Minera. Oil distribution transformers up to kva. eco design. Minera at a glance. Standards

Similar documents
Certified for best-in-class performance, reliability, and safety. Trihal sets a new standard for dry-type cast resin transformers

BC IMPREGO Impregnated dry type transformers and autotransformers

History of the company. TUMETIC and TUNORMA: Tailor-Made Technology

Key features. DESIGNS: - Conservator type - Hermetically sealed

ABB Transformers Egypt

TGK Prefabricated Substation Technical Data

CBGS-0. Medium voltage distribution

ÒÌÃ TRANSFORMERS. ÒÌÃ 1250 kv.a

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

1500 kva Pad Mount Transformer GRDY/14400V Primary - 208Y/120 Wye Secondary - Oil Cooled

tests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.

Schneider Electric PV Skid. Optimized solar power conversion system tailored to enhance any North American PV power plant

INESING GROUP. Power System Solution

Current transformers

Distribution Transformers. The most comprehensive range of solutions for distribution transformer applications

Maximum temp. rise in oil by 40 thermometer above design ambient (deg C) specified time Short circuit rating (Sec) for As per IS 2026

Green T.HE. High efficiency Transformers. THE Global specialist in electrical and digital building infrastructures

Distribution transformers Efficiency over life-cycle

ABB Ltd. FACTORY IN HANOI

TeSys Enclosed Starters. Let TeSys watch over your machinery

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

PIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution

Cast resin transformers

500 kva Pad Mount Transformer V Delta Primary - 208Y/120 Secondary - NEMA 4X - Oil Cooled

Powering industry since 1947.

OLIVER ONLINE VOLTAGE REGULATION

The PowerLogic wireless range is designed to retrofit existing switchboards, and enhance energy efficiency of buildings in operation for many years.

CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION

TeSys D, K. Catalogue 2017 'S335' series contactors for electrodomestic applications. schneider-electric.com

TeSys Enclosed Starters. Let TeSys ensure safety in your simple motor applications

CAST RESIN TRANSFORMERS

I B D Q I B D Q O I B D Q O

Maximize your ROI. Conext CL-60 String Inverter. The ideal solution for decentralized power plants and commercial rooftops

SECTION PADMOUNT TRANSFORMER - OIL FILLED

AC/DC Arc Furnace and Ladle Furnace Transformers

DISTRIBUTION TRANSFORMERS CATALOGUE

Cloud-connected solution for utility-scale renewable power

Medium Voltage Distribution Catalogue Flusarc Make the most of your energy

MEDIUM POWER TRANSFORMER

Compact Integrated Distribution Substation (CIDS)

Galaxy Receiving and Unpacking 09/

HVX Series. 36 kv Medium Voltage Vacuum circuit breaker. Make the most of your energy SM. Medium Voltage Distribution Catalogue 2015

A flexible and efficient residential solar solution. Conext RL single-phase grid-tie inverter

COMPACT SUBSTATION GUIDE

Transformer Stations

Power IT Liquid Filled Transformers. IEC standard, small and medium, rated power 2000kVA, HV 36kV

Cloud-connected solution for utility-scale renewable power

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

P2 : About Us. P3 : Elsewedy Transformers. P4 : Why Elsewedy Dry Type Transformer? P6 : Cast Resin Dry Transformers. P7 : Technical Data Sheets

MCset 17.5 kv. Civil engineering guide April Medium Voltage Distribution

Simple and smart power factor correction

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

Square D General Purpose Relays

vertical fuse switch disconnectors

Technical Specification of GECOL. Packaged Transformers

Electrical network protection VIP30, VIP35. User s manual 12/2008

Fuji Electric. Oil immersed. Transformer FTU08A1-E-0024

YOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

Protection and control VIP30, VIP35. Relays technical manual

Electrical network management. Schneider Electric. Acti 9 iem2000 Technical Datasheet

TAE pole Contactors

DRY TYPE TRANSFORMERS

DRY TYPE TRANSFORMERS

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer

Easy Choice for Energy Efficiency

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

Study and operate the protection features associated with the neutral plans with manual troubleshooting. S.L.T.-TR22 Bench

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

The construction features of EdM transformers

DM Condenser bushings, kV DURESCA

HPS EnduraCoil. Cast Resin Transformer

Medium voltage NEX switchgear Withdrawable circuit breaker. Quite simply efficient

