Products Tde Macno. User s Manual BRAKING UNIT. Cod. MP00401E00 V_1.0

Similar documents
SINUS K 13. ACCESSORIES Braking resistors APPLICATION TABLES 78/160 INSTALLATION INSTRUCTIONS

Features IN THIS CHAPTER

Electronic Ballast EVG 2000-T

1.5KW DC-DC Converter Specification

Regenerative DC Common Bus Supply

GTS 15/25/40/50/60/75/90/120A

Quick guide. Plug-in fans GPPM with FC101_106 August 2014

STR3. Step Motor Drive. User Manual

J1000 D E F I 1000 J1000 J1000 J1000 J1000

Brake Chopper BC BC 4.1. Instruction and Operation Manual

R820 REV2 SERIES SCR POWER CONTROLS NOVEMBER 2017

RVS-AX Instruction Manual

AT30 SERIES BATTERY CHARGER

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

TECHNICAL DATA SHEET KVA UPS Systemss

Insulation method Zero-cross function Indicators Applicable output load Model number Phototriac coupler Yes Yes (See page 6) Main Circuit

MX431 Generator Automatic Voltage Regulator Operation Manual

GTS-L4 5 / 10 / 15 TECHNICAL DATA

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

EPS/ELA-Series User Manual EPS/ELA 250W

GTZ 25 / 40 / 55. TECHNICAL DATA General features. Category of use: AC51, AC53a

American Traction Systems

Models. Output current max.* Output Power max. Low Line : VAC High Line: VAC 24 VDC / 12 A 240 W. Back up battery

SD700FR. Regenerative Active Front End VARIABLE SPEED DRIVES POWER ELECTRONICS / SD700 SERIES 4 QUADRANT. icool

POWER kva

EFFEKTA Power Supplies

(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2

SOLID STATE POWER CONTROLLERS ACL-series AC1-series AC3-series ACF3-series DAC3- series

The information in this chapter will enable you to: 90VAC to 50/60 Hz

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Output Current Input Current Over Load VDC VDC ma ma(typ.) ma(typ.) VDC μf %

Technical Data Sheets

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

User Guide. Mini Maestro. Variable Speed Drive for Permanent-magnet DC Servo-motors. Part Number: Issue: 5.

GTS-L 5 / 10 / 15 POWER SOLID STATE RELAYS WITH LOGIC CONTROL TECHNICAL DATA

4HS MultiPower Submersible Pumps. Installation and Operating Manual.

SOLSTART Instruction Manual

World Class Power Solutions. Rectifiers. For Stationary Battery Systems in Nuclear Power Plants

Technical Data Sheets

Application Note. Common Bussing AC Drives. For 650 and 690+ series drives APP-AC-03

Mini Maestro Drive. User Guide. Variable Speed Drive for Permanentmagnet DC Servo-motors. Part Number: Issue Number: 4

ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/ V(45kW)

SR3-mini. Step Motor Drive User Manual. AMP & MOONS Automation

PowerOhm Installation Manual for LG ATV Series Braking Modules

TRIPS AND FAULT FINDING

CX-SERIES ADVANCED BATTERY CHARGER

POWER SUPPLIES. Control Transformers p8-1 Modular Power Supplies p8-2 Switching Power Supplies p8-3 Automatic Battery Chargers p PAGE

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

POWER kva

Indice Pag. 1. Indice

Features. Description. Table of Contents

TECHNICAL DATA SHEET B8033FXS kva 3Ph(In) 3Ph(Out)

FR-BU2-1.5K to 55K FR-BU2-H7.5K to H280K

Technical Data Sheets

TECHNICAL BROCHURE BSPDDRIVE. Aquavar SPD (Single Pump Drive) SIMPLEX VARIABLE SPEED PUMP CONTROLLER FOR SUBMERSIBLE AND CENTRIFUGAL PUMPS

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

Solar. Fuji Electric Asia Pacific Pte. Ltd. Solar (PV) Pumping Inverter

TECHNICAL DATA SHEET B8031 FXS kva 3Ph(In) 1Ph(Out)

Ordering Information. Switching Power Supply S82F. Industrial-Grade Power Supply for General or Peak Load Applications SWITCHING POWER SUPPLIES

