VR400/VR800 series UNIVERSAL GAS VALVES CLASS A SERVO REGULATED COMBINATION VALVES APPLICATION. Contents PRODUCT HANDBOOK. General

Similar documents
VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION

VE4000 & VE5000 SERIES

VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION

VE Series. Class "A" Gas Valves. Product handbook APPLICATION CONTENTS. General. Technical. Installation and operation. Various

Honeywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION

VQ400M SERIES CLASS A COMBINATION VALVES INSTRUCTION SHEET APPLICATION

S4562C 1085 COMBI BOARD APPLICATION. Contents PRODUCT HANDBOOK. General

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating GB-M(P) 057 D01

/

B21 Series BASOTROL Gas Valve

822 NOVAMIX GAS FLOW RATE ADJUSTMENT AS A FUNCTION OF THE AIR FLOW GAS/AIR RATIO 1:1 DOUBLE AUTOMATIC SOLENOID SHUT-OFF VALVE

BGD278 Series BASOTROL CE Approved Gas Valve

Old documentation - Only for your information! Product is not available any more!

BGD258 Series BASOTROL CE Approved Class A Gas Valve

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function Integrated bypass valve MB-D(LE) B07

SERIES 2000 GAS SAFETY SHUT OFF VALVE

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) 403 B01 MB-D(LE) 053 B01

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) B01

GasMultiBloc Combined regulator and safety shut-off valves Two-stage function Integrated bypass valve MB-ZRD(LE) B07

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) 403 B01

MBC-300-SE MBC-700-SE MBC-1200-SE MBC-300-N MBC-700-N

GasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-300-VEF MBC-700-VEF MBC-1200-VEF

Electro- Hydraulic Actuator Gas Valves GH-5000

VML. elektrogas.com. Safety solenoid valves for gas Slow opening and fast closing type DN10 DN80 EE

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) B01

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function Integrated bypass valve MB-D(LE) B07

MBC-300-SE MBC-700-SE MBC-1200-SE MBC-300-N MBC-700-N

GasMultiBloc Combined regulator and safety shut-off valves Two-stage function MB-ZRD(LE) B01

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil

VMH. www. delta-elektrogas.com. Safety shut off valves for gas with hydraulic actuator DN65 DN200 EE

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

Governor with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

3 Edition Product brochure GB AGA

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG Variable air/gas ratio control with solenoid valve VAV

Tightness control TC. Product brochure GB Edition 12.10

AQUASTATS THERMOSTAT APPLICATION

Gas Pressure Governors

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

VLF45... Hot Air Valves. Siemens Building Technologies HVAC Products

3/3 servo directional control valve with mechanical position feedback

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

Solenoid Valve DF-SB-series

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

Mounting and Operating Instructions EB 8111/8112 EN. Valve Series V2001 Globe Valve Type 3321

Mounting and Operating Instructions EB 5868/5869 EN

HANDBOOK SOLENOID VALVES. Ed SOLENOID VALVES VS-ED 01/ ENG 1

Mounting and Operating Instructions EB 8097 EN. Pneumatic Control Valves Type and Type

Mounting and Operating Instructions EB 3913 EN. Electropneumatic Converters i/p Converter Type

Solenoid Valve DF-SA-series

Type 2511/12. Type Type 2030 Cable plug. ASI cable plug. Dosing control. General technical data Orifice Type 6518

Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5

LKS 160 FOR AIR DAMPERS ON MULTI-STAGE AND MODULATING BURNERS

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

HYDRAULIC CONTROL VALVES

Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5

CHALLENGER Propane to Natural Gas Instructions

Black Teknigas. Powerseat Eco Gas Safety Shut-Off Valve. Technical, Installation and Maintenance Details. WattsIndustries.co.uk

Mounting and Operating Instructions EB 8097 EN. Type and Type Pneumatic Control Valves

