Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

Similar documents
3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

3M Cold Shrink QT-III Silicone Rubber Termination

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

Cold Shrink QS T Trifurcating Transition Splice Kit

QT-III Cold Shrink Silicone Rubber

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

3M Mechanical Shearbolt Connectors, QCI Series

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

ELB ES. Product Installation Instructions

Cable Ties. Data Sheet

Branch Splice QS-2001B

3M Locator Plate

3M Cold Shrink Splice Kits, QS T Series

Cold Shrink Silicone Rubber Termination Kit QT-III 7620-S, 7690-S and 7680-S Series kv

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

3M Locator Plate

3M Cross-Connect Cabinets 4220SVC and 4220SVE Tall Skirt Installation Guide

3M Products for Electrical Networks Wind Farm Capabilities. Leading Edge. Electrical Solutions for. Wind Farms

3M Electrical Tapes Product Selection Guide. Insulate & Protect. with Quality Tapes. Preliminary

3 Reenterable Encapsulated PST Dome Closure

ELB ELB

3M Closure System 2-Type Cover (505)

SLiC Aerial Terminal and Spiral End Seal for use with AMP* Quiet Front Terminal Blocks

Data Sheet July For RoHS information, please visit

3M Ladder Kit 3M710/MS 2 -TMK-LK

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900 µm Instructions

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900-µm. Instructions. October C

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

3M Textool Test and Burn-In Sockets for 1.0 mm Area Array Packages Including Ball Grid Array and Land Grid Array

3M Electrical Markets Division. Rubber, Mastic and Specialty Tapes Application Guide. Choose the. Right Tape. for your. Electrical Project

710 Splicing Rig. Instructions. January E

HVS S 15kV Class

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

Installation Instructions

3M No Polish LC/APC Connector SM, Angle Splice, 250/900 µm 8830-APC/AS

DISTRIBUTION CONNECTORS SECTION DF COMPRESSION TERMINALS. Aluminum Compression Lugs Aluminum Bi-Metal Pin Terminals Copper Compression Lugs

3M Cable Ties Product Guide. Made in USA. & Plenum Rated

3M Pleated Foil I/O Cable Assemblies MDR Series

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

3M Mini D Ribbon (MDR) Cable Assembly.050 High Speed Video Data Transmission System, 50 Position 14X50-SZWB-XXX-0NC

High Voltage Joints and Terminations up to 72,5 kv 145 kv

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

QTII (X) Series Silicone Rubber Cold Shrink Termination Kits

3M No Polish LC Connector SM and MM, Flat Splice, 250/900 µm

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

3M Fiber Dome Closure FDC 10

(K),(M)430TB/G Up to 36 kv

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

CP 600V Cable Protectors

I nstallation I nstruction Heatshrink Term ination For 3 Core Polym eric Cables 7.2 kv to 3 6 kv

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

8400 Series Fiber Distribution System

Installation Instruction EPP /92

3M Cushion-Mount Plus Plate Mounting Tapes with Easy Mount Adhesive

Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

Repair Method for 3M Resilient Floor Protection System

C Power Connection Kit

Door Edge Protection Film 36 inch

3M Cold Shrink QT-III Silicone Rubber Skirted and Inverted Skirted Termination Kits, 7640-S, 7650-S and 7660-S Series 5, 8, 15, 25/28 and 35 kv

K SERIES PUSH ON & BULLET TERMINALS

Installation Instructions

GM Specification Annual Test Data

SLiC Aerial Closures

GM Specification Annual Test Data

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

Model 1100B CHG Terminator. Installation Instructions

3M Connector System 0.050" x 0.100" Pitch. 3M Tripolarized Wiremount Socket - Series 820 3M 4-Wall, Tripolarized Header - Series 810

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

3M CP2 Press-Fit Headers and Sockets, 2 mm

Transcription:

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief) Instruction Sheet IEEE Std. No. 48 1990 Class 1 Termination 5/8.7 kv Class 95 kv BIL Kit Contents: 3 Hi K, Tracking Resistant, Silicone Rubber Terminations 3 Preformed Ground Braids 3 Constant Force Springs 6 Strips Sealing Mastic (black with white release liners, bagged) 1 3M Cable Preparation Kit CC 2 1 Instruction Sheet Kit Selection Chart NOTE: Final determination factor is cable insulation diameter. Kit Number Primary Insulation O.D. Range Jacket O.D. Range Conductor Size Range (AWG & kcmil) 5 kv 8.7 kv 7621 T 95 7622 T 95 0.48 " 0.89 " (8 22,6 mm) 0.64 " 1.08 " (16,3 27,4 mm) 0.65 " 1.05 " (16,6 26,8 mm) 0.97 " 1.48 " (24,6 37,7 mm) 2 3/0 4 2/0 4/0 400 3/0 300 7624 T 95 0.83 " 1.53 " (21,1 38,9 mm) 1.12 " 1.87 " (28,4 47,5 mm) 500 750 350 700 7625 T 95 1.05 " 1.80 " (26,7 45,7 mm) 1.39 " 2.40 " (35,2 61,0 mm) 700 1500 600 1250 Tape Shield (page 2) Wire Shield (page 6) UniShield (page 11) 3M Silicone Rubber Indoor Termination Kits QT-III for Single Conductor Tape Shield, Wire Shield and UniShield Cables 7622 T 95 7624 T 95 7621 T 95 7625 T 95 78-8126-9910-2 m CAUTION Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling high-voltage electrical equipment. De-energize and ground all electrical systems before installing product.

Correct Installation of Termination Vinyl Tape Marker Ridge at End of Stress Controlling Compound Ridge at End of Cable Insulation Shield (Semi-Con) Semi-Con Insulation Shield Stress Controlling Compound Cable Insulation Conductor Silicone Top Seal Instructions for Tape Shielded Cable A. Prepare Cable 1. Check to be sure cable size fits within kit range as shown in Table 1 (cover page). 2. Prepare cable using dimensions shown in (Figure 1). Be sure to allow for depth of terminal lug. If necessary to prevent tape shield from unrolling, TEMPORARILY hold down edge with a single wrap of vinyl electrical tape. NOTE: Provide an additional 1/4" (6 mm) exposed conductor to account for growth during crimping of ALUMINUM lugs or connectors. 3. Select one of six mastic strips from kit and remove white release liners. Using light tension, wrap a band of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 1). Cut off excess. Figure 1 Jacket Removal Length Depth Of Terminal Lug + Growth Allowance 6 " (152 mm) 2 " (63,5 mm) 1/4" (6 mm) 1 1/4" (32 mm) Semi-Con Tape Shield 1 ST Mastic Seal Cable Jacket 2

B. Install Ground Braid 1. Position pre-formed ground braid with short tail over tape shield directly adjacent to cable jacket cut edge. Position long tail of ground braid, extending over cable jacket with solder block over mastic strip (Figure 2). Secure ground braid to cable jacket 3 " (89 mm) from cable semi-con edge using vinyl tape (Figure 2). NOTE: Position vinyl tape with care, it also serves as a marker for positioning the jacket seal. Figure 2 4 " (114 mm) Semi-Con Edge Tape Shield Ground Braid Cable Jacket Edge Solder Block 1 ST Mastic Strip Vinyl Tape Marker 2. Wrap ground braid around cable tape shield one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. Wrap spring in same direction as ground braid (Figure 3). Cinch (tighten) the spring after wrapping the final winding. 3. Select second mastic strip from kit and remove white release liners. Apply a second mastic band over solder block on ground braid and previously applied mastic (Figure 3). Cut off excess. Figure 3 Constant Force Spring Tape Shield Ground Braid 1 ST Mastic Strip Solder Block 2 ND Mastic Strip Trim Cable Tape Shield Ground Braid Leg 3