MJWI20 SERIES FEATURES PRODUCT OVERVIEW. DC/DC Converter 20W, Highest Power Density MINMAX MJWI20 Series

The High Power Stack Horizon

User Guide. Mini Maestro Drive. Variable Speed Drive for Permanent-magnet DC Servo-motors. Part Number: Issue Number: 2

Soft Starter. Types RSBD. Product Description. Type Selection. Ordering Code RSB D E V 61 HP

SDC,Inc. SCR-Regenerative Ac Drive

Manual for Inverter system type PCI05

SR8-Plus 2 Phase Step Motor Drive

PowerOhm Installation Manual for BM R Series Braking Modules

(typ.) (Range) ±18 330# 89 MPW MPW

Documentation. RM-BV4 Micro DP. Filter control

TDBU Series Dynamic brake unit user manual

Output Current Input Current Reflected Ripple. Efficiency (typ.) Load VDC VDC ma ma ma(typ.) ma(typ.) ma (typ.) VDC μf % MKW40-12S033

GTZ 25 / 40 / 55. THREE-PHASE SOLID STATE RELAYS WITH LOGIC CONTROL Vdc / Vac PROFILE. TECHNICAL DATA General features

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

INSTALLATION, OPERATION & MAINTENANCE SERIES ABC11B-120-XX BATTERY CHARGERS

Basic Characteristics Data

Switching Power Supply

Sorensen XG 1700 Series 1700 W A Watt, 1U Programmable DC Power Supplies V. Key Features. Key Modes

HBC DC-DC Series Data Sheet 300-Watt Half-Brick Converters

TC-500PD8. Switching Power Supply ( PS2 A T X 500W 8 0+ ) SPECIFICATION. Revision: 2.0

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP

CD3000S-1PH Thyristor Unit Heater Break version

Sola/Hevi-Duty S3K Series Mini-Tower UPS

ECONOMISER SERIES E2T USER MANUAL

Residual Current Protective Devices / Arc Fault Detection Devices (AFDDs)

8BVE0500HW General information. 2 Order data 8BVE0500HW

Battery, Mounting and Cables - Battery and Cables Description and Operation

CDBR-B. Dynamic Braking Unit Instruction Manual. April 2009 Part Number: R1 Copyright 2009 Electromotive Systems

PowerOhm Installation Manual for BM R Series Braking Modules

Output Current Input Current Reflected Ripple. Efficiency (typ.) Load VDC VDC ma ma ma(typ.) ma(typ.) ma (typ.) VDC μf % MKW40-12S033

VDC VDC ma ma ma(typ.) ma(typ.) ma (typ.) VDC μf % MKW40-12S

20 amps 220 amps, 60 Hz VDC VAC G3PA-420B-VD-2 DC amps 440 amps, 60 Hz G3PA-450B-VD-2 DC12-24

SINUS PENTA 2T/4T SINUS PENTA 2T/4T

GENERALITIES TECHNICAL FEATURES

(typ.) (Range) Input Specifications Parameter Model Min. Typ. Max. Unit 12V Input Models Input Surge Voltage (100ms.

4TCH Submersible Pumps. Installation and Operating Manual

CENTROIDTM. AC Brushless Drive. Product Spec Sheet

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC

SmartVFD HVAC FEATURES APPLICATION SPECIFICATION DATA

MaxPak Plus Analog DC V S Drive

Transcription:

Products Tde Macno User s Manual BRAKING UNIT Cod. MP00401E00 V_1.0

SUMMARY 1 GENERAL DESCRIPTION... 2 2 USE LIMITATIONS... 2 2.1 Climatic Class... 2 2.2 Resistance To Chemically Active Substances... 2 2.3 RESISTANCE TO VIBRATIONS... 3 2.4 PROTECTION AND POLLUTION DEGREE... 3 2.5 STORAGE... 3 2.5.1 Storage Environmental Conditions... 3 2.5.2 Recovery Procedure after Storage... 3 3 INSTALLATION INSTRUCTIONS... 4 3.1 Installation... 4 3.2 Mechanical Dimensions... 5 3.3 Confined space: power loss... 5 3.4 General Features... 6 4 POWER PART... 6 4.1 Power Circuit... 6 4.2 Description of the Power Terminals... 6 4.3 Wiring the Power Part... 7 4.4 Power Components... 7 5 Control Part... 8 5.1 Description of the Terminal Block... 9 5.2 Description of the Configuration DIP-SWITCHES... 10 5.3 Description of Signalling Leds... 10 5.4 Examples of signal connections... 11 5.4.1 Wiring as Stand Alone Unit... 11 5.4.2 Wiring for Master Slave Operation... 12 5.4.3 Wiring for Slave Operation... 12 6 DESCRIPTION IMPLEMENTED FUNCTIONS... 13 6.1 Setting the Level of Braking Activation... 13 6.2 Slave Function... 13 6.3 Manage of the Cooling Fans Function... 13 6.4 Managing Messages and Alarms... 13 MP00401E00 V_1.0 1