Clean and Compact MV Drive

Medium Voltage Distribution. Fuses. from 3.6 to 36 kv. Catalogue 2012

TRANSFORMERS UP TO 750 kv

Quality Reliability Flexibility. Trasformatori di potenza in olio Oil Transformers

Medium Voltage Distribution FLUSARC P-LA. Up to 36 kv 630 A 25 ka. Catalogue 2010

Electrical distribution and safety for homes Catalogue SquareD Consumer units and protection devices

www. ElectricalPartManuals. com Substation Transformers Primary or Secondary Open

www. ElectricalPartManuals. com WeSTinghouse Secondary Unit Substation Transformers (Power Centers) Descriptive Bulletin Page 1

750 kva Transformer V Delta Primary Voltage - 480Y/277 Wye-N Voltage Secondary - NEMA 3R

PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Wiring devices Asfora 2015 catalogue

Technical Data. Low Voltage Regulation System LVRSys. Flexible solution for power utilities. Voltage stabilization for industrial grids

Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC

2013 JEAN MÜLLER Products

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker

Clean and compact drive for energy savings. Altivar Medium-voltage variable speed drive 0.3 to 10 MW

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

GENERAL INFORMATION POLE MOUNT TRANSFORMER SINGLE PHASE PAD MOUNT TRANSFORMER SINGLE PHASE POLE MOUNT TRANSFORMER THREE PHASE 17

Galaxy VX Battery Breaker Trip Board (GVXBBTB) and Battery Breaker Capacitor Board (GVXBBCB)

A VIETNAMESE MEMBER OF A WORLD - WIDE FAMILY

www. ElectricalPartManuals. com Substation Transformers Primary or Secondary Unit

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

Galaxy VM. Battery Breaker Box Installation 09/

Medium Voltage Distribution Maintenance Guide I 2013 Premset. 15 kv compact modular vacuum switchgear with Shielded Solid Insulation System

INESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation

Transcription:

Minera Oil distribution transformers up to 3 150 kva Minera at a glance Mineral oil-immersed, 50 Hz, three-phase distribution transformers with the following characteristics: Hermetically sealed with integral filling Cover bolted to the tank ONAN Mineral oil in accordance with IEC 60296 Indoor / outdoor use (depending on selected fittings and options) Anti-corrosion surface treatment: corrositivity category class C3, Medium durability (according to ISO 12944-2) inal colour RAL 7033 Standards These transformers comply with standards: EN 50588-1 (supersedes EN 50464-1:2007, EN 50541-1:2011) EN 60076-1 Ecodesign regulation EU 548-2014 eco design

Overview schneider-electric.com 2 Standard fitting One 3 or 5 positions de-energized tap changer on the cover, with padlocking facility 3 HV porcelain bushings amps (plug-in bushings available) on tank cover 4 LV flat bars starting from 50 kva 4 LV porcelain bushings (from 50 to 3 150 kva) 4 bidirectional flat rollers, lifting and untanking lugs 2 pulling eyes on the frame 2 s on the cover 1 filling plug 1 draining device according to EN 50216-4 or DIN 42551 1 aluminium rating plate Rating Plate Minimum info that needs to be stated on the rating plate in addition to EN 60076-1 standards. P0, the measured no load loss at rated voltage and rated frequency, on the rated tap The name of the no load loss class for transformers with Sr 3 150 kva Pk, the measured loss at rated current and rated frequency on the rated tap corrected to reference temperature according to EN 60076-1 The name of the load loss class for transformers with Sr 3 150 kva or dual voltage transformers, the maximum rated power at the lower voltage Conductor mass and the nature of the conductor Core mass and the nature of the core material or medium power pole mounted transformers, a visible display or pole-mounted operation only Options Protection relays (DMCR or DGPT2 ) on the filling plug 1 free, thermometer pocket Control device in the thermometer pocket (pointer thermometer with 0 or 2 contacts max, 2-contact thermostat, etc.) 3 HV porcelain bushings A (plug-in bushings available) on tank cover 4 LV porcelain bushings on tank cover (available from 50 kva) LV, cable box IP21 or IP54 Locking device for plug-in bushings (with or without lock) 3 mobile connectors for plug-in bushings straight or elbow (cable characteristics must be specified) Liquid retention bund The above options concern usual cases and are not restrictive. or additional information, please consult Schneider Electric.

