MANUAL INSTALLATION. Venturi FX. VFX Series. v100 Issue Date: 11/22/ Price Industries Limited. All rights reserved.

Similar documents
MANUAL INSTALLATION. Venturi Valve. VV Series. v203 - Issue Date: 03/25/ Price Industries Limited. All rights reserved.

Venturi Valve. 2 For more information visit v100. Actuator. Potentiometer. Lever Arm. Airflow Area AIRFLOW.

LDV / LDVQ 5000 AIR VOLUME CONTROL VALVE INSTALLATION MANUAL. Date: 02 / 10 Reference # : F-36. w w w. p r i c e - h v a c. c o m

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

ACCESSORIES & OPTIONS FOR VENTURI AND VENTURI FX VALVES

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

COMPACT CAGE RACK VALVES

The IAQ50 Air Damper/Monitor Installation and Maintenance Manual

Fan Powered Low Profile Variable Volume Terminal Units

MODEL 8630-CRC-S, 8630-CRC-P PRESSURA CLEAN ROOM PRESSURE CONTROLLER

ACCUSTATION SUBMITTAL MATERIALS

Variable Air Volume Dampers

HORD INSTALLATION & SERVICE MANUAL. Hospital Operating Room Diffusers INSTALLATION & SERVICE MANUAL. Date: 06 / 12 Reference # : E-10 1

Laboratory Solutions. pricecriticalcontrols.com

ACCUVALVE MODEL AVT6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVT6000 AVT6 - - DWG. NO: REVISION: REV. DATE:

SDL Single-Duct, Low-Height, VAV Terminals

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions

Installation, Operation and Maintenance Manual

Safety & Installation Instructions

MODEL 8636 / 8636-LN / 8636-BAC SUREFLOW ROOM PRESSURE CONTROLLER

Installation, Operation and Maintenance Manual

Low Pressure Sensor. Overview. Specifications. Installation and Operation

Installation Manual. HEPALERT LED LIGHT Kit Installation, Operation, and Maintenance Manual for the TLF Diffuser

SINGLE DUCT TERMINAL UNITS 30X/HQX SERIES

University of Delaware

MODEL 8682 SUREFLOW ADAPTIVE OFFSET CONTROLLER

MODEL 8631-CRM/8631-CRC PRESSURA CLEAN ROOM PRESSURE MONITOR/CONTROLLER

TABLE OF CONTENTS SPECIFICATIONS 3 INSTALLATION 4. Direct Mount 4. Ducted Installations 5. Installing Plenum 5. Machine Mount Stand 5.

Technical information

TSS Single-Duct VAV Terminals

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

ACCUVALVE MODEL AVC6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVC6000 AVC6 - - DWG. NO: REVISION: REV. DATE:

SECTION AIR INTAKE SYSTEM

RETROFIT TERMINAL UNITS

MODEL 8631-HM(-BAC)/8631-HC(-BAC) PRESSURA ROOM PRESSURE MONITOR/CONTROLLER

Installation Instructions

SINGLE DUCT TERMINAL UNITS

SINGLE DUCT VAV TERMINALS MODELS TSS & TSL TSS TSL. New Release Form NOM1 (808) INSTALLATION, OPERATION & MAINTENANCE

Installation Instructions

Healthcare Solutions Room Pressure Monitors and Controls

Installation, Operation and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS

Portable Oil Free Silent Series Compressor Operating Instructions

P RO W ALL V ENTILATION H OODS INSTALLATION INSTRUCTIONS

Installation, Operation and Maintenance Manual

Laboratory Exhaust Air Terminal

SINGLE DUCT AIR TERMINAL UNITS

100% OUTSIDE AIR MAKE-UP UNITS WITH DISCHARGE TEMPERATURE CONTROL & c.pco DIRECT DIGITAL CONTROL MODULE

Installation, Operation and Maintenance Manual

Owner s Information Manual

SAFETY INSTRUCTIONS Before installation and operation, read these instructions carefully and use this product only in the manner described by the manu

MANUAL INSTALLATION. Modular Floor Diffusers. MFD Series. v102 Issue Date: 03/23/ Price Industries Limited. All rights reserved.