1 GENERAL DESCRIPTION This braking module (BU), along with its braking resistor, is used to limit the DC BUS voltage when power is supplied by a generator, if the line input stage is unable to feed the field power back into the line. This occurs when the input stage consists of a rectifier bridge or a regenerative unit (AFE Active front End) which goes into current limit, or when line regeneration is disabled. During this operation, the power supplied by the DC BUS (intermediate circuit) is converted into heat dissipated in the external braking resistor. The braking module can work as an independent unit or can be controlled by an external smart unit. It is also possible to use several braking modules connected in parallel, each with its own external braking resistor. 2 USE LIMITATIONS The environmental limitations to the use of the braking module under normal operating conditions are described hereinafter. 2.1 Climatic Class Class 3K3 ACCORDING TO EN 60721-3-3 Environmental Parameter Limits Unit of measurement operating temperature (1) 0 40 C humidity 5 85 % atmospheric pressure 70 106 (2) kpa maximum surrounding air velocity 1 m/s maximum temperature gradient 0.5 C/min maximum thermal radiation 700 W/m 2 condensation NO precipitation with wind NO (3) water other than rain NO ice formation NO Table 1 (1) Climatic Class 3K3 envisages a 5 40 C use limitation; however, the converter can work at a room temperature as low as 0 C. The maximum operating temperature of the converter reaches 45 C without output thermal current derating. (2) The atmospheric pressure limitations correspond to an operating range of 0 3000m above sea level. At altitudes exceeding 1000 m a.s.l., the rated power of the Braking Unit must be derated by 1% every 100m. (3) The converter must be installed inside a cabinet (never install it outside). 2.2 Resistance To Chemically Active Substances Class 3C1R according to EN 60721-3-3 Environmental Maximum Unit of Environmental Maximum parameter value measurement parameter value sea salts NO - hydrofluoric acid 0,001 Unit of measurement mg/m 3 sulphur dioxide 0,01 mg/m 3 0,0012 ammonia 0,03 cm 3 /m 3 mg/m 3 0,0037 hydrogen sulphide 0,0015 cm 3 /m 3 mg/m 3 0,042 ozone 0,004 cm 3 /m 3 mg/m 3 0,001 chlorine 0,001 cm 3 /m 3 mg/m 3 0,002 nitrogen oxide 0,01 cm 3 /m 3 mg/m 3 0,00034 hydrochloric acid 0,001 cm 3 /m 3 mg/m 3 0,005 cm 3 /m 3 0,00066 cm 3 /m 3 Table 2 2 MP00401E00 V_1.0

2.3 RESISTANCE TO VIBRATIONS As regards vibrations, the Unit has the following limitations: 10Hz frequency 57Hz 0.075 mm (width) 57Hz frequency 150Hz 1 g Table 3 If vibration levels exceed the above values, proper vibration damping measures should be considered. 2.4 PROTECTION AND POLLUTION DEGREE Protection degree IP20 (1) Pollution degree 2 (2) Table 4 (1) With suitable protections on input and output bars (2) Non-conductive pollution and occasionally and temporarily - conductive pollution generated by condensation. 2.5 STORAGE 2.5.1 STORAGE ENVIRONMENTAL CONDITIONS temperature -10 60 C humidity 5 95 % condensation NO Table 5 2.5.2 RECOVERY PROCEDURE AFTER STORAGE The drive cannot be used immediately after a storage period. To prevent failures, use the following recovery procedure. STEP 1: Non-powered Converter temperature 15 35 C humidity 5 75 % condensation atmospheric pressure 86 106 kpa recovery time (1) 1 h Table 6 NO (1) After this recovery time, there should be no trace of condensation inside or outside the drive (well-ventilated environment). STEP 2: For long storage periods (one or more months), always proceed to regenerate the electrolytic capacitors of the power BUS. Leave the converter powered through the + and terminals for 30min to 1hour, without deriving power from the DC Bus generator. Once the regeneration process has been completed, the converter can work normally. MP00401E00 V_1.0 3

