Installation. Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Table of Contents. Instruction Sheet

Similar documents
Installation and Operation

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Installation, Operation, and Maintenance

Instructions for Operation and Maintenance

Installation and Operation

Inspection and Maintenance

Instructions for Installation

Installation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv

S&C Vista Underground Distribution Switchgear

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)

Instructions for Installation and Operation

S&C Loadbuster Disconnects

Installation and Operation

Instructions for Installation and Operation

Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

Cleaning Flooded Gear

Instructions for Installation

S&C Circuit-Switchers Mark VI Installed on S&C Mounting Pedestals 84- through 102-inch Phase Spacing Outdoor Transmission (69 kv through 138 kv)

Cleaning Flooded Gear

S&C Source-Transfer Vista Underground Distribution Switchgear

S&C Type XS Fuse Cutouts

S&C Type XS Fuse Cutouts

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons

Specifications. S&C Alduti-Rupter Switchesa Indoor Distribution (4.8 kv through 34.5 kv) Conditions of Sale SPECIAL TO THIS PRODUCT: How to Order

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)

S&C Mini-Rupter Switches Application The Standard Mounting Arrangement Scheme for S&C Mini-Rupter Switches Typical ED, reduced from full 11 size.

Installation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

Effective November 2016 Supersedes February 2012 (S )

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)

Installation. S&C Circuit-Switchers Mark VI 69-kV 51-inch Phase Spacing Single Pedestal Design Outdoor Transmission.

Operation. S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles. Table of Contents

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

Specifications. S&C Type XS Fuse Cutouts. Outdoor Distribution (4.16 kv through 25 kv)

Installation And Operation

Operation. S&C Source-Transfer Vista Underground Distribution Switchgear. Pad-Mounted, Dry-Vault-Mounted, Wet-Vault-Mounted, and UnderCover Styles

Installation and Operation

Installation Instructions For Motor Control Center (MCC) Units

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

SPECIFICATION BULLETIN

Figure 1. Kearney Type HX cutout.

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

Effective March 2015 Supersedes S August 2012

ibusway for Data Center

Specifications. S&C Mini-Rupter Switches Indoor Distribution (4.16 kv through 25 kv) Manually Operated Styles

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

S&C Manual PME Pad-Mounted Gear

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

Installation. S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) Table of Contents

Galaxy Receiving and Unpacking 09/

Type NR oil switch installation and operation instructions

Hubbell has a policy of continuous product improvement. Please visit hubbellpowersystems.com to confirm current design specifications.

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

Vacuum Circuit Breaker (Vehicle)

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

OPERATIONS MANUAL LEVER CHAIN HOIST

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

BREAK-SAFE Load Break & Pick-up Tool

www. ElectricalPartManuals. com SPECIFICATIONS Page 1 of 24 March 24, 2003

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

BREAK-SAFE Load Break & Pick-up Tool

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

SPECIFICATIONS. S&C Alduti-Rupter Switches with Power Fusesa SPECIFICATION BULLETIN Indoor Distribution (4.8 kv and 13.

INSTRUCTIONS For Field Assembly and Installation

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

Model NTX7 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006

WARNING. TYPE PSI/II PAD-MOUNT SWITCHGEAR with Non-Loadbreak Fuse Mountings 15kV 25kV INSTRUCTIONS. Qualified Persons. For Installation and Operation

TYPE AST. Grounding Switch. ALL Ratings INSTALLATION & INSTRUCTION MANUAL

Mechanical Hoists. NOTICE: For latest revision of our Catalog and Literature, please visit our web site:

Effective November 2016 Supersedes September 1998 (S )

Operator's Manual. Storage System. Ultrasound Probe Cabinet. Manufactured by:

MFG. CO. INC. DODGE CITY, KANSAS (620) Electric Truck Auger. Owners Manual

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment

Pretest Module 29 High Voltage Unit 1

IB PowlVac ITE-HK Remote Racking Device

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

Outdoor Padmount Switching Products

Installation Instructions Electric Heaters 5 20 kw

INSTRUCTIONS Ç CAUTION. S&C Power Fuses Types SMD-1A, SMD-2B, SMD-2C, and SMD-3. For Field Assembly and Installation NOTE INSTRUCTION SHEET

NX indoor current-limiting fuses

Installation and Operation Manual. Manufacturers of Innovative Materials Handling Equipment since 1957.