Start-Up, Operation and Service Instructions

Operations & Maintenance Manual DFH-1000 DUCTLESS FUME HOOD

SECTION AIR TERMINAL UNITS

NSGV PT-1000 PORTABLE WELDING STATION I, O & M MANUAL

Dual Duct Variable Air Volume Terminal (Model TDS)

FAN POWERED TERMINAL UNITS

Laboratory Exhaust Air Terminal

LIQUID LEVEL FLOAT SWITCH. F7 Series INSTALLATION AND OPERATIONS MANUAL. Single-Point, Vertically-Mounted Liquid Level Float Switch

FOR USE IN SOLUTION AIR HANDLING UNITS

Products for Indoor Air Quality and Control

Laboratory Room Single Duct Supply Air Terminal

Air Handling Unit Construction Checklist

Copyright 2017 ORIFLOW LLC. Operating Instructions for Cobra and Lynx Duct Leakage Testers

FAN POWERED TERMINAL UNITS

M100F Incremental Motor Actuator R81F Interface Board

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc.

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

WARNING Warnings are indicated when mishandling this product might result in death or serious injury to the user.

MANUAL INSTALLATION. Active Chilled Beam Linear. ACBL Series. v101 Issue Date: 04/10/ Price Industries Limited. All rights reserved.

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT DRIVE XBL FANS

Jet Fans. Instruction Manual READ AND SAVE THESE INSTRUCTIONS WARRANTY

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

ATP-2040 Electric Damper Actuator/Transmitter

LABORATORY ZERO AIR GENERATOR MODEL N-GC1500 USER S MANUAL

DUST COLLECTOR (BOTTOM REMOVAL BAG & CAGE) INSTALLATION AND OPERATING INSTRUCTIONS

Installation, Operation, and Maintenance Instructions

RT Series Step Down Transformer for RT Series UPS 6-10kVA UL Input Vac Output Vac User Guide

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes:

MODEL SCA Installation and Operation Manual Important:

Direct Coupled Damper Actuator Model MY6050A1001

General Installation Instructions for Valves and Gates

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

Installation/ Operation Maintenance. VariTrac Dampers

INSTALLATION MANUAL TBH/TBV BELT DRIVE BLOWER-COIL UNITS HORIZONTAL. Redefine your comfort zone.

MOTORIZED VOLUME DAMPER

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

Slide Gates INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS. 295-E-002 Effective

Advanced Outdoor Airflow Control, DCV Control and Alarm Solution for OA Applications Document Name: QG_EAC1100_A_R3A

Compact Low Pressure Sensor

Air Measuring Products AMD AMS IAQ

HA/HAB Fiberglass Wall Mount Ventilators

NMQB24-MFT, NMQX24-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

NMB (X) 24-MFT. Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

High Performance Fan Coils FCHG Genesis Series Horizontal

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

Transcription:

MANUAL INSTALLATION Venturi FX VFX Series v100 Issue Date: 11/22/16 2016 Price Industries Limited. All rights reserved.

TABLE OF CONTENTS Product Overview Safety Precautions... 1 Caution to Contractors...1 General...2 Receiving Inspection...2 Flow Data...3 Installation and Mounting Instructions Installing the Venturi FX Unit...4 Controls...7 Wiring Diagram... 9 Display Navigation Start Up and Operation...10 Troubleshooting...10 Replacement Parts...10

PRODUCT OVERVIEW Safety Precautions 1. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction. 2. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities. 3. Use this unit only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer: PRICE INDUSTRIES 2975 Shawnee Ridge Court Suwanee, Georgia USA 30024 (770) 623-8050 Fax (770) 663-6404 Caution to Contractors Venturi FX valves are not intended for use as temporary heat or ventilation sources during building construction. The units are not designed nor equipped to operate in a dusty construction environment. Internal parts can become coated in construction dust, resulting in loss of calibration and excess wear on the product which in turn can contribute to reduced life. Technical Support 1-866-884-3524 criticalcontrols@priceindustries.com www.pricecriticalcontrols.com 4. Before servicing or cleaning unit, switch power off at service panel and lock service panel to prevent power from being switched on accidentally. 5. Protect flammable materials nearby when brazing. Use flame and heat protection barriers where needed. Always have a fire extinguisher ready. 6. The manufacturer assumes no responsibility for personal injury or property damage resulting from improper handling, installation, service or operation of the product. pricecriticalcontrols.com VENTURI FX - Manual 1