3 INSTALLATION INSTRUCTIONS 3.1 INSTALLATION The Braking Unit (BRU) should always be installed in places meeting the environmental requirements in Chapter Use Limitations. Moreover, all control and display devices should be easily accessible at all times.any other equipment must be installed at a reasonable distance from the drive, in order to prevent any metal residues from drilling operations or from metal cables from falling into the drive. Under no circumstances can the converter be mounted near easily flammable material. Figure 1 shows the minimum clearances required to ensure proper cooling of the power part. Figure 1 NOTE: Use four M6 screws to fix the Braking Unit to the cabinet panel. 4 MP00401E00 V_1.0

3.2 MECHANICAL DIMENSIONS Figure 2 3.3 CONFINED SPACE: POWER LOSS The table below shows the total power loss of a Braking Unit when it is operating at its rated current, including losses due to regulation and ventilation. If the Braking Unit is installed in a confined space, such as a cabinet, make sure that the temperature inside the cabinet does not exceed the maximum ambient temperature allowed for the Braking Unit. If needed, provide sufficient air ventilation to remove the heat generated by the Braking Unit and other components. Size Total Power Loss [A] [W] 85 170 125 240 250 470 Table 7 MP00401E00 V_1.0 5

3.4 GENERAL FEATURES Braking Unit Size 85 125 250 Input voltage [Vdc] 400 720 Capacity of the intermediate circuit [ F] 820 1230 1800 Output thermal current (1) [Adc] 85 125 250 Output peak current [Adc] 170 250 500 Brake activation voltage [Vdc] 680 / 730 /770 Brake deactivation voltage [Vdc] 650 /700 /740 Table 8 NOTE: (1) 1% derating every 100 m, for altitudes exceeding 1000m above sea level. 4 POWER PART 4.1 POWER CIRCUIT The power diagram of the Braking Unit (figure 3) consists of the following: - Brake IGBT for dissipating the power fed back to the power BUS by the converters - Capacity on the intermediate stage - Switching mode power supply for generating the power required by the internal logic and the cooling fans + + Capacity F - Fly-back Figure 3 IGBT 4.2 DESCRIPTION OF THE POWER TERMINALS Table 9 contains a description of the power terminals (power bars) and their meaning. + - Power supply input side (top) Terminal Description + Power BUS positive terminal - Power BUS negative terminal Braking resistor wiring side (bottom) Terminal Description + Power BUS positive terminal to be used solely for wiring the braking resistor F Brake IGBT Collector to be used for wiring the braking resistor Table 9 + F 6 MP00401E00 V_1.0

4.3 WIRING THE POWER PART Figure 4 shows the power connection for the Braking Unit. The fuses and cables to be used are detailed in section 4.4 Power Components. WARNING: When several Braking Units are used (in case of master slave operation, or of several Braking Units controlled by a smart unit) each Braking Unit must have its own braking resistor. In fact, the outputs of two or more Braking Units MAY NOT be connected in parallel. + DC BUS - DC BUS Fuses Fuses PE + - PE + - PE BRAKING UNIT 1 + F BRAKING UNIT N + F Braking Resistor 1 Braking resistor N Figure 4 4.4 POWER COMPONENTS Table 10 contains a list of the power components that are recommended to ensure proper operation of the Braking Unit. The fuses indicated are used to protect wiring to the Braking Unit. Size Ultrafast fuses for cable protection (PVC) @ Tambient=40 C Wiring cable section Nominal current rating I 2 T fuses < I 2 T cable @5s Minimum shortcircuit current Fuse voltage Section of +, -, +, F cables Section of GROUND cable [A] [A] [KA 2 s] [A] [Vac] [mm 2 ] [mm 2 ] 85 160-450 <16200 1800 690 35 25 125 200-630 <33062 2571 690 50 35 250 400-1250 <190440 6172 690 120 70 10 Table Table 11 indicates the minimum values of the external braking resistors as a function of the activation voltage of the braking circuit itself. This table also shows the maximum thermal capacities and maximum peak capacities at the minimum resistance value of the braking resistor. Size Minimum value of braking resistor Maximum thermal capacity at minimum resistance Maximum peak capacity at minimum resistance 680V 730V 770V 680V 730V 770V 680V 730V 770V [A] [ ] [ ] [ ] [KW] [KW] [KW] [KW] [KW] [KW] 85 4 4,3 4,5 57,8 62,1 65,5 115,6 124,1 130,9 125 2,7 2,9 3,1 85,0 91,3 96,3 170,0 182,5 192,5 250 1,4 1,45 1,54 170,0 182,5 192,5 340,0 365,0 385,0 Table 11 MP00401E00 V_1.0 7

