Flood Dosed System Worksheet

Similar documents
Washtenaw County DESIGN PROCEDURES AND ENGINEERING STANDARDS FOR PRESSURE DISTRIBUTION NETWORKS

PUMP TYPES. Pump Sizing. Dose to Gravity. Pumping to Gravity Distribution. Systems that need a Lift. Distribution Box and Tiered Trenches.

Worksheet for pressure distribution system design Long form with instructions and tables Rev. August 2007

Pressure Distribution. Western Canada Onsite Wastewater Management Association

Turbine STEP System SIMPLEX OR DUPLEX

Pressure Distribution Design

PRESSURE DISTRIBUTION COMPONENT MANUAL FOR PRIVATE ONSITE WASTEWATER TREATMENT SYSTEMS (VERSION 2.0) January 30, 2001

EQUAL DISTRIBUTION OF WASTEWATER USING LOW-PRESSURE DISTRIBUTION Larry D. Stephens, P.E. *

grundfos smartflo SmartFlo System Sizing Pocket Guide Curves and sizing information for all SmartFlo systems

AMERICAN RECIRCULATING SAND FILTER SYSTEMS

OPERATION MANUAL NT80 NOMAD TRANS-FLO AIR-OPERATED DOUBLE DIAPHRAGM PUMPS. A JDA Global Company. 5/13 rev.2

Self Cleaning Hood System Installation, Operation, and Maintenance Manual

ABCD BFDC BEDA AB CDEFCC

OPERATION MANUAL. ALUMINUM Models. 316 S.S. Models NTG50 NOMAD TRANS-FLO AIR-OPERATED DOUBLE DIAPHRAGM PUMPS. A JDA Global Company. 1/14 rev.

OPERATION MANUAL. ALUMINUM Models. 316 S.S. Models NTG40 NOMAD TRANS-FLO AIR-OPERATED DOUBLE DIAPHRAGM PUMPS. A JDA Global Company. 1/14, Rev.

BLOWER PERFORMANCE CHART

CHAPTER 7 PUMPING SYSTEM DESIGN

Piping Systems. J. David Bankston, Jr., and Fred Eugene Baker*

ON-SITE WASTEWATER PRODUCTS

OWS OPERATIONS & MAINTENANCE

Private Wastewater System Catalog. DSG - La Crosse (800)

Engineering & Design Data

Hydraulic Calculations

OPERATION MANUAL. ALUMINUM Models. 316 S.S. Models NTG25 NOMAD TRANS-FLO AIR-OPERATED DOUBLE DIAPHRAGM PUMPS. A JDA Global Company. 1/14 rev.

Aqua Green Utility Inc.

INLINE 1100 STAGED PALLET SYSTEM. franklinwater.com

FLOOD PROTECTION SHUT DOWN VALVE (3 and smaller)

ONSITE WASTEWATER TREATMENT SYSTEM Property Transfer Certification Instructions and Inspection Report

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4

OPERATION MANUAL. DUCTILE Models NT100 NOMAD TRANS-FLO AIR-OPERATED DOUBLE DIAPHRAGM PUMPS. A JDA Global Company. 5/13 rev.2

Septic Tanks. Effluent Screen Cleaning. Effluent Screens. Surveying Abbreviations. Installation Keys. Septic Tanks, Holding Tanks & Pump Tanks

Instruction Guide: Residential Earth Loop Pressure Drop Calculation and Pump Sizing

LITERS PER MINUTE TOTAL HEAD IN FEET TOTAL HEAD IN METERS GALLONS PER MINUTE

WSB clean: Installation Manual

Model AM2 M40 Panel Installation, Operation, and Maintenance Manual

OPERATION MANUAL NT50 NOMAD TRANS-FLO AIR-OPERATED DOUBLE DIAPHRAGM PUMPS. A JDA Global Company. 7/11 rev. 1

Air in your Pipes? Choosing the Correct Air Valves For Your System. Presented by John Skalla DeZURIK, Inc.

ME3H/ME3F SERIES. Automatic and manual models. Single phase power only 115 or 230 volt.

COURSE # 343 UNIT 4: ADVANTEX WASTEWATER TREATMENT SYSTEM. What you will learn in this lesson

W4100, W4200 & W4300 Electric Pump

MIDLAND PRECAST COMPANY, L.C. Tel: Hwy 14 PO Box 63 Toll Free: Corydon, Iowa Fax:

Pump Specifications 405 Series Commercial Drain Pump (High-Temp)

Table of Contents. Item Page #

ASP Submersible Bore Hole Stainless Steel Pumps

Propeller Meters. Flow measurement solutions for water and wastewater

Boand Arena Septic to Sewer Duplex Grinder Pumps (Commercial) Engineering Analysis

Pump Specifications. D3648LSG, D3648LSGX Series Omnivore 2HP Duplex Grinder Packages LITERS PER SECOND

WATER SYSTEM SIZING Introduction Residential Water System Sizing

Orenco Automatic Distributing Valve Assemblies

Lube Level Maintainer

RSD FIRE PROTECTION, INC 737 SO. CEDAR ROAD NEW LENOX, ILLINOIS

RSD FIRE PROTECTION, INC 737 SO. CEDAR ROAD NEW LENOX, ILLINOIS

Power-Limiting Cables

LCD Annunciator Installation Instructions

SPD50H/100H. Performance Data SPD100H SPD50H. Wholesale Products Page: Section: Performance Data Dated: April 2002 Supersedes: January 2001

Lube Level Maintainer

ABL FIRE PROTECTION 300 HOKE STREET RALEIGH, NC

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

Mark 6127 Series. Pressure Regulators Mark 6127 Series. Pressure Reducing Valves. Valve Features. Operation

OPERATION MANUAL. ALUMINUM Models 316 S.S. Models AIR-OPERATED DOUBLE DIAPHRAGM PUMPS .5 METALLIC PUMP PWR-FLO TM AIR DISTRIBUTION SYSTEM NPF 15

Felco Industries, Ltd Grant Creek Road P O Box Missoula, Montana (406) Fax (406)

TECHNICAL INFORMATION Bulletin

E-Z Treat Installation Guidelines

Felco Industries, Ltd Grant Creek Road P.O. Box Missoula, Montana (406) Fax (406)

Recirculating Media Filters OWNER'S MANUAL

Technical Bulletin. 1.0 Introduction

Installation Instructions

Water System Sizing Worksheet. Joe Agricola Example

MODEL "454L" MOBILE HIGH PRODUCTION CENTRAL MIX PLANT

Piping Systems in Dewatering Applications

Basins, Floats & Accessories

REDUCED DIAMETER SUBMERSIBLE PUMPS

Mark 5108 Series. Back Pressure Regulating Valves Mark 5108 Series. Back Pressure Regulating Valves. Valve Features. Operation

HYDROMATIC SPX50/SPX50H EXPLOSION PROOF, SEWAGE EJECTOR

Pumping Station. Marisa Handajani

LITERS PER MINUTE GALLONS PER MINUTE

Lube Level Maintainer

GCG ASSOCIATES, INC. PROFESSIONAL CIVIL ENGINEERS AND LAND SURVEYORS 84 Main Street Wilmington, Massachusetts 01887

LEAD FREE * LFF113RFP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology

FireLock NXT Deluge Valve. With Deluge Trim Grooved x Grooved. System No. Submitted By Spec Sect Para Location Date Approved Date

Pump Control Ball Valve for Energy Savings

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim

INSTALLATION INSTRUCTIONS RECOMMENDED MODELS

Fully Automatic Bilge Pump INSTRUCTION MANUAL

Aquavar e-abii. TECHNICAL BROCHURE BAQUAeABII VARIABLE SPEED CONSTANT PRESSURE SYSTEMS

PRE-INSTALLATION GUIDE

Your Premier Pump Choice!

HYDROMATIC SPD50H/100H SUBMERSIBLE HIGH HEAD, DOUBLE SEAL EFFLUENT

SPECIFICATIONS EFFLUENT/SUMP SIMPLEX SYSTEM ZOELLER SUBMERSIBLE DEWATERING OR EFFLUENT PUMPS

MODEL 7ASX-8 SPECIFICATION

BSM ROTARY GEAR PUMPS

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve

Viking s helical gear reducers are available in three basic sizes, each size offering several gear ratios.

