C7170A,B Encapsulated Temperature Sensor

Similar documents
C7046A,B,C,D Air Temperature Sensors

Immersion Wells and Compression Fittings FOR TEMPERATURE CONTROLLERS

Immersion Wells and Compression Fittings FOR TEMPERATURE CONTROLLERS

L404F,T,V PressureTrol Controllers

ML6425, ML7425 Spring Return Electric Linear Valve Actuators

ML6420, ML7420 Non-Spring Return Electric Linear Valve Actuators

V5197A Firing Rate Gas Valve

The ES /118 Explosion-Proof Housings

ML6420, ML7420 Non-Spring Return Electric Linear Valve Actuators

AT120A-E; AT140A-E; AT150A,B,D-F; AT160B; AT175A-D,F Transformers

Q345A, Q3451, Q3481, Q348A, Q348B, Q362A, Q373A, Q381A and Q3452 Intermittent Pilot Burner/Igniter-Sensors

BCS Modutrol Motor M7484A

M436A/M836A,B Damper Motors

V9055A,D Modulating Fluid Power Gas Valve Actuator

AD592/592-10K Non-Room Units with a Junction Box, Weatherproof (WP) or Weather Tight (EU) Enclosure

TS Series TS Series

Series 41 and 81 Modutrol IV Motors

V5011N Two-Way Threaded Globe Valve

AD592/592-10K Non-Room Sensors in BAPI-Box, BAPI-Box 2 or BAPI-Box 4 BA/592-x-(BB, BB2, BB4) Temperature Sensor Instructions & Operation

V51E Butterfly Valve. The valve mechanism is equipped with strain release springs.

Q345A, Q3451, Q3481, Q348A, Q348B, Q362A, Q373A, Q381A and Q3452 Intermittent Pilot Burner/Igniter-Sensors PRODUCT DATA

MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 Fast-Acting, Two-Position Actuators

Q7800C Integrated Burner Control Subpanel

Q5020A-D Globe Valve Linkages FOR DIRECT COUPLED ACTUATORS

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

D690 Round Damper LOW-LEAKAGE, SINGLE-BLADE FEATURES APPLICATION PRODUCT DATA. Contents

V4043 and V4044 Motorized Valves

V5011N Two-Way Threaded Globe Valve

Remote Temperature Controllers. Quick Selection Guide

ML7421A,B Electric Linear Valve Actuator

MS4120F, MS4620F, MS8120F, S2024-F, S20230-F Fast-Acting, Two-Position Actuators

Pipe Temperature Sensors. Model TE-703 / 704

35 and 70 lb-in. Non-Spring Return Direct Coupled Actuators ML6161, ML7161, ML6174, ML7174

Series 71, 72, and 76 Modutrol IV Motors

V5055A-F Industrial Gas Valves

Introduction. Series A99 Temperature Sensors. Features and Benefits

A91 Series Thermistor Temperature Sensors For Duct, Immersion and Space Sensing

Temperature Transmitters

UV100A Ultraviolet Systems UV100A1000 AND UV100A1018 AIR TREATMENT SYSTEMS UV100A1059 AND UV100A2008 SURFACE TREATMENT SYSTEMS

R182J, R482J, R845A, R847A, R882J, RA89A, RA832A Switching Relays

Series A99 Temperature Sensors. Features and Benefits. The A99 temperature sensor line includes various models, such as:

FEATURES APPLICATION PRODUCT DATA

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration

Thermal Expansion Absorber For Potable Water TX SERIES TANKS

Q7130A, Q7230A, Q7330A Modutrol IV Interface Modules

ComfortPoint Programmable Lon, VAV/Unitary Controllers

SetPoint 150 Controller Installation Manual

Duct Temperature Sensors. Model TE-701 / 702

Temperature Sensors. Description. Specification

A419ABG-3C Electronic Temperature Control

T915A-D,F,M,P Proportional Temperature Controllers

SLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS

CO 2 Room Sensor in the BAPI-Stat Quantum Prime Style Enclosure

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

Q5024A,B Globe Valve Linkages FOR DIRECT COUPLED ACTUATORS

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

VOC Room Sensor in the BAPI-Stat 3 Enclosure with Differential Ground Configuration