Surface Regulations and Policies

Owner s Information Manual

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

Indoor or Outdoor 2400 to 14,400 Volts 600 to 14,400 Kvac, 3 Phase, 60 Hz

TYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV

Medium Voltage Metal-Enclosed Switches

SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

Transcription:

Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Installation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction Sheet.... 2 Retain this Instruction Sheet.... 2 Warranty... 2 Proper Application Ratings... 3 Application Notes.... 3 Single-Pole Switching... 4 Restrictions on Overhead and Underground Use.... 4 Clearance Requirements for Use on Pad-Mounted Gear.. 5 Operating Considerations... 6 Safety Information Understanding Safety-Alert Messages... 8 Following Safety Instructions.... 8 Replacement Instructions and Labels.... 8 Location of Safety Labels... 9 Safety Precautions.... 10 Shipping and Handling Inspection...11 Operation Overhead Distribution Devices...13 Pad-Mounted Gear... 16 Understanding the Operation Counter.... 18 December 5, 2016 S&C Electric Company 2001-2016, all rights reserved Instruction Sheet 811-505

Introduction Qualified Persons Read this Instruction Sheet Retain this Instruction Sheet Warranty WARNING The equipment covered by this publication must be installed, oper ated, and maintained by qualified persons who are knowledgeable in the installation, operation, and maintenance of overhead electric power distribution equipment along with the associated hazards. A qualified person is one who is trained and competent in: The skills and techniques necessary to distinguish exposed live parts from nonlive parts of electrical equipment The skills and techniques necessary to determine the proper approach distances corresponding to the voltages to which the qualified person will be exposed The proper use of the special precautionary techniques, per sonal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electrical equipment These instructions are intended only for such qualified persons. They are not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment. NOTICE Read this instruction sheet thoroughly and carefully before installing or operating your Loadbuster The S&C Loadbreak Tool. Familiarize yourself with the Safety Information and Safety Precautions on pages 8 through 10. The latest version of this publication is available online in PDF format at sandc.com/support/product-literature.asp. This instruction sheet should be available for reference wherever and whenever the Loadbuster tool is to be used. Retain this instruction sheet in the Loadbuster tool carrying case (optional), or designate a loca tion where you can easily retrieve and refer to this publication. The warranty and/or obligations described in S&C s standard conditions of sale, as set forth in Price Sheet 150, plus any special warranty provisions, as set forth in the applicable product-line specification bulletin, are exclusive. The remedies provided in the former for breach of these warranties shall constitute the immediate purchaser s or end user s exclusive remedy and a fulfillment of all seller s liability. In no event shall the seller s liability to the immediate purchaser or end user exceed the price of the specific product gives rise to the immediate purchaser s or end user s claim. All other warranties, whether express or implied or arising by operation of law, course of dealing, usage of trade, or otherwise, are excluded. The only warranties are those stated in Price Sheet 150, and THERE ARE NO EXPRESS OR IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. ANY EXPRESS WARRANTY OR OTHER OBLIGATION PROVIDED IN PRICE SHEET 150 IS GRANTED ONLY TO THE IMMEDIATE PURCHASER AND END USER, AS DEFINED THEREIN. OTHER THAN AN END USER, NO REMOTE PURCHASER MAY RELY ON ANY AFFIRMATION OF FACT OR PROMISE THAT RELATES TO THE GOODS DESCRIBED HEREIN, ANY DESCRIPTION THAT RELATES TO THE GOODS, OR ANY REMEDIAL PROMISE INCLUDED IN PRICE SHEET 150. 2 S&C Instruction Sheet 811-505