V5197A Firing Rate Gas Valve

Manually operated safety shut-off valve HSAV HSAV/5

VGD20... VGD40... Double Gas Valves. Siemens Building Technologies Landis & Staefa Division

Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5

A408 GB. Pneumatic oil and diesel pumps 1:1

Valve monitoring system VDK 200 A S02

Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5

CVR-625. Compact Vibrating Rod Instruction Manual

Chapter 6: Check Valves

Mounting and Operating Instructions EB 8227 EN. Pneumatic Control Valve Type 3331/BR 31a Special version Type 3331/3278. Type 3331 Butterfly Valve

SV2 Series Safety Shut-off Valves

70 Series 8700 End Mount Three Phase Brake Instructions IP43 (NEMA 2) Housing

LHW-3P Load Holding Valve Winch

Valves. Rapid opening and closing solenoid valves VMR (E1110 rev /11/2012)

Solenoid Valve ST-IA-series

SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

Typetested for liquid fuels and liquefied petroleum gas (LPG) in the liquid phase (see Data Sheet T 8022 EN) Version according to ANSI standards

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

Combination controls CG 10

Fisher 657 Diaphragm Actuator Sizes and 87

Type 6213 EV, 6281 EV

2/2 or 3/2-way Solenoid Valve, with pivoted armature and isolating diaphragm

70 Series 8700 End Mount Three Phase Brake Instructions IP56 (NEMA 4) Housing

Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black

VKF41...C. Butterfly Valves. Building Technologies Division Industry Sector

VLF45... Hot Air Valves. Building Technologies Division

Injection Oilers, Micro Pumps

Technical Principles of Valves

Air Operated Valve Control Valve

Mounting and Operating Instructions EB 8091 EN. Pneumatic Control Valve Type and Type Type with 120 cm 2 actuator

WARNING Warnings are indicated when mishandling this product might result in death or serious injury to the user.

Series 240 Type Gas and Type Gas Automatic Shut-off Valves for Gases (valve class D)

YARWAY NARVIK STANDARD DUTY A.T.-TEMP DESUPERHEATER MODEL 38/48

NARVIK-YARWAY. Heavy Duty A.T. - Temp Desuperheater Model: 18/54 and 28/64

Solenoid Valve ST-SA-series

MS Application. Features. Proportional Valve Actuator General Instructions

Productinformatie BAFA.NL BAFA.NL A.U.K. MÜLLER GMBH & CO. KG

KE-M02 configuration Configuratie documentatie documentation KE-M02

Solenoid valves for gas VAS, Double solenoid valves VCS

Motorized Butterfly Valve

Mounting and Operating Instructions EB 8039 EN. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve

Transcription:

UNIVERSAL GAS VALVES VR00/VR800 series CLASS A SERVO REGULATED COMBINATION VALVES APPLICATION PRODUCT HANDBOOK The VR00 Series class A servo regulated combination valves are used for control and regulation of gaseous fuels in gas fired power burners, atmospheric gas boilers, melting furnaces, incinerators and other gas consuming appliances. These servo regulated combination valves are available in Three different versions: VR1/VR81 (pipe sizes 1/ ) VR0/VR80 (pipe sizes / ) VR/VR8 (pipe sizes 1 ) Subject to change without notice. Printed in the Netherlands. General Contents Description... Features... Technical Specifications... Performance characteristics... Capacity curves... -- 8 Dimensional drawings... 9 -- Installation and Operation Installation... 11 Adjustments and final checkout... 1 Construction and working principles... 1 Various Standards and approvals... 1 Ordering information... 1 Replacement parts and accessories... 0 ENR--90 0R--NE

DESCRIPTION The VR00/VR800 series class A servo regulated combination valves are suitable for the control of gaseous fuels in gas consuming appliances according to international standards. The VR00/VR800 series meet the class A + A specification according EN 11. The VR00/VR800 series have 1/, /, and 1 straight flanged pipe connection. The VR00/VR800 series are standard equipped with two main valves V1 and V. Safety valve V1 is always fast opening/closing. The second valve (V) can be either fast (with flow regulation) or slow (= with flow regulation and adjustable opening). The pressure regulating valve is located between V1 and V. The VR00/VR800 series are available for Direct Burner Ignition (DBI) and Intermittent Pilot (IP) applications. At both sides of the main body flange connections are provided to mount either an: inlet pressure switch C0VR serie interim pressure switch C0VR serie Valve Proving System (VPS) + pressure switch. These accessories can be mounted on various positions of the main body of the VR00/VR800 series.