Quality Value Assurance

Sequencing Batch Reactor. Reference Manual. Only modules bearing the NSF logo and designated PS1-XX are certified to NSF/ANSI Standards 40 and 245

Design Information. Designing Your Dust Collection System. Typical dust or fume collection system

elbow ball check valves Patents no.: US 8,146,618 B2, US 8,082,949 B2 in-line ball check valves Patent no.: US 8,146,618 B2 PRODUCT CATALOG

ENGINEERED PRODUCTS. Project: Unit Tag: MS-80-D-3 Page 1 of 5

Installation Manual. Omnivore Grinder Pump Retrofit Unit LSG202-RE. LSGX202-RE 2Hp, V, 1 phase, Automatic LSG202-REX

Installation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps

Transcription:

Number of bedrooms Flood Dosed System Worksheet Septic tank size Minimum 1000 gallons Dosing tank size Minimum 800 gallons or 1 bedroom smaller than septic tank size whichever is larger Filter: gravity(in septic tank) or pressure(on delivery line) Make Model A/V alarms are required for filters. Use of a gravity filter will require a filter alarm in addition to the pump alarm. Discharge Rate: Select a discharge rate from the chart. GPM Delivery Line & Friction Loss: Delivery line diameter is selected using the friction loss chart in the state rule. The chart lists velocity (v) and friction loss head (H f ) for a given flow (gpm) in each diameter of pipe in the chart. You must use a diameter pipe that produces a velocity of at least 2 fps for your flow rate. This velocity provides scouring action to help keep the delivery line clean. Velocities above 5 fps should be avoided. Diameter of delivery line Use the fitting schedule and fitting friction loss chart on the following pages to determine the equivalent length of pipe added to the actual delivery line length to compensate for friction loss due to fittings. Page 1 of 6

Fitting A. Quantity of each type and size used. B. Equivalent Pipe Length from chart in state rule or manufacturer specs C. Total equivalent pipe length for each fitting type and size. Multiply A x B Example: 90⁰ elbow, standard sharp 2-3 2 =8.6ft 3x8.6=25.8ft 3-1 3 =11.1ft 1x11.1=11.1ft 90⁰ elbow, standard sharp 90⁰ elbow long sweep radius 45⁰ elbow standard Tee use branch flow value Multiply A x B x 2 to account for both branches of Tee Gate Valve Male/female adapter Check valve Union/cam lock Pressure filter Page 2 of 6

Grand Total of column C This is the equivalent length of pipe added on the delivery line length due to the friction loss of the fittings. Add the grand total of equivalent pipe length to the actual length of the delivery line to calculate total friction loss. Delivery line length ft + equivalent length ft = ft of pipe total Find friction loss factor in chart from state rule. See page 6. H f = Total ft of pipe 100 x H f = feet of friction loss in the delivery line. Total Design Head A. Friction loss in delivery line ft B. Elevation difference (pump to manifold) ft Total design head =A+B ft Pump Sizing Pump sizing criteria 1. Total design head ft 2. Total discharge rate gpm Page 3 of 6

Plot this design point on the pump curve. It must be below (to the left of the curve). See the example on the next page. Example: Middle 1/3 of the curve is the target The design point is 12 feet of head and a total discharge rate of 32 gpm. Draw a line from the origin (0,0) through the design point to the pump curve. The line should cross the curve in the middle 1/3 for optimum efficiency and pump life. Draw a line straight down from the point where this line crosses the curve (represented by the dotted line). The difference between the dotted line and total discharge rate of the system should be at least a 10% difference, but not more than 20 gpm. Pump s make, model Pump performance curve included with plan Dosing Chamber *NOTE: Only effluent, sewage or grinder pumps may be used. The dose volume for a flood dosed system is the daily design flow plus the drain back volume from the delivery line, if it drains back to the tank. Daily design flow equals the number of bedrooms x 150 gallons per day= gpd Length of delivery line ft x gallons per foot of pipe (found in chart from state rule, located on the next page)= gallons drain back from delivery line. Daily design flow + drain back= total dose volume You must know the gallons per inch in the dosing chamber (from manufacturer) to calculate how many inches the pump float must travel from the on to off positions to dose the correct volume. Page 4 of 6

Total dose volume gallons per inch in dosing chamber = inches travel from pump on to pump off. All electrical connections will be made in a NEMA 4X junction box. It is preferred that the junction box be outside the riser and that it is not directly connected to any conduit that extends into the riser. All openings into riser must be made gas and moisture tight. Dosing chamber will have a riser to surface. Dosing Chamber will have audio and visual alarm. Plans A scale drawing of the proposed system including all applicable worksheet items, bird s eye view, cross sectional view, and required ground surface elevations is included. The system is staked/flagged and the system area is fenced(if required by ECHD) and ready for a site review. Page 5 of 6

Page 6 of 6