Proper Application Ratings WARNING Loadbuster tool must only be used for specific switching applica tions that are within the ratings of the tool selected. Loadbuster tool ratings are listed on a ratings label attached to the chassis of the tool. Item Rating kv Amps, Interrupting Nom. Max Nom. Max Catalog Number Loadbuster The S&C Loadbreak Tool use with overhead distribution devices 14.4/25 27 600 900 5300R3 Loadbuster The S&C Loadbreak Tool use in suitably designed pad-mounted gear 14.4/25 27 600 900 5300R3-E Loadbuster The S&C Loadbreak Tool use with overhead distribution devices 25/34.5 38 600 900 5400R3 Application Notes When used with appropriately designed hook-equipped disconnects, cutouts, power fuses, fuse limiters, and padmounted gear, the Loadbuster tool is suitable for these live-switch ing duties of single- or three-phase overhead distribution circuits through 34.5 kv and underground distribution cir cuits through 25 kv: Transformer switching transformer load currents up through 600 amperes nominal, 900 amperes maximum, as well as transformer magnetizing currents associated with the applicable loads Line switching load splitting (parallel or loop switching) and load dropping of currents up through 600 amperes nominal, 900 amperes maximum; also line dropping (charging currents typical for distribution systems of these voltage ratings) Cable switching load splitting (parallel or loop switching) and load dropping of currents up through 600 amperes nominal, 900 amperes maximum; also cable dropping (charging currents typical for distribution systems of these voltage ratings) Capacitor bank switching switching of single capacitor banks as follows: Loadbuster Catalog Number 5300R3 5400R3 Nominal System Voltage, kv, Three-Phase 12 thru 14.4 16 20.8 thru 23.9 24.9 and 26 20.8 thru 23.9 24.9 and 26 27.6 34.5 Maximum Capacitor Bank Rating, kvac, Three Phase Solidly or Effectively Grounded System Single1 Banks, Grounded-Wye Connected 1800 2400 3000 3600 3000 3600 3600 4800 Single1 Banks, Ungrounded-Wye Connected 1800 2400 3000 3600 3600 Ungrounded System Single1 Banks, Grounded- or Ungrounded-Wye Connected 1800 2400 3000 3600 3600 1 Loadbuster tools must not be used for switching parallel ( back-to-back ) capacitor banks. Loadbuster tools must not be used for switching ungrounded-wye con nected banks or grounded-wye connected banks on ungrounded sys tems where maximum system operating voltage exceeds 18 kv for Loadbuster S&C s Loadbreak Tool, Catalog Number 5300R3; or 29 kv for Loadbuster S&C s Loadbreak Tool, Catalog Number 5400R3. S&C Instruction Sheet 811-505 3

Proper Application Single-Pole Switching In single-pole switching of ungrounded-primary threephase transformers or banks (or single-phase transform ers connected line to line), circuit connections or parameters may, in some cases, produce excessive overvoltages. In particular, for the following applications above 22 kv, single-pole switching by any means including with the use of the Load buster tool should be performed only under the conditions stated in italics: Switching unloaded or lightly loaded delta-connected or ungrounded-primary wye-wye connected three-phase transformers or banks (or line-to-line connected singlephase transformers), rated 150 kva or less three-phase, or 50 kva or less single-phase or of any kva rating when combined with unloaded cables or lines where the maximum system operating voltage exceeds 22 kv. (Single-pole switching should be per formed only if each phase is carrying 5% load or more, or if the transformer or bank is temporarily grounded at the primary neutral during switching.) Switching loaded or unloaded ungrounded-primary wyedelta connected three-phase transformers or banks alone or combined with unloaded cables or lines where maximum system operating voltage exceeds 22 kv. (Single-pole switching should be per formed only if each phase is carrying 5% load or more and if the lightingload phase is always switched open first (or switched closed last), or if the trans former or bank is temporarily grounded at the pri mary neutral during switching.) Restrictions on Overhead and Underground Use The Loadbuster Loadbreak Tool must be used only with disconnects, cutouts, power fuses, fuse limiters, or pad-mounted gear that meet S&C s applicable minimum construction specifica tions found in the current revision of the following publication: DATA BULLETIN 811-60: Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Minimum Construction Specifica tions for Disconnects, Cutouts, and Power Fuses Qualifying for Use with the Loadbuster Tool NOTICE Loadbuster the S&C Loadbreak tool, Catalog Number 5400R3, rated 25/34.5 kv, must not be used with metalenclosed switchgear, metal-enclosed switches or fuses, or pad-mounted gear, of any make. 4 S&C Instruction Sheet 811-505

