www. ElectricalPartManuals. com Instructions for Digitrip RMS 500 Trip Unit I.L A Page

Similar documents
www. ElectricalPartManuals. com Instructions for Digitrip RMS 600 Trip Unit I.L A

www. ElectricalPartManuals. com Instructions for Digitrip RMS 700 Trip Unit

Instructions for Digitrip RMS 510 Trip Unit. Page. 1.1 Protection Information UL Listed Devices Test Procedure...

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

Instructions for The Digitrip RMS Pole and 4-Pole Trip Unit Installation and Operation with K-Frame Series C Circuit Breakers

Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

www. ElectricalPartManuals. com !tell Cutler-Hammer I.L A WARNING Instructions for Digitrip RMS 510 Trip Unit

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

Instructions for Digitrip Models 220, 520, 520i, 520M, and 520Mi Trip Units for use only in Cutler-Hammer Magnum and Magnum DS Circuit Breakers

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

Digitrip RMS and Digitrip OPTIM Trip Units Used with R-Frame Circuit Breakers

www. ElectricalPartManuals. com ltciil Cutler-Hammer A WARNING

www. ElectricalPartManuals. com Digitrip RMS Trip Units Used with Type SPB Systems Pow-R Breakers Page

Q and M-Frame Circuit Breaker Instruction Leaflet for Installation and Operation for Thermal Magnetic Trip Units

Advanced Test Equipment Rentals ATEC (2832)

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Instructions for Field Testing of Systems Pow-R Breakers. l.l File www. ElectricalPartManuals. com. Effective June, 1979

Eaton Digitrip RMS and Digitrip OPTIM Trip Units with Types DSII and DSLII Low Voltage Power Circuit Breakers

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Individual breakers in separate enclosures can be applied in low voltage distribution systems through 600 volts Ac, 50/60 Hertz.

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

A. Submit manufacturer's literature and technical data before starting work.

www. ElectricalPartManuals. com Systems Pow-R Breaker Transfer Switches Technical Data Page 1

SIEMENS. Microprocessor-Based Tripping System. Static lrip III. www. ElectricalPartManuals. com

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

Table of Contents. For latest version, visit:

Instructions for Digitrip Models 1150 and 1150i Trip Units for use only in Cutler-Hammer Magnum and Magnum DS Circuit Breakers

Cutler-Hammer. Installation Instructions for the ND OPTIM 550 PowerNet and/or Zone Interlock Accessories (ICK 550N, ZGK550N, ZGPK550N) I.L.

Master Connection Diagram Series C R-Frame Circuit Breaker with DIGITRIP RMS Trip Units

Instructions for Digitrip Models 520V and 520MCV for use only in Cutler-Hammer Type VCP-T, VCP-TR and T-VAC, T-VACR Circuit Breakers

A WARNING. Installation Instructions for KD, HKD, KDC, CKD, CHKD Circuit Breakers I.L. 29C092C

2.2. Molded Case Circuit Breakers. Contents. NG-Frame ( Amperes) Series G

Cutler-Hammer I.L. 29C160G WARNING NOTICE 1-0 INTRODUCTION. General Information

Table Line and Load Terminals. Terminal Body Material. Wire Type. Aluminum Copper Aluminum. English English English.

Cutler-Hammer. Installation Instructions for Undervoltage Release Mechanism (Handle Reset) with LED for E 2 L and E 2 LM Mining Circuit Breakers

SURE TRIP SLT-201 SECONDARY TEST SET

Moulded case circuit breakers

SURE TRIP RETRO KITS

N-frame Circuit Breaker

I.L. 29C121A WARNING 1. INTRODUCTION. Maximum Freq. Maximum Dielectric Voltage Current Withstand (V) (A) Voltage (V)

Table Types LD, HLD and LDC Thermal-Magnetic Circuit Breakers with Interchangeable Trip Units

Selection and Application Guide Supplement. WL UL Pole Circuit Breakers. usa.siemens.com/wlbreaker

Installation Instructions for NW, HNW, and NWC Circuit Breakers and N-frame Series C Molded Case Switches

Magnum IEC Air Circuit Breakers and Drawout Cassette Engineering Data

PORTABLE CURRENT SOURCE FOR CIRCUIT BREAKER AND MOTOR OVERLOAD TESTING INSTRUCTION MANUAL PI-250B. Release 1.0 April 5, 2013

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

Mar H: SUPPLEMENTAL PARALLELING GEAR (16315-H)

I.L. 29C184A File WARNING

www. ElectricalPartManuals. com Instructions for Ground Fault Protection Systems INTRODUCTION SENSOR Fig. 1 Cu"ent Monitor

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

SURE-TRIP OEM RELACEMENT TRIP UNIT

Magnum IEC Low Voltage Air Circuit Breakers

TYPES DS II AND DSL II METAL ENCLOSED LOW VOLTAGE POWER CIRCUIT BREAKERS

320 to 327 M Series Low and Medium Voltage Motor Protection Relays

This Specification Data Sheet brought to you by: Trinity Blvd. Fort Worth, Texas /

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

University of Houston Master Construction Specifications Insert Project Name

AP/UP, AP/MIL Series Magnetic Circuit Protectors

Instructions for the Digitrip RMS Pole and 4-Pole Trip Unit Installation and Operation with L-Frame and MOL-Frame Series C Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers

KD LV Motor Protection Relay

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism

SECTION MOTOR CONTROL

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

Selective Coordination

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

with Electronic Trip Units

GE Consumer & Industrial Electrical Distribution. Power Break II. Insulated Case Circuit Breakers

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

209 Series. Magnetic Circuit Protectors

! WARNING I.L D WARNING GENERAL INFORMATION

Electromagnetic Industries LLP

Tmax Molded Case Circuit Breakers

Low voltage circuit breakers

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

209/219/229/249/279 Series Magnetic Circuit Protectors

INSTRUCTIONS. seconds. the tween the end of the bearing screw and the. top of the shaft. The moving contact is a small silver hemisphere

Tmax Molded Case Circuit Breakers

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

Installation Instructions for Type SM Safety Handle Mechanism for L-Frame Series C Circuit Breakers and Molded Case Switches

Type SOQ Negative Sequence Time Overcurrent Relay

Courtesy of CMA/Flodyne/Hydradyne Motion Control Hydraulic Pneumatic Electrical Mechanical (800) RG H ZG E C

GENSET CONTROL MODULE A121A / A241A

Zone Selective Interlock Module. For GE Circuit Breakers

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

Cutler-Hammer May 2001

Switchgear. Low Voltage

Electrical network protection VIP30, VIP35. User s manual 12/2008

Transcription:

nstructions for Digitrip RMS Unit Table of Contents. General Description............... Protection................2 nformation............................3 Testing........................... 2. UL Listed Devices..................... 3. Principle of Operation................ 3. General...................... 3.2 and Operation ndicators............... 3.3 Test Provisions..................... 3. 4 Making Current Release (Discriminator)...... 3. nstantaneous Override........... 3. Zone nterlocking...................... 4. Protection Settings...................... 4. General.............................. 4.2 Long Delay Settings.............. 4.3 Long Delay Settings.............. 4.4 Short Delay Pick-up Settings............ 4. Short Delay Settings............ nstantaneous Pick-up Settings.............. 4.7 Ground Fault Current Pick-up Settings... 4.8 Ground Fault Delay Settings....... ntegral Test Panel - Test Procedure........... General............................2 When To Test.....................3 Test Provision...................4 Mode of Conducting Tests.............. 4. Control Power....................... 4.2 By Not ping the Breaker.............. 4.3 By ping the Breaker................ Back-up Battery......................... General............................... 2 Battery Check..................... 3 Battery Replacement............ Auxiliary Power Module............... 8. Rating Plug............................... 9. References..................... 9. Type DS Low Voltage AC Power Circuit Breakers.................... 9.2 Type SPB Systems Pow-R Breakers..... 9.3 Digitrip RMS Assemblies............. 9.4 Series C R-Frame Molded Case Circuit Breakers................ 4. 7. WARNNG DO NOT ATTEMPT TO NSTALL OR PERFORM MAN TENANCE ON EQUPMENT WHLE T S ENERGZED. DEATH OR SEVERE PERSONAL NJURY CAN RESULT FROM CONTACT WTH ENERGZED EQUPMENT. ALWAYS VERFY THAT NO VOLTAGE S PRESENT BEFORE PROCEEDNG WTH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY PROCEDURES. THE WESTNGHOUSE ELECTRC CORPORATON S NOT LABLE FOR THE MSAPPL CATON OR MSNSTALLATON OF TS PRODUCTS. Page 4 4 4 8 8 8 8 9 9 9 9 The user is cautioned to observe all recommendations, warnings and cautions relating to the safety of personnel and equipment, as well as all general and local health and safety laws, codes, and procedures. The recommendations and information contained herein are based on Westinghouse experience and judgement, but should Effective May, 989 Supersedes.L. 29-8 dated March, 988.L. 29-8-A not be considered to be all-inclusive or covering every application or circumstance which may arise. lf any questions arise, contact Westinghouse Electric Corporation for further information or instructions.. General Description. Protection The Digitrip RMS Unit, illustrated in Fig., is a microprocessor based type trip suitable for use in type SPB Systems Pow-R circuit breakers and types DS and DSL low voltage AC power circuit breakers and Series C R-Frame molded case circuit breakers. The trip unit provides true RMS current sensing for proper correlation with thermal characteristics of conductors and equipment. nterchangeable rating plugs are provided to establish the continuous current rating of each circuit breaker. The Digitrip RMS Unit is completely self-contained and when the circuit breaker is closed, requires no external control power to operate its protection systems. t operates from current signal levels and control power derived through current sensors integrally mounted in the circuit breaker. The Digitrip RMS Unit is available in six optional protection models. Each trip unit may be equipped with a maximum of five phase and two ground (time-current) adjustments to meet specific application requirements. These protection models include the following types which are further illustrated in the nameplate examples shown in Fig. 2. Figure Type Protection 2. Long /nstantaneous 2.2 Long /Short 2.3 Long /Short /nstantaneous 2.4 Long /nstantaneous/ground 2. Long /Short /Ground 2. Long /Short /nstantaneous/ Ground.2 nformation dentifier (L) (LS) (LS) (LG) (LSG) (LS G) Red LED indicators are provided on the face of the trip unit to indicate the mode of an automatic trip operation. A battery is provided to maintain the mode of trip LED indication following an automatic trip operation. Green LEOs are provided to indicate the operational status of the trip unit and the status of the back-up battery mounted in the rating plug..3 Testing An integral test panel, including a test selector switch and test and reset pushbuttons, is provided to test the circuit breaker in either a "" or "No-" test mode under qualified conditions. 2. UL Listed Devices Digitrip RMS Units are listed by the Underwriters Laboratories, nc. for use in types SPB, DS and DSL and Series C R-Frame circuit breakers under UL File E789.