B. Install Ground Braid (continued) 4. Wrap two half-lapped layers of vinyl tape around mastic seal, constant force spring and exposed tape shield (Figure 4). NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 3/4" (19 mm) must be exposed. Take care to leave part of ground braid exposed between tape marker and mastic. SPECIAL NOTE FOR CLOTH OR PAPER SEMI-CON INSULATION SHIELD In cables with cloth or paper semi-conductive shields it is recommended the shield be over wrapped with one half-lapped layer of highly stretched semi-conductive rubber tape such as Scotch Electrical Semi-Conducting Tape 13. Figure 4 Semi-Con Tape Shield Constant Force Spring Two Half-Lapped Layers Vinyl Tape Mastic Seal Vinyl Tape Marker C. Install Lug or Connector 1. Check to insure 3M Termination Assembly QT-III fits over the selected lug. If lug (Figure 5) will not fit through the termination core, clean the insulation (per Step D.) and slide termination on cable before installing lug. Do not remove core at this time. Figure 5 Clearance Connector/Lug NOTE: Refer to pages 15 17 for 3M connector/lug crimping information. 2. Position connector/lug and crimp according to manufacturer s directions. Remove excess oxide inhibitor and sharp crimp flashings following crimping. D. Clean Cable Insulation and Lug Barrel Using Standard Practice 1. Wipe the cable insulation with one of the solvent saturated pads from the 3M Cable Preparation Kit CC-2. Do not allow solvent to touch semi-con insulation shield! 2. If abrasive must be used: a. Use on insulation only. Do not use abrasive on semi-con insulation shield! b. Use only aluminum oxide abrasive; grit 120 or finer, included in 3M Cable Preparation Kit CC-2. c. Be careful not to reduce the cable insulation diameter below that allowed by the kit. 4

E. Install Termination 1. Side the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 6). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 6) NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue supporting the assembly. Do not push or pull the termination assembly while unwinding the core. Figure 6 Counter-Clockwise Vinyl Tape Marker NOTE: The material being removed at this step is mixed polymers and can be recycled with waste. 2. When using a short barrel lug or connector on smaller size cable it may be necessary to trim any excess termination insulator from the lug or connector. 3. Connect ground braid to system ground according to standard practice. 5

Correct Installation of Termination Vinyl Tape Marker Ridge at End of Stress Controlling Compound Ridge at End of Cable Insulation Shield (Semi-Con) Semi-Con Insulation Shield Stress Controlling Compound Cable Insulation Conductor Silicone Top Seal Instructions for Wire Shielded Cable A. Prepare Cable 1. Check to be sure cable size fits within kit range as shown in Table 1 (cover page). 2. Prepare cable using dimensions shown in (Figure 7 and Figure 8). Be sure to allow for depth of terminal lug. NOTE: Provide an additional 1/4" (6 mm) of exposed conductor to account for growth during crimping of ALUMINUM lugs or connectors as follows: Figure 7 Jacket Removal Length Depth Of Terminal Lug + Growth Allowance 6" (152 mm) 2 " (63,5 mm) Cable Jacket Semi-Con Shield Wires 6

A. Prepare Cable (continued) 3. Bend leading 1" (25 mm) of exposed shield wires back upon themselves to jacket edge (Figure 8). Figure 8 1" (25 mm) 2" (51 mm) Semi-Con Shield Wires Cable Jacket Edge B. Install Ground Braid 1. Select one of six mastic strips from kit and remove white release liners. Using light tension, wrap a band of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 9). Cut off excess. Figure 9 1/4" (6 mm) 1 ST Mastic Seal Cable Jacket Semi-Con 2. Position pre-formed ground braid with short tail over wire shield directly adjacent to cable jacket cut edge. Position long tail of ground braid, extending over cable jacket with solder block over mastic strip (Figure 10). Secure ground braid to cable jacket 3 " (89 mm) from cable semi-con edge using vinyl tape (Figure 10). NOTE: Position vinyl tape with care, it also serves as a marker for positioning the jacket seal. Figure 10 4 " (114 mm) Semi-Con Edge Shield Wire Ground Braid Cable Jacket Edge Solder Block 1 ST Mastic Strip Vinyl Tape Marker 7