FEATURES Class A servo regulated combination valve for control of gaseous fuels in gas consuming appliances in accordance with international standards. Main body with two shut -off valves with single seat. Options for mounting flanged minimum and/or interim pressure switches. Valve Proving System (VPS). Closing time: < 1 second. Coils field replaceable. Coils suitable for permanent energization. Fine mesh screen (strainer) between inlet flange and main body. Various pressure tap points at main body available, when no additional valves or pressure switches are used. Second main valve, either with fast opening, or characterized opening mechanism (slow) with adjustable maximum flow rate and step pressure. Rectifier boards field replaceable. Plug connector according to DIN 0. All adjustments are located on the top of the valve. Different pressure ranges. Suitable for electric modulation. Suitable for electric two stage regulator. Suitable for gas/air modulation. Connections for IP application.

SPECIFICATIONS The specifications described in this chapter are related to the main gas valve (see also Performance characteristics on page ). The VR00/VR800 series must be used in combination with a burner programmer. Models VR1/VR81 (DN1) VR0/VR80 (DN0) VR/VR8 (DN) Optional: adjustable opening characteristics, page 1. For detailed regulator specifications of models with suffix M, suffix F, suffix P or suffix V see the appropriate Product Handbook. VRxxFy: EN1C--0001 VRxxMy: ENR--9009 VRxxPy: ENR--90 VRxxVy: ENR--9017 Dimensions See dimensional drawings and table on page Pipe sizes Inlet and outlet straight flange connection: 1/, /, and 1. (all internal pipe thread according to ISO 7--1) Capacity See capacity curves on page, 7, and 8 Minimum regulating capacity VR1/VR81: 1 m /hr. VR0/VR80: 1 m /hr. VR/VR8: 1. m /hr. Maximum operating pressure VR00XX00 series: 00 mbar VR00XX000 series: 0 mbar VR800XX series: 0 mbar Connections (see fig. 1. and 1. ) 1/8 pressure taps at inlet and outlet flanges. At the main body 8 flange connections are provided to mount either an: pressure switches (min. or max.) Valve Proving System (VPS). Two 1/8 connections for IP applications. Torsion and bending stress Pipe connections meet group according to EN 11 requirements. Valve Classification Class A + A according EN 1/EN 11 Regulator Classification Class C according EN 1/EN 88 Supply voltages Line voltage: 0 Vac, 0/0 Hz Other voltages on request. Electrical equipment DC current coils with combined rectifier inside the cover. Electrical connections Standard DIN plug connector Ambient temperature range --1... 0 C Coil insulation solenoid valves Insulation material according class F. Enclosure IP Body material Aluminium alloy die cast Strainer Fine mesh screen (diameter 0. mm), AISI 0 steel, serviceable after removing inlet flange screws. Meets requirements for strainer according EN 11. Closing spring AISI 0 steel Valve plunger Coated Fe 0 Seals and gaskets Hydrocarbon resistant NBR and Viton rubber types. Flange kit The kit consist of: -- 1 flange with sealing plug, -- 1 O --ring and screws. Table 1. Flange kits O.S. number Size (Rp) Remarks KTCOMB1 1/ with plug KTCOMB0 / with plug KTCOMB 1 with plug Table. Power consumption (W) VR00/VR800 series Model 0 Vac V1 V W ma W ma VR1/VR81 1 7 1 7 VR0/VR80 1 7 1 7 VR/VR8 19 90 19 90

