ALDI # CITY, STATE SUPERMARKET MultiPath RTUTYPE 9 (RTU1) CESMPU025REVAV9 Date: December 1, 2014 2013 Consolidated Energy Solutions, Inc.
UNIT FEATURES CES TYPE VAV9 Unit features include: 25 ton MultiPath Dehumidification Rooftop Unit 1 Digital scroll compressor & 1 on/off compressor (R410a) 2 Independent refrigerant circuits Refrigerant heat reclaim coil Outside air, return air, and bypass air damper with DDC actuators Fully modulation DDC actuators for MultiPath control Factory installed custom controls with VAV support Natural gas heat with 4stage control 5 year compressor warranty Stainless steel drain pan sloped ptrap Direct drive BI plenum supply fan with VFD Double wall construction with foam insulation (R13) Permanent frame replaceable media filters (MERV7) 115v convenience outlet (Factory Wired) Phase & brownout protection Factory mounted disconnect Factory installed return air CO2 sensor Field installed items by EMS installer (supplied by others): Supply air temperature sensor in ductwork, space temperature and space humidity (see controls specification) and Ethernet communication
UNIT SPECIFICATIONS JOB NAME ALDI TYPE VAV9 NUMBER OF UNITS AT SITE 1 (TAG RTU1) UNIT MODEL NUMBER CESMPU025REVAV9 PLACEMENT OF UNIT(S) HORIZONTAL, OUTDOOR, SEATED ON ROOF CURB CLIMATIC REGION TYPE 9 DESIGN ALTITUDE / STATION PRESSURE 615 FT / 14. PSI TOTAL UNIT SUPPLY AIR 8000 CFM O/A DESIGN CONDITIONS 92 DB F / 79 WB F O/A QUANTITY 1500 CFM R/A DESIGN CONDITIONS 75 DB F / 64 WB F R/A QUANTITY 6500 CFM GROSS UNIT CAPACITY 287.14 MBH GROSS SENSIBLE CAPACITY 160.13 MBH LATENT CAPACITY 127.01 MBH DEHUMIDIFICATION 114.72 LB/H LEAVING COIL TEMPERATURE.63 F FAN HEAT 8.78 MBH UNIT EER/ IEER RATING 11.4 / 14.1 ESP / TSP 0.35 WC / 1.57 2.22 WC FILTER / DX COIL FACE VELOCITY 384.00 FPM / 304.20 FPM UNIT WEIGHT 3000 LBS RECLAIM COIL (DRY) 100 LBS ROOFCURB WEIGHT 250 LBS FAN TYPE 27" DIRECT DRIVE BACKWARD CURVED PLENUM FAN MOTOR BHP / RPM / HP 3.09 4.17 / 1024 1120 / 5 VFD TYPE OF AUXILIARY HEAT NATURAL GAS, 4STAGE INLET GAS LINE 1 MINIMUM/ MAXIMUM INLET PRESSURE 6.0 WC / 10.5 WC IGNITION NONSTANDING, SPARK, RELIGHT GAS INPUT / OUTPUT / EFFICIENCY 405.00 MBH / 328.10 MBH / 81% ELECTRICAL S/A MOTOR AMPS COMPRESSOR MOTORS RLA CONDENSER FAN MOTORS FLA COMBUSTION MOTORS CONTROL UNIT FULL LOAD AMP (FLA) MINIMUM CURRENT AMP (MCA) MAXIMUM OVERCURRENT (MOP) 460V / 3 PHASE / 60 HZ 1 @ 8.1 AMPS 2 @ 18.6 AMPS 3 @ 2.3 AMPS 2 @ 0.9 AMPS 1 @ 0.9 AMPS 52 AMPS 57 AMPS 70 AMPS CES Condenser Sound Power Level 25 30 Ton 63 125 250 500 1000 2000 4000 8000 LwA Inlet 97 91 89 87 83 80 77 76 89 Outlet 98 95 88 88 84 80 77 75 90 Total 101 96 92 91 86 83 80 79 92 Tested in Accordance with AMCA 300 Revised for new fan test sound data 9/17/08 CES 25 30 Ton Condenser Sound Pressure Level 63 125 250 500 1000 2000 4000 8000 dba Inlet 79 73 72 69 65 62 59 58 71 Outlet 81 77 70 70 66 62 59 58 72 Total 83 79 74 73 69 65 62 61 75 Sound Pressure Level in a Hemispherical Free Field Distance (ft) = 10
HEAT RECLAIM COIL SELECTION PROJECT: ALDI TYPE 9 DESIGN Coil Size: 50L x 42W Row Deep 1 FPI 10 Coil Face area 14.58 CFM 7500 Face Velocity 514.3 fpm Bypass CFM 0 Tube diameter 1/2 FTR BTU/HR Design TD Connections IN OUT 40 123,371 40 1 3/8 1 3/8
CLEARANCES LOCATION OUTSIDE AIR (BACK) CONTROLS SIDE (FRONT) LEFT SIDE RIGHT SIDE TOP UNIT SIZE 25 TON 6 60 UNOBSTRUCTED DETAIL A DETAIL B DETAIL C FRONT VIEW TOP VIEW NOTE: ALL DIMENSIONS IN INCHES 11/20/2014
CLEARANCES LOCATION OUTSIDE AIR (BACK) CONTROLS SIDE (FRONT) LEFT SIDE RIGHT SIDE TOP UNIT SIZE 25 TON 6 60 UNOBSTRUCTED CONTROL CABINET VIEW NOTE: ALL DIMENSIONS IN INCHES 11/20/2014
CLEARANCES LOCATION OUTSIDE AIR (BACK) CONTROLS SIDE (FRONT) LEFT SIDE RIGHT SIDE TOP UNIT SIZE 25 TON 6 60 UNOBSTRUCTED RIGHT SIDE VIEW NOTE: ALL DIMENSIONS IN INCHES 11/20/2014
CLEARANCES LOCATION OUTSIDE AIR (BACK) CONTROLS SIDE (FRONT) LEFT SIDE RIGHT SIDE TOP UNIT SIZE 25 TON 6 60 UNOBSTRUCTED DETAIL A DETAIL B DETAIL C FRONT VIEW PIPE CHASE VIEW NOTE: ALL DIMENSIONS IN INCHES 11/20/2014
Type 4 Roof Curb NOTES: NOT TO SCALE 14" HEIGHT (OTHER HEIGHTS AVAILABLE) 18GA GALVANIZED STEEL ALL DIMENSIONS IN INCHES 11/20/2014
TO CSTB1 () 9 SUPPLY FAN 1 COMBUSTION FAN MOTOR HEAT STAGE 1 HEAT STAGE 2 HEAT STAGE 3 HEAT STAGE 4 COMPRESSOR 2 REHEAT / RECLAIM 1 REHEAT / RECLAIM 2* CONDENSER FAN 1 CONDENSER FAN 2 CONDENSER FAN 3* (When Applicable) R13 R11 C R14 R12 R15 NC C R10 R9 VisoGraph Remote Display R8 Remote Display C Clear Back View Red Black R7 VNR R6 60 61 62 VNR Clear Red Black Remove shield wire From both ends Belden 8771 SPACE TEMPERATURE 2 SPACE HUMIDITY OR DP 2 COMMON FOR TEMPS GND FOR HUM AND TRANS 12V HUMIDITY OR DP 2 SPC HUM White Black Shield Supply TO CSTB 1 () FUSE 5X20 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 109110111 112 113 114 115116117 118 119 120121122 R5 Expansion Dip Switch CAN Bus LAN Term gnd PWR ON ALARM Tx Rx Tx Rx 100 101 102 103 104 1 2 3 4 1 2 3 7 9 16 40 41 42 43 44 45 46 47 49 50 21 22 25 5152 53 54 55 56 57 58 59 60 61 28 29 8 BLACK 18 GAUGE RED 18 GAUGE NOTE: VAV CONNECTIONS ARE FIELD INSTALLED. ERV CONNECTIONS ARE FACTORY INSTALLED WHEN THE UNIT IS EQUIPPED WITH AN ERV. SPACE TEMP 2 AND HUMIDITY/ DEWPOINT 2 ARE OPTIONAL AND FIELD INSTALLED. VAV DAMPER VAV FAN SPEED GND FOR AO POINTS VAV BOOSTER HEAT VAV FAN ERV WHEEL ERV POWER EXHAUST ERV BYPASS COMMON ERV STORE EXHAUST R4 R3 R2 () () TO CSTB1 BELDON 8641 14 GAUGE 3WIRE TWISTED PAIR C R1 ICONTROLLER WITH EXPANSION 90 06/10/2014 70 71 72 73 76 77 78 79 80 81 84 85 86 87 88 icontroller Master RS5 Slave RS5 CAN BUS REMOTE DISPLAY GND GND VNR Term GND Term 97 98 99 100 101 102 103 104 105 Term LED1 ALARM JMP1 Tx Rx Tx Rx Tx Rx Modem Ext. Modem Reset Internal Modem White Black Shield Supply 1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 40 41 42 43 21 22 23 24 25 61 26 28 29 VISOGRAPH (SEE DETAIL) 60 61 62 VNR SEE TERMINAL CONNECTION DETAIL BELDON 8641 14 GAUGE 3WIRE TWISTED PAIR BELDON 8641 14 GAUGE 3WIRE TWISTED PAIR FIELD INSTALLED BYPASS AIR DAMPER BAD OUTDOOR AIR DAMPER OAD RETURN AIR DAMPER RAD DIGITAL COMP 1 DC1 VARIABLE FREQ DRIVE VFD GROUND FOR ANALOG OUTS GROUND FOR DIGITAL IN SMOKE DETECTOR EMR AIRFLOW SWITCH AFS CLOGGED FILTER SWITCH CFS LOAD SHED* LS () () () TO CSTB1 TO CSTB1 GND MODBUS COMMUNICATION CONNECTION EXPANSION BOARD 1 9 MAINTAIN POLARITY Note: USE AN ISOLATED TRANSFORMER 50VA DO NOT SHARE POWER WITH ANALOG OUTPUTS 120Vac Terminal 1 16 Detail GROUND FOR POWERED SENSORS COMMON FOR TEMP SENSORS OUTDOOR TEMPERATURE OAT 0500 PSI TRANS COMP1 SUCT INDOOR HUMIDITY RHDP SPACE TEMP SPACE SUPPLY TEMP SUPLY 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 CO2 SENSOR CO2 MIX AIR TEMP MIX RETURN AIR TEMP RETN 0667 PSI TRANS COMP 2 DISC OUTDOOR HUMIDITY ODRH 5VDC TRANSDUCERS 12VDC HUMIDITY OR DEWPOINT icontroller MAINTAIN POLARITY 1 9 RED 18 GAUGE BLACK 18 GAUGE Note: USE AN ISOLATED TRANSFORMER 50VA DO NOT SHARE POWER WITH ANALOG OUTPUTS 120Vac