Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

Similar documents
Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

Compact Circuit Protector (CCP) Application Note

Now - Up To 400A Mains!

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

Electrical Safety and Reliability: Short-Circuit Current Rating (SCCR) Equipment SCCR made easy

The easiest and fastest way to select and specify the right fuse

Devices for Branch Circuits and Feeders

Downtime Reduction, Workplace Safety & Code Compliance SERVICES TO INCREASE YOUR PRODUCTIVITY THROUGH PROTECTION

Photovoltaic System Overcurrent Protection

Photovoltaic System Overcurrent Protection

Selecting Protective Devices

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

A case study in solving SCCR issues

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

Selective Coordination Enforcement:

Quik-Spec Coordination Panelboard

HVAC and Refrigeration Circuit Protection Solutions. Compact and safe HVAC/R circuit protection

Suggestion on How to Use

Selective Coordination

Fuseology. Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression. Optima Fuse Holders & Overcurrent Protection Modules.


KT7. Methods. of Applying. & Molded Case Circuit Breakers F119. Motor Circuit Controllers

Low Voltage Fuses For Motor Protection

Application note Compact Circuit Protector (CCP2) Smaller, better... the Power of Space

What's New with UL508A Codes & Standards Presented by Jeff Woolfolk Manufacturing in America March 14-15, 2018

Selective Coordination Requirements

Short-Circuit Current Rating - SCCR Watlow Power Controllers

ECET Circuit Design Motor Loads. Branch Circuits. Article 210

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

FUSES VERSUS CIRCUIT BREAKERS FOR LOW VOLTAGE APPLICATIONS

MAGNETIC MOTOR STARTERS

ACW Molded-Case Circuit Breaker UL 489 Listed

The easiest and fastest way to select and specify the right control circuit fuse

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

NH Dual NHIndicator Fuse System Fuse System

Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals?

Applying Interrupting Rating: Circuit Breakers

Applying Interrupting Rating: Circuit Breakers

Bussmann series Quik-Spec Coordination Panelboard

SIGNAL WORDS QUALIFIED PERSON

Solar Combiner Solutions

Electrical Safety and Overcurrent Protection

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

Overcurrent Protection According to the 2011 NEC

Panel SCCR 50kA RMS Symmetrical 480V Maximum

Specification made simple for selective coordination in a compact size

Selection Guide Motor Control Device Solutions

Low-Peak 600V Class RK1

Series KTU7 UL489 Molded Case Circuit Breakers

Motor Protection. Presented By. Scott Peele PE

FUSE: SAFE & RELIABLE

Products for enhancing electrical safety and reliability

ECET Distribution System Protection. Overcurrent Protection

Type E/F Simplex & Duplex Pump Controllers

Overcurrent protection fundamentals

Series KTU7 UL489 Molded Case Circuit Breakers

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

Fuseology. Dual-Element, Time-Delay Fuse Operation

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Compact Modular Fuse Holders With the Industry s Best Ratings Products for PV, IEC and UL Applications

Equipment Protection. Transformers 600V or Less

ECET 211 Electric Machines & Controls Lecture 1-3 (Part 2) Electrical Safety in the Workplace Electrical Safety in the Workplace

TeSys Motor Starter Solutions for the North American Market

A. Submit manufacturer's literature and technical data before starting work.

Fuseology. High Speed Fuses

Motor Protection. Voltage Unbalance & Single-Phasing

Equipment Protection. Transformers 600V or Less

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Quik-Spec Electrical Gear

Service Entrance Methods

Cooper Bussmann. Guide. Downtime Reduction, Workplace Safety & Code Compliance. Section Contents

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse

BRANCH CIRCUIT PROTECTION FUSED COORDINATION PANELBOARD

ACHIEVING MAXIMUM BENEFITS WITH A FUSE PROTECTED MOTOR CONTROL CENTER

Miniature circuit breaker Application guide

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

Selective Coordination

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Quik-Spec Coordination Panelboard

CENTERLINE 2100 Motor Control Centers

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Harmonization of IEC and North American Safety Standards

ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits

Horizontal Circuit Switchers

IN2 Enclosed Switches and Circuit Breakers

Equipment Protection. Listed or Labeled Equipment. Panelboards. Branch Circuit Protection HVAC. Appliances. Supplementary Protection

WARREN COUNTY, N.Y. M/E REFERENCE

Quick Start Guide TS 910 & TS 920

Multi-Pak Group Control

Ferrule fuses. High Speed Fuses

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

Industry Automation Control Components

TERMS AND DEFINITIONS

Application Techniques. North American Standards, Configurations, and Ratings: Introduction to Motor Circuit Design

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

Power System Solutions (PSS)

F Motor Circuit Controllers. Series KT7 Motor Circuit Controllers. KT4 Manual Motor Starters. General Description...F2

C E R T I F I C A T E O F C O M P L I A N C E

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

Transcription:

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

Are You Ready For The New SCCR Marking Requirements? What Is A Short-Circuit Current Rating (SCCR)? SCCRs on components and assemblies represent the maximum level of short-circuit current that the component or assembly can withstand and is used for determining compliance with NEC 110.10.This rating can be marked on individual components or assemblies. Assembly ratings take into account all components contained within the equipment. A common mistake is to assume that the interrupting rating of the overcurrent protective device protecting the circuit represents the SCCR for the entire circuit. Interrupting ratings, used for compliance with NEC 110.9, apply solely to the overcurrent protective device. It is the characteristics of the overcurrent protective device (e.g. opening time, let-through energy) that need to be used in determining compliance with NEC 110.10, not the interrupting rating. CAUTION: Short-circuit current ratings (SCCRs) are different than interrupting ratings marked on overcurrent protective devices. Who Is Affected By The SCCR Markings The 2005 NEC has requirements for anyone building equipment listed to the 2005 NEC or to UL508A and requires the following to be marked with an SCCR: Industrial control panels [409.110 ] Industrial machinery electrical panels [670.3(A)] HVAC equipment [440.4(B)] Meter disconnect switches [230.82(3)] Motor controllers [430.8 ] Effective April, 2006, all equipment listed to UL508A will be required to be marked with an assembly SCCR. Inspectors and installers need this information in order to ensure compliance with NEC 110.10. Equipment installed where fault current levels exceed their shortcircuit current can be hazardous to persons and property. SCCRs marked on components and assemblies make it easier to verify proper protection for components and assemblies for specific applications whether it be the initial installation or relocation of equipment. How Is SCCR Determined? For meter disconnect switches and motor controllers, this withstand level or SCCR is often determined by product testing. For assemblies, the marking can be determined through product listing or by an approved method. With the release of the UL508A Industrial Control Panel standard, an industry approved method is now available. Any method used, whether UL508A or another approved method, should be based upon the weakest link approach. In other words, the assembly should be limited to installation where fault levels do not exceed the withstand rating of devices with the lowest SCCR.The marking determined should represent the limits of the assembly for a safe installation. Current-limiting overcurrent protective devices can be used in the feeder or branch circuits to increase the assembly SCCR where lower rated components are used. Who Is Affected Facility/Process Engineers/ Consulting Engineers Control Panel Builders/ Machine Builders/ HVAC Manufacturers Electrical Contractors Electrical Inspectors How Are They Affected Need to specify end use equipment with ratings adequate for available short-circuit current. Need to determine and mark the assembly short-circuit current rating on the equipment being built. Need to market equipment with ratings at least as high as their competition. Need assurance that the equipment installed is adequate for the available short-circuit current at the point of installation, to avoid red tags and lost time and labor. Need to assure that the available short-circuit current where equipment is being installed does not exceed the rating marked on the equipment.

Use this table to initiate the process of identifying the short-circuit current rating of your components and devices in power circuits. For further information contact your local Cooper Bussmann sales engineer, Cooper Bussmann Application Engineering, or visit www.cooperbussmann.com. Supply and OCPD Branch Circuit Fuses UL489 Circuit UL98 Fusible UL98 Non-Fusible UL1429 Pullout 200kA* 5kA 200kA* 5kA 10kA 5kA Molded Case Switch Feeder Circuit OCPD and Components Branch Circuit Fuses UL489 Circuit UL98 Fusible UL98 Non-Fusible Power Distribution Blocks 200kA* 5kA 200kA* 5kA 10kA 200kA* Fuse Holder Branch Circuit OCPD and Components 200kA* Branch Circuit Fuses UL489 Circuit UL98 Fusible 5kA 200kA* 5kA UL98 Non-Fusible Magnetic Motor Starter Type E Self Protected Starter 5kA Molded Case Switch + Instantaneous Trip Circuit *Class CC, J, T, R, and L UL248 Branch Circuit Type Fuses. **When used in conjunction with Class CC, J, T, R, and L UL248 Branch Circuit Type Fuses. ***50HP or less 480V Default value increases to 10kA when protected by fuses +Combination Rating is used for Sweep 1. For Sweep 2 IR=5kA (Default Value)

Default Value Your Value Glossary of Terms Industrial Control Panel - An assembly of a systematic and standard arrangement of two or more components such as motor controllers, overload relays, fused disconnect switches, fuses, and circuit breakers and related control devices such as pushbutton stations, selector switches, timers, switches, and control relays with associated wiring, terminal blocks, pilot lights and similar components. Interrupting Rating - The highest current at rated voltage that a device is intended to interrupt under standard test conditions. 10kA Busbar 5kA Molded Case Switch Short-Circuit Current Rating The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding the defined acceptance criteria Control Circuit A circuit that carries the electric signals directing the performance of a controller, and which does not carry the main power circuit. A control circuit is, in most cases, limited to 15 amp. Power Circuit Conductors and components of supply, branch, and feeder circuits, supplying main line power to loads such as heaters, motors, lighting, receptacles, power transformers, and appliances. Fuse Holder UL508 Manual Motor Starter UL508 Switch Drives Contactors Receptacle GFCI Receptacle 200kA* 10kA 2kA