PERFORMANCE CHARACTERISTICS Opening time Dead time maximum 1 second. The first valve (V1) opens in less than 1 second. The second valve (V) can be either a fast opening valve which reaches 0% of the adjustable outlet pressure within 0 sec. after start flow or a characterized opening valve which is adjustable from 1 up to 0 seconds, at rated capacity. The opening characteristic is factory set at approximately seconds at the following conditions: ϑ measured at 80 % of rated capacity -- 0 mbar supply pressure -- nominal voltage -- 0 _C --. mbar pressure drop -- no step pressure Due to the influence of ambient temperature (--1... 0 _C) the adjusted opening time of seconds measured at 80% of adjusted flow rate can vary + / -- seconds. Maximum allowable leakage Each VR00 combination valve has been factory tested to meet the following leakage requirements: outerwall: 0 cm. /h at test pressure of and 0 mbar. safety valve: 0 cm. /h at test pressure of and 0 mbar. main valve : 0 cm. /h at test pressure of and 0 mbar. High pressure test In the OFF condition, the VR00 valve will withstand 1. bar (air) inlet pressure without damage. Attempts to operate the VR00, while in this condition, will not cause damage. Oscillation Maximum oscillation under all circumstances 0. mbar. Tap sensitivity of outlet pressure set point For all gases the maximum deviation may be 1 mbar. Repeatability of outlet pressure set point For all gases the maximum deviation from set point is ± 0. mbar or + % of the set point value, whichever is the greatest. Table. Total set point shift Pressure range Tolerance (mbar)... 7 % of the set point value or 1 mbar whichever is the greatest... 0 * % of the set point value or 1 mbar whichever is the greatest 8... 0 % of the set point value or. mbar whichever is the greatest *... 0 mbar regulation not to be specified on valves with 0 mbar inlet pressure. Closing time (V1, V ) Less than 1 second for all valves. Maximum working frequency 1 cycle per minute Duty cycle Coil suitable for permanent energization in cooperation with ignition controller Operational voltage range The combination gas valve will function satisfactory between 8% and 1% of the rated voltage. Table. Design life Model Number of cycles VR1/VR81 VR0/VR80 00,000 VR/VR8

CAPACITY CURVES AND RECOMMENDED WORKING AREA Capacity curves servo regulated combination gas valves Table. Capacity in m / h air at np =mbar 1/ DN1 0 0 00 0 00 0 0 0 0 0 0 p(kpa) 1 0.8 8 n n p (mbar) 0. 0. 0. 0. 0. Vn (m /h) Air dv=1 0.1 1 Methane dv 0. 1 8 0 0 0 0 0 80 0 00 00 8 0 0 0 0 0 80 0 00 00 Fig. 1. Capacity curves for VR1/VR81 series (DN1)

CAPACITY CURVES AND RECOMMENDED WORKING AREA Capacity curves servo regulated combination gas valves Table. Capacity in m / h air at np =mbar / DN0 9 0 0 00 0 00 0 0 0 0 0 0 p(kpa) 1 0.8 8 n n p (mbar) 0. 0. 0. 0. 0. Vn (m /h) Air dv=1 0.1 1 Methane dv 0. 1 8 0 0 0 0 0 80 0 00 00 8 0 0 0 0 0 80 0 00 00 Fig.. Capacity curves for VR0/VR80 series (DN0) 7

CAPACITY CURVES AND RECOMMENDED WORKING AREA Capacity curves servo regulated combination gas valves Table 7. Capacity in m / h air at np =mbar 1 DN 1 0 0 00 0 00 1 0 0 0 0 0 0 1 0.8 8 n n p(kpa) p (mbar) 0. 0. 0. 0. 0. Vn (m /h) Air dv=1 0.1 1 Methane dv 0. 1 8 0 0 0 0 0 80 0 00 00 8 0 0 0 0 0 80 0 00 00 Fig.. Capacity curves for VR/VR8 series (DN) 8