Overview schneider-electric.com 3 Ecodesign regulation EU 548-2014 Maximal Loss levels Statement on Loss tolerances: - No tolerance on transformer design - 5% tolerance for end user checks Additional data requested on the name plates - Loss level and measured values - Type and weight of mail materials used - CE Marking is MANDATORY Minera Oil Type Transformers maximum loss levels according to Ecodesign: Insulation voltage MV 24 kv & LV 1.1 kv - A0Ck kva - A0Bk > kva Insulation voltage: MV 36 kv & LV 1.1 kv - A0 +15% Ck +10% kva - A0 +15% Bk +10% > kva DM105300 A 0 A k B k C k D k

A0AK schneider-electric.com 4 Electrical characteristics Power (kva) 50 100 160 200 315 0 500 800 1 1600 0 Primary voltage (V) 0 Isolation level (kv) up to 24 Secondary voltage (V) HV tapping range (%) Vector group 0 ±2x2,5 Dyn No-load losses (W) 90 145 210 300 360 430 510 600 650 770 950 1200 1450 1750 Load losses at 75 C (W) Impedance voltage (%) HV bushings acc.din LV bushings acc.din 875 1475 2350 2750 3 3850 4600 50 7000 9000 1 100 18000 2 4 20/30 0 Max. altitude (m) Max ambient temperature ( C) MV/LV windings material AI/AI

A0AK schneider-electric.com 5 Dimensions and weights Bushings are marked according to IEC standard. SM27 SM26 lifting lug HV side tap changer D: Height over LV cable box (optional accessory, compatible with HV plug-in bushings only). Dimensions and weights are for guidance only. K D C 125 J 38 B free thermometer pocket rating plate 1W 1V 1U 2W 2V 2U 2N H H H A filling plug corrugated panels in the corners according to cooling needs LV side Dimensions Rated power (kva) 50 100 160 200 315 0 500 800 1 1600 0 Lenght A 1080 1080 1160 1180 1210 1260 1 1320 1350 1600 1580 1810 2010 2180 2390 Width B 7 7 760 760 780 800 800 930 930 990 1080 1080 1180 1350 1350 Height on cover C 695 775 715 1025 855 1135 1005 1275 1275 1295 1445 1445 1595 1805 1967 Height on bushings D 1080 1160 1100 1410 12 1520 1390 1660 1620 1680 1830 1830 1980 2190 2420 Distance between HV bushings Distance between HV bushings H 265 265 265 265 265 265 265 265 265 265 265 265 265 265 265 150 150 150 150 150 150 150 150 150 150 150 150 165 165 220 Roller distance J 520 520 520 520 520 670 670 670 670 670 820 820 820 1070 1070 Roller diam I 125 125 125 125 125 125 125 125 125 125 160 160 160 200 200 Roller K 92.5 92.5 92.5 92.5 92.5 92.5 92.5 92.5 92.5 92.5 117 117 117 1 1 Weight (kg) Rated power (kva) 50 100 160 200 315 0 500 800 1 1600 0 Total weight 580 7 1090 1190 1430 1600 1880 2110 2520 3030 3170 3890 4800 5670 Oil weight 198 192 195 231 252 290 315 376 398 501 601 611 670 895 1060

schneider-electric.com 6 A0BK Electrical characteristics Power (kva) 50 100 160 200 315 0 500 800 1 1600 0 Primary voltage (V) Isolation level (kv) Secondary voltage (V) HV tapping range (%) Vector group No-load losses (W) Load losses at 75 C (W) Impedance voltage (%) HV bushings acc.din LV bushings acc.din Max. altitude (m) Max ambient temperature ( C) MV/LV windings material 0 up to 24 0 ±2x2,5 Dyn 90 145 210 300 360 430 510 600 650 770 950 1200 1450 1750 2200 875 1475 2350 2750 3 3850 4600 50 7000 9000 1 100 18000 2 27500 4 6 20/30 AI/AI 0 3/4500 1/5000