2 Typical LED ndicator --- Red Phase -- Curve Ground -- Curve Typical Setting Viewing Window Fig. Typical Digitrip RMS Unit with Rating Plug nstalled @ Westinghouse Digital ProtectiOn Digitrip RMS [ l Cell No. --- Long Delay Setting [!]n NPPH Made m U.S.A. VJ N Lithium Battery Only Long Delay T] Sec. At n b]'"" lnst Breaker s n T J in Test o T] n n t!us NPPH Fig. 2. Long /nstantaneous Protection (L) Nameplate @ T ---Keyed Receptacle for Auxiliary Power Module ---Circuit Breaker Assembly Cell Location Reference ntegral Test Module Unit Pushbutton Westinghouse Digital Protection Digitrip RMS Celi Na. DS Rating Plug -- Unit Operational Status Green LED Typical Setting Adjustment,-----,NPPH Made U.S.A r- % N Lithium Battery Only o Long Delay Long Delay to' Setting Tme [!] n T) Sec At n Short Delay '----, Pckup Breaker s n T, r::: n J in '@. "' Short Delay '----., [] Sec. Test o ;:us NPPH Fig. 2.2 Long /Short Protection (LS) Nameplate

@ Westinghouse Dgital Protection Dgitrp RMS ( l Cell No. --- Long Delay Long Delay Settmg [!]n [DSec At n * Short Delay Pckup NP2PHO Made m U S.A '/, N Lithium Battery Only Breaker s, n n T ' n Short Delay '-----., 2t OJ Sec. Test '"" Trp [!)n t n us lnst NP2PH2 Fig. 2.3 Long /Short /nstantaneous Protection (LS) Nameplate @ Westinghouse Dgtal Protection Digtrip RMS Cell No Long Delay Setting [!]n NP2PH Made n U.S.A Y3 N lithium Battery Only Long Delay '-----' Tme (DSec. At n Breaker Trps Gnd. Fault Pickup,n n T n '@ n Short Delay '-----., * 2t OJ Sec Test o QJ Sec ;;''"" t n!us Gnd. Overnde/Dscnmmator Short Delay Pckup NP2PH3 Fig. 2. Long /Short Protection (LSG) Nameplate @ Westinghouse Digital Protection Dgtrp RMS CeliNa.,.--------------., Long Delay Setting OJ n Gnd. Fault Pickup n Breaker s n T n Test Gnd. Fault lnst o Sec [!)n Gnd. lnst NP2PH Fig. 2.4 Long /nstantaneous/ground Protection (LG) Nameplate @ Westmghouse Digital ProtectiOn Digtrp RMS Cell No.,----,NP2PH Made m U S.A long Delay Settng OJ n, NP2PHO Made n U.S.A '/' N Lthum Battery Only Long Delay [DSec- At n y, N Lithium Battery Only Long Delay '--- ---' (TSec.- At n Breaker s Gnd. Fault Pickup, n n T n n '' Short Delay * 2t OJ Sec Test Gnd. Fault Sec. [T n Short Delay Pckup :""' '"" Tnp o :us Gnd. lnst NP2PH4 Fig. 2. Long /Short /nstantaneous/ground Protection (LSG) Nameplate 3

4 3. Principle of Operation 3. General The Digitrip RMS Unit provides three basic functions: Protection, nformation and Testing. A typical trip unit and rating plug are illustrated in Fig.. ndividual product instruction leaflets referenced in Sections 9. and 9.2 illustrate typical Digitrip RMS Units installed in specific breakers. The trip unit uses the NTEL MCS- family of microcomputers to perform its numeric and logic functions. The principle of operation can best be described by referring to the block diagram shown in Fig. 3. n the Digitrip RMS Unit all required sensing and tripping power to operate its protection function is derived from the current sensors in the circuit breaker. The secondary current signals from these sensors provide the correct magnitude of current for protection functions as well as tripping power during normal circuit breaker operating periods. Using these current signals in the protection function, analog voltages are developed across various calibrating resistors including: ) Phase current 2) Ground fault current (when supplied) 3) Rating plug The resulting analog voltages are multiplexed into an analogto-digital converter and the output data fed into the microcomputer chip along the data bus. The microcomputer, in cyclic fashion, repeatedly scans the resultant voltage values across each calibrating resistor and N "" A B + + (r- ) ) c + enters these values into its RAM or Read/Write Memory. This data, which is used to calculate true RMS current values, is repeatedly compared with the pre-set protection function pickup settings and other operating data stored in the ROM or Read Only Memory. The microcomputer software program is then used, in decision tree fashion, to initiate protection functions including tripping actions through the low energy flux transfer trip coil in the circuit breaker. 3.2 and Operation ndicators Red colored LEOs, as shown in Figs. and 2, indicate on the face of the trip unit the mode of trip of any automatic trip operation. As indicated in Fig. 2, each LED is strategically located in the related segment of the time-current curve depicted on the face of the trip unit. The mode of trip is identified by the segment of the time-current curve in which the LED is turned "On". Following an automatic trip operation, a back-up battery, as indicated in Figs. 3 and, is provided to supply power to the LEOs. A green colored battery check LED and a test pushbutton as shown in Figs. and, are provided to check the status of the battery. A trip reset pushbutton, as shown in Fig., is provided to turn "Off" the LEOs following a trip operation. A green colored LED, as shown in Fig., indicates the operational status of the trip unit. Once the load current through the circuit breaker exceeds approximately 2% of the frame or sensor rating, the green LED will flash "On" and "Off" once each second. A flashing green LED is an indication of a properly operating trip unit. - ------------- ------ ----- --------- ------ ---- r--------' yyy Aux CT's and GFP Summing CT Bridge Circuits Fig. 3 Digitrip RMS Block Diagram with Breaker nterface Auxiliary Power Module nput (When Used) f--- Power Supply ;ypical Phase or Ground :-- Calibration Resistor 7 -r-r r : r- +3V ±.... j' < Rating? Plug // )_'..._, r ))

