058 1013 963 900 Low 1055 1015 980 930 880 950 914 882 837 792 * Includes Return Air Filter and Largest Electric Heater. APPLICATION FACTORS - Rated CFM vs. Actual CFM % OF RATED AIR FLOW 80 % 90 % RATED CFM 110 % 120 % CAPACITY FACTOR 0.96 0.98 1.00 1.02 1.03 4 Unitary Products Group
CFM / TAP SELECTION - F2FV HIGH SPEED COOLING AND HEAT PUMP CFM JUMPER SETTING F+FV060 "COOL TAP" "ADJ TAP" 2100 "A" "B" 1980 "B" "B" 1860 "A" "A" 1750 "B" "A" 1675 "A" "C" 1605 "C" "B" 1575 "B" "C" 1510 "D" "B" 1420 "C" "A" 1335 "D" "A" 1280 "C" "C" 1200 "D" "C" "DELAY" TAP Jumper at "A" Jumper at "B" Jumper at "C" Jumper at "D" ELECTRIC HEAT CFM TAP SELECTIONS F+FV060 "HEAT" 1860 "A" 1750 "B" 1420 "C" 1335 "D" DELAY PROFILE UNIT TYPE N/A Two Stage Condensor System with TXV or with Solenoid Valve System without TXV or without Solenoid Valve NOTES: 1. Both the "COOL" and the "ADJ" tap must be set for the cooling CFM. 2. Fan only CFM = 63 % of high speed cooling. 3. Low speed cooling used only with two stage outdoor units. (Speed is preset to 65 % of high speed). 4. Dehumidification speed is 85 % of cooling speed. 5. When operating in both heat pump and electric heat modes, the CFM will be whichever is greater. 6. CFM indicator light flashes once for every 100 CFM. (ie : 12 Flashes is 1200 CFM) PHYSICAL AND ELECTRICAL DATA F2RP / F2RC 018 024 030 036(RP) 036(RC) Blower - Diameter x Width 9 x 6 10 x 6 10 x 8 10 x 8 10 x 8 Motor HP 1/4 1/4 1/3 1/2 1/2 Nominal RPM 1075 1075 1075 1075 1075 Voltage 208/230 Amps Full Load 1.6 / 1.4 1.6 / 1.4 2.5 / 2.2 3.3 / 2.9 3.3 / 2.9 Locked Rotor 3.3 / 2.9 3.3 / 2.9 6.2 / 5.5 7.4 / 6.5 7.4 / 6.5 Filter 1 Type DISPOSABLE or PERMANENT Size 16 x 21 16 x 21 16 x 21 20 x 21 16 x 21 Shipping / Operating Weight (lbs.) - RP 87 / 92 93 / 98 100 / 105 109 / 115 - Shipping / Operating Weight (lbs.) - RC 87 / 92 90/ /95 90 / 95-100 / 105 F2RP / F2RC 040 042 045 048 060 F2FV060 Blower - Diameter x Width 10 x 8 10 x 8 10 x 10 11 x 10 11 x 10 11 x 10 Motor HP 1/3 3/4 1/3 1/2 3/4 1.0 Nominal RPM 1075 1130 925 1085 1100 1200 Voltage 208/230 Amps Full Load 2.5 / 2.2 4.4 / 3.8 3.0 / 2.7 2.6 / 2.3 4.4 / 3.8 7.8 / 7.0 Locked Rotor 6.2 / 5.5 11.9 / 10.3 4.8 / 4.1 4.6 / 4.0 8.4 / 7.3 Filter 1 Type DISPOSABLE or PERMANENT Size 16 x 21 20 x 21 22 x 21 22 x 21 22 x 21 22 x 21 Shipping / Operating Weight (lbs.) - RP 115 / 121 115 / 121 144 / 150 142 / 148 149 / 155 160 Shipping / Operating Weight (lbs.)- RC 115 / 121 1 Field Supplied ELECTRICAL DATA - Cooling Only with No Heat Power Kit (1 & 3 Ø) Total Motor Amps Minimum Circuit Ampacity F+RP/FP/RC/RP 208V 230V 208V 230V Maximum O.C.P.D. Minimum Wire Size A.W.G. 018 1.6 1.5 2.0 1.9 15 14 024 1.6 1.5 2.0 1.9 15 14 030 2.5 2.3 3.2 2.9 15 14 036 3.3 3.0 4.2 3.8 15 14 040 2.5 2.3 3.2 2.9 15 14 042 4.4 4.0 5.5 5.0 15 14 045 3.1 2.6 3.9 3.3 15 14 048 3.9 3.5 4.9 4.3 15 14 060 4.6 4.4 5.8 5.5 15 14 Unitary Products Group 5