A0BK schneider-electric.com 7 Dimensions and weights Bushings are marked according to IEC standard. SM27 SM26 lifting lug HV side tap changer D: Height over LV cable box (optional accessory, compatible with HV plug-in bushings only). Dimensions and weights are for guidance only. K D C 125 J 38 B free thermometer pocket rating plate 1W 1V 1U 2W 2V 2U 2N H H H A filling plug corrugated panels in the corners according to cooling needs LV side Dimensions Rated power (kva) 50 100 160 200 315 0 500 800 1 1600 0 Lenght A 1080 1080 1160 1180 1210 1260 1 1320 1350 1600 1580 1810 2010 2180 2390 2350 Width B 7 7 760 760 780 800 800 930 930 990 1080 1080 1180 1350 1350 1310 Height on cover C Height on bushings D Distance between HV bushings Distance between HV bushings H Roller distance J 695 775 715 1025 855 1135 1005 1275 1275 1295 1445 1445 1595 1805 1967 1780 1080 1160 1100 1410 12 1520 1390 1660 1620 1680 1830 1830 1980 2190 2420 0 265 265 265 265 265 265 265 265 265 265 265 265 265 265 265 265 150 150 150 150 150 150 150 150 150 150 150 150 165 165 220 220 520 520 520 520 520 670 670 670 670 670 820 820 820 1070 1070 1070 Roller diam I 125 125 125 125 125 125 125 125 125 125 160 160 160 200 200 200 Roller K 50 50 50 70 70 70 Sound power level 39 41 44 46 47 49 50 51 52 53 55 56 58 60 63 64 Weight (kg) Rated power (kva) 50 100 160 200 315 0 500 800 1 1600 0 Total weight 580 7 1090 1190 1430 1600 1880 2110 2520 3030 3170 3890 4800 5670 6520 Oil weight 190 185 195 231 252 290 315 376 398 501 601 611 670 895 1060 1190 Conductor weight 60 84 107 124 146 148 191 210 299 411 425 443 575 607 618 868 Core weight 154 277 452 441 500 624 718 820 922 912 1068 1138 1412 1720 2153 2356

A0CK schneider-electric.com 8 Electrical characteristics Power (kva) 50 100 160 200 315 0 500 800 Primary voltage (V) 0 Secondary voltage (V) up to 24 Isolation level (kv) 420 HV tapping range (%) Vector group ±2x2,5 Dyn5 No-load losses (W) 90 145 210 300 360 430 510 600 650 770 Load losses at 75 C (W) Impedance voltage (%) HV bushings acc.din LV bushings acc.din 1100 1750 2350 2750 3 3900 4600 5500 6500 80 10500 4 20/30 0 Max. altitude (m) Max ambient temperature ( C) MV/LV windings material AI/AI

A0CK schneider-electric.com 9 Dimensions and weights Bushings are marked according to IEC standard. SM27 SM26 lifting lug HV side tap changer D: Height over LV cable box (optional accessory, compatible with HV plug-in bushings only). Dimensions and weights are for guidance only. K D C 125 J 38 B free thermometer pocket rating plate 1W 1V 1U 2W 2V 2U 2N H H H A filling plug corrugated panels in the corners according to cooling needs LV side Dimensions Rated power (kva) 50 100 160 200 315 0 500 800 Lenght A 870 980 1110 1130 1120 1170 1230 1 1460 1770 1880 Width B 7 7 7 7 780 910 930 990 10100 1030 1160 Height on cover C 925 965 1005 1045 1025 1045 1025 1235 1275 1295 1485 Height on bushings D 1310 1350 1390 1430 1410 1430 1410 1620 1660 1680 1870 Distance between HV bushings Distance between HV bushings H 265 265 265 265 265 265 265 265 265 265 265 150 150 150 150 150 150 150 150 150 150 150 Roller distance J 520 520 520 520 520 670 670 670 670 670 820 Roller diam I 125 125 125 125 125 125 125 125 125 125 160 Roller K 92.5 92.5 92.5 92.5 92.5 92.5 92.5 92.5 92.5 92.5 117 Weight (kg) Rated power (kva) 50 100 160 200 315 0 500 800 Total weight 460 650 9 1030 1020 1230 1360 1710 1970 2270 2990 Oil weight 111 150 206 220 218 241 260 337 397 455 565