Proper Application Although the interrupting ratings of Loadbuster S&C s Loadbreak Tool, Cata log Number 5400R3, rated 25/34.5 kv, are equally applica ble at lower voltages, it must not be used with the following devices because the fuse tube or blade travel of such devices is too short to accommodate the Load buster tool s operating stroke: Cutouts, power fuses, or fuse limiters of any make, rated 110 kv BIL or less Disconnects, cutouts, power fuses, or fuse limiters, of any make rated 7.2/14.4 kv, 7.8/13.8 kv, 8.25 kv, or less Disconnects, of any make rated 125 kv BIL or less S&C Fuse Cutouts Type XS, Station Style, Catalog Number 189131 (with or without catalog number sup plements) Loadbuster tools should not be used for any applications where maximum system operating voltage exceeds the Loadbuster tool s maximum voltage rating. Clearance Requirements for Use in Pad-Mounted Gear For applications of Loadbuster S&C s Loadbreak Tool (Catalog Number 5300R3 E) in pad-mounted gear, the Loadbuster tool must be equipped with an extended insulating hood (Catalog Number NA-1034) and the padmounted gear must be equipped with rigid insulating barriers to prevent: Accidental contact of the Loadbuster tool s metal parts with adjacent phases during switching Accidental grounding of the Loadbuster tool s metal parts to enclosure walls, door stiles, or switch mounting bases during switching Specifically, barriers must ensure the following mini mum clearances between metal parts of the Loadbuster tool and ground during a switching operation: Maximum System Operating Voltage, kv Clearance, Inches (mm) Up through 15.5 1 (26) Above 15.5 through 27 2 (51) S&C Instruction Sheet 811-505 5

Operating Considerations Never position the Loadbuster tool so its outer tube obscures the line of vision. (See Figure 1 on page 7 for correct positioning.) To coordinate Loadbuster S&C s Loadbreak Tool s (Catalog Number 5300R3) maximum voltage rating of 27 kv when used with fuse cutouts, disconnects, power fuses, or fuse limiters of made by other manufacture, the open gap on the cutout, discon nect, fuse, or fuse limiter when the tool is ready to trip must approximate 3⅞ inches (99 mm) minimum. (For more details, see S&C Data Bulletin 811-60.) To coordinate the Loadbuster tool s (Catalog Number 5400R3) maximum voltage rating of 38 kv when used with fuse cutouts, disconnects, power fuses, or fuse limiters of other manufacture, the open gap on the cut out, disconnect, fuse, or fuse limiter when the tool is ready to trip must approximate 5¼ inches (134 mm) minimum. (For a more detailed discussion of this and other requirements, see S&C Data Bulletin 811-60.) After each operation, immediately remove the Loadbuster tool from the fuse cutout, disconnect, power fuse, fuse lim iter, or pad-mounted gear and reset it. Instructions for resetting the Loadbuster tool can be found in Step 5 on page 15. NOTICE A carrying case, Catalog Number 5380R1, is recommended for the Loadbuster tool. The molded, high-density polyethylene carrying case protects the Loadbuster tool against potentially damaging vibration, mechanical shock, and contamination during storage or trans port. 6 S&C Instruction Sheet 811-505