DIMENSIONAL DRAWINGS VR1/VR81 AND VR0/VR80 Slow Open 18 1. 7. 8 Fast Open 1 Optional: characterized opening mechanism 1. Pressure switch inlet pressure 19. G 1/ G / Optional Pressure switch for intermediate pressure. 7 Fig.. Dimensional drawing VR1/VR81 (DN1) and VR0/VR80 series (DN0) 9

DIMENSIONAL DRAWINGS VR/VR8 Slow Open 18 1. 7. 8 Fast Open 1 Optional: characterized opening mechanism 18. Pressure switch inlet pressure 9. G 1 G 11/ Optional Pressure switch for intermediate pressure. 7 Fig.. Dimensional drawing VR/VR8 series (DN)

INSTALLATION IMPORTANT Read these instructions carefully. Failure to follow the intructions could damage the product or cause a hazardous condition. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. The installation has to be carried out by qualified personel only. Carry out a thorough checkout when installation is completed. CAUTION S S S Turn off gas supply before installation. Disconnect power supply to the valve actuator before beginning the installation to prevent electrical shock and damage to the equipment. Do not remove the seal over valve inlet and outlet, until ready to connect piping. WARNING Tightness test after installation S Spray all pipe connections and gaskets with a good quality gas leak detection spray. S Start the appliance and check for bubbles. If a leak is found in a pipe connection, remake the joint. A gasket leak can usually be stopped by tightening the mounting screws, otherwise, replace the gas valve. Electrical connection CAUTION S Switch off power supply before making electrical connections. S All wiring must comply with local codes, ordiances and regulations. Use lead wire which can withstand C ambient. Wiring Follow the instructions supplied by the appliance manufacturer. Refer to fig.. and fig. 7. S The valve must be installed so that the arrow on the valve points in the direction of the gas flow (gas pressure helps to close the valve). V1 1 N Mounting position The gas valve can be mounted plus or minus 90 degrees from the vertical. V Mounting location The distance between the gas valve and the wall/ground, must be at least 0 cm. Main gas connection 1. Take care that dirt does not enter the gas valve during handling. Remove the flanges from the valve.. Use a sound taper fitting with thread according to ISO 7--1 or new, properly reamed pipe free from swarf.. Apply a moderate amount of good quality thread compound to the pipe for fitting only, leaving the two end threads bare, PTFE tape may be used as an alternative.. Screw the flanges onto the pipes.. Ensure that the inlet and outlet flanges are in line and separate from each other enough to allow the valve to be mounted between the flanges without damaging the O --ring. 7. Place the O --ring. If necessary grease it slightly to keep it in place. 8. Mount the gas valve between the flanges using the bolts for each flange. 9. Complete the electrical connections as instructed in the Electrical Connection section. Fig.. Three pin electrical plug connector (according to ISO 00) for IP applications. V1 + V 1 Fig. 7. Three pin electrical plug connector (according to ISO 00) for DBI applications. V1 1 V Fig. 8. Connection diagram VR00 N 11

ADJUSTMENTS AND FINAL CHECKOUT The procedures described in this chapter are related to the adjustments on the main gas valve. For adjustments on the other additional functionalities (e.g. pressure switch), refer to the included instruction sheet of the product in question in the package. WARNING Adjustments must be made by qualified personel only. To ensure a safe closing of the valves, it is essential that voltage over the terminals of operators is reduced to0volts. Fig. 9. nd valve fast opening The following characteristics can be adjusted: flow rate Flow rate adjustment 1. Remove the cap from the cover.. Turn adjustment screw counter--clockwise to increase or clockwise to decrease the flow rate. nd valve (slow opening) The following characteristics can be adjusted: flow rate step pressure IMPORTANT To ensure a satisfactory setting of the valve the pressure drop over the valve should be at least % of the supply pressure or. mbar which ever is the greatest. Flow rate adjustment ( see fig. 9. and fig. ) 1. Remove the cap from top of the coil by loosening both screws.. Place a wrench on the adjustment hexagon nut.. Turn wrench counter--clockwise to increase or clockwise to decrease the flow rate.. Replace cap on top of the coil. Step pressure adjustment (see fig. 11. ) 1. Remove the cap from top of the coil by loosening both screws.. Place a screw driver in the slot of adjustment screw which is situated in center of the valve.. Turn screw driver counter--clockwise to increase or clockwise to decrease step pressure.. Replace cap on top of the coil. Fig.. Fig. 11. Fig. 1. 1

Opening speed adjustment (see fig. 1. ) Opening speed is factory set at customer settings, the adjustment screw is sealed. Poutlet Flow regulation Pressure tap points The VR00/VR800 series has a number of connections points for measuring pressure, mounting a pressure switch, or IP applications. The following pressures can be measured: 1. Inlet pressure. Interim pressure (pressure between the two shut--off valves). Outlet pressure The corresponding numbers can be found on the sides of the valve. Step pressure Opening speed regulation time Fig. 1. Characterized opening. Adjustment outlet pressure Disconnect pressure feedback connection (if applicable) Fig. 1. Pressure tap points Energize both electric operators in order to have gas input to burner. Check gas input to the appliance using a clocking gas meter or alternatively a pressure gauge connected to the outlet pressure tap. Remove pressure regulator cap screw to expose pressure regulator adjustment screw. Slowly turn adjustment screw with a small screw driver until the burner pressure required is recorded on the pressure gauge. Turn adjustment screw clockwise to increase or counter--clockwise to decrease gas pressure to the burner. For non--regulating mode (LP gas) turn adjustment screw clockwise until it stops. Replace pressure regulator cap screw. Connect pressure feedback connection (if applicable). Fig. 1. Pressure tap points Final checkout of the installation Set the appliance in operation after any adjustment and observe several complete cycles to ensure that all burner components function correctly. 1

CONSTRUCTION AND WORKING PRINCIPLES Servo pressure regulation working. The VR00/VR800 series servo regulated combination gas valves are x class A fail safe shut--off valves. The valve is opened by energizing the direct ON/OFF operators. Each operator consists of a coil and a stop sleeve assy. Inside the stop sleeve assy is a plunger which is connected to a rubber valve and which is able to move up and down and thus opening or closing the valve. The plunger is coated with an anti friction material. Flow regulation is done by adjustable plunger stroke. A strainer made out of AISI0 is incorporated between inlet flange and main body. The valve closing spring are made of AISI0. Seals and gaskets are manufactured out of hydrocarbon resistant NBR according to DIN and EN 91 The VR00/VR800 series features the positive servo system, i.e. the regulating valve is closed by spring pressure in the normal shut down position and can only be opened when gas pressure is sufficient to overcome the spring force. This valuable built in safety feature ensures the regulating valve will automatically close in the event of power or gas supply failure. The heart of the system is the servo pressure regulator which consists of a pressure relief valve integrated in a regulator diaphragm which is fitted above and controls the regulating valve. When both operators are energized, inlet gas flows through the servo orifice into the servo system and into the regulator. This servo gas moves the regulating diaphragm upwards enough to open the regulating valve. As soon as the regulating valve has opened, the outlet pressure generated by the VR00/VR800 series will be sensed by the regulator diaphragm via the feedback channel. When the force operated by the pressure is greater than that preset by the adjustment screw, the regulator valve opens relieving some of the working pressure. This reduces the force against the regulating valve spring allowing the regulating valve to close proportionately. Thus the regulating valve limits the outlet (or burner) pressure to the preset level. As a result, outlet pressure is continuously maintained by comparing it to the preset pressure and adjusting the position of the regulating valve accordingly. This means that a constant outlet pressure is maintained regardless of inlet pressure variations. At shut down, the small volume of working gas in the regulator and in the diaphragm chamber is dumped into the main outlet chamber. A reference pressure feedback connection further regulates the outlet pressure by compensating for differences in the air pressure in the combustion chamber and at the valve. If pressure regulation working is not needed, the regulator spring can be blocked by turning the adjustment screw down until it stops or the pressure regulation is removed. In these cases the full servo gas pressure opens the regulating valve as far as the pressure drop allows. Servo valve Fig. 1. Servo pressure regulator working 1

STANDARDS AND APPROVALS Standards The VR00/VR800 series servo regulated combination valves have been designed to meet the European Standard EN 1. The safety shut--off valve meets class A requirements. According to bending stress the combination valve meets the highest requirements. Regarding electric safety, the VR00/VR800 series can be used in appliances according to European Standard for a household electrical requirements EN 0 series and industrial applications. The VR00/VR800 series also meet all Electro Magnetic Compatibility standards for non--industrial and industrial appliances. Approvals The VR00/VR800 series servo regulated class A combination valves conform with the following EC--directives: Gas Appliance Directive (90/9/EEC) PIN: 00AT1198 Low Voltage Directive (7//EEC) Electro Magnetic Compatibility Directive (89//EEC) The fact that the VR00/VR800 series are certified to European Standard EN 1 means that this series meets more stringent requirements than laid down in the essential requirements stated in the directives and therefore meets the requirements in all EC and EFTA countries. Details can be found in the Approvals List. The registration number specific for each O.S. number is mentioned on the label of the control. 1

ORDERING INFORMATION Ordering Specification number VR xx A A 1xxx VR: class A combination gas valve Specification number : line voltage 8: low voltage 1: 00 mbar max. inlet pressure : 0 mbar max. inlet pressure Straight flange connection 1 DN1 (1/ ) 0: DN0 (/ ) :DN (1 ) NOTE: Flanges to be ordered separately (see Flange kits ) Pressure switch (Min. C0VR00 serie) is standard included C097 on request available Characteristics nd valve A: Second valve fast opening, DBI applications B: Characterized opening for DBI applications E: Second valve fast opening, IP applications F: Characterized opening for IP applications Type of pressure regulator A: Pressure regulator F: Integrated gas/air 1:1 with venturi mixing unit. M: Modureg P: Hi--Lo V: Gas/air 1:1 Fig. 17. Ordering information VR00/VR800 series combination valves 1

How to select your valve Standard the VR00/VR800 series servo regulated combination valves are equipped with two main valves V1 and V. Safety valve V1 is always fast opening/closing. The second valve (V) can be either fast or slow (= with flow regulation and adjustable opening). At the main body flange connections (8) are provided to mount either pressure switches, a pilot valve, or a VPS + pressure switch. These additional functionalities can be mounted on various positions of the main body of the VR00. X Y W V VQAB09 -VWXY O.S. number Position specification V W Y X Table 8. VR00 series positions and additional fuctionalities chart Type Code Positions V W X Y C0VR000 (... 0 mbar) 1 D D D D C0VR01 (0... 1 mbar) D D D D C0VR000 (0...00 mbar) D D D D A01A + C08A (wired) D D Use the digits behind the OS number to specify which option you need in which position. Example: With a... 0 mbar pressure switch on position V, the full O.S. number will be VRAB09--00. If you do not want any additional option the O.S. number will be VRAB09--0000 17

REPLACEMENTS 1 7 8 1 11 1 1 1 EV 1 EV 9 18 17 1 Coloured Transparent Transparent Coloured Fig. 18. Exploded view of the VR00/VR800 series 18