Minera up to 36 kv schneider-electric.com 10 Electrical characteristics up to 36kV AoCk up to 36kV AoBk Power (kva) 50 100 160 200 315 0 500 800 1 1600 0 Primary voltage (V) Isolation level (kv) Secondary voltage (V) HV tapping range (%) Vector group No-load losses (W) Load losses at 75 C (W) Impedance voltage (%) HV bushings acc.din LV bushings acc.din Max. altitude (m) Max ambient temperature ( C) MV/LV windings material 35000 0 up to 36 ±2x2,5 Dyn5 103 166 241 287 345 414 494 586 690 747 885 1092 1380 1667 2012 2530 1210 1925 2585 3025 3575 4290 5060 6050 7150 92 11550 12100 150 19800 24200 30 4 6 /30 Cu/ Cu Cu/ AI AI/ AI 3/4500 1/5000

Minera up to 36 kv schneider-electric.com 11 Dimensions and weights Bushings are marked according to IEC standard. SM27 SM26 lifting lug HV side tap changer D: Height over LV cable box (optional accessory, compatible with HV plug-in bushings only). Dimensions and weights are for guidance only. K D C 125 J 38 B free thermometer pocket rating plate 1W 1V 1U 2W 2V 2U 2N H H H A filling plug corrugated panels in the corners according to cooling needs LV side Dimensions Rated power (kva) 50 100 160 200 315 0 500 800 1 1600 0 Lenght A 1090 1150 12 12 1280 1280 1330 1310 1410 1520 1680 17 1970 2390 2480 2680 Width B 7 480 800 790 820 810 8 1010 910 1030 1100 1050 1120 1390 1370 1500 Height on cover C Height on bushings D Distance between HV bushings Distance between HV bushings H Roller distance J 1150 1130 1260 1310 13 1330 1430 1510 1570 1550 1680 1930 1950 2080 2270 2370 16 1620 1750 1800 1830 1820 1920 2060 20 2170 2420 24 2570 2760 2860 265 265 265 265 265 265 265 265 265 265 265 265 265 265 265 265 150 150 150 150 150 150 150 150 150 150 150 150 165 165 220 220 520 520 520 520 520 670 670 670 670 670 820 820 820 1070 1070 1070 Roller diam I 125 125 125 125 125 125 125 125 125 125 160 160 160 160 200 200 Roller K 50 50 50 50 70 70 Sound power level 29 35 36 43 44 50 47 50 51 51 56 60 58 48 Weight (kg) Rated power (kva) 50 100 160 200 315 0 500 800 1 1600 0 Total weight 660 1080 1280 1430 1480 1620 1920 2170 2480 2830 3230 3970 4300 2160 6 89 Oil weight 215 251 3 375 379 392 465 5 572 666 722 949 996 1116 19 2005 Conductor weight 69 92 78 95 97 130 137 168 199 273 303 376 447 506 577 672 Core weight 167 439 537 603 6 689 791 814 1041 1027 1155 1491 1601 1737 2337 3462 Note: AoCk up to kva and AoBk between kva and kva.

schneider-electric.com/producturl 12 Terminations Rated current (A) LV flat-bars On request 1 1 1 1 1 1 1 1600 0 0 5000 LV porcelain bushings 4500 LV Terminations HV Terminations - EN 50180 SM29 SM28 Ø 11 63 Ø 14,5 1 A 12 52 155 Ø 11 63 97,5 Ø 14,5 1600 A 12 221 52 0 A LV bus-bars terminations - EN 50387 (standard from kva) M 20 178 10 60 60 26 17 Ø 14 263 26 M 30 100 15 3 100 Ø 14,5 Ø 11 A A A A LV porcelain bushings - EN 50386 (standard from 50 to 160 kva option for other powers) 100 50 25 20 Ø 14 M 42 106,5 120 15 12 52 372 50 50 50 120 120 60 30 Ø 14 M 48 20 35 Ø 18 A 150 20 12 45 450 70 70 Ø18 135 50 4500A 120 50 150 25 50 Ø 18 5000 A M 55 20 45 310 SM31 SM30 255 HV plug-in bushings A/24 kv (standard). 35 M 12 200 485 locking device A HV porcelain bushing A (option) 87 290 locking device eco design Schneider Electric Industries SAS 35 rue Joseph Monier 90 Rueil-Malmaison, rance Phone : +33 (0)1 41 29 70 00 SAS capital social 928 298 512 954 503 439 RCS Nanterre www.schneider-electric.com NRJED315632EN -18102016 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.