M100F Incremental Motor Actuator R81F Interface Board

SEN and SEN Outdoor Air Temperature Sensors

TS Temperature Sensor and Transducers. Product Bulletin. Wide range of mounting types and signal outputs

* * Rev. 9 01/18 Product Manual

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies

Differential Pressure Transmitter

VC2, VC4, VC60, VC8 ON-OFF ACTUATOR FOR VC SERIES BALANCED HYDRONIC VALVES SPECIFICATIONS INSTALLATION INSTRUCTIONS

General Information... Temperature/Resistance Table... Part Numbering Examples for RTD s. High Temperature MgO Elements (RA)...

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

ENC 150 REFERENCE MANUAL ACU-RITE

Submersible Averaging Duct Transmitters BA/T#SA Temperature Transmitter Installation & Operations

System 350 P352AB Electronic Pressure Control Series

BAPI-Stat 3 Room Sensor

STERILMATIC DIGITAL ELECTRIC STERILIZER PARTS AND SERVICE MANUAL

Sanitary RTDs and Temperature Transmitters

Excel 15 W7760A BUILDING MANAGER

V4062A,B,D HI-LO-OFF Fluid Power Gas Valve Actuator

A11 Series Low Temperature Cutout Control

BAS Construction Checklist

1/16 DIN Temperature Controller E5CS

Powers Controls TT 184 Temperature Transmitters

Distributed By: M&M Control Service, Inc PRODUCT PRODUCT CODE RESOURCE DOCUMENTS PAGE #

TE-6300 Series Temperature Sensors

CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

Revision THERMO TECHNOLOGIES. USDT 2001 Differential Controller. Installation and User s Guide

TMD90A Dual Input Digital Thermometer

Signet 2760 DryLoc ph/orp Preamplifier

Northwest RV Supply Manual Compliments of Printed From TROUBLESHOOTING

203365A 120 Vac to 220/240 Vac Conversion Kit For Electronic Air Cleaners

Figure 1: WPR2 Dimensions and Hardware

Insertion Temperature/Humidity/ Dewpoint temperature Sensor HTY78X3/HY78X3/HTY78X6/HY78X6/HY79X3

TE-6300 Series Temperature Sensors

System 350 S350P Proportional Plus Integral Temperature Stage Module

TE-6300 Series Temperature Sensors Catalog Page

PRECISION DC CURRENT SHUNT STANDARDS. The Most Accurate and Widely Recommended DC Shunt Available Today!

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

ST Wiring diagram. Product description. Temperature controller. Order number

PS1201A00, PS1202A00 and PS2401A00 Replacement Power Supplies for Electronic Air Cleaners

PVC1000 Series. Microsystems, Inc. Pirani Vacuum Sensors. PVC1000 Series. Description. Features. Applications. Absolute Maximum Ratings

AQUASTATS THERMOSTAT APPLICATION

SIGNET 2760 DryLoc ph/orp Preamplifier

P66 Series Electronic Fan Speed Controls

TS , -850 Series TS , -850 Series TS-57031, TS

Transcription:

C7170A,B Encapsulated Temperature Sensor The C7170A,B Temperature Sensors are for use with electronic controllers where linear PTC sensors are required (W7100, W7600, W7620, or Excel 500, for example), and with R7380J,L Indicating Controllers in immersion or strap-mounted discharge applications. Requires no settings or calibration. Platinum positive temperature coefficient (PTC) sensing element. High accuracy temperature sensing (+/-2 F [1.1 C]) for wide range of temperatures (-40 F to +257 F [-40 C to +125 C]). Resistance range is 2900 to 4400 ohms (C7170A); 840 to 1500 ohms (C7170B). Can be located up to 1195 ft [364 m] from the R7380. Suitable for mounting in immersion well. Can be strapmounted to discharge pipe of boiler or chiller. CONTENTS Specifications... 2 Ordering Information... 2 Installation... 3 Operation and Checkout... 5 G. R. Rev. 5-93 Honeywell Inc. 1993 Form Number 63-2045 2 1 63-2045 2