5 CONTROL PART 8 MP00401E00 V_1.0

5.1 DESCRIPTION OF THE TERMINAL BLOCK Table 12 provides the details for the control terminal block and fiber optics. Terminal Description M1-1 +24VOUT Output auxiliary voltage 21.6 26.5V as referred to 0POUT. Maximum output current 100mA. M1-2 0POUT +24VOUT auxiliary voltage common. M1-3 BRAKE EN. Logic input. Enables the braking circuit. This input is optoisolated from the internal regulation and is referred to 0V BR EN. (M1-4). This logic input is in parallel with the brake activation command supplied via fiber optics (BRAKE EN.) and with the command that is generated internally (when the slave function is disabled). Input voltage range 21.6 26.5V, absorbed current 10mA. M1-4 0V BR EN. BRAKE EN. (M1-3) logic input common. M1-5 L.O.1 Logic output for activating the braking circuit. M1-6 /L.O.1 This logic output is optoisolated from the internal regulation. The transistor is conductive when this output is active. Imax=60mA, Vmax=30V M1-7 L.O.2 Pre-alarm logic input: the radiator temperature is approaching the alarm threshold. M1-8 /L.O.2 This logic output is optoisolated from the internal regulation. The transistor is conductive when this output is active. Imax=60mA, Vmax=30V M1-9 DR OK N.O. DRIVE OK logic output M1-10 DR OK COM M1-11 DR OK N.C. Clean contact relay (energised under normal operating conditions) Features of the relay: 250VAC 8A. DR OK N.C. M1-12 0V Internal regulation common. M1-13 VBUS Logic output as referred to 0V (M1-12) and proportional to the BUS voltage (ratio 1:100). M1-14 SHIELD Output: +8V / 2mA FIBRE OPTICS BRAKE EN. Description Logic input. Enables the braking circuit. Light on = braking is active DRIVE OK This logic input is in parallel with the brake activation command supplied via terminal M1-3 (BRAKE EN.) and with the command that is generated internally (when the slave function is disabled). DRIVE OK logic output Light on = No alarm present Table 12 MP00401E00 V_1.0 9

5.2 DESCRIPTION OF THE CONFIGURATION DIP-SWITCHES On the front panel there are two Dip-switches that enable users to customize their Braking Unit. The first Dip-switch enables the setting of up to three different activation voltages for the braking circuit. By contrast, the second one enables the user to operate the Braking Unit as if it were controlled from outside (that is, as a slave only). Table 13 provides a description of these Dip-switches. SW1: used to set the brake activation and deactivation thresholds SW1-1 SW1-2 Brake activation voltage [Vdc] Brake deactivation voltage [Vdc] OFF OFF 680 650 ON OFF 730 700 OFF ON 770 740 ON ON 770 740 SW2: used to set the unit for slave operation SW2-1 SW2-2 Description OFF X The internal brake activation circuit, which goes in parallel with the brake activation commands supplied via logic inputs (terminal M1-3 or fiber optics BRAKE EN.), is on. ON X The brake activation command is supplied solely and exclusively via logic inputs (terminal M1-3 or fiber optics BRAKE EN.) The Braking Unit operates as a SLAVE. Table 13 5.3 DESCRIPTION OF SIGNALLING LEDS On the front panel of the Braking Unit there are some signalling leds. They allow the users to check the configuration of the Unit itself and provide immediate troubleshooting information in case of an alarm. Their meaning is shown in Table 14 Name 680V 730V 770V SLAVE DRIVE OK MAX VOLT MIN VOLT OVER TEMP POWER FAULT Signalling leds Description Brake activation voltage is set to 680Vdc (when this led is on). Brake activation voltage is set to 730Vdc (when this led is on). Brake activation voltage is set to 770Vdc (when this led is on). Operation as a SLAVE: the brake activation command is supplied solely and exclusively via logic inputs (terminal M1-3 or fiber optics BRAKE EN.) (steady on = operation as a SLAVE) This led indicates that the drive is ready (steady on = OK) DC BUS overvoltage alarm (led on = alarm). DC BUS undervoltage alarm (led on = alarm). Heat sink overtemperature alarm (led on = alarm). Brake IGBT power fault alarm (led on = alarm). Table 14 10 MP00401E00 V_1.0