B. Install Ground Braid (continued) 3. Wrap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. Wrap spring in same direction as ground braid (Figure 11). Cinch (tighten) the spring after wrapping the final winding. 4. Select second mastic strip from kit and remove white release liners. Apply a second mastic band over solder block on ground braid and previously applied mastic (Figure 11). Cut off excess. Figure 11 Constant Force Spring Shield Wires Ground Braid 1 ST Mastic Strip Solder Block 2 ND Mastic Strip Trim Cable Wire Shield Ground Braid Leg 5. Wrap two half-lapped layers of vinyl tape around mastic seal, constant force spring and exposed shield wires (Figure 12). NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 3/4" (19 mm) must be exposed. SPECIAL NOTE FOR CLOTH OR PAPER SEMI-CON INSULATED SHIELD In cables with cloth or paper semi-conductive shields, it is recommended the shield be over wrapped with one half-lapped layer of highly stretched semi-conductive rubber tape such as Scotch Electrical Semi-Conducting Tape 13. Figure 12 1 1/4 " (32 mm) Semi-Con Shield Wires Constant Force Spring Two Half-Lapped Layers Vinyl Tape Mastic Seal Vinyl Tape Marker 8

C. Install Lug or Connector 1. Check to insure 3M Termination Assembly QT-III fits over the selected lug. If lug (Figure 13). will not fit through the termination core, clean the insulation (per Step D.) and slide termination on cable before installing lug. Do not remove core at this time. Figure 13 Clearance Connector/Lug NOTE: Refer to pages 15 17 for 3M connector/lug crimping information. 2. Position connector/lug and crimp according to manufacturer s directions. Remove excess oxide inhibitor and sharp crimp flashings following crimping. D. Clean Cable Insulation and Lug Barrel Using Standard Practice 1. Wipe the cable insulation with one of the solvent saturated pads from the 3M Cable Preparation Kit CC-2. Do not allow solvent to touch semi-con insulation shield! 2. If abrasive must be used: a. Use on insulation only. Do not use abrasive on semi-con insulation shield! b. Use only aluminum oxide abrasive; grit 120 or finer, included in 3M Cable Preparation Kit CC-2. c. Be careful not to reduce the cable insulation diameter below that allowed by the kit. E. Install Termination 1. Side the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 14). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 14) NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue supporting the assembly. Do not push or pull the termination assembly while unwinding the core. Figure 14 Counter-Clockwise Vinyl Tape Marker NOTE: The material being removed at this step is mixed polymers and can be recycled with waste. 2. When using a short barrel lug or connector on smaller size cable it may be necessary to trim any excess termination insulator from the lug or connector. 3. Connect ground braid to system ground according to standard practice. 9

Correct Installation of Termination Vinyl Tape Marker Ridge at End of Stress Controlling Compound Ridge at End of Cable Insulation Shield (Semi-Con) Semi-Con Stress Controlling Compound Cable Insulation Conductor Silicone Top Seal Instructions for UniShield Cable A. Prepare Cable 1. Check to be sure cable size fits within kit range as shown in Table 1 (cover page). 2. Prepare cable using dimensions shown in (Figure 15). Be sure to allow for depth of terminal lug. NOTE: Provide an additional 1/4" (6 mm) of exposed conductor to account for growth during crimping of ALUMINUM lugs or connectors as follows: 3. Pull shield wires through semi-conductive jacket to leading edge of constant force spring (Figure 15). Figure 15 Depth Of Terminal Lug + Growth Allowance 4 3/4" (121 mm) Semi-Conductive Jacket Constant Force Spring Shield Wires 10