Operating Considerations For usual operating conditions, the Loadbuster tool is fas tened to a universal pole (stick) not less than six feet long (eight feet for Catalog Number 5400R3) with the frame of the tool in line with the pole. As shown in Figure 1, Detail A or B, Loadbuster tool must be attached so it reaches across in front of the fuse cutout, disconnect, power fuse, or fuse limiter. That is, the Loadbuster anchor must be hooked to the attachment hook on the far side of the device. The Loadbuster tool should never be attached with its anchor hooked on the closest side of the fuse cutout or other device as shown in Detail C or D. Attach ing the tool in this manner would not only obscure the operator s line of vision, but it could also result in placing a bending stress on the tool and make disen gagement difficult. When the Loadbuster tool is properly attached, as shown in Figure 1, Detail A or B, a downward pull of the pole to open the fuse cutout, disconnect, power fuse, or fuse limiter extends the Loadbuster tool and charges an internal spring. At a predetermined point in the opening stroke, a trigger inside the tool trips, releasing the charged spring thus separating the internal contacts and interrupting the circuit. Suc cessful operation is independent of the speed with which the fuse cutout, disconnect, power fuse, or fuse limiter is opened. NOTICE When operating from a bucket truck, stay at least five feet below the device and in front of fuse cutouts, fuse limiters, and vertically mounted dis connects and fuses. When disconnects are mounted inverted, approach the attachment hook from the hinge end, staying well below the device to be opened so excessive horizontal force is not exerted on the insulator. (See Figures 2 and 3 on page 12.) Detail A. Correct approach. Detail C. Incorrect approach. Detail B. Correct approach. Although many words and illustrations are used here to describe the operation of the Loadbuster tool, correct techniques can be mastered quite easily. It is advis able, however, to spend a reasonable amount of time practicing with the Loadbuster tool on a de-energized fuse cutout, power fuse, fuse limiter, or disconnect. The operating steps illustrated in Figures 4 through 7, covering opening of a power fuse, apply equally to a fuse cutout, fuse limiter, or disconnect. Never This!... or This! Detail D. Incorrect approach. Figure 1. Correct and incorrect approach for Loadbuster The S&C Loadbreak Tool. S&C Instruction Sheet 811-505 7

Safety Information Understanding Safety-Alert Messages Several types of safety-alert messages may appear throughout this instruction sheet are on labels attached to the crate, packing, and equipment. Familiarize yourself with these types of messages and the importance of these various signal words. DANGER DANGER identifies the most serious and immediate hazards that will likely result in serious personal injury or death if instructions, including recommended precautions, are not followed. WARNING WARNING identifies hazards or unsafe practices that can result in serious personal injury or death if instructions, including recommended precautions, are not followed. CAUTION CAUTION identifies hazards or unsafe practices that can result in minor personal injury if instructions, including recommended precautions, are not followed. NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed. Following Safety Instructions If you do not understand any portion of this instruction sheet and need assistance, contact your nearest S&C Sales Office or S&C Authorized Distributor. Their telephone numbers are listed on S&C s website sandc.com, or call S&C Headquarters at (773) 338-1000; in Canada, call S&C Electric Canada Ltd. at (416) 249-9171. NOTICE Read this instruction sheet thoroughly and carefully before installing or operating your S&C Loadbuster Tool. Replacement Instructions and Labels If you need additional copies of this instruction sheet, contact your nearest S&C Sales Office, S&C Authorized Distributor, S&C Headquarters, or S&C Electric Canada Ltd. It is important that any missing, damaged, or faded labels on the equipment be replaced immediately. Replacement labels are available by contacting your nearest S&C Sales Office, S&C Authorized Distributor, S&C Headquarters, or S&C Electric Canada Ltd. 8 S&C Instruction Sheet 811-505

Safety Information Location of Safety Labels A A A B B B Reorder Information for Safety Information Location Safety Alert Message Description Part Number A NOTE To ensure resetting, depress telescoping tube until orange band... G-5840R1 B WARNING RESET AFTER EACH OPERATION To check for proper resetting... G-4401 (for 5300R3) G-4401 (for 5300R3-E) G-4320 (for 5400R3) S&C Instruction Sheet 811-505 9

Safety Precautions DANGER The Loadbuster Loadbreak Tool is used to switch equipment that operates at high voltage. Failure to observe the precautions below will result in serious personal injury or death. Some of these precautions may differ from your company s operating procedures and rules. Where a discrepancy exists, follow your company s operating procedures and rules. 1. QUALIFIED PERSONS. Access to a Loadbuster Loadbreak Tool must be restricted only to qualified persons. 2. SAFETY PROCEDURES. Always follow safe operating procedures and rules. Always maintain proper clearance from energized components. 3. PERSONAL PROTECTIVE EQUIPMENT. Always use suitable protective equipment such as rubber gloves, rubber mats, hard hats, safety glasses, arc-flash clothing, and fall protection in accordance with safe operating procedures and rules. 4. SAFETY LABELS and TAGS. Do not remove or obscure any of the DANGER, WARNING, CAUTION, or NOTICE labels. Remove tags ONLY if instructed to do so. 5. ENERGIZED COMPONENTS. Always consider all parts live until de-energized, tested, and grounded. 6. MAINTAINING PROPER CLEARANCE. Always maintain proper clearance from energized components. 7. OPERATION. Never position the Loadbuster Loadbreak Tool so the outer tube obscures your line of vision. (See Figure 1 on page 7 for correct positioning.) 8. RESETTING. Keep hands clear during resetting. The Loadbuster tool is spring loaded. Pulling the resetting latch will cause the anchor end of the tool to move down quickly. Keep hands in the position shown in Figure 7 on page 15. 10 S&C Instruction Sheet 811-505