5.4 EXAMPLES OF SIGNAL CONNECTIONS 5.4.1 Wiring as Stand Alone Unit M1-3 M1-4 BRAKE EN 0V BR EN +24VOUT 0POUT L.O.1 M1-1 M1-2 M1-5 To the control for common zeros /L.O.1 L.O.2 /L.O.2 DR OK COM DR OK NC DR OK NO M1-6 M1-7 M1-8 M1-9 M1-10 M1-11 To the control for prealarm signals To the control for alarm signals 0V M1-12 100 VBUS SCHIELD M1-13 M1-14 Figure 5 The brake enable command is generated internally. The logic outputs and analog signal are used merely for diagnostic purposes (troubleshooting). MP00401E00 V_1.0 11

5.4.2 Wiring for Master Slave Operation In the diagram below, the Master supplies the brake activation command to the slave via the L.O.1 logic output. If you wish to set up the second Braking Unit as a slave, follow the instructions provided in section 5.2 Description of the Configuration DIP-SWITCHES. The series of the two DRIVE OK clean contacts is wired to the control for diagnostic purposes. You can also use the series of L.O.2 logic outputs for the purpose of recognizing any pre-alarm condition on one of the two Braking Units. Finally, you can also use a master-slave configuration with several slaves. All you have to do is connect the L.O.1 logic output of the master to all BRAKE EN inputs (the 0POUT of the master must be connected in common to the 0V BR EN of the slaves). All DRIVE OK contacts must be placed in series, so as to send any alarms to the control. M1-3 M1-4 BRAKE EN 0V BR EN +24VOUT 0POUT L.O.1 M1-1 M1-2 M1-5 To the control for common zeros M1-3 M1-4 BRAKE EN 0V BR EN +24VOUT 0POUT L.O.1 M1-1 M1-2 M1-5 /L.O.1 L.O.2 M1-6 M1-7 /L.O.1 L.O.2 M1-6 M1-7 /L.O.2 DR OK COM DR OK NC DR OK NO M1-8 M1-9 M1-10 M1-11 /L.O.2 DR OK COM DR OK NC DR OK NO M1-8 M1-9 M1-10 M1-11 To the control for alarm signals 0V M1-12 0V M1-12 100 VBUS SCHIELD M1-13 M1-14 100 VBUS SCHIELD M1-13 M1-14 MASTER Figure 6 SLAVE 5.4.3 Wiring for Slave Operation This Braking Unit can be configured to operate as a slave and to receive the brake activation command and supply the DRIVE OK signal to a smart unit, via fiber optics. The smart unit can receive the signal proportional to the power BUS voltage from the Braking Unit itself. The wiring diagram to be used in this case is shown in the following figure. BRAKE EN DRIVE OK Brake command DRIVE OK management DR OK COM DR OK NC DR OK NO 0V 100 VBUS SCHIELD M1-10 M1-11 M1-9 M1-12 M1-13 M1-14 SMART UNIT Voltage reading DC BUS SCHIELD SLAVE MASTER Figure 7 12 MP00401E00 V_1.0

6 DESCRIPTION IMPLEMENTED FUNCTIONS 6.1 Setting the Level of Braking Activation The braking unit is predisposed to work with three different thresholds of the brake circuit that can be set by the customer using the dip switches on the front panel (see section 5.2 Description of configuration DIP-SWITCH). The setting of the activation threshold of brake circuit must take into account: a) Nominal supply voltage of the intermediate stage (DC BUS). b) Activation voltage of the maximum voltage alarm of the converters connected to the intermediate stage. For mains voltages of 380-440Vac, you can use voltages insertion braking 680Vdc or 730Vdc bearing in mind that the trigger threshold brake must be less than the alarm to the maximum voltage of the converters connected. For mains to 480Vac mains, however, you must set the trigger brake 770Vdc. The factory configuration involves setting the threshold of brake circuit to 730V (700V to release tension). 6.2 Slave Function Is possible to configure the braking unit as a slave excluding the circuit that internally generates the command to active the brake circuit (see section 5.2 for setting DIP-SWITCH description of the configuration). In this way, braking is controlled exclusively by an external command provided by the terminal or via optical fiber (for signal connections see section 5.4.3 Connection for master - slave and 5.4.4 Connecting to operate as a slave). 6.3 Manage of the Cooling Fans Function Very often the braking unit is used in applications in which works for short periods, or only in a state of emergency stop of the entire electrical system. To avoid doing work continuously and unnecessarily the cooling fans of the radiator, the control commands the ignition only when the temperature of the radiator exceeds 70 C. The switching off, however, occurs when the temperature drops below 59 C. This function allows you to have a reduced consumption under normal working conditions. 6.4 Managing Messages and Alarms The brake unit has a series of alarms that remove the consent of to the insertion of the braking circuit and have the purpose of preventing failure of the brake unit itself. There are, then, of simple messages that do not alter the operation of the same brake unit, but that may be useful to know the status of operation of the system. MP00401E00 V_1.0 13

Messages and alarms are managed in the following table: Name MAX VOLT MIN VOLT FANS FAULT OVER TEMP POWER FAULT MESSAGES / ALARMS Description Maximum alarm voltage of the intermediate stage. The protection is activated when the bus voltage exceeds 800Vdc. The alarm removes the consent to the braking IGBT control and is not stored. In contrast, the alarm signal (red LED MAX VOLT) is retained even when the protection is no longer active. To reset the display is necessary to disconnect the power supply. The intervention of the maximum voltage is switch the output of DRIVE OK that must be handled by the control. Undervoltage alarm of the intermediate stage. The protection is activated when the bus voltage is less than 400Vdc. The alarm removes the consent to the braking IGBT command, but it is not stored. The intervention of this alarm must be to change the output status of DRIVE OK and turn on the red LED MIN VOLT on the front. The LED goes off when the voltage exceeds 400Vdc. The DRIVE was just OK changes the voltage is greater than 400V. Signaling of temperature of the radiator next to the maximum threshold temperature. The message indicates that the radiator temperature exceeds 78.5 C, and then there may be one or more cooling fans latches (for their failure or a failure of the circuit that commands them). Another reason why you can get in this condition is that the thermal current output from the brake exceeds the nominal one. The message is covered when the radiator temperature drops below 77 C. When this message is present, it activates the logic output L.O.2 and will not turn on no led display and DRIVE OK does not change state. Maximum temperature alarm sink. The heatsink temperature exceeds 80 C. As for the signaling FANS FAULT, there could be one or more cooling fans latches or the thermal current outputted from the braking unit exceeds the nominal one. In this case is taken off the consent, is removed the consent of the enable circuit braking, the DRIVE OK contact status is changed and you turn on the OVER TEMP yellow LED on the front. The protection is restored when the radiator temperature drops below 79 C. Under the temperature recovery is restored the consent of to the insertion of the brake circuit and the DRIVE OK, so it returns to the normal operation status. The OVER TEMP LED on the front panel is lit. To reset the display is necessary to disconnect the power supply. Alarm power brake unit. Indicates the intervention of the braking IGBT desaturation protection. With the intervention of the protection is removed the consent of the enable circuit braking, the DRIVE OK contact status is changed and you turn on the POWER FAULT red led on the front panel. The alarm and the display remain stored so to reset it is necessary to remove the power supply. 14 MP00401E00 V_1.0

s.p.a. tecnologie digitali elettroniche Via dell Oreficeria, 41 36100 Vicenza - Italy Tel +39 0444 343555 Fax +39 0444 343509 www.tdemacno.com