A. Prepare Cable (continued) 4. Remove constant force spring. Bend shield wires back upon cable jacket 1" (25 mm). Cut excess shield wire and discard (Figure 16). Figure 16 Depth Of Terminal Lug + Growth Allowance 6 (152 mm) 1 1/4 (32 mm) Semi-Conductive Jacket Fold Back Shield Wires 5. Remove semi-conductive jacket to dimension shown in Figure 17. NOTE: To ease jacket removal, install constant force spring as shown in Figure 17 and ring cut 80% through jacket. Remove jacket sections by pulling against constant force spring. DO NOT BELL SEMI-CON JACKET. Remove constant force spring. Some UniShield cables feature dual-layer semi-conductive jackets. Both layers must be removed during cable preparation. Figure 17 Depth Of Terminal Lug + Growth Allowance 3 (89 mm) 2 (63,5 mm) 1 1/4 (32 mm) Semi-Conductive Jacket Cut Line Constant Force Spring Fold Back Shield Wires B. Install Ground Braid 1. Select one of six mastic strips from kit and remove white release liners. Using light tension, wrap a band of mastic around the cable semi-conductive jacket 1/4 (6 mm) from shield wires (Figure 18). Cut off excess. Figure 18 1/4 (6 mm) Semi-Con Shield Wires 1 ST Mastic Seal 11

B. Install Ground Braid (continued) 2. Position pre-formed ground braid with short tail directly over cut edge of folded back shield wires. Position long tail of ground braid, extending over cable semi-conductive jacket with solder block over mastic strip (Figure 19). Secure ground braid to cable semi-conductive jacket 3 " (89 mm) from cable semi-con edge using vinyl tape (Figure 19). NOTE: Position vinyl tape with care, it also serves as a marker for positioning the jacket seal. Figure 19 4 " (114 mm) Solder Block 1 ST Mastic Strip Vinyl Tape Marker Semi-Con Edge Shield Wire Ground Braid 3. Wrap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. Wrap spring in same direction as ground braid (Figure 20). Cinch (tighten) the spring after wrapping the final winding. 4. Select second mastic strip from kit and remove white release liners. Apply a second mastic band over solder block on ground braid and previously applied mastic (Figure 20). Cut off excess. Figure 20 Constant Force Spring Shield Wires Ground Braid 1 ST Mastic Strip Solder Block 2 ND Mastic Strip Trim Cable Wire Shield Ground Braid Leg 12

B. Install Ground Braid (continued) 5. Wrap two half-lapped layers of vinyl tape around mastic seal, constant force spring and exposed shield wires (Figure 21). NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 3/4 (19 mm) must be exposed. Figure 21 1 1/4 (32 mm) Semi-Con Shield Wires Constant Force Spring Two Half-Lapped Layers Vinyl Tape Mastic Seal Vinyl Tape Marker C. Install Lug or Connector 1. Check to insure 3M Termination Assembly QT III fits over the selected lug. If lug (Figure 22) will not fit through the termination core, clean the insulation (per Step D.) and slide termination on cable before installing lug. Do not remove core at this time. Figure 22 Clearance Connector/Lug NOTE: Refer to pages 15 17 for 3M connector/lug crimping information. 2. Position connector/lug and crimp according to manufacturer s directions. Remove excess oxide inhibitor and sharp crimp flashings following crimping. D. Clean Cable Insulation and Lug Barrel Using Standard Practice 1. Wipe the cable insulation with one of the solvent saturated pads from the 3M Cable Preparation Kit CC 2. Do not allow solvent to touch semi-con insulation shield! 2. If abrasive must be used: a. Use on insulation only. Do not use abrasive on semi-con insulation shield! b. Use only aluminum oxide abrasive; grit 120 or finer, included in 3M Cable Preparation Kit CC 2. c. Be careful not to reduce the cable insulation diameter below that allowed by the kit. 13

E. Install Termination 1. Side the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 23). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 23) NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue supporting the assembly. Do not push or pull the termination assembly while unwinding the core. Figure 23 Counter-Clockwise Vinyl Tape Marker NOTE: The material being removed at this step is mixed polymers and can be recycled with waste. 2. When using a short barrel lug or connector on smaller size cable it may be necessary to trim any excess termination insulator from the lug or connector. 3. Connect ground braid to system ground according to standard practice. 14