C7170A,B SPECIFICATIONS ORDERING INFORMATION Specifications IMPORTANT: The specifications given in this publication do not include normal manufacturing tolerances. Therefore, an individual unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed. MODEL: The C7170A,B Temperature Sensors are for use with electronic controllers where linear PTC sensors are required (W7100, W7600, W7620, or Excel 500, for example), and with R7380J,L Indicating Controllers in immersion or strap-mounted discharge applications. C7170A: Use with W7100, W7600, W7620, R7380J,L. C7170B: Use with Excel 500. ELECTRICAL RATING: 30 Vac maximum. TEMPERATURE SENSOR RESISTANCE: (see Figs. 5 and 6) Temperature C -10 0 10 20 30 40 Temperature F 14 32 50 68 86 104 Resistance in 3,178 3,266 3,353 3,440 3,527 3,613 ohms C7170A Resistance in 961 1,000 1,039 1,078 1,117 1,155 ohms C7170B MOUNTING: Strap-on or immersion mounting; see Accessories. DIMENSIONS: See Fig. 1. LEADWIRE LENGTH (Specify when ordering): 24 in. [61 cm] pigtail leads 80 in. [240 cm] quick connect LEAD LENGTH: 1195 ft [364 m] maximum. ACCESSORIES: 4074CAV: Shielded Cable, 50 ft [15 m]. 4074CAW: Shielded Cable, 100 ft [30.4 m]. 4074CAY: Shielded Cable, 200 ft [61 m]. 105900 Pipe Strap: Fits up to 3/4 in. [19 mm] O.D. pipe. 121371A Immersion Well: 1/2 in. [13 mm] NPT copper. 121371E Immersion Well: 1/2 in. [13 mm] NPT stainless steel. 107408 Heat Conductive Compound: 4 oz. [113 g] can. Fig. 1 Approximate dimensions of C7170A Encapsulated Temperature Sensor in in. [mm]. 2-5/8 (66) SENSING ACCURACY: With R7380, +/-2 F [1.1 C]. AMBIENT TEMPERATURE RANGES: Operating and Shipping: -40 F to +257 F [-40 C to +125 C]. HUMIDITY: 90 percent relative humidity at 90 F [32 C] noncondensing environment. 3/8 (9.5) M8060 Ordering Information When purchasing replacement and modernization products from your TRADELINE wholesaler or distributor, refer to the TRADELINE Catalog or price sheets for complete ordering number, or specify 1. Model number. 2. Leadwire length. 3. Accessories, if required. 4. Order additional system components and accessories as needed. In Canada Honeywell Limited/Limitee, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service offices in all principal cities of the world. 2