ELECTRICAL DATA - 1 Ø F2RP / F2RC/ F2FP 018N06 024N06 030N06 036N06 040N06 042N06 045N06 048N06 060N06 Total Heat 1 KW Staging** Heater KW MBH W1 Only W2 Only W1 + W2 208 240 208 240 208 240 208 240 208 240 2HK*6500206A 1.9 2.5 6.5 8.5 1.9 2.5 - - 1.9 2.5 2HK*6500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 5.7 7.5 2HK*6500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 5.7 7.5 2HK*6501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 7.6 10.0 2HK*6500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 5.7 7.5 2HK*6501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 7.6 10.0 2HK16501506A 11.3 15.0 38.6 51.2 3.8 5.0 7.6 10.0 11.4 15.0 2HK*6500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 5.7 7.5 2HK*6501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 7.6 10.0 2HK16501506A 11.3 15.0 38.6 51.2 3.8 5.0 7.6 10.0 11.4 15.0 2HK*6500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.8 2.5 5.6 7.5 2HK*6501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.7 5.0 7.5 10.0 2HK16501506A 11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0 2HK*6500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 5.7 7.5 2HK*6501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 7.6 10.0 2HK16501506A 11.3 15.0 38.6 51.2 3.8 5.0 7.6 10.0 11.4 15.0 2HK*6500806A 5.6 7.5 19.1 25.6 3.8 5.0 5.6 7.5 5.6 7.5 2HK*6501006A 7.5 10.0 25.6 34.1 3.8 5.0 7.5 10.0 7.5 10.0 2HK16501506A 11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0 2HK*6501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 7.6 10.0 2HK16501506A 11.3 15.0 38.6 51.2 3.8 5.0 7.6 10.0 11.4 15.0 2HK16502006A 15.0 20.0 51.2 68.2 3.8 5.0 11.3 15.0 15.1 20.0 2HK16502506A 18.8 25.0 64.2 85.3 3.8 5.0 15.0 20.0 18.8 25.0 2HK*6501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 7.6 10.0 2HK16501506A 11.3 15.0 38.6 51.2 3.8 5.0 7.6 10.0 11.4 15.0 2HK16502006A 15.0 20.0 51.2 68.2 3.8 5.0 11.3 15.0 15.1 20.0 2HK16502506A 18.8 25.0 64.2 85.3 3.8 5.0 15.0 20.0 18.8 25.0 2HK*6500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 5.6 7.5 2HK*6501006A 7.5 10.0 25.6 34.1 3.8 5.0 7.5 10.0 7.5 10.0 F2FV060 2HK16501506A 11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0 2HK16502006A 15.0 20.0 51.2 68.3 3.8 5.0 7.5 10.0 15.0 20.0 2HK16502506A 18.8 25.0 64.2 85.3 3.8 5.0 11.3 15.0 18.8 25.0 NOTE: F2FP040 & F2FP045 - Only available with factory installed horizontal drain pan. * 0 or 1 as follows: 0 = No Breaker, 1 = Breaker. 1 See Conversion Table below : FOR KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT 208V OPERATION, MULTIPLY 240V TABULATED KW & MBH BY.751 230V 240V.918 **ALTERNATE ELECTRIC HEAT STAGING FOR AUXILIARY HEAT DURING DEFROST Defrost Output (66) Heater Size (208 / 240 V) Connected To 7.5 KW 10-20 KW 25 KW W1 3.8 3.8 / 5 3.8 / 5 W2 5.6 7.5 7.5 / 10 11.3 / 15 Adjust values in Table above when used. 6 Unitary Products Group