Tooling Index 30014 thru 30045 One hole Lug and Crimping Information for 3M Scotchlok 31036 thru 31068 One hole long barrel Copper Lugs 31145 thru 31178 Two hole Cable Size AWG/ kcmil Stud Size (in.) 3MScotchlok Copper Lug Number Burndy Corporation CRIMPING TOOL-DIE SETS (NUMBER OF CRIMPS) Thomas & Betts Corporation Square D Co. Anderson Div. MD6 MY29 Y34A Y35, Y39, Y45*, Y46* TBM 5 TBM 8 TBM 15 VC6 3, VC6 FT** 6 10 1/4 5/16 30014 30015 30016 6AWG U5CRT Blue Blue Universal 4 10 1/4 30018 30019 30021 W161 4AWG A4CR U4CRT Grey Grey Universal 2 1/4 5/16 30022 30023 30024 W162(2) 2AWG A2CR U2CRT(2) Brown Brown 33 Universal(2) 1 5/16 30027 30028 1AWG A1CR U1CRT(2) Green Green 37 Universal(2) 1/0 5/16 30031 30032 W163(2) 1/0 A25R U25RT Pink(2) Pink(2) 42H(2) Universal 2/0 30036 31036 W241(2) W241 2/0 2/0(2) A26R A26R(2) U26RT(2) U26RT Black(2) Black Black(2) Black 45 45(2) Universal Universal(2) 3/0 30041 31041 W243(2) W243 3/0 3/0(2) A27R A27R(2) U27RT(2) U27RT Orange(2) Orange Orange(2) Orange 50 50(2) Universal(2) Universal 4/0 30045 31045 31145 BG BG(4) BG(4) 4/0 4/0(2) 4/0(2) A28R(2) U28RT(2) U28RT U28RT Purple(2) Purple Purple Purple(2) Purple Purple 54H(2) 54H 54H Universal(2) Universal Universal 250 31049 31149 W166(4) 250(2) A29R(2) U29RT Yellow(2) Yellow(2) 62(2) Universal(2) 300 31053 31153 A30R(2) U30RT White 66 Universal 350 31056 31156 A31R(2) U31RT Red(4) 71H(4) 400 31060 31160 A32R(2) U32RT Blue(4) 76H(4) 500 5/8 31066 31067 31166 A34R(2) U34RT Brown(4) 87H(4) 600 31068 31168 U36RT Green(4) 94H(4) 750 31172 1000 31178 Y39, Y45, Y46 U39RT(5) Y45: S44RT(6) Y46: P44RT(6) 106H(4) 125H(4) * Y45 and Y46 accept all Y35 dies ( U series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter. ** Anderson VC6 3, VC6 FT, VC8C and Burndy Y1000 require no die se 15