Find It, Fix It, Forget It FIND IT Look for... the Weakest Link The SCCR marking for the assembly will be based upon the lowest short-circuit current or withstand rating of any power circuit component contained within the assembly or the weakest link. Many components used in industrial control panels, industrial machinery and HVAC equipment may be the weakest link, including: motor controllers definite purpose contactors supplemental protectors circuit breakers (with low interrupting ratings) power distribution blocks. FIX IT How To Get A Higher SCCR So Equipment Isn t Limited By fixing these weakest links, higher SCCRs can be achieved. In general, there are three options: 1. Use overcurrent protective devices with higher interrupting ratings Overcurrent protective devices with low interrupting ratings often become the weakest link and limit the SCCR of the assembly. The interrupting ratings of the overcurrent protective devices used directly affects the assembly rating. The only fix is to use devices with higher interrupting ratings. 2. Use current limitation to fix low rated components It only takes one component with a low SCCR to limit the entire assembly. Many of the components used in industrial control applications have low short-circuit current ratings. Fix these low rated components and the assembly rating by using current limitation. Since current-limiting fuses reduce high level short-circuit currents to a minimal level, they allow the use of these lower rated devices while providing a higher SCCR. 3. Buy more expensive components with higher ratings A 65kA circuit breaker will more than double your cost compared to a 14kA circuit breaker. The fusible solution provides an interrupting rating as high as 200kA, at a comparable cost to your existing design, making it the most economical solution. FORGET IT Use Current-Limiting Fuses Not only can modern current-limiting fusible solutions fix undesired weak links and obtain a high assembly short-circuit current rating, they can also provide enhancements to your design in the areas of flexibility of installation, increased workplace safety, and reliable protection through the life of your equipment. These enhancements take care of the hassle associated with equipment with limited ratings so you can FORGET IT! Benefits of Using Cooper Bussmann Current- Limiting Fuses Straight Voltage Ratings: Straight voltage ratings allow for more installations where equipment can be installed. Straight voltage rated equipment can be installed in any type of electrical system. With a straight voltage rating you can ship it anywhere and not have to worry. High Assembly SCCRs: High SCCRs allow for more applications where equipment can be installed. With a high SCCR you can ship it anywhere and not have to worry. A wider range of fault current levels provides assurance that the equipment will be installed correctly and safely. Meets the UL508A and NEC requirements for SCCR marking. Marketing advantage over competitive equipment with a lower rating. Increased Flexibility In Panel Use and Installation: Valuable time that was spent gathering information for proper application is drastically reduced with fuses because modern current-limiting fuses can provide high assembly SCCRs and straight voltage ratings since they have: - High Interrupting Ratings of 200,000A or more - Excellent current limitation to protect low rated components at high short-circuit current levels - Straight voltage ratings so they can be installed in any type of application independent of the grounding scheme used, unlike devices with a slash voltage rating which are limited to installation in ONLY a solidly grounded wye type system

Cooper Bussmann Products And Technical Support Delivered Worldwide Customer Assistance Customer Satisfaction Team The Cooper Bussmann Customer Satisfaction Team is available to answer questions regarding Cooper Bussmann products and services. Calls should be made Monday Friday, 8:00 a.m. 4:30 p.m. Central Time for all US time zones. The Customer Satisfaction Team can be reached via: Phone: 636-527-3877 Toll-free fax: 800-544-2570 E-mail: busscustsat@cooperbussmann.com Emergency and After-Hours Orders To accommodate time-critical needs, Cooper Bussmann offers emergency and after-hours service for next flight out or will call. Customers pay only standard price for the circuit protection device, rush freight charges and a modest emergency fee for this service. Emergency and after-hours orders should be placed through the Customer Satisfaction Team. Call: Monday Friday, 8:00 a.m. 4:30 p.m. Central Time 636-527-3877 After hours 314-995-1342 Application Engineering Application Engineering assistance is available to all customers. The Application Engineering team is staffed by degreed electrical engineers and available by phone with technical and application support Monday Friday, 8:00 a.m. 5:00 p.m. Central Time. Application Engineering can be reached via phone, fax or email: Phone: 636-527-1270 Fax: 636-527-1607 E-mail: fusetech@cooperbussmann.com Online Resources Visit www.cooperbussmann.com for the following services: Product cross reference Arc-flash calculator SCCR calculator Training modules Your Authorized Cooper Bussmann Distributor is: 2005 Cooper Bussmann St. Louis, MO 63178 636-394-2877 www.cooperbussmann.com Printed in USA Reorder #7009 1-06-5M