Shipping and Handling Inspection Examine the shipment for external evidence of damage as soon after receipt as possible, preferably before removal from the carrier s conveyance. Check the bill of lading to make sure all listed shipping skids, crates, cartons, and containers are present. If there is visible loss and/or damage: 1. Notify the delivering carrier immediately. 2. Ask for a carrier inspection. 3. Note condition of shipment on all copies of the delivery receipt. 4. File a claim with the carrier. If concealed damaged is discovered: 1. Notify the delivering carrier within 15 days of receipt of shipment. 2. Ask for a carrier inspection. 3. File a claim with the carrier. Notify S&C Electric Company in all instances of loss or damage. S&C Instruction Sheet 811-505 11

Operation Figure 2. Recommended aerial bucket positions for an operator using the Loadbuster tool with overhead distribution devices. Figure 3. Recommended pole positions for an operator using the Loadbuster tool with overhead distribution devices. 12 S&C Instruction Sheet 811-505

Operation Overhead Distribution Devices Check for proper resetting of the Loadbuster tool by extending the tool about three inches (77 mm) by hand. Throughout this travel, an increasing spring resistance should be felt. NOTICE Although the text and figures that follow describe the operation of the Loadbuster tool with SMD-20 power fuses, the procedure is equally applicable to fuse cutouts, disconnects, power fuses, and fuse limiters. Step 1 Reach across in front of the power fuse with the Loadbuster tool and hook the anchor, located at the top of Loadbuster tool over the attachment hook on the far side of the power fuse. See Figure 4. Step 2 Swing the Loadbuster tool toward the power fuse and pass the Loadbuster tool pull-ring hook through the pull-ring on the power fuse. The pull-ring latch will deflect and, upon com plete entry of the pull-ring, will spring back, locking the Loadbuster tool to the pull-ring. The Loadbuster tool is now connected across the upper contact of the power fuse. See Figure 4. Attachment hook Anchor Anchor Pull-ring Pull-ring hook Pull-ring latch Figure 4. The Loadbuster tool connected to an S&C Power Fuse Type SMD-20, Outdoor Distribution. S&C Instruction Sheet 811-505 13

Operation Step 3 To open the circuit, operate the Loadbuster tool with a firm, steady pull until it is extended to its maximum length. See Figure 5. Avoid jerking and hesitating. The resetting latch will keep it open. Generally, there will be no indication of circuit interruption but minor arcing may be noted at the pull-ring hook and at the anchor, particu larly when interrupting load currents approach the rating of the tool. The only sound will be that of the Loadbuster tool tripping. Step 4 To detach the Loadbuster tool after circuit interruption, first raise it slightly and disengage the anchor from the attachment hook. CAUTION When the Loadbuster tool is raised, the open gap distance is reduced. Careless manipulation could decrease the open gap to the point where flashover will occur. Next, bring the power fuse toward its fully open posi tion as illustrated in Figure 6 (this procedure is recom mended as uniform practice because disconnects will not necessarily open fully by gravity). Remove the Loadbuster tool from the pull-ring by turning the pole. This will deflect the pull-ring latch to release the pull-ring. On fuse cutouts, fuse limiters or power fuses on which the fuse tube or power fuse will drop fully open by gravity, it may be preferred to remove the Loadbuster tool by rolling it off both the attachment hook and pull-ring at the same time merely by twisting the pole after the Loadbuster tool has been tripped and fully extended. To perform this operation easily and smoothly, always roll the Loadbuster tool so it rotates in an upward direction. Figure 5. The Loadbuster tool in the tripped position. Figure 6. Detaching the Loadbuster tool from a power fuse. 14 S&C Instruction Sheet 811-505

Operation Step 5 To reset the Loadbuster tool for the next operation, hold as shown in Figure 7. Extend the tool slightly and lift the resetting latch with the thumb. With the latch up, press down on the inner tube assembly until the tool is closed completely so the trigger can reset itself. When reset properly, the orange paint on the inner tube assembly will no longer be visible. Check for proper resetting by extending the tool about three inches (77 mm). Throughout this travel an increasing spring resistance should be felt. Press down on the inner tube Resetting latch Figure 7. Resetting the Loadbuster tool. S&C Instruction Sheet 811-505 15

Operation Pad-Mounted Gear The Loadbuster S&C s Loadbreak Tool (Catalog Number 5300R3-E) makes an inter rupter switch out of every power fuse or disconnect switch in pad-mounted gear suitably equipped with the attachment hook. Operation in padmounted gear is simi lar to that of overhead distribution devices in most respects. CAUTION To avoid partial opening or flashover, Loadbuster Loadbreak Tool, Catalog Number 5400R3 rated 25/34.5 kv, must not be used with metal enclosed switchgear, metal-enclosed fuses, or pad-mounted gear. There is not enough clearance to use the 5400R3 on these devices. Before using the Loadbuster tool in pad-mounted gear, review Clearance Requirements for Use in Pad-Mounted Gear, page 5. Also review information presented under Overhead Distribution Devices, pages 13 through 15. When using the Loadbuster tool in pad-mounted gear, avoid any tendency to grasp the pole close to the Loadbuster tool end. Be sure, instead, to grasp the pole near the end opposite the Loadbuster tool. Although the text and figures following describe the operation of the Loadbuster S&C s Loadbreak Tool (Catalog Number 5300R3-E) with power fuses in padmounted gear, the procedure is equally applicable to that employed with disconnect switches in pad-mounted gear. Figure 8. The Loadbuster anchor connected to an attachment hook. 16 S&C Instruction Sheet 811-505 Figure 9. The Loadbuster tool connected to a power fuse.

Operation Step 6 Reach across in front of the fuse unit or holder with the Loadbuster tool and hook the anchor, located at top of the Loadbuster tool, over the attachment hook on the far side of the fuse unit or holder. See Figure 8 on page 16. Note that only one attachment hook is provided. Step 7 Swing the Loadbuster tool toward the fuse unit or holder and pass the Loadbuster tool pull-ring hook through the pull-ring of the fuse unit or holder. The pull-ring latch will deflect and, upon complete entry of the pull-ring hook, will spring back, locking the Loadbuster tool to the pull-ring. The Loadbuster tool is now connected across the upper contact of the power fuse. See Figure 9 on page 16. Step 8 To open the circuit, operate the Loadbuster tool with a firm, steady pull until it is extended to its maximum length. See Figure 10. Avoid jerking and hesitation. The resetting latch will keep it open. Commutation arcing may be noted at the pull-ring hook and at the anchor, but the only sound will be that of the Loadbuster tool tripping. Step 9 To detach the Loadbuster tool after circuit interruption, roll the tool upward by turning the pole. See Figure 11. This will deflect the pull-ring latch to release the pull-ring hook from the pull-ring of the fuse unit or holder. Disen gage the anchor from the attachment hook and withdraw the tool. Step 10 Reset the Loadbuster tool for the next operation as described in Step 5 on page 15. Figure 10. The Loadbuster tool in a tripped position. Figure 11. Detaching the Loadbuster tool from a power fuse. S&C Instruction Sheet 811-505 17

Operation Understanding the Operation Counter Loadbuster tools manufactured after March 2003 are equipped with a non-resettable operation counter feature that lets you monitor the use of your tools to make more informed decisions with regard to inspection and maintenance. The operation counter is built into the Loadbuster tool s silencer and can be easily added to existing tools. Figure 12. The Loadbuster tool s operation counter. 18 S&C Instruction Sheet 811-505