Replacement of coils (see fig 18. ) WARNING Disconnect power supply before 1. Remove screws (1) on top of cover.. Lift cover ().. Remove three screws () hydraulic unit ().. Lift hydraulic unit ().. Remove mounting bracket ().. Remove blade spring (). 7. Loosen and remove screw first operator (7). 8. Remove top plate (8). 9. Disconnect leads coils (9) from circuit board ().. Lift coil assy (11) from operator (1). 11. Remove flux tube (1) from coil assy. 1. Remove coil (1) from tube (1). 1. Place new coil in tube with leads on top and in slot of the tube. 1. Replace flux tube into coil assy from top. 1. Place assy on operator with leads on top and in slot of operator. 1. Connect leads. 17. Replace top plate and fasten it with screw. 18. Replace blade spring. 19. Replace mounting bracket. 0. Replace cap or hydraulic unit and fasten it with screws. 1. Check if seal cover is mounted correctly and correct if needed.. Replace cover and fasten it with screws. Remark: for fast openening versions, operations and are not applicable. Replacement of hydraulic slow open unit (see fig 18. ) WARNING Disconnect power supply before 1. Remove screws (1) on top of cover.. Lift cover ().. Remove three screws () from hydraulic unit ().. Lift hydraulic unit ().. Place new hydraulic unit and fasten it with screws.. Check if seal cover is mounted correctly and correct if needed. 7. Replace cover and fasten it with screws. Replacement of pressure regulator (see fig 18. ) WARNING Disconnect power supply before 1. Disconnect pressure feedback connection (if present).. Loosen and remove screws (17) from regulator (18).. Lift regulator (18).. Remove rubber gasket (19).. Place new gasket.. Place new regulator and fasten it with screws. 7. Reconnect pressure feedback connection. 8. Reconnect pressure and power supply. 9. Energize valve.. Check for leakage. Replacement of rectifier board (see fig 18. ) WARNING Disconnect power supply before 1. Remove screws (1) on top of cover.. Lift cover ().. Disconnect leads coils (9) from circuit board ().. remove screw (1) from printed circuit board.. Lift printed circuit board.. Place new printed circuit board. 7. Replace and fasten screw in printed circuit board. 8. Connect leads. 9. Check if seal cover is mounted correctly and correct if needed.. Replace cover and fasten screws. 19

REPLACEMENT PARTS AND ACCESSORIES IMPORTANT When ordering replacement coils include the complete valve O.S. number, in order to provide the coil with proper product identification sticker. Model WARNING S S S S S S Take care that only qualified persons carry out the installation of parts, accessories, and add on components. Follow the installation instructions included in the package. Check that the selected part, accessory or add on component is the correct one for the application in question. Replace the old gaskets with the new ones supplied in the package and check for leakage when the supply is switched on again. After installation and/or replacement has been completed, a gas leak test must be carried out. Also check the gas valve for satisfactory operation after fitting accessories. Table 9. Coils for VR00/VR800 series Order Rated Packing number Voltage qty (Vac) 00 mbar BBE000 0 D 1 V1 BBE001 1 D 1 DN1 BBE00 D 1 DN0 BBE000 0 D 1 V BBE001 1 D 1 Table. Rectifier boards for VR00/VR800 series Model Order number Rated Voltage Packing qty (Vac) IP application CSE00 0 1 DN1 DN0 CSE00 1 1 DN CSE008 1 DBI application CSE00 0 1 DN1 DN0 CSE00 1 1 DN CSE007 1 Model DN0 DN Table 11. Slow open units Order number GFO0001 Table 1. Regulators Regulator type Range O.S.number Standard d regulator.... 0 V0E 0... 7 V0E 11... 0 V0E 1119 High - Low regulator... 00 VA 0... 7 VA 1 8... 0 VA 00 BBE00 D 1 BBE00 0 D 1 V1 BBE00 1 D 1 DN BBE007 D 1 BBE00 0 D 1 V BBE00 1 D 1 BBE007 D 1 Home and Building Control Combustion Controls Center Europe Honeywell BV Honeywell UGV S.r.l. Phileas Foggstraat 7 Via Ferrero 1 781 AJ Emmen 090 Cascine -Vica Rivoli (TO) The Netherlands Turin, Italy Tel: +1 ( -)91 9911 Tel: +9 (011)97 8 11 Fax: +1 ( -)91 900 Fax: +1 (011)97 8 http://europe.hbc.honeywell.com 0