PRODUCT OVERVIEW General The Price Venturi FX is designed specifically for room pressure applications. The VFX uses noninvasive pressure ports to measure the flow. Variable volume valves are designed to accept direct digital controls (DDC) based on airflow sensor feedback. All VFX valves will be shipped with the actuator mounted and calibrated. VENTURI FX Receiving Inspection After unpacking the assembly, check carefully for shipping damage. If any damage is found, report it immediately to the delivering carrier. Damage may result from improper handling. Never carry or lift the valve by the control box. 2 VENTURI FX - Manual pricecriticalcontrols.com

PRODUCT OVERVIEW Flow Data NOTES: Unit Size 1. Factory calibrated controls must be selected within the above flow range limits. When setting the flow, the value must be greater than the minimum setting and within the range limits. Selection of air flow below the listed values is not recommended. Stability and accuracy may not be acceptable at lower than recommended air flow limits. 2. Please refer to VFX submittals for all dimensional data. 3. Weights are +/- 5 lbs depending on options Min. Flow (CFM) Airflow Range Max. Flow (CFM) 4. Valves are rated to operate between 32-120 F within 10-95% RH non-condensing. Weight (lbs) 108 80 800 19 110 120 1300 20 112 180 1800 22 114 250 2500 24 pricecriticalcontrols.com VENTURI FX - Manual 3

INSTALLATION AND MOUNTING INSTRUCTIONS Installing the Venturi FX Unit Before Installation FIGURE 1 1. Visually inspect the valve for damage. If damage is found, DO NOT INSTALL. Please contact a Price representative. 2. Visually inspect the red tamper proof paint located on the actuator. If paint is cracked, DO NOT INSTALL. Please contact a Price representative. 3. During operation, the blade damper of the valve may extend past the discharge of the valve. Ensure that a minimum three inches (3 in.) of duct space is clear of obstacles from the valve discharge. General Installation 1. Ductwork to be supported within eighteen inches (18 in.) of the Venturi FX unless otherwise specified. 2. Mount valve according to the airflow direction arrow on the AIRFLOW label. When the valve is installed, the airflow arrow direction should agree with the system airflow. 3. Leave eight inches (8 in.) of free space in all directions of the controls enclosure to facilitate future access. FIGURE 2 PRICE ORDER NO: JOB NAME: UNIT TAG: LINE: SERIAL NO: UNIT SIZE: FLOW RANGE: ORIENTATION: SPECIFICATIONS www.pricecriticalcontrols.com criticalcontrols@priceindustries.com criticalcontrols@price-hvac.com 678-578-7495 CFM @ 70 F, 0 FT ELEV. - PLEASE REFER TO MANUAL FOR ELEV. CORRECTION TESTED: QA: DATE: *O 00000000000001A001* Slip-Connection Venturi FX 1. Mount the Venturi FX by slipping both the inlet and the discharge one inch (1 in.) into the appropriate sized ductwork. 2. Fasten the Venturi FX to the ductwork using six (6) sheet metal screws per a slip connection as shown in Figure 2. 3. Seal the duct work using duct sealer as shown in Figure 3. 1 inch FIGURE 3 4 VENTURI FX - Manual pricecriticalcontrols.com

INSTALLATION AND MOUNTING INSTRUCTIONS Slip-Connection Venturi FX with Drawband Clamps 1. Slide drawband clamps completely onto the inlet and discharge ductwork as shown in Figure 4. FIGURE 4 2. Mount the Venturi FX by slipping both the inlet and the discharge one inch (1 in.) into the appropriate sized ductwork Size 14 Configuration 3. Apply appropriate duct tape to seal valve to duct work if required. Two full wraps around the connection is recommended. 4. Slide the drawband clamps onto the valve ensuring that at least one and a half inches (1.5 in.) of the drawband clamps are in contact with the valve body as shown in Figure 5. Size 8, 10, 12 Configuration FIGURE 5 5. Tighten both nuts to ensure that the drawband clamp is tightly fastened to the valve body and duct work. Neither the valve nor the band clamp should shift after fastening. Size 14 Configuration Flange-Connection Venturi FX 1. Align the duct flange holes with the venturi flange holes and fasten using a bolt, lockwasher and nut. Fasten every hole to reduce airflow leakage as shown in Figure 6. NOTE: To minimize airflow leakage, use a gasket between the ductwork flange and the venturi flange or seal with duct sealant once connecting bolts are tightened. Flange-Connection Venturi FX with Companion Flanges 1. Slide companion flanges completely onto the inlet and discharge ductwork with the flanged end of the companion flanges toward the free space. Size 8, 10, 12 Configuration FIGURE 6 2. Align hole pattern to match opposing companion flange as shown in Figure 7. 3. Continuously weld companion flange to duct work to ensure zero leakage. 4. Follow Installation of Flange-Connection Venturi FX to complete installation of Venturi FX. FIGURE 7 pricecriticalcontrols.com VENTURI FX - Manual 5

Air flow VENTURI FX INSTALLATION AND MOUNTING INSTRUCTIONS Venturi FX with Silencer 1. Position silencer before the inlet of the Venturi FX when the Venturi FX is operating as an exhaust valve. Position silencer on the discharge of the Venturi FX when the Venturi FX is operating as a supply valve. Configurations shown in Figure 8. FIGURE 8 SUPPLY CONFIGURATION 2. Price recommends that the silencer be installed prior to installing the Venturi FX. EXHAUST CONFIGURATION Air flow Air flow 3. Use the support method prescribed for the duct work in the job specifications. FIGURE 9 4. Mount the silencer to the duct. The slip connection should overlap a minimum of one inch (1 in.) to ensure a proper fit as shown in Figure 9. 5. Mount the Venturi FX by slipping the appropriate end into the available duct work and the other into the free slip connection of the silencer. Each slip connection should overlap a minimum one inch (1 in.) to ensure a proper fit. FIGURE 10 6. Fasten all connections using six (6) sheet metal screws per a slip connection as shown in Figure 10. 7. Seal slip connections using duct sealer as shown in Figure 11. Venturi FX with Water Coil Please refer to the Water Coils Service and Installation Manual for full installation instructions. Manual available on the Price website at www.priceindustries.com. 1. Water coils are only available in supply orientation. 2. Configuration as shown in Figure 12. FIGURE 11 1 inch 3. Use the support method prescribed for the duct work in the job specifications. Venturi FX with Electric Coil Please refer to the Electric Coils for VAV Terminals Manual for full installation instructions. Manual available on the Price website at www.priceindustries.com. 1. Electric coils are only available in supply orientation. 2. Configuration as shown in Figure 13. 3. Use the support method prescribed for the duct work in the job specifications. FIGURE 12 FIGURE 13 Supply Configuration Air flow 6 VENTURI FX - Manual pricecriticalcontrols.com

INSTALLATION AND MOUNTING INSTRUCTIONS Controls 2 TO 10 VDC CONTROL Actuation Price Venturi FX valves are shipped with a factory mounted actuator. Price offers two actuator control solutions for the VFX: 1. 2-10 VDC Line Volts 24 VAC Transformer BIk (1) Red (2) Wht (3) Common- Hot + Y Input, 2 to 10v 2. Floating point Control signal (2-10 VDC) Org (5) U Output, 2 to 10v Please note that floating point and 2-10 VDC actuators are only available in standard speed. 1 0 CAUTION Do not press the actuator clutch when airflow is present. Pressing the actuator clutch while airflow is present may damage the actuator. FLOATING POINT CONTROL 24 VAC Transformer TC and PC Controllers Line Volts BIk (1) Red (2) Common- + Please refer to the TC and PC Installation Manuals available on the Price Critical Controls website at www.pricecriticalcontrols.com NOTE: The indication of direction (1 or 0) may be changed by Price to ensure that the actuator operates as specified by the customer. The indication of direction is valid for switch position 1. Wht (3) 1 0 + pricecriticalcontrols.com VENTURI FX - Manual 7

INSTALLATION AND MOUNTING INSTRUCTIONS PTX - Pressure Transducer Price s Pressure Transducer (PTX) is a compact differential pressure output module that utilizