EISHO TEK. Vacuum Circuit Breaker

Similar documents
User manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

PATENT PENDING. Phone: (877) Operation and Service Manual

HD4-LMT. MV SF6 Circuit Breaker Installation and Service Instructions kv 1,250 A 31.5 ka

HV6FS-MLD Vacuum Circuit Breakers Drawout Type 4.8 & 7.2kV Voltage Classes (Fast Closing w/uv Release)

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive

HCV-6KAU Vacuum Contactor, 7.2kV 720A 7.2kA HCV-6KALU Vacuum Contactor, 7.2kV 720A 7.2kA

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B Overcurrent Protective Device)

INSTRUCTION MANUAL. HV6FS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes (Fast Closing) INSTALLATION - OPERATION - MAINTENANCE

INSTRUCTION MANUAL. HV6AS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes INSTALLATION - OPERATION - MAINTENANCE

1. Safety practices General Introduction Standards...3

Vacuum Circuit Breaker Type VAD-3

INSTRUCTION MANUAL. HCV-1JBU Vacuum Contactor, 1.5kV - 600A HCV-1KAU Vacuum Contactor, 1.5kV - 720A

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label.

CR193 Vacuum Limitamp* Contactors

AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

F3S-TGR-KHL1/-KHL3/-KHL3R

VD4 Installation and service instructions kv A ka

Florham Park, NJ USA Call (ASCO) for sales or service

Air-insulated switchgear UniGear type ZS1

Service Instructions. Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B Overcurrent Protective Device)

WARNING. Electric Recovery Winch. General Safety Precautions

Installation, Operation and Maintenance Manual

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS36

section-page Table 1. Transfer switching device ratings. Conditional short circuit current

INSTALLATION & OPERATION MANUAL

maintenance of the winch. All information in this publication is based on the latest production information available at the time of printing.

Instruction Manual 15kV KVAN-1125M 1200/2000A Maxi-Vac Medium-Voltage Vacuum Circuit Breaker

EVS RP6020. Instruction Manual

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-31B Overcurrent Protective Device)

3AK OPERATING INSTRUCTIONS. Vacuum circuit-breaker module 3AK1 and 3AK3

S&C Type FVR Substation Circuit Breaker

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

MV12 SINGLE BUSBAR VACUUM SWITCHGEAR 12KV, 800/1250/2000/2500A, 25/31.5kA INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTION MANUAL

UniSec Maintenance solutions

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

Outdoor vacuum breaker for railway applications - FSK II

INSTALLATION & OPERATION MANUAL

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

Heavy Duty Hoist WARNING. General Safety Precautions. Thank you for purchasing a

VD4. Installation and service instructions kv A ka

Florham Park, NJ USA Call (ASCO) for sales or service

TECHNICAL DESCRIPTION

Vacuum Circuit Breaker (Vehicle)

33KV INDOOR SWITCHGEAR

RP Instruction Manual

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-31B Overcurrent Protective Device)

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS12

SF 6 Gas Insulated Load Break Switch

Operating Instructions

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

ADVAC Model 3 Medium Voltage Vacuum Circuit Breaker Installation and Operation Manual

Publication No.: PSG

GE CONSUMER & INDUSTRIAL

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps

HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA

INSTALLATION & OPERATION MANUAL

IB PowlVac ITE-HK Remote Racking Device

I. General Safety Precautions

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

Butterfly Valve Type 58 (PDCPD)

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B,21B,22B,31B Overcurrent Protective Device)

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS

cause injury to humans and other physical damage. : Gives information that does not fall in the WARNING or CAUTION categories.

Medium voltage vacuum circuit breaker. E-VAC series

HARRINGTON PEERLESS ELECTRIC CHAIN HOIST CODE SH (SINGLE PHASE)

Outdoor Vacuum Circuit Breaker - Type OVB-SDB. Instruction for Storage, Installation, Service and Maintenance

4. MAINTENANCE MANUAL

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Instruction Manual. Table of Contents. Powder Clutch, Brake MODEL ZKB-AN,BN Powder Clutch ZKB-YN,XN Powder Brake

Powered by Safety 01.4IB Powell GIS (Gas Insulated Switchgear)

VD4 Installation and service instructions 36 kv A ka

panasonic.net/id/pidsx/global Solve issues related to machine safety and other safety measures with a safety door switch with key!

HL (AZH) Limit Switches

SG-B1 SERIES / SG-A1 SERIES

Instruction Manual for Electric Vehicle (EV) Quick Charging Connector

I. Safety Requirement WARNING. ATV/UTV Winch

INSTRUCTION MANUAL. HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA INSTALLATION - OPERATION - MAINTENANCE

Installation Manual. E-design A Transfer Switches A

ADVAC TM Model 03 Medium Voltage Vacuum Power Circuit Breakers and Auxiliary

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps

11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls

GE Electrical Distribution. Gerapid High Speed DC Circuit Breakers. On the move. imagination at work

DIGITAL BATTERY TORQUE WRENCH (BC-RAD SELECT) USER GUIDE

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Descriptive Bulletin. R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

ABB ADVAC TM. INSTALLATION/MAINTENANCE INSTRUCTIONS Medium Voltage Vacuum Power Circuit Breakers and Auxiliary Devices

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

Transcription:

EISHO TEK Vacuum Circuit Breaker TYPE:SV1-12 INSTRUCTION MANUAL Operation and Maintenance Version TAIWAN CALSONIC

SAFETY PRECAUTIONS For safety reason, this equipment should be handled by personnel who has ample knowledge and technical skill required. Prior to usage of the equipment, please read through this instruction manual and all other documents concerned, and handle the equipment properly. Handling should be exercised after mastering required knowledge on the equipment, information on safety and all precautions. After reading of this instruction manual, please keep this in the place accessible to anyone to use the equipment.! Danger Because of high voltage, the following items must be observed: Don't access near to high voltage charged portion. Be sure the circuit breaker is off and withdrawn while handling the switchgear. Front covers of devices must be attached in use. To avoid receiving electrical shock both main circuit and control circuit must be off (de-energised). During the operation of the equipment, please be sure the following items to be observed:! Caution Don't use under the condition exceeding the rated values. If it is not operated in order, grounding fault or short circuit fault due to insulation breakdown, fire due to over-heat, bursting due to mal-operation of switchgear may take place. Don't touch or insert hand or part of body into the operation mechanism. When the CB indicator shows 'ON' or the CB closing spring indicator shows 'CHARGED', don't insert hand or part of body into CB. Prior to maintenance, discharge the CB closing spring and confirm the CB closing spring indicator shows 'DISCHARGED'. Don't reform the interlock mechanism. For safety reason use our standard operating handle and don't use any other handle. Owing to deformation, there may be a chance to invite injury. If a failure or abnormal phenomenon should occur, or if you have any questions concerning the handling of the circuit breaker, contact our branch or sales offices, providing us with the information shown below. Name of device Serial No. Date of manufacture Listed on the nameplate. Type Detail of the failure or abnormal phenomenon and situation before and after the occurrence.

CONTENTS 1. RATING AND OUTLINE DRAWING 1-1 Ratings 1 1-2 Outline drawing 2 1-3 Internal connection diagram 3 2. DESCRIPTION 4 3. MANUAL OPERATION (Manual stored energy type and stored energy type) 5 3-1 Charging 5 3-2 Closing 5 3-3 Opening 5 3-4 Putting into SERVICE and ISOLATED operation 5 4. UNLOADING AND PREPARATION FOR OPERATION 4-1 Unloading 7 4-2 Unpacking 7 4-3 Transportation 7 4-4 Checking after unpacking 8 4-5 Storage 8 4-6 Inspection during storage 8 4-7 Installation 8 4-8 Inspection and procedure before operation 8 5. MAINTENANCE AND INSPECTION 5-1 Caution at inspection 9 5-2 Patrol inspection 9 5-3 Periodical inspection 9 5-4 Detail inspection 14 5-5 Special inspection 15 5-6 Trouble shootings 15

1. RATING AND OUTLINE DRAWING 1-1 Ratings Type Table 1 Ratings VZA-12 Rated voltage (kv) 12 Rated normal current (A) 630/1250A Rated frequency (Hz) 50/60 Insulation level 1min power frequency (kv rms.) 1.2 50μs impulse (kv perk) Rated short-circuit breaking current (ka) 25 Rated short-circuit making current (ka peak) 65 Rated short-time withstand current (ka-s) 25-3 Operating duty 28 75 O-0.3sec-CO-15sec-CO Rated closing time (s) 0.05 Rated opening time (s) 0.035 Rated break time (s) 0.05 Rated TRV for Rate of rise (kv/μs) 0.34 terminal fault TRV peak voltage (kv) 20.6 Type of operating mechanism Tripping system Motor charged spring stored energy Shunt trip Spring charge motor Auxiliary voltage 110Vdc Closing coil Auxiliary voltage 110Vdc Tripping coil Auxiliary voltage 110Vdc Applicable standard IEC62271-100(2012)

1-2. OUT LINE DRAWING Fig.1 Outline drawing

1-3. INTERNAL CONNECTION DIAGRAM Fig.2 Internal connection diagram

2. DESCRIPTION The Meidensha VZA-12 vacuum circuit breaker employs the vacuum interrupter which has excellent interruption efficiency. The vacuum circuit breaker is extremely reliable in service, require only a minimum of maintenance and have a long life expectancy. The Meidensha VZA-12 vacuum circuit breaker meets the requirements of IEC62771-100. Closing spring can be charged motor.. The three breaker poles with vacuum interrupter, are mounted on a common truck housing. The moving contacts in vacuum interrupters are opened and closed by springs. In order to ensure the maximum performance and dependable operation, it is suggested that the operator reads this instruction manual carefully to be well acquainted with all the features of this vacuum circuit breaker. Safety precaution This circuit breaker uses powerful springs for operation. Prior to the inspection of open/closing characteristics and the parts replacement work, the vacuum circuit breaker shall be operated to be the following conditions. VCB status OFF Closing spring DISCHARGED Control and motor circuits OPEND

3. MANUAL OPERATION(Manual stored energy type and Motor stored energy type) Motor-operated vacuum circuit breakers can be actuated by hand if the control supply should fail. 3-1. Charging (See Fig.3) Insert the charging handle to the manual charging shaft and clockwise until a clicking sound is heard. At this time the charge-discharge indicator shows CHARGED. The operator is protected for any risk when sudden recovery of control source during charging by a preventive device charging handle. 3-2. Closing (See Fig.3) Press the manual close button to close the vacuum circuit breaker. The ON-OFF indicator will show ON and the charge-discharge indicator will show DISCHARGED. The closing spring is automatically recharged by the motor mechanism immediately after the breaker is closed. On-hand operated breakers, the closing can be recharged by hand. 3-3. Opening (See Fig.3) The tripping spring is charged during closing operation. Press the manual trip button to open the vacuum circuit breaker. The ON-OFF indicator will show OFF. 3-4. Putting into SERVICE and ISOLATED operation (See Fig.3,4) When setting the VCB in switchgear, use the following procedure. (1) Confirm the VCB is OFF position. (2) Slide the VCB handle inward. (3) Insert the VCB into switchgear. (4) Confirm the VCB is located in proper position. (5) Slide the VCB handle outward. (6) Connect the cable connector. When setting the VCB from the ISOLATED to the SERVICE position, use the following procedures. (1) Confirm the VCB is OFF position. (2) Insert the draw out handle to the shaft for draw in and out, and rotate clockwise until a clicking sound is heard. This position is SERVICE position. (3) When the vacuum circuit breaker is set from the SERVICE to the ISOLATED position, insert the draw out handle into the VCB shaft and rotate un-clockwise until a clicking sound is heard. This position is ISOLATED position.

MANUAL TRIP BUTTON MANUAL CHARGING MANUAL CLOSE BUTTON ON-OFF INDICATOR PIN FOR DRAW IN AND OUT CHARGE-DISCHARGE INDICATOR Handle Fig.3 MANUAL OPERATING POSITION DRAW OUT HANDLE Handle Fig.4 OPERATING CONDITION

4. UNLOADING AND PREPARATION FOR OPERATION 4-1. Unloading Use crane or fork lift, operate it slowly not to give any shock to the vacuum circuit breaker. 4-2. Unpacking It is recommended unpack the circuit breaker earlier when it is arrived. Be careful, not to damage the circuit breaker especially insulating material, vacuum interrupters, main circuit connectors and front panel. 4-3. Transportation Lift the circuit breaker as illustrated in Fig.5 if necessary. Don t hold upper conductor and lower conductor to move the circuit breaker. Fig.5 Lift the circuit breaker

4-4. Checking after unpacking Check the following and report to Meidensha or representing organization when any defect is found. (1). Quantity, Type, Ratings and etc. (2). Damages such as bends, cut and serious scratches. (3). Loss or loose fitting of bolts and nuts. (4). Quantity and Type of accessories and spare parts it any. 4-5. Storage It is recommended to put the circuit breaker into operation as soon as possible after unpacking. However, if storage is un-avoidable, the followings shall be observed. (1). Store unpacked. (2). Store indoor on flat floor, in clean and dry atmosphere without corrosive gas, water and dust (especially cement dust). (3). Cover with plastic sheet to protect dust, small animals, insects especially spiders invasion. (4). Open circuit Breaker and release closing spring. 4-6. Inspection during storage If longer storage is un-avoidable, check the followings yearly. (1). Rust, if any remove it. (2). Dust, dirt and spider web on surface of insulating material, if any clean with dry clean cloth. (3). Loss or loose fitting of bolts and nuts, and damages. 4-7. Installation (1). Confirm the circuit breaker is open and closing spring is discharged with respective mechanical indicator. (2). Check the circuit breaker following to the previous Item 4-6. 4-8. Inspection and procedure before operation (1). Measure insulation resistance by 1000V and 500V megger. The following shall be observed. Phase to phase of main circuit ; 500MΩ Main circuit to earth ; 500MΩ Control circuit to earth ; 2 MΩ (2). Check smooth operation of circuit breaker in-out to and from the cubicle, and interlocking mechanism.

(3). Check circuit breaker operation manually first. Place the circuit breaker at isolated position, and operate the MCCB for control and motor circuit to OFF position. Charge closing spring with manual charging handle and close circuit breaker with manual closing button after charge the spring fully. (4). Be cautions not to leave any tools and material at the circuit breaker. 5. MAINTENANCE AND INSPECTION Basic interval of inspections is show in Table as practical interval, is to be decided by the usage condition and frequency of operation etc. It is recommended to carry out periodical inspection after one year operation then settle the interval by the result. Circuit Breaker shall be replaced when the number of operation is reached to the following figure. Number of mechanical operation 10,000 times Number of electrical operation Rated load current interruption Rated breaking current interruption 10,000 times 30 times 5-1. Caution at inspection The following items shall be observed for inspection. (1). Keep off dangerous zone of the circuit breaker when inspect alive. (2). Don t drop tools or other materials while working. (3). After the inspection. a). Don t leave any tools and materials. b). Don t forget tighten the bolts and nuts loosened work. c). Clean insulating material and vacuum interrupters with dry clean cloth. (4). Tightening torque of bolts and nuts are shown in Table 2. Table 2. Bolt diameter Standard Torque Nm (kgfcm) 3 4 5 6 8 10 12 78 Ncm (8 kgfcm) 186 Ncm (19 kgfcm) 392 Ncm (40 kgfcm) 637 Ncm (65 kgfcm) 1500 Ncm (154 kgfcm) 3020 Ncm (308 kgfcm) 5190 Ncm (530 kgfcm)

5-2. Patrol inspection It is recommended to inspect the alive circuit breaker visually keeping off dangerous zone on each patrol. If any abnormality is found, stop operation immediately and investigate the circuit breaker. No. Item Contents Remarks 1 General Condensation, ingress of dust, rain. Abnormal sound, smell, color. 2 ON-OFF indicator Normal or not 3 Charge-Discharge Normal or not indication 4 Operation counter Check No. of operation. Replace circuit breaker, if the No. is 10000 or more. 5-3. Periodical inspection It is recommended to carry out periodical inspection on the circuit breaker each 3 years basically. However, the practical interval is to be decided by location, frequency of operation and etc. No. Classification Items Contents Basic period 1 Circuit breaker General Record No. of operation. Clean dust, dirt, moisture with dry three years general clean cloth. Check breakdown or damage. 2 Pole unit Insulating Material Clean dust, dirt, moisture with dry clean cloth. three years The detail is show in Figs. 9. Main circuit conductor Check loose fitting of bolts and nuts. three years 3 Operating mechanism General Clean all parts, check loose fitting of bolts and nuts. three years Check loss or damage of stopper and etc. Oiling Oil with Topas JL15 Fluid (Synthetic hydrocarbon) at three years specified position (NOK KLUEBER make). The detail is show in Figs. 6, 7. 4 Control device General Check rust or loosing of connection at terminal. three years

No. Classification Items Contents Basic period 5 Operation test 6 Insulation resistance ON-OFF operation Main circuit Control circuit Operate manually and electrically few times each, and check operation of all parts. Check ON-OFF and Charge-Discharge indicator. Measure insulation resistance with 1000V meggar. If below 500MΩ for phase to and phase to earth, investigate the cause. Measure insulation resistance of control circuit to earth 500V meggar. If bellow 2MΩ, investigate the cause. three years three years three years Application Part Name Main Manufacture compounds Uncovered friction part TOPAS L52 Synthetic NOK Co. (Gear teeth, etc.) Covered friction part (Bearings, etc.). (Grease) TOPAS JL15 FLUID (Oil) hydrocarbon oil with lithium soap NOTE: Any other lubricants must not be used. In the serious case, using others may result in a malfunction of the mechanisms.

Fig.6 Lubrication points Operator mechanism

Fig.7 Lubrication points Operator mechanism

5-4. Detail inspection Inspect the following item in addition to the item in 5-3 periodical inspection. No. Classificatio Item Contents Basic period n 1 Pole unit Vacuum degree Use vacuum checker or apply AC22kV for 1min across the six years contact. No flashover : good. Main circuit contact Make sure of the state of grease, wipe off old grease if needed, and six years apply new grease to the contact section. Grease uses MOLYKOTE BR2 plus. The detail is show in Figs. 10. 2 Operating mechanism Dimensions Check gap between tripping coil and trip hook to the Fig. 8. six years Springs Check rust, flaws or deformation six years Coils Check continuity and loose terminal. six years 3 Operation test Operating characteristi cs Confirm no abnormality with manual operation and test with electrical operation. See the criteria below and if exceed the limit, investigate the cause. six years Item Criteria Spring charge Min. operation voltage Less than 85% Charging time Less than 15sec Closing operation Min. operation voltage Less than 75% Closing time Less than 60ms Opening operation Min. operation voltage Less than 60% Opening time Less than 50ms

A B 0.5~1.5mm 19~21mm Fig.8 Clearance

the dry, clean rag is used for cleaning. Wipe the insulation frame and insulation cover of dust. It is checking the existence of cracks, when insulator cleans. Insulation cover Insulation frame Fig.9 Cleaning part Contact 1 The old lubricate (6 places) applied to contact is wipe off. 2 The new lubricate is applied to contact. Lubricate : MOLYKOTE BR2 plus Contact Fig.10 Lubrication point

5-5. Special inspection This test shall be carried out before detail test (5-4) when no. of current interruption of vacuum interrupter is reached to the following figure. No. of interruption Fault current about 20 times. Load current about 5,000 times. Items Detail inspection (5-4) 5-6. Trouble shootings In case of replacement, disassembling and reconditioning, please contact the manufacturer. Trouble 1 Trouble 2 Trouble 3 Cause Action Closing Motor not failure moving Closing spring is not charged Closing spring charged Motor Moving Closing magnet (52C) not moving 1. Power source abnormal 1 Faulty connector contact 2 Switchgear side power source abnormal 2. 52X1, 52X2 Not moving 1 Coil opening circuit 2 Limit switch contact fault 3. 52X1, 52X2 Contact faulty 1 Contact drop out or stained 1 Replacement of connector 2 Investigation of cause 3 Replacement of PCB 4 Replacement of limit switch Replacement of PCB 4. Motor faulty Replacement of motor 5.Rectifier faulty Replacement of PCB 1. Decelerator faulty 1 Replacement 1 Shaft broken decelerator and motor 2 Replacement of decelerator 2. Pushing claw faulty 1 Reset speed Decreased 1. Power source faulty 1 Connector contact faulty 2 Switchgear side power source faulty Investigation of cause 1 Replacement of connector 2 Investigation of power supply

Trouble 1 Trouble 2 Trouble 3 Cause Action 2. Closing control circuit Replacement contact faulty 1 52Y b-contact faulty 2 52X1 b-contact contact faulty 3 52 b-contact faulty 3. 52C Open circuit Replacement of 52C 4.Rectifier faulty Replacement of PCB Closing failure Tripping failure Closing spring charged Tripping magnet (52T) not moving Tripping magnet (52T) moving Closing magnet (52C) moving 2. Closing hook load is Increased. 1 Due to aged grease, closing latch load is increased. 1. Power source faulty 1 Connector contact faulty 2 Switchgear side power source faulty 1 Lubrication or disassembling reconditioning 1 Replacement of connector 2 Investigation of power supply 2. Auxiliary contact faulty Replacement of auxiliary switch 3. 52T open circuit Replacement of 52T 4. Magnet faulty 1 Moving iron core jammed. Disassembling or replacement 5. Rectifier faulty Replacement of PCB 1. Load increment of Disassembling tripping hook or roller reconditioning 1 Degrading of grease 2 Foreign material ingress into bearing 2. Abnormal engagement between tripping hook and roller 1 Grease adherence 2 Foreign material ingress 3 Rusting 4 Deformation 1 Disassembling or reconditioning 2 Disassembling or reconditioning 3 Replacement 4 Replacement