ELECTRICAL DATA - 1 Ø (SINGLE SOURCE POWER SUPPLY) - COPPER WIRE F2RP / F2RC / F2FP Heater Field Wiring Min. Circuit Ampacity Max. O.C.P. 2 Amps/Type 75 C Wire Size - AWG 208V 240V 208V 240V 208V 240V 2HK*6500206A 13.4 14.8 15 15 14 14 018N06 2HK*6500506A 24.9 27.8 25 30 10 10 2HK*6500806A 35.7 40.8 40 45 8 8 2HK*6500506A 24.9 27.8 25 30 10 10 024N06 2HK*6500806A 35.7 40.8 40 45 8 8 2HK*6501006A 47.1 53.8 50 60 8 6 2HK*6500506A 26.0 28.8 30 30 10 10 030N06 2HK*6500806A 36.8 41.8 40 45 8 8 2HK*6501006A 48.2 54.8 50 60 8 6 2HK16501506A 71.1 80.9 80 90 4 3 2HK*6500506A 27.0 29.7 30 30 10 10 036N06 2HK*6500806A 37.8 42.7 40 45 8 8 2HK*6501006A 49.3 55.7 50 60 8 6 2HK16501506A 72.1 81.8 80 90 4 3 2HK*6500506A 26.0 28.8 30 30 10 10 040N06 2HK*6500806A 36.8 41.8 40 45 8 8 2HK*6501006A 48.2 54.8 50 60 8 6 2HK16501506A 71.1 80.9 80 90 4 3 2HK*6500506A 28.3 30.8 30 35 10 8 042N06 2HK*6500806A 39.1 43.8 40 45 8 8 2HK*6501006A 50.6 56.8 60 60 6 6 2HK16501506A 73.4 82.9 80 90 4 3 2HK*6500506A 26.7 29.4 30 30 10 10 045N06 2HK*6500806A 37.5 42.4 40 45 8 8 2HK*6501006A 49.0 55.5 50 60 8 6 2HK16501506A 71.8 81.5 80 90 4 3 2HK*6501006A 50.0 56.3 50 60 8 6 048N06 2HK16501506A 72.8 82.4 80 90 4 3 2HK16502006A 95.0 108.5 100 110 3 2 2HK16502506A 117.9 134.5 125 150 2 1/0 2HK*6501006A 51.4 57.6 60 60 6 6 060N06 2HK16501506A 74.3 83.6 80 90 4 3 2HK16502006A 96.5 109.7 100 110 3 2 2HK16502506A 119.3 135.7 125 150 1 1/0 2HK*6500806A 43.8 47.8 45 50 8 8 2HK*6501006A 55.2 60.8 60 70 6 4 F2FV060 2HK16501506A 78.0 86.9 80 90 4 3 2HK16502006A 100.2 112.9 110 125 2 1 2HK16502506A 123.1 139.0 125 150 1 1/0 * 0 or 1 as follows: 0 = No Breaker, 1 = Breaker. 2 O. C.P. = Over-Current Protection. ELECTRICAL DATA - 1 Ø (MULTI-SOURCE POWER SUPPLY) - COPPER WIRE Heater Min. Circuit Ampacity Max. Time Delay Fuse 75 C Wire Size - AWG Circuit Circuit Circuit 1st 2nd 3rd 1st 2nd 3rd 1st 2nd 3rd 208/240 208/240 208/240 208/240 208/240 208/240 208/240 208/240 208/240 F2RP(RC)030N06 2HK16501506A 25.7/28.8 45.1/52.1-30/30 50/60-10/10 8/6 - F2RP(RC)036N06 2HK16501506A 26.8/29.7 45.1/52.1-30/30 50/60-10/10 8/6 - F2FP040 2HK16501506A 25.7/28.8 45.1/52.1-30/30 50/60-10/10 8/6 - F2RP042N06 2HK16501506A 28.1/30.8 45.1/52.1-30/35 50/60-10/8 8/6 - F2FP045 2HK16501506A 26.5/29.4 45.1/52.1-30/30 50/60-10/10 8/6 - F2FP048N06 F2FP060N06 F2FV060 2HK16501506A 27.5/30.3 45.1/52.1-30/35 50/60-10/10 8/6-2HK16502006A 50.0/56.3 45.1/52.1-50/60 50/60-8/6 8/6-2HK16502506A 27.5/30.3 45.1/52.1 45.1/52.1 30/35 50/60 50/60 10/10 8/6 8/6 2HK16501506A 28.9/31.5 45.1/52.1-30/35 50/60-10/8 8/6-2HK16502006A 51.5/57.6 45.1/52.1-60/60 50/60-6/6 8/6-2HK16502506A 28.9/31.5 45.1/52.1 45.1/52.1 30/35 50/60 50/60 10/8 8/6 8/6 2HK16501506A 32.7/34.8 45.1/52.1-35/35 50/60-8/8 8/6-2HK16502006A 55.2/60.8 45.1/52.1-60/60 50/60-6/6 8/6-2HK16502506A 32.7/34.8 45.1/52.1 45.1/52.1 35/35 50/60 50/60 8/8 8/6 8/6 Unitary Products Group 7
ELECTRICAL DATA - 3 Ø Total Heat 1 KW Staging** Heater KW MBH W1 Only W2 Only W1 + W2 208 240 208 240 208 240 208 240 208 240 F2RC/RP024 F2RC/RP030 F2RC/RP036 F2FP040 F2RC/RP042 F2FP045 F2FP048 F2FP060 F2FV060 2HK06501525B 11.3 15.0 38.8 51.2 3.8 5.0 7.5 10.0 11.3 15.0 ELECTRICAL DATA - 3 Ø (SINGLE SOURCE POWER SUPPLY) - COPPER WIRE Field Wiring Heater Min. Circuit Ampacity Max. O.C.P. 2 Amps/Type 75 C Wire Size - AWG 208V 240V 208V 240V 208V 240V F2RC/RP024 2HK06501025B 41.3 46.6 45 50 8 8 F2RC/RP030 2HK06501025B 42.3 47.5 45 50 8 8 2HK06501525B 42.3 47.5 45 50 8 8 F2RC/RP036 2HK06501025B 43.2 48.3 45 50 8 8 2HK06501525B 43.2 48.3 45 50 8 8 F2FP040 2HK06501025B 42.3 47.5 45 50 8 8 2HK06501525B 42.3 47.5 45 50 8 8 F2RC/RP042 2HK06501025B 44.4 49.3 45 50 8 8 2HK06501525B 44.4 49.3 45 50 8 8 F2FP045 2HK06501025B 43.0 48.1 45 50 8 8 2HK06501525B 43.0 48.1 45 50 8 8 F2FP048 2HK06501025B 43.9 48.8 45 50 8 8 2HK06501525B 43.9 48.8 45 50 8 8 F2FP060 2HK06501025B 45.2 49.9 50 50 8 8 2HK06501525B 45.2 49.9 50 50 8 8 F2FV060 2HK06501025B 48.6 52.9 50 60 8 6 2HK06501525B 48.6 52.9 50 60 8 6 1 See Conversion Table page 6. 2 O.C.P. = Over-Current Protection ** If first stage heat or 66 is connected to W1, otherwise refer to Table at bottom of page 6. WIRING DIAGRAMS - COOLING S COOLING ONLY S WITH F2RC / FC / RP / FP COOLING S WITH ELECTRIC HEAT WITH F2RC / FC / RP / FP 8 Unitary Products Group
WIRING DIAGRAMS - COOLING S & F2FV WITH ELECTRIC HEAT NOTE: Thermostat terminal "W" not used for cooling only. WIRING DIAGRAMS - COOLING H*DS with F2FV Variable Speed Only NOTE: Thermostat terminal "W1, W2 " not used for cooling only. Unitary Products Group 9
WIRING DIAGRAMS - HEAT PUMP S with F2RP / FP WIRING DIAGRAMS - HEAT PUMP S with F2FV IMPORTANT NOTE: HEAT PUMP JUMPER ON THE CFM SELECTION BOARD MUST BE REMOVED WHEN AIR HANDLER IS USED WITH A HEAT PUMP UNIT. 10 Unitary Products Group
WIRING DIAGRAMS - HEAT PUMP - E*FH Only with F2RP / FP R WIRING DIAGRAMS - HEAT PUMP with F2FV with Electric Heat IMPORTANT NOTE: HEAT PUMP JUMPER ON THE CFM SELECTION BOARD MUST BE REMOVED WHEN AIR HANDLER IS USED WITH A HEAT PUMP UNIT. Unitary Products Group 11
TYPICAL INSTALLATION TYPICAL APPLICATIONS UPFLOW HORIZONTAL * * * Requires Horizontal Pan Accessory Unitary Products Group 5005 York Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A. Copyright by York International Corporation 1998. All Rights Reserved. Code: EBY, EGY 535.02-TG4Y Supersedes: 535.02-TG4Y (997)