Tooling Index Lug and Crimping Information for 3M Scotchlok Copper/Aluminum Lugs 40016 thru 40079 One hole 40132 thru 40178 Two hole CRIMPING TOOL-DIE SETS (NUMBER OF CRIMPS) Cable Size AWG/ kcmil Stud Size (in.) Scotch- 3M Scotchlok Lug Number Burndy Corporation MD6 MY29 Y34A Y35, Y39, Y45*, Y46* Thomas & Betts Corporation Y1000* TBM 5 TBM 8 TBM 12 TBM 15 Square D Co. Anderson Div. VC6 3** VC6 FT** ITT Blackburn Co. Kearny Nat l Div. VC8C** OD58 TYPE O 6 5/16 40016 W161 6AWG A6CAB U6CABT Grey Grey 29 BY19 J 4 5/16 40020 W162 4AWG A4CAB U4CABT Green(2) Green(2) 37 BY53 P 2 40024 40025 W163 W163 2AWG 2AWG A2CAB A2CAB U2CABT U2CABT Pink(2) Pink(2) Pink(2) Pink(2) 42H(2) 42H(2) BY23 BY23 1 40028 40029 W163 W163 1AWG 1AWG A1CAR A1CAR U1CART U1CART Gold(2) Gold(2) Gold(2) Gold(2) 45 45 BY23 BY23 1/0 40032 40033 40132 W241 W241 W241 1/0 1/0 1/0 A25AR A25AR A25AR U25ART U25ART U25ART Tan(2) Tan(2) Tan(2) Tan(2) Tan(2) Tan(2) 50 50 50 BY25 BY25 BY25 5/8 1 5/8 1 5/8 1 2/0 40037 40137 BG(4) BG(4) 2/0 2/0 A26AR(2) A26AR(2) U26ART(2) U26ART(2) Olive(2) Olive(2) Olive(2) Olive(2) 54H(2) 54H(2) (2) (2) BY31C BY31C 5/8 1 5/8 1 3/0 40041 40141 W166(4) W166(4) 3/0 3/0 A27AR(2) A27AR(2) U27ART(2) U27ART(2) Ruby(2) Ruby(2) Ruby(2) Ruby(2) 60(2) 60(2) (2) (2) 737 737 4/0 5/8 40045 40046 40145 W660(4) W660(4) W660(4) 4/0 (2) 4/0 (2) 4/0 (2) A28AR(2) A28AR(2) A28AR(2) U28ART(2) U28ART(2) U28ART(2) White(4) White(4) White(4) 66(4) 66(4) 66(4) (2) (2) (2) BY35C(4) BY35C(4) BY35C(4) 840(4) 840(4) 840(4) 250 5/8 40049 40050 40149 W249 W249 W249 A29AR(2) A29AR(2) A29AR(2) U29ART(2) U29ART(2) U29ART(2) 71H(4) 71H(4) 71H(4) 71H(2) 71H(2) 71H(2) 300 40053 40153 A30AR(2) A30AR(2) U30ART(2) U30ART(2) 76H(4) 76H(4) 76H(2) 76H(2) 350 5/8 40056 40057 40156 U31ART(2) U31ART(2) U31ART(2) 87H(4) 87H(4) 87H(4) 87H 87H 87H 400 40160 U32ART(4) 94H(4) 94H(4) (2) 500 5/8 40067 40166 U34ART(4) U34ART(4) 106H(4) 106H(4) 106H 106H (2) (2) 600 40170 U36ART(4) 115H 750 5/8 40073 40172 U39ART(4) U39ART(4) 125H(5) 125H(5) 1000 5/8 40079 40178 S44ART(4) S44ART(4) 140H(4) 140H(4) * Y45 and Y46 accept all Y35 dies ( U series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter. ** Anderson VC6 3, VC6 FT, VC8C and Burndy Y1000 require no die set. 16

Tooling Index Crimping Information for 3M Stem Connectors Copper/Aluminum Conductor Size 3M Connector Number CRIMPING TABLE FOR 3M STEM TYPE CONNECTOR Recommended Crimping Tools Manufacturer Mech. Tool Die (No. Crimps) Hydraulic Die (No. Crimps) Burndy MD6 BG(4), W243(4) Y35, Y39, Y45** U25ART(2), U243(2) 2 Solid SC0002 Kearny 0 51, 0 52 5/8 1 (4) 12, 20, 40, Ton 5/8 1(4) 1, 2 SC0001 1/0 SC0010 T & B TBM 8 Olive(2) TBM 15 50(2)* Anderson VC6 Universal(2) Burndy MD6 W669(0) 840(5)* Y35, Y39, Y45** U28ART(2) 2/0 SC0020 Kearny 0 51, 0 52 840(5)* WH 1, WH 2 840(2) 3/0 SC0030 4/0 SC0040 T & B TBM 8 White(4) TBM 15 66 Anderson - VC6 Universal(2) * Y45 and Y46 accept all Y35 dies ( U series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter. ** Anderson VC6 3, VC6 FT, VC8C and Burndy Y1000 require no die set. 17

3M, Scotch and Scotchlok are trademarks of 3M Company. UniShield is a trademark of General Cable Technologies. Important Notice All statements, technical information, and recommendations related to 3M s products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use. Any statements related to the product which are not contained in 3M s current publications, or any contrary statements contained on your purchase order shall have no force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M. Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture at the time of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of the legal theory asserted. 3 Electrical Markets Division 6801 River Place Blvd. Austin, TX 78726-9000 800-245-3523 Fax 800-245-0329 www.3m.com/electrical Please Recycle. Printed in USA. 3M 2008. All Rights Reserved. 78-8126-9910-2