BOILER C7170A,B INSTALLATION Installation WHEN INSTALLING THIS PRODUCT 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. Installer must be a trained, experienced service technician. 4. After installation is complete, check out product operation as provided in these instructions. Disconnect power supply before making wiring connections to prevent electrical shock or equipment damage. LOCATION AND MOUNTING The C7170A,B Encapsulated Temperature Sensor can be installed by strapping the sensor to the outside of a boiler or chiller output pipe, or by placing the sensor in the fluid of a boiler or chiller using an immersion well. Instructions for both types of installations follow. 3. Press the sensor bulb into the heat conductive compound and fasten to the discharge pipe with 105900 Pipe Clamp, duct hanger wire or with metal hose clamps. See Fig. 2. IMPORTANT: Do not overtighten clamps to the point of distorting the sensor. Overtightening the clamps could cause a shift in calibration or failure of the sensor. Fig. 2 Strap-on mounting of C7170A,B Encapsulated Temperature Sensor on boiler/chiller discharge pipe. T-CLAMP HEAT CONDUCTIVE COMPOUND SUPPLY WATER PIPE UP TO 3/4 in. O.D. SENSOR LEAD WIRES Strapping The C7170A,B To A Boiler Or Chiller Output Pipe Some applications require that the sensor be strapped to the outside of a pipe. Strap-on mounting avoids the need for an immersion well and pipe fittings, and also eliminates the system draining, refilling, and bleeding necessary to install the immersion well. The 105900 Pipe Strap or metal hose clamps can be used in this application. The pipe strap will fit up to 3/4 in. O.D. pipe. External mounting of the sensor produces a slight offset in the temperature control point. The control temperature could be increased up to 5 F [2.8 C] with a bare sensor strapped to the discharge pipe. Use a heat conductive compound and apply insulation around the C7170A,B and pipe to decrease the temperature offset. Obtain any necessary straps, clamps and insulation locally. The sensor bulb should be located at a point on the discharge pipe approximately 3 ft [1 m] from the boiler or chiller. Refer to Fig. 2. PROCEDURE 1. Remove any insulation on the pipe, leaving about 6 in. [15 cm] of the pipe exposed. With care, most insulating materials may be able to be reused to cover the sensor when the installation is complete. 2. Clean the pipe surface for good sensor-to-pipe contact. Apply heat conductive compound to the pipe at the selected location. LEAD WIRES LEAD WIRES APPROX. 3 FT [0.9 M] C7170A STRAPPED TO PIPE DO NOT OVERTIGHTEN CLAMPS TO THE POINT OF DISTORTING THE SENSOR. OVERTIGHTENING CLAMPS WILL CAUSE A SIGNIFICANT SHIFT IN CALIBRATION. FOAM TAPED OVER STRAPPED SENSOR C7170A DISCHARGE PIPE DUCT HANGER WIRE OR METAL HOSE CLAMPS FOAM RUBBER WRAP (EXTENDS 6 in. [152.4 mm] BEYOND ENDS OF SENSOR) DISCHARGE PIPE DUCT TAPE M5250A 3 63-2045 2

C7170A,B INSTALLATION 4. If available, replace the pipe insulation; otherwise, cover the sensor with foam rubber insulation extending at least 6 in. [15 cm] past each end of the sensor. Overlap the foam wrap at least one-third the diameter of the pipe. 5. Fasten the insulation in place with duct tape. Do not allow the duct tape to contact the pipe. Installing The C7170A,B In An Immersion Well When the C7170A,B sensor is mounted in the fluid of the boiler or chiller system, an immersion well (not included, see Accessories) must be used to hold the sensor bulb in the system. Locate an existing pipe plug in the system where a representative fluid temperature can be monitored. If an existing pipe plug is not available, a hole must be tapped or an adapter inserted into a pipe junction at the boiler/chiller. When installing the C7170A,B in an immersion well, make sure that the lead wire end of the sensor capsule is completely covered by heat conductive compound to protect the sensor from damage caused by water condensation. See Fig. 3. PROCEDURE 1. Drain system until the fluid level is below the pipe tapping. 2. Remove the pipe plug from the tapping, and clean the hole threads. 3. Apply a moderate amount of pipe dope to the immersion well threads, and screw the well into the hole. 4. Fill the space between the sensor and the well with heat conductive compound for optimum temperature response. Place the heat conductive compound into the well. Push the sensor into the bottom of the well. Tape the leadwires to a fixed object close to the well but off the boiler or chiller to prevent the sensor from being pulled out. 5. Make sure the leadwire end of the sensor is completely covered by heat conductive compound to protect the sensor from water condensation damage. 6. Refill the system. Check for fluid leaks at the well when the system is in operation. Fig. 3 C7170A,B Encapsulated Temperature Sensor installed in immersion well. COVER SENSOR LEADS WITH HEAT CONDUCTIVE COMPOUND SENSOR PLACED IN WELL WIRING Wiring should be kept at least one foot away from large inductive loads such as motors line starters, lighting ballasts, and large power distribution panels. Failure to follow these wiring practices may introduce electrical interference (noise) which can cause erratic system operation. Shielded cable is required in installations where these guidelines cannot be met. Ground shield only to grounded controller case. IMPORTANT: Erratic temperature readings from a sensor can be caused by the wiring practices described below. These must be avoided to assure proper operation. Use shielded cable to reduce interference if rerouting of sensor wiring is not possible. a. Do not route temperature sensor wiring with building power wiring, next to control contactors or near light dimming circuits, electric motors or welding equipment. b. Avoid poor wiring connections. c. Avoid intermittent or missing building earth ground. Do not mount sensor in incorrect environment. Resistance in the C7170A Sensor wiring positively offsets the temperature sensed by 1 degree F for every 4.8 ohms [8.6 ohms/ C] of resistance. Use short wire lengths or larger gauge wire when longer lengths are necessary. Resistance in the C7170B Sensor wiring positively offsets the temperature sensed by one degree Fahrenheit for every 2.1 ohms [1 degree Celsius for every 3.85 ohms] of resistance. Use short wire lengths or use larger gauge wire when longer wire lengths are necessary. Procedure 1. Disconnect power supply before making wiring connections to prevent electric shock or equipment damage. All wiring must agree with local codes, ordinances, and regulations. 2. Wire the C7170A,B to the controller using the procedures and diagrams for that device. Keep wiring runs as short as practical but less than 1195 ft [364 m]. If wiring distances longer than 50 ft are expected, order the shielded cable, see Accessories. A general wiring hookup is shown in Fig. 4. For specific limitations and wiring diagrams, refer to the instructions provided with the controller used with this sensor. 1/2 NPT IMMERSION WELL M5249 4

Fig. 4 General wiring hookup for C7170A,B Encapsulated Temperature Sensor. C7170A,B INSTALLATION OPERATION AND CHECKOUT SENSOR TERMINALS CONTROLLER M18975 Operation and Checkout OPERATION The C7170A,B is a highly accurate solid state sensor for use in applications requiring a broad temperature sensing range. Unlike thermistors, the C7170A,B has a positive temperature coefficient (PTC); resistance increases as the temperature increases. As shown in Fig. 5, the resistance curve for the C7170A increases by 4.8 ohms per degree Fahrenheit temperature rise [8.6 ohms per degree Celsius]. Since the C7170A curve represented in Fig. 5 is the same as the curve used by the C7100A sensor, these sensors are interchangeable. As shown in Fig. 6, the resistance curve for the C7170B increases by 2.1 ohms per degree Fahrenheit temperature rise [3.85 ohms per degree Celsius]. Since the C7170B curve in Fig. 6 is the same as the curve used by the C7100D, C7130B, and C7031-PT1000 Sensors, these sensors are all interchangeable. CHECKOUT 1. Measure the fluid temperature at the sensor location with an accurate thermometer +1-1 F [0.5 C], allowing time for the thermometer to stabilize before reading. Use an ohmmeter to measure the resistance across the sensor wires. Then verify sensor accuracy with the temperature/resistance curve in Fig. 5 or 6. 2. Check shield ground on wiring (zero resistance to ground). Replace if necessary. 3. Check connectors at both ends of the wiring for the proper connection. Tighten or replace as necessary. 4. Check sensor for correct installation: clamps (where used) not too tight, heat conductive compound correctly applied (see Installation section). Fig. 5 C7170A temperature/resistance curve. RESISTANCE (OHMS) 4200 4000 3800 3600 3400 3200 3484 6.5 OHMS AT 77 F (25 C) F 20 40 60 80 100 120 140 160 180 200 220 C -7 0 10 20 30 40 50 60 70 80 90 100 TEMPERATURE (DEGREES) M2829 Fig. 6 C7170B temperature/resistance curve. RESISTANCE (OHMS) 1400 1317 1231 1145 1059 1097 0.08 OHMS AT 77 F [25 C] 973 20 40 60 80 100 120 140 160 180 200 F 220 C -7 0 10 20 30 40 50 60 70 80 90 100 TEMPERATURE (DEGREES) M2824 5 63-2045 2

Automation and Control Solutions Honeywell International Inc. Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 6