3.3 Test Provisions An integral test panel, including a test selector switch and test and reset pushbuttons, is provided to test the circuit breaker in either a TRP or NO-TRP test mode under qualified conditions. See Section. For bench testing of the trip unit alone or of the trip unit while it is installed in the circuit breaker, an optional Auxiliary Power Module (Cat. No. PRTAAPM) as shown in Fig. 7 is available. This Auxiliary Power Module, which operates from a separate 2 Vac supply, may also be used when a drawout type circuit breaker is in any of its four cell positions, i.e., "Connected", "Test", "Disconnected" and "Withdrawn" (or "Removed.") 3.4 Making Current Release (Discriminator) When the DGTRP RMS Unit is not equipped with an adjustable instantaneous protection setting, i.e., types LS or LSG, a making current release (or discriminator) circuit is provided. This circuit will prevent the circuit breaker from being closed and latched-in on a faulted circuit. The non-adjustable release is pre-set at eleven () times the installed rating plug ampere rating On). The making current release is armed only for the first ten ( ) cycles following an initial circuit breaker closing operation with a load cu rrent exceeding approximately 2% ofthe circuit breaker frame or sensor rating. Should the load current through the circuit breaker drop to a value less than this, the release will re-arm. The release, once armed, will remain armed until the load current passing through the circuit breaker exceeds approximately 2% for cycles. Any trip operation initiated by the making current release will trip the circuit breaker instantaneously. 3. nstantaneous Override n addition, when the Digitrip RMS Unit is not equipped with an adjustable instantaneous setting, i.e., types LS or LSG, a high-set non-adjustable instantaneous override trip circuit is provided. This high level tripping action is pre-set to a specific value that reflects the short time withstand rating of the circuit breaker in which the trip unit is installed. Specific values vary between circuit breaker types and ratings. For specific information, refer to the supplementary leaflets and/or time-current curves referenced in Sections 9. and 9.2. 3. Zone nterlocking As indicated in the block diagram in Fig. 3, zone interlock signals are provided. For Digitrip RMS Units equipped with either ground fault or short time protection functions or both, separate zone interlocking circuits are provided. When utilized, these input/output signals must be connected in the ultimate equipment assembly in line with details provided with the specific circuit breaker connection diagrams supplied with the circuit breaker and referenced in Sections 9. and 9.2. Similarly, if the zone interlocking function is chosen not to be used, defeater connections on each circuit must be added as illustrated in the same referenced diagrams. 4. Protection Settings 4. General Prior to placing any circuit breaker in operation, all available protection settings should be set using values as recommended by the specifying engineer responsible for the installation. The number of settings that must be made will be a ----- ----------- -- ----------, Unit Operating Status ndicator nput Typical Cause of LEOs ntegral ~ Located on Front Panel lb -+--- Protection Test..._ Panel Functon Switch Settings and Push buttons! A A -" Multiplexer Central Multiplexer : v,, ' r (MUX) t-. Processor (MUX) ' Data Bus r Unit (CPU) r- - t Flux Transfer Shunt Zone L_ - (FTST) or Direct nterlock Actuator (DTAl Circuitry Analog Override FET Circuit N OUT

factor of the protection model supplied as illustrated in Figs. 2. through 2.. Each settings is made with an eight position rotary switch using a small screwdriver. The selected setting for each adjustment will appear in the small rectangular opening as illustrated in Fig.. The installed rating plug establishes the maximum continuous current rating of the circuit breaker. All current pick-up settings in the protection module are defined in per unit multiples of the ampere rating O n ) of the installed rating plug. To illustrate the portion of the protection curve being adjusted, simulated -Current curves are pictured on the face of the trip unit. The particular setting to be adjusted is located in close proximity to its portion of the simulated -Current curve. Should an automatic trip occur as a result of a fault current exceeding the pre-selected value in this portion of the Current curve, the red LED shown in this segment of the simulated -Current curve will turn "ON". The available settings, along with the illustrated effect of changing the settings, are given in Figs. 4. through 4.7. 4.2 Long Delay Settings Eight (8) available settings, as illustrated in Fig. 4., range from. to. On). Each setting is expressed as a multiple of the maximum ampere rating On) of the installed rating plug. 4.3 Long Delay Settings Eight (8) available settings, as illustrated in Fig. 4.2, range from 2 to 24 seconds. These settings represent total clearing times at a current value equal to six () times the installed rating plug ampere rating On). 4.4 Short Delay Pick-Up Settings As illustrated in Fig. 4.3, eight (8) available settings range from 2 to On) with two variable settings of S and S2. These variable settings depend upon the type of circuit breaker in which the trip unit is installed. Specific information on these settings is given in the supplemental instruction leaflet referenced in Sections 9. and 9.2 that is supplied with the circuit breaker. Specific information is also shown on the rating plug and on the applicable time-current curve. 4. Short Delay Settings As illustrated in Fig. 4.4, two different curve configurations are possible, i.e., flat or 2t response. The configuration selected will be a factor of the type of selective coordination being developed. The 2t response will provide a longer time delay in the low-end of the short delay pick-up range than will the flat response setting. Five flat (.,.2,.3,.4,. sec.) and three Pt (.,.3,. sec.) response time delay settings are provided. The l>t response settings are identified by the suffix asterisk (*) that appears in the setting viewing window. The Pt response is applicable only up to eight (8) times the ampere rating of the installed rating plug On). After this value is exceeded, the l2t response configuration reverts to a flat response. 4. nstantaneous Pick-up Settings As illustrated in Fig. 4., eight (8) available settings range from 2 to On) with two variable settings M and M2. These variable settings depend upon the type of circuit breaker in which the trip unit is installed. Specific information on these settings is given in the supplemental instruction leaflet referenced in Sections 9. and 9.2 that is supplied with the circuit breaker. Specific information is also shown on the rating plug and on the applicable -Current curve. 4.7 Ground Fault Current Pick-up Settings As illustrated in Fig. 4., eight (8) available settings are given in alphabetical notations from A to K. (There is no "G" notation). Specific setting values are a function of the installed rating plug. n general, the pick-up settings range from.2 to. times the ampere rating On) of the installed rating plug up to a maximum pick-up value of 2 A. However, in the lower ampere rating plug values, an error factor can occur in the Digitrip RMS Unit since it is completely self-powered using only the input from the installed current sensors. Refer to Table, Note 2 for additional information. Specific current pick-up values are tabulated in Table and on the ground fault -Current curve of the applicable circuit breaker. Under primary injection test conditions, when the external auxiliary power module shown in Fig. 7 is used, the tabulated values should be in effect. The tabulated values shown in Table are based on the use of a residual current sensing scheme with the same rated current sensor in all phase and neutral conductors. Refer to the applicable supplemental circuit breaker instruction leaflet for values applicable to alternate sensing schemes. 4.8 Ground Fault Delay Settings As illustrated in Fig. 4.7, two different curve configurations are possible, i.e., flat or Pt response. The configuration selected will be a factor of the type of selective coordination being developed. The Pt response will provide a longer time delay in the low-end of the ground fault pick-up range than will the flat response setting. Table - Ground Fault Current Pickup Settings PCKUP SETTNGS GROUND FAULT CURRENTS (AMPERES)Gl A B C D E F H K 2 3 3 4 7 2 7 8 2 2 @ _c 2 3 88 2 88 2 7 7 Ul 3 9 2 8 22 3 UJ c: UJ 4 2 4 2 24 3 4 a.. :2: 8 2 24 3 3 4 8 2 24 28 32 4 48 8 <.? ::;) 2 3 3 4 -' a.. 2 3 3 42 48 72 9 2 <.? z 4 48 4 8 9 2 2 f= <( 2 7 8 2 2 2 c: 24 72 84 9 2 2 2 2 UJ -'...J 2 2 7 87 2 2 2 2 <( f- 3 7 9 2 2 2 2 2 CJ) z - 32 8 9 2 2 2 2 2 2 4 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Gl Tolerances on pickup levels are :<:: % of values shown n chart. Ground fault pickup levels shown are nominal values when tested with external control power present. Without external control power such as is the case with the Digitrip RMS, ground pickup levels may exceed these values up to the E setting of that particular rating plug. @ Refer to Type OS, Type SPB or Series C A-Frame supplemental instruction leaflets given in Section 9 for list of available rating plugs with each type circuit breaker. 7

L) Fig. 4. Long Delay Ampere Pickup Settings,.ro Long Delay / ;;" ] 2, """' ' ' ' ' ' ', ' '.vj Fig. 4.2 Long Delay Settings {'.. r'.........., ',,n,, Short Delay -: :', Pickup.,.,.7'.8,.8,.9,.9,. n Multiples of Rating Plug Amperes (n) 4, 7,, 2,, 2, 24 Seconds at s Rating Plug Amperes(lnl 2. 2.. 3. 4 S S ', '-..,, Qn ', ', l :,_':':::3,_:-_:-_=-=3, -_-_} Amperes ( n) Fig. 4.3 Short Delay Current Pickup Settings,, 2 n Multiples of Rating Plug ("., ' ' ' ',._.. ""'- '.r"" Short Delay Q] Sec. (S) " :'">.. u M _ j... ---} --- f"'l "'-,.._, ' =]m ", ',,j ' ' ', ', w ',.=-.3 *n Viewing Window r'l ndicates l't Type Response Fig. 4.4 Short Delay Settings [] n st. n r- l -- w.'.2,.3,.4,. Seconds with Flat Response.*,.3*,.* Seconds with l't Response l2t Response Returns to Flat Response at Approximately Bin Fig. 4. nstantaneous Current Pickup Settings Gnd-Fault [] Pickup n 2, 2., 3, 4,,, M,, M 2 n Multiples of Rating Plug Amperes (lnl A, B,C, D E, F, H, K Fig. 4. Ground Fault Current Pickup Settings Specific Amperes Given on Circuit Breaker -Current Curve and in Table 7

8 *n Viewing Window ndicates l't Type Response,.,.,.., ' --- '] ---' :. '---- : _, Gnd Fault [] Sec. Fig. 4.7 Ground Fault Delay Settings.'.2,.3,.4,. Seconds with Flat Response. *,.3*,.* Seconds with l't Response l't Response Returns to Flat Response at Approximately.2 n Five flat (.,.2,.3,.4,. sec.) and three l't (.,.3,. sec.) response time delay settings are provided. The l't response settings are identified by the suffix asterisk (*) that appears in the setting viewing window. The l't response is applicable only up to.2 times the ampere rating of the installed rating plug (n). Beyond this value, the l't response configuration reverts to a flat response.. ntegral Test Panel -Test Procedure. General As illustrated in Figs. and, an integral test panel is provided to test the Digitrip RMS Unit. Adequate no-trip settings are provided to insure that the trip unit is operational without tripping the circuit breaker. CAUTON THE TRPPNG OF A CRCUT BREAKER UNDER "TEST CONDTONS" WHLE T S N SERVCE AND CAR RYNG LOAD CURRENT, WHETHER DONE BY NTE GRAL OR EXTERNAL TEST MEANS, S NOT RECOMMENDED. ANY SUCH TRPPNG OPERATON WLL CAUSE DS RUPTON OF SERVCE AND POSSBLE PERSONAL NJURY RESULTNG FROM UNNECESSARY SWTCHNG OF CONNECTED EQUPMENT. TESTNG OF A CRCUT BREAKER THAT RESULTS N THE TRPPNG OF THE CRCUT BREAKER SHOULD BE DONE ONLY WTH THE CRCUT BREAKER N THE "TEST" OR "DSCONNECTED" CELL POSTONS OR WHLE THE CRCUT BREAKER S ON A TEST BENCH. Breaker s n T and GFT @} n Test @ Fig. ntegral Test Panel CD Phase Current With T ( ) Phase 'Current Without, 2, 3,8and () CD Ground Current Wlth GFT Ground Current Without GF NOTES: CD See write-up for in-service test trip limitations. unit reset required following all automatic trip and test operations. @ Test operation begins with release of pushbutton. To preserve the primary protection function of the trip unit, all in-service testing under "" or "No-" conditions must be done at load current values no greater than 4% of the plug rating (n). Any attempt to conduct in-service testing above this value will be *automatically aborted by the trip unit. Since the Digitrip RMS Unit is completely self-powered using energy derived from the current sensors installed in the circuit breaker, all in-service tests conducted should be conducted with the auxiliary control power module, shown in Fig. 7, plugged into the trip unit. This action will avoid operational difficulties caused by load current levels that are too low to operate the trip unit..2 When To Test Tests can be conducted with the breaker in the "connected" cell position while carrying load current. However, as stated in the caution note in Section., good practice will limit circuit breaker in-service "trip tests", where required, to maintenance periods during times of minimum load conditions. Testing, prior to start-up can best be accomplished with the breaker out of its cell or in the "Test", "Disconnected" or "Withdrawn" (or Removed) cell positions. Note: Since time-current settings are based on desired system coordination and protection schemes, the protection settings selected and preset under Section 4. above should not be altered during or as a part of any routine test sequence..3 Test Provision As indicated in Fig., six different test settings (, 2, 3, T, 8 and OX n) are available for testing the phase elements of the trip unit and two (GF, GFT) are provided for testing the ground elements. One setting under each test mode (T and GFT) will initiate a tripping action of the circuit breaker. With appropriate pre-set selections of the phase protection settings, an ample range of settings under the "No " condition are available to test the long time, short time and instantaneous trip settings without tripping the circuit breaker. n the "GF" test position, the amount of test current is adequate to prove the operating condition of t he trip unit without tripping the circuit breaker. This is not to be construed as a calibration *No abort signal will occur for tests conducted unless the current breaker is carrying load current.

test. The value of the simulated test current is. per unit of the rating plug value..4 Mode of Conducting Tests.4. Control Power nstall the Auxiliary Power Module (Cat. No. PRTAAPM) to insure control power is available for testing..4.2 By Not ping the Breaker. Should the circuit breaker be in the cell "Connected" position and carrying load current, make sure that the circuit breaker is carrying no more than 4% of the plug ampere rating O n ). 2. Place the test selector switch in one of the six "No " test settings, i.e.,, 2, 3, 8,, or GF. 3. Depress the "Test" pushbutton and release it - the test is initiated when the pushbutton is released. 4. Should any of the various protection settings be less than the selected "No " test value, then the LED related to that function will turn on signifying successful completion of the test action. Note: For long delay tests there will be some period of time between start of test and LED turn "ON".. the trip unit by depressing and releasing the " " pushbutton. All LEOs turned "ON" by the "No " test action should turn "OFF". Fig.. View with Hinged Cover Closed Hinged Cover Fig. Typical Rating Plug Fig..2 View with Hinged Cover Open and Battery nstalled Circuit Breaker Type dentification ----+ Plug dentification --- Battery Check Pushbutton ----+ Battery ----' Check LED Should an actual overload or fault condition occur during an in-service, "No Test" sequence, the protection function will override the test function, and the circuit breaker will trip automatically as pre-programmed with the various -Current settings. Note: The " " pushbutton may be depressed at any time. However, should a test initiated via the integral test panel be in progress, it would be aborted. A test initiated via the integral test panel may be aborted at any time by depressing the " " pushbutton..4.3 By ping the Breaker. Make sure that the circuit breaker is carrying no more than 4% of the plug ampere rating On). 2. Place the test selector switch in one of the two "" test settings, i.e., T or GFT. 3. Depress the "Test" pushbutton and release it - the test is initiated when the pushbutton is released. 4. Should any of the various protection settings be less than the selected "" test value, the circuit breaker will trip and the LED related to that function will turn "ON" following the test action.. the trip unit by depressing and releasing the " " pushbutton. All LEOs turned "ON" resulting from the "" test action should turn "OFF". -,.----Retention Screw Variable Settings Fig..3 View with Hinged Cover Open and Battery Removed Polarity Marks 9

---. Unit Plug Fig. 7 Auxiliary Power Module. and reclose the circuit breaker following established operating procedures.. Back-up Battery. General As indicated in Figs. 3 and, a back-up battery is provided to maintain the mode of trip LED indication in the Digitrip RMS Unit. The back-up battery is located in the rating plug along with a battery check pushbutton and a green battery check LED..2 Battery Check The battery is a long life, lithium photo type unit. The ready status of the battery can be checked at any time by depressing the battery check pushbutton and observing the "On" condition of the battery check LED as shown in Fig... f the battery check LED does not turn "ON", replace the battery..3 Battery Replacement Should the battery require replacement, it can be easily replaced from the front of the trip unit by lowering the hinged cover of the rating plug as shown in Fig..2. The battery can then be removed by pulling the battery tab as shown in Fig..3. Note: The battery can be replaced at any time with the circuit breaker in service without affecting the operation of the circuit breaker and its protection fu nction. The replacement battery should be the same type or equivalent. Acceptable 3. volt lithium batteries may be obtained from the following companies under their type designation indicated: Company Varta Batteries, nc. Clarbrook Road Elmsford, N.Y. 23 Duracell South Broadway Tangtown, N.Y. 9 {94) 9-7 Union Carbide Corp. Battery Products Div. Eveready 39 Old Ridgebury Road Danbury, CT 87- {23) 794-748 Model CR /3N DL 3N 2L-7BP L--- Plug for 2 Vac Receptacle CAUTON CARE SHOULD BE EXERCSED WHEN REPLACNG A BATTERY TO NSURE THAT THE CORRECT POLAR TES ARE OBSERVED. POLARTY MARKNGS ARE SHOWN ON THE RATNG PLUG WHEN THE HNGED COVER S OPEN AS NDCATED N FGS..2 AND.3. 7. Auxiliary Power Module The Auxiliary Power Module {Cat. No. PRTAAPM), illustrated in Fig. 7, is an encapsulated power supply that requires a 2 Vac input at either or Hz. t provides an output of 32 Vdc {nominal 4 Vdc open circuit) which can be used for testing a Digitrip RMS Unit. When drawout construction is provided, any circuit breaker equipped with a Digitrip RMS Unit can be conveniently set and tested while the circuit breaker is out of its cell or in its cell in the "Disconnect" or "Withdrawn" positions using the Auxiliary Power Module. The Auxiliary Power Module is equipped with a unique plugin connector suitable only for plugging into the keyed receptacle of a Digitrip RMS Unit. This prohibits the possible use of an incorrect, but similar, type power module. The location of the keyed receptacle for the auxiliary power module is shown in Fig.. 8. Rating Plug The rating plugs, as illustrated in Figs. and, are used to establish the continuous ampere rating of the related circuit breaker. All pick-up settings of the protection functions of the trip unit, i.e., long delay, short delay, instantaneous and ground fault are selected as a multiple of the rating plug rating!lnl Different types and ratings are available to match the desired ampere rating and type of circuit breaker into which the trip unit is to be installed. Also, since the rating plugs are frequency sensitive, specific types are available for or Hz system applications. Complete catalog descriptions of all available rating plugs are given in the applicable circuit breaker supplementary instruction leaflets. References to these documents are given in Sections 9. and 9.2.

9. References 9. Type OS Low Voltage AC Power Circuit Breakers.B. 33-79-F.B. 33-79-F Supplement No. SC-428-87 SC-428-87 SC-4279-87 8B8 nstructions for Low-Voltage Power Circuit Breakers Types DS and DSL Section 8A Supplement Circuit Breaker Automatic ping System When Using Digitrip RMS Assembly (L) for Type DS Circuit Breakers (LS) for Type DS Circuit Breakers (G) for Type DS Circuit Breakers Connection Diagram for Type DS Circuit Breakers 9.2 Type SPB Systems Pow-R Breakers.L. 29-8.L. 29-8 SC-4283-87 SC-4284-87 SC-4282-87.S. 4 nstruction for the Systems Pow-R Breaker and Drawout Mechanism Supplementary nstructions for the Systems Pow-R Breaker used with the Digitrip RMS Assembly (L) for Type SPB Systems Pow-R Breaker (LS) for Type SPB Systems Pow-R Breaker (G) for Type SPB Systems Pow-R Breaker SPB Master Connection Diagram using Digitrip RMS Assemblies 9.3 Digitrip RMS Assemblies.L. 29-8.L. 29-82.L. 29-83.L. 29-84 nstructions for Digitrip RMS Unit nstructions for Digitrip RMS Unit nstructions for Digitrip RMS 7 Unit nstructions for Digitrip RMS 8 Unit 9.4 Series C R-Frame Molded Case Circuit Breakers 29-29-7 29-77 SC-482-89 SC-483-89 SC-484-89.L. 29C79 Frame Book Frame nstruction Leaflet Supplement nstructions for Series C R Frame used with the Digitrip RMS Assembly (L) for Type RD Circuit Breakers (LS) for Type RD Circuit Breakers (G) for Type RD Circuit Breakers Master Connection Diagram for Series C R-Frame Circuit Breaker with Digitrip RMS

2 Westinghouse Electric Corporation Distribution and Control Business Unit Electrical Components Division Pittsburgh, PA 22 Style No. C9H

nstructions for Digitrip RMS Unit Table of Contents. General Description.... Protection....2 nformation....3 Testing... 2. UL Listed Devices... 3. Principle of Operation... 3. General... 3.2 and Operation ndicators... 3.3 Test Provisions... 3.4 Making Current Release (Discriminator)... 3. nstantaneous Override... 3. Zone nterlocking... Protection Settings... 4. General... 4.2 Long Delay Settings... 4.3 Long Delay Settings... 4.4 Short Delay Pick-up Settings... 4. Short Delay Settings... nstantaneous Pick-up Settings... 4.7 Ground Fault Current Pick-up Settings... Ground Fault Delay Settings.... ntegral Test Panel - Test Procedure.... General....2 When To Test....3 Test Provision....4 Mode of Conducting Tests....4. Control Power....4.2 By Not ping the Breaker....4.3 By ping the Breaker.... Back-up Battery.... General....2 Battery Check....3 Battery Replacement... 7. Auxiliary Power Module... 8. Rating Plug... 9. References... 9. Type OS Low Voltage AC Power Circuit Breakers... 9.2 Type SPB Systems Pow-R Breakers... 9.3 Digitrip RMS Assemblies... 9.4 Series C R-Frame Molded Case Circuit Breakers... 4. 4. 4.8 WARNNG DO NOT ATTEMPT TO NSTALL OR PERFORM MAN TENANCE ON EQUPMENT WHLE T S ENERGZED. DEATH OR SEVERE PERSONAL NJURY CAN RESULT FROM CONTACT WTH ENERGZED EQUPMENT. ALWAYS VERFY THAT NO VOLTAG E S PRESENT BEFORE PROCEEDNG WTH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY PROCEDURES. THE WESTNGHOUSE ELECTRC CORPORATON S NOT LABLE FOR THE MSAPPL CATON OR MSNSTALLATON OF TS PRODUCTS. Page 4 4 4 8 8 8 8 9 9 9 9 The user is cautioned to observe all recommendations, warnings and cautions relating to the safety of personnel and equipment. as well as all general and local health and safety laws, codes, and procedures. The recommendations and information contained herein are based on Westinghouse experience and judgement, but should Effective May, 989 Supersedes.L. 29-8 dated March, 988.L. 29-8-A not be considered to be all-inclusive or covering every application or circumstance which may arise. f any questions arise, contact Westinghouse Electric Corporation for further information or instructions.. General Description. Protection The Digitrip RMS Unit, illustrated in Fig., is a microprocessor based type trip suitable for use in type SPB Systems Pow-R circuit breakers and types DS and DSL low voltage AC power circuit breakers and Series C R-Frame molded case circuit breakers. The trip unit provides true RMS current sensing for proper correlation with thermal characteristics of conductors and equipment. nterchangeable rating plugs are provided to establish the continuous current rating of each circuit breaker. The Digitrip RMS Unit is completely self-contained and when the circuit breaker is closed, requires no external control power to operate its protection systems. t operates from current signal levels and control power derived through current sensors integrally mounted in the circuit breaker. The Digitrip RMS Unit is available in six optional protection models. Each trip unit may be equipped with a maximum of five phase and two ground (time-current) adjustments to meet specific application requirements. These protection models include the following types which are further illustrated in the nameplate examples shown in Fig. 2. Figure Type Protection 2. Long /nstantaneous 2.2 Long /Short 2.3 Long /Short /nstantaneous 2.4 Long /nstantaneous/ground 2. Long /Short /Ground 2. Long /Short /nstantaneous/ Ground.2 nformation dentifier (L) (LS) (LS) (LG) (LSG) (LSG) Red LED indicators are provided on the face of the trip unit to indicate the mode of an automatic trip operation. A battery is provided to maintain the mode of trip LED indication following an automatic trip operation. Green LEOs are provided to indicate the operational status of the trip unit and the status of the back-up battery mounted in the rating plug..3 Testing An integral test panel, including a test selector switch and test and reset pushbuttons, is provided to test the circuit breaker in either a "" or "No-" test mode under qualified conditions. 2. UL Lited Devices Digitrip RMS Units are listed by the Underwriters Laboratories, nc. for use in types SPB, DS and DSL and Series C R-Frame circuit breakers under UL File E789.

2 Typical LED ndicator--- Red Phase -- Curve Ground -- Curve Typical Setting Viewing Window Fig. Typical Digitrip RMS Unit with Rating Plug nstalled @ Westinghouse Digital Protectmn Digitrip RMS [ l Cell No --- Long Delay Setting QJ n Long Delay T) sec- At n NPPH Made tn U S.A '"" lnst y, N Lithum Battery Only [] n Breaker s n T ill n Test ;:us NPPH Fig. 2. Long /nstantaneous Protection (L) Nameplate @ Westinghouse Dgttal Protection SPB Rating Plug Digtrp RMS Cell No Cat Must Use With Sensor Ratet! n iralet!ll i Hz Only ---Keyed Receptacle for Auxiliary Power Module ---Circuit Breaker Assembly Cell Location Reference -- DS..-..fi,..:-,f..-Rating Plug -- Unit Pushbutton -- Unit Operational Status Green LED -- Typical Setting Adjustment,----,NPPH Made m U.S.A Long Delay :8: Setting QJ n Long Delay TJ Sec- At n Short Delay u Ptckup, n ' Short Delay Tme * = 2t QJ Sec. y, N Lithium Battery Only Breaker s n T ill n Test o!us NPPHll Fig. 2.2 Long /Short Protection (LS) Nameplate

Westinghouse Digtal Protection Digitrip RMS ( l Cell No. --- long Delay g Settmg [j] n * NP2PH Made m U.S A![YoN lithium Battery Only long Delay [) Tme Sec- At n Short Delay Prckup, n Short Delay '----.. Tme lnst 2t Sec. [) n @ n st. Breaker Tnps n T n Test o us NP2PH2 Fig. 2.3 Long /Short /nstantaneous Protection (LS) Nameplate Westinghouse Digtal Protection Dgitnp RMS Cell No. ====:::::J NP2H Made m u.s.a r Long Delay Setting OJ n long Delay [) Sec- At Si n Gnd. Fault Pckup Short Delay Prckup, n n Short Delay '----.. * Sec. 2t..>'"" Sec Gnd. Ovemde/Dscnmlnatar /, N lthrum Battery Only Breaker Tnps n ST n Test Tnp Unit Status NPPH3 @ Fig. 2. Long /Short Protection (LSG) Nameplate Westinghouse Dgtal Protection Digitnp RMS Cell No. Gnd. Fault Pickup []n '-..,:. - long Delay Tme [) Sec- At Si n Gnd. Fault Tme QJ Sec. n st. '/o N lithium Battery Only NP2PH Made m U.S A. n st. [] n Breaker s n ST (] n Test Unit Status NPPH o Fig. 2.4 Long /nstantaneous/ground Protection (LG) Nameplate @ Westinghouse Digital Protection Digitnp RMS Cell No. r-----,np2ph Made m U S.A Gnd. Fault Pckup n y, N lithium Battery Only Long DelayiL----' Tme [) Sec.- At Sin Short Delay Prckup, n ' Gnd. Fault t Sec Gnd. lnst Breaker Tnps n ST (] n Test NPPH4 o Fig. 2. Long /Short /nstantaneous/ground Protection (LSG) Nameplate 3

4 3. Principle of Operation 3. General The Digitrip RMS Unit provides three basic functions: Protection, nformation and Testing. A typical trip unit and rating plug are illustrated in Fig.. ndividual product instruction leaflets referenced in Sections 9. and 9.2 illustrate typical Digitrip RMS Units installed in specific breakers. The trip unit uses the NTEL MCS- family of microcomputers to perform its numeric and logic functions. The principle of operation can best be described by referring to the block diagram shown in Fig. 3. n the Digitrip RMS Unit all required sensing and tripping power to operate its protection function is derived from the current sensors in the circuit breaker. The secondary current signals from these sensors provide the correct magnitude of current for protection functions as well as tripping power during normal circuit breaker operating periods. Using these current signals in the protection function, analog voltages are developed across various calibrating resistors including: ) Phase current 2) Ground fault current (when supplied) 3) Rating plug The resulting analog voltages are multiplexed into an analogto-digital converter and the output data fed into the microcomputer chip along the data bus. The microcomputer, in cyclic fashion, repeatedly scans the resultant voltage values across each calibrating resistor and N A B C + + + ( ) ) -----_J Aux CT's and GFP ( f,lf---+--..., Summing ---- ( CT enters these values into its RAM or Read/Write Memory. This data, which is used to calculate true RMS current values, is repeatedly compared with the pre-set protection function pickup settings and other operating data stored in the ROM or Read Only Memory. The microcomputer software program is then used, in decision tree fashion, to initiate protection functions including tripping actions through the low energy flux transfer trip coil in the circuit breaker. 3.2 and Operation ndicators Red colored LEOs, as shown in Figs. and 2, indicate on the face of the trip unit the mode of trip of any automatic trip operation. As indicated in Fig. 2, each LED is strategically located in the related segment of the time-current curve depicted on the face of the trip unit. The mode of trip is identified by the segment of the time-current curve in which the LED is turned "On". Following an automatic trip operation, a back-up battery, as indicated in Figs. 3 and, is provided to supply power to the LEOs. A green colored battery check LED and a test pushbutton as shown in Figs. and, are provided to check the status of the battery. A trip reset pushbutton, as shown in Fig., is provided to turn "Off" the LEOs following a trip operation. A green colored LED, as shown in Fig., indicates the operational status of the trip unit. Once the load current through the circuit breaker exceeds approximately 2% of the frame or sensor rating, the green LED will flash "On" and "Off" once each second. A flashing green LED is an indication of a properly operating trip unit. r- ------------ --- ------ ----------------------- Bridge Circuits Fig. 3 Digitrip RMS Block Diagram with Breaker nterface Auxiliary Power Module nput (When Used) / --- Power Supply Typical Phase or Ground Calibration Resistor f' ))>-

3.3 Test Provisions An integral test panel, including a test selector switch and test and reset pushbuttons, is provided to test the circuit breaker in either a TRP or NO-TRP test mode under qualified conditions. See Section. For bench testing of the trip unit alone or of the trip unit while it is installed in the circuit breaker, an optional Auxiliary Power Module (Cat. No. PRTAAPM) as shown in Fig. 7 is available. This Auxiliary Power Module, which operates from a separate 2 Vac supply, may also be used when a drawout type circuit breaker is in any of its four cell positions, i.e., "Connected", "Test", "Disconnected" and "Withdrawn" (or "Removed.") 3.4 Making Current Release (Discriminator) When the DGTRP RMS Unit is not equipped with an adjustable instantaneous protection setting, i.e., types LS or LSG, a making current release (or discriminator) circuit is provided. This circuit will prevent the circuit breaker from being closed and latched-in on a faulted circuit. The non-adjustable release is pre-set at eleven () times the installed rating plug ampere rating Onl The making current release is armed only for the first ten () cycles following an initial circuit breaker closing operation with a load current exceeding approximately 2% ofthe circuit breaker frame or sensor rating. Should the load current through the circuit breaker drop to a value less than this, the release will re-arm. The release, once armed, will remain armed until the load current passing through the circuit breaker exceeds approximately 2% for cycles. Any trip operation initiated by the making current release will trip the circuit breaker instantaneously. - - - -- - - - --, - - - ---- - -- -- - - - - - - Unit Operating Status ndicator ~ Typical Cause of LEOs Located on Front Panel Multiplexer (MUX) ntegral Test!+ Panel 3. nstantaneous Override n addition, when the Digitrip RMS Unit is not equipped with an adjustable instantaneous setting, i.e., types LS or LSG, a high-set non-adjustable instantaneous override trip circuit is provided. This high level tripping action is pre-set to a specific value that reflects the short time withstand rating of the circuit breaker in which the trip unit is installed. Specific values vary between circuit breaker types and ratings. For specific information, refer to the supplementary leaflets and/or time-current curves referenced in Sections 9. and 9.2. 3. Zone nterlocking As indicated in the block diagram in Fig. 3, zone interlock signals are provided. For Digitrip RMS Units equipped with either ground fault or short time protection functions or both, separate zone interlocking circuits are provided. When utilized, these input/output signals must be connected in the ultimate equipment assembly in line with details provided with the specific circuit breaker connection diagrams supplied with the circuit breaker and referenced in Sections 9. and 9.2. Similarly, if the zone interlocking function is chosen not to be used, defeater connections on each circuit must be added as illustrated in the same referenced diagrams. 4. Protection Settings 4. General ==== A Multiplexer Central "f r (MUX) t-.. Processor Data Bus Unit (CPU) ;--- 9 t L_ Flux Transfer Shunt -- - (FTST) or Direct Actuator (DTAl Analog Override ET Circuit L-- _-...J Prior to placing any circuit breaker in operation, all available protection settings should be set using values as recommended by the specifying engineer responsible for the installation. The number of settings that must be made will be a nput } +- Protection Functon t t Switch Settings and Pushbuttons Zone nterlock Circuitry N OUT

factor of the protection model supplied as illustrated in Figs. 2. through 2.. Each settings is made with an eight position rotary switch using a small screwdriver. The selected setting for each adjustment will appear in the small rectangular opening as illustrated in Fig.. The installed rating plug establishes the maximum continuous current rating of the circuit breaker. All current pick-up settings in the protection module are defined in per unit multiples of the ampere rating ( n ) of the installed rating plug. To illustrate the portion of the protection curve being adjusted, simulated -Current curves are pictured on the face of the trip unit. The particular setting to be adjusted is located in close proximity to its portion of the simulated -Current curve. Should an automatic trip occur as a result of a fault current exceeding the pre-selected value in this portion of the Current curve, the red LED shown in this segment of the simulated -Current curve will turn "ON". The available settings, along with the illustrated effect of changing the settings, are given in Figs. 4. through 4.7. 4.2 Long Delay Settings Eight (8) available settings, as illustrated in Fig. 4., range from. to. (n). Each setting is expressed as a multiple of the maximum ampere rating ( n ) of the installed rating plug. 4.3 Long Delay Settings Eight (8) available settings, as illustrated in Fig. 4.2, range from 2 to 24 seconds. These settings represent total clearing times at a current value equal to six () times the installed rating plug ampere rating (n). 4.4 Short Delay Pick-Up Settings As illustrated in Fig. 4.3, eight (8) available settings range from 2 to (n) with two variable settings of and 2. These variable settings depend upon the type of circuit breaker in which the trip unit is installed. Specific information on these settings is given in the supplemental instruction leaflet referenced in Sections 9. and 9.2 that is supplied with the circuit breaker. Specific information is also shown on the rating plug and on the applicable time-current curve. 4. Short Delay Settings As illustrated in Fig. 4.4, two different curve configurations are possible, i.e., flat or l't response. The configuration selected will be a factor of the type of selective coordination being developed. The l't response will provide a longer time delay in the low-end of the short delay pick-up range than will the flat response setting. Five flat (.,.2,.3,.4,. sec.) and three l't (.,.3,. sec.) response time delay settings are provided. The l't response settings are identified by the suffix asterisk (*) that appears in the setting viewing window. The 2t response is applicable only up to eight (8) times the ampere rating of the installed rating plug (n). After this value is exceeded, the 2t response configuration reverts to a flat response. 4. nstantaneous Pick-up Settings As illustrated in Fig. 4., eight (8) available settings range from 2 to ( n ) with two variable settings M and M2. These variable settings depend upon the type of circuit breaker in which the trip unit is installed. Specific information on these settings is given in the supplemental instruction leaflet referenced in Sections 9. and 9.2 that is supplied with the circuit breaker. Specific information is also shown on the rating plug and on the applicable -Current curve. 4.7 Ground Fault Current Pick-up Settings As illustrated in Fig. 4., eight (8) available settings are given in alphabetical notations from A to K. (There is no "G" notation). Specific setting values are a function of the installed rating plug. n general, the pick-up settings range from.2 to. times the ampere rating ( n ) of the installed rating plug up to a maximum pick-up value of 2 A. However, in the lower ampere rating plug values, an error factor can occur in the Digitrip RMS Unit since it is completely self-powered using only the input from the installed current sensors. Refer to Table, Note 2 for additional information. Specific current pick-up values are tabulated in Table and on the ground fa ult -Current curve of the applicable circuit breaker. Under primary injection test conditions, when the external auxiliary power module shown in Fig. 7 is used, the tabulated values should be in effect. The tabulated values shown in Ta ble are based on the use of a residual current sensing scheme with the same rated current sensor in all phase and neutral conductors. Refer to the applicable supplemental circuit breaker instruction leaflet for values applicable to alternate sensing schemes. 4.8 Ground Fault Delay Settings As illustrated in Fig. 4.7, two different curve configurations are possible, i.e., flat or l't response. The configuration selected will be a factor of the type of selective coordination being developed. The l2t response will provide a longer time delay in the low-end of the ground fault pick-up range than will the flat response setting. Table - Ground Fault Current Pickup Settings @ PCKUP SETT NGS GROUND FAULT CURRENTS (AMPERES) CD AC2) 8 C D E F H K 2 3 3 4 7 2 7 8 2 2...: 2 3 7 88 2 88 2 ifi 3 7 9 2 8 22 3 UJ a: UJ 4 2 4 2 24 3 4 a._ 2 8 2 24 3 3 4 8 2 24 28 32 4 48 8 (.? :::J 2 3 3 4 7 _J a._ 2 3 3 42 48 72 9 2 (.? z 4 48 4 8 9 2 2 f= <l: 2 7 8 2 2 2 a: 24 72 84 9 2 2 2 2 UJ _J _J 2 2 7 87 2 2 2 2 <l: f- 3 9 2 2 2 2 2 (f) 32 8 9 2 2 2 2 2 2 7 4 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 CD Tolerances on pickup levels are ± % of values shown n chart. Ground fault pickup levels shown are nominal values when tested with external control power present. Without exte rnal control power such as is the case with the Digitrip RMS, ground pickup levels may exceed these values up to the E setting of that particular rating plug. @ Refer to Type DS, Type SPB or Series C R-Frame supplemental instruction leaflets given in Section 9 for list of available rating plugs with each type circuit breaker.

.. Jl L) w l l Fig. 4. Long Dela y Ampere Pickup Settings,.r- :!t'l, Long Delay h.j Fig. 4.2 Long Dela y Settings!'...... '....,.., Short Delay '; l'.. Available Sttgs.,.,.7'.8,.8,.9,.9,. n Multiples of Rating Plug Amperes Unl 2, 4, 7,, 2,, 2, 24 Seconds at s Rating Plug Amperes(lnl n {'.. 2, 2., 3, 4 Pickup :.... '.. [),, S,, S, n :, n Multiples of / : Rating Plug ',, ',,_:-:::) :-:-= t_-_-_-_} Amperes Unl Fig. 4.3 Short Delay Current Pickup Settings "", ' ', ' '. ' -.--.. "- '/" Short Delay Sec. " ""-..., - u,-, ---] *n Viewing Window ndicates l't Type Response --- "" l,.,.j Fig. 4.4 Short Delay Settings []] lnst n r- i_j w.'.2,.3,.4,. Seconds with Flat Response.*,.3*,.* Seconds with 2t Response l't Response Returns to Flat Response at Approximately Bin Fig. 4. nstantaneous Current Pickup Settings 2, 2., 3, 4,,, M,, M, n Multiples of Rating Plug Amperes Onl Gnd-Fault [] m n A, B, C, D E, F, H, K Specific Amperes Given on Circuit Breaker -Current Curve and in Table Pickup Fig. 4. Ground Fault Current Pickup Settings 7

8 *n Viewing Window ndicates 2t Type Response '- "" Gnd Fault [] Sec : r"'- ---] _ '--- --- : _ Fig. 4.7 Ground Fault Delay Settings.'.2,.3,.4,. Seconds with Flat Response.*,.3*,.* Seconds wth l't Response l't Response Returns to Flat Response at Approxmately.2 n Five flat (.,.2,.3,.4,. sec.) and three l't (.,.3,. sec.) response time delay settings are provided. The l't response settings are identified by the suffix asterisk (*) that appears in the setting viewing window. The l't response is applicable only up to.2 times the ampere rating of the installed rating plug (n). Beyond this value, the l't response configuration reverts to a flat response.. ntegral Test Panel - Test Procedure. General As illustrated in Figs. and, an integral test panel is provided to test the Digitrip RMS Unit. Adequate no-trip settings are provided to insure that the trip unit is operational without tripping the circuit breaker. CAUTON THE TRPPNG OF A CRCUT BREAKER UNDER "TEST CONDTONS" WHLE T S N SERVCE AND CAR RYNG LOAD CURRENT, WHETHER DONE BY NTE GRAL OR EXTERNAL TEST MEANS, S NOT RECOMMENDED. ANY SUCH TRPPNG OPERATON WLL CAUSE DS RJPTON OF SERVCE AND POSSBLE PERSONAL NJURY RESULTNG FROM UNNECESSARY SWTCHNG OF CONNECTED EQUPMENT. TESTNG OF A CRCUT BREAKER THAT RESULTS N THE TRPPNG OF THE CRCUT BREAKER SHOULD BE DONE ONLY WTH THE CRCUT BREAKER N THE "TEST" OR "DSCONNECTED" CELL POSTONS OR WHLE THE CRCUT BREAKER S ON A TEST BENCH. Breaker s n T and GFT ] n Test @ Fig. ntegral Test Panel CD Phase Current With T ( ) Phase 'Current Without, 2, 3, 8 and ( ) CD Ground Current Wlth GFT Ground Current Without Tri p GF NOTES: CD See write-up for in-service test trip limitations. unit reset required following all automatic trip and test operations. @ Test operation begins with release of pushbutton. To preserve the primary protection function of the trip unit, all in-service testing under "" or "No-" conditions must be done at load current values no greater than 4% of the plug rating (n). Any attempt to conduct in-service testing above this value will be *automatically aborted by the trip unit. Since the Digitrip RMS Unit is completely self-powered using energy derived from the current sensors installed in the circuit breaker, all in-service tests conducted should be conducted with the auxiliary control power module, shown in Fig. 7, plugged into the trip unit. This action will avoid operational difficulties caused by load current levels that are too low to operate the trip unit..2 When To Test Tests can be conducted with the breaker in the "connected" cell position while carrying load current. However, as stated in the caution note in Section., good practice will limit circuit breaker in-service "trip tests", where required, to maintenance periods during times of minimum load conditions. Testing, prior to start-up can best be accomplished with the breaker out of its cell or in the "Test", "Disconnected" or "Withdrawn" (or Removed) cell positions. Note: Since time-current settings are based on desired system coordination and protection schemes, the protection settings selected and preset under Section 4. above should not be altered during or as a part of any routine test sequence..3 Test Provision As indicated in Fig., six different test settings (, 2, 3, T, 8 and OX n) are available for testing the phase elements of the trip unit and two (GF, GFT) are provided for testing the ground elements. One setting under each test mode (T and GFT) will initiate a tripping action of the circuit breaker. With appropriate pre-set selections of the phase protection settings, an ample range of settings under the "No " condition are available to test the long time, short time and instantaneous trip settings without tripping the circuit breaker. n the "GF" test position, the amount of test current is adequate to prove the operating condition of the trip unit without tripping the circuit breaker. This is not to be construed as a calibration *No abort signal will occur for tests conducted unless the current breaker is carrying load current.

test. The value of the simulated test current is. per unit of the rating plug value..4 Mode of Conducting Tests.4. Control Power nstall the Auxiliary Power Module (Cat. No. PRTAAPM) to insure control power is available for testing..4.2 By Not ping the Breaker. Should the circuit breaker be in the cell "Connected" position and carrying load current, make sure that the circuit breaker is carrying no more than 4% of the plug ampere rating ( n ). 2. Place the test selector switch in one of the six "No " test settings, i.e.,, 2, 3, 8,, or GF. 3. Depress the "Test" pushbutton and release it - the test is initiated when the pushbutton is released. 4. Should any of the various protection settings be less than the selected "No " test value, then the LED related to that function will turn on signifying successful completion of the test action. Note: For long delay tests there will be some period of time between start of test and LED turn "ON".. the trip unit by depressing and releasing the " " pushbutton. All LEOs turned "ON" by the "No " test action should turn "OFF". Fig.. View with Hinged Cover Closed Hinged Cover Fig. Typical Rating Plug Circuit Breaker Type dentification ----+ Plug dentification --- Battery Check Pushbutton -- Battery ---' Check LED Fig..2 View with Hinged Cover Open and Battery nstalled Should an actual overload or fault condition occur during an in-service, "No Test" sequence, the protection function will override the test function, and the circuit breaker will trip automatically as pre-programmed with the various -Current settings. Note: The " " pushbutton may be depressed at any time. However, should a test initiated via the integral test panel be in progress, it would be aborted. A test initiated via the integral test panel may be aborted at any time by depressing the " " pushbutton..4.3 By ping the Breaker. Make sure that the circuit breaker is carrying no more than 4% of the plug ampere rating ( n ). 2. Place the test selector switch in one of the two "" test settings, i.e., T or GFT. 3. Depress the "Test" pushbutton and release it - the test is initiated when the pushbutton is released. 4. Should any of the various protection settings be less than the selected "" test value, the circuit breaker will trip and the LED related to that function will turn "ON" following the test action.. the trip unit by depressing and releasing the " " pushbutton. All LEOs turned "ON" resulting from the "" test action should turn "OFF". 4---- Retention Screw Variable Settings Fig..3 View with Hinged Cover Open and Battery Removed Polarity Marks 9

--- Unit Plug Fig. 7 Auxiliary Power Module. and reclose the circuit breaker following established operating procedures.. Back-up Battery. General As indicated in Figs. 3 and, a back-up battery is provided to maintain the mode of trip LED indication in the Digitrip RMS Unit. The back-up battery is located in the rating plug along with a battery check pushbutton and a green battery check LED..2 Battery Check The battery is a long life, lithium photo type unit. The ready status of the battery can be checked at any time by depressing the battery check pushbutton and observing the "On" condition of the battery check LED as shown in Fig... f the battery check LED does not turn "ON", replace the battery..3 Battery Replacement Should the battery require replacement, it can be easily replaced from the front of the trip unit by lowering the hinged cover of the rating plug as shown in Fig..2. The battery can then be removed by pulling the battery tab as shown in Fig..3. Note: The battery can be replaced at any time with the circuit breaker in service without affecting the operation of the circuit breaker and its protection function. The replacement battery should be the same type or equivalent. Acceptable 3. volt lithium batteries may be obtained from the following companies under their type designation indicated: Company Varta Batteries, nc. Clarbrook Road Elmsford, N.Y. 23 Duracell South Broadway Tangtown, N.Y. 9 (94) 9-7 Union Carbide Corp. Battery Products Div. Eveready 39 Old Ridgebury Road Danbury, CT 87- (23) 794-748 Model CR /3N DL /3N 2L-7BP L---- Plug for 2 Vac Receptacle CAUTON CARE SHOULD BE EXERCSED WHEN REPLACNG A BATTERY TO NSURE THAT THE CORRECT POLAR TES ARE OBSERVED. POLARTY MARKNGS ARE SHOWN ON THE RATNG PLUG WHEN THE HNGED COVER S OPEN AS NDCATED N FGS..2 AND.3. 7. Auxiliary Power Module The Auxiliary Power Module (Cat. No. PRTAAPM), illustrated in Fig. 7, is an encapsulated power supply that requires a 2 Vac input at either or Hz. t provides an output of 32 Vdc (nominal 4 Vdc open circuit) which can be used for testing a Digitrip RMS Unit. When drawout construction is provided, any circuit breaker equipped with a Digitrip RMS Unit can be conveniently set and tested while the circuit breaker is out of its cell or in its cell in the "Disconnect" or "Withdrawn" positions using the Auxiliary Power Module. The Auxiliary Power Module is equipped with a unique plugin connector suitable only for plugging into the keyed receptacle of a Digitrip RMS Unit. This prohibits the possible use of an incorrect, but similar, type power module. The location of the keyed receptacle for the auxiliary power module is shown in Fig.. 8. Rating Plug The rating plugs, as illustrated in Figs. and, are used to establish the continuous ampere rating of the related circuit breaker. All pick-up settings of the protection functions of the trip unit, i.e., long delay, short delay, instantaneous and ground fault are selected as a multiple of the rating plug rating Onl Different types and ratings are available to match the desired ampere rating and type of circuit breaker into which the trip unit is to be installed. Also, since the rating plugs are frequency sensitive, specific types are available for or Hz system applications. Complete catalog descriptions of all available rating plugs are given in the applicable circuit breaker supplementary instruction leaflets. References to these documents are given in Sections 9. and 9.2.

9. References 9. Type DS Low Voltage AC Power Circuit Breakers.B. 33-79-F.B. 33-79-F Supplement No. SC-428-87 SC-428-87 SC-4279-87 8B8 nstructions for Low-Voltage Power Circuit Breakers Types OS and DSL Section 8A Supplement Circuit Breaker Automatic ping System When Using Digitrip RMS Assembly (L) for Type DS Circuit Breakers (LS) for Type OS Circuit Breakers (G) for Type OS Circuit Breakers Connection Diagram for Type OS Circuit Breakers 9.2 Type SPB Systems Pow-R Breakers.L. 29-8.L. 29-8 SC-4283-87 SC-4284-87 SC-4282-87.S. 4 nstruction for the Systems Pow-R Breaker and Drawout Mechanism Supplementary nstructions for the Systems Pow-R Breaker used with the Digitrip RMS Assembly (L) for Type SPB Systems Pow-R Breaker (LS) for Type SPB Systems Pow-R Breaker (G) for Type SPB Systems Pow-R Breaker SPB Master Connection Diagram using Digitrip RMS Assemblies 9.3 Digitrip RMS Assemblies.L. 29-8.L. 29-82.L. 29-83.L. 29-84 nstructions for Digitrip RMS Unit nstructions for Digitrip RMS Unit nstructions for Digitrip RMS 7 Unit nstructions for Digitrip RMS 8 Unit 9.4 Series C R-Frame Molded Case Circuit Breakers 29-29- 7 29-77 SC-482-89 SC-483-89 SC-484-89.L. 29C79 Frame Book Frame nstruction Leaflet Supplement nstructions for Series C R Frame used with the Digitrip RMS Assembly (L) for Type RD Circuit Breakers (LS) for Type RD Circuit Breakers (G) for Type RD Circuit Breakers Master Connection Diagram for Series C R-Frame Circuit Breaker with Digitrip RMS

2 Westinghouse Electric Corporation Distribution and Control Business Unit Electrical Components Division Pittsburgh, PA 22 Style No. C9H

nstructions for Digitrip RMS Unit Table of Contents. General Description.... Protection....2 nformation....3 Testing... 2. UL Listed Devices... 3. Principle of Operation... 3. General... 3.2 and Operation ndicators... 3.3 Test Provisions... 3.4 Making Current Release (Discriminator)... 3. nstantaneous Override... 3. Zone nterlocking... 4. Protection Settings... 4. General... 4.2 Long Delay Settings... 4.3 Long Delay Settings... 4.4 Short Delay Pick-up Settings... Short Delay Settings... 4. nstantaneous Pick-up Settings... 4.7 Ground Fault Current Pick-up Settings... 4.8 Ground Fault Delay Settings.... ntegral Test Panel - Test Procedure.... General....2 When To Test....3 Test Provision....4 Mode of Conducting Tests....4. Control Power....4.2 By Not ping the Breaker....4.3 By ping the Breaker.... Back-up Battery..... General....2 Battery Check....3 Battery Replacement... 7. Auxiliary Power Module... 8. Rating Plug... 9. References... 9. Type DS Low Voltage AC Power Circuit Breakers... 9.2 Type SPB Systems Pow-R Breakers... 9.3 Digitrip RMS Assemblies... 9.4 Series C R-Frame Molded Case Circuit Breakers... 4. WARNNG DO NOT ATTEMPT TO NSTALL OR PERFORM MAN TENANCE ON EQUPMENT WHLE T S ENERGZED. DEATH OR SEVERE PERSONAL NJURY CAN RESULT FROM CONTACT WTH ENERGZED EQUPMENT. ALWAYS VERFY THAT NO VOLTAGE S PRESENT BEFORE PROCEEDNG WTH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY PROCEDURES. THE WESTNGHOUSE ELECTRC CORPORATON S NOT LABLE FOR THE MSAPPL CATON OR MSNSTALLATON OF TS PRODUCTS. Page 4 4 4 8 8 8 8 9 9 9 9 The user is cautioned to observe all recommendations, warnings and cautions relating to the safety of personnel and equipment, as well as all general and local health and safety laws, codes, and procedures. The recommendations and information contained herein are based on Westinghouse experience and judgement, but should Effective May, 989 Supersedes.L. 29-8 dated March, 988.L. 29-8-A not be considered to be all-inclusive or covering every application or circumstance which may arise. lf,any questions arise, contact Westinghouse Electric Corporation for further information or instructions.. General Description. Protection The Digitrip RMS Unit, illustrated in Fig., is a microprocessor based type trip suitable for use in type SPB Systems Pow-R circuit breakers and types DS and DSL low voltage AC power circuit breakers and Series C R-Frame molded case circuit breakers. The trip un'it provides true RMS current sensing for proper correlation with thermal characteristics of conductors and equipment. nterchangeable rating plugs are provided to establish the continuous current rating of each circuit breaker. The Digitrip RMS Unit is completely self-contained and when the circuit breaker is closed, requires no external control power to operate its protection systems. t operates from current signal levels and control power derived through current sensors integrally mounted in the circuit breaker. The Digitrip RMS Unit is available in six optional protection models. Each trip unit may be equipped with a maximum of five phase and two ground (time-current) adjustments to meet specific application requirements. These protection models include the following types which are further illustrated in the nameplate examples shown in Fig. 2. Figure Type Protection 2. Long /nstantaneous 2.2 Long /Short 2.3 Long /Short /nstantaneous 2.4 Long /nstantaneous/ground 2. Long /Short /Ground 2. Long /Short /nstantaneous/ Ground.2 nformation dentifier (L) (LS) (LS) (LG) (LSG) (LS G) Red LED indicators are provided on the face of the trip unit to indicate the mode of an automatic trip operation. A battery is provided to maintain the mode of trip LED indication following an automatic trip operation. Green LEOs are provided to indicate the operational status of the trip unit and the status of the back-up battery mounted in the rating plug..3 Testing An integral test panel, including a test selector switch and test and reset pushbuttons, is provided to test the circuit breaker in either a "" or "No-" test mode under qualified conditions. 2. UL Listed Devices Digitrip RMS Units are listed by the Underwriters Laboratories, nc. for use in types SPB, DS and DSL and Series C R-Frame circuit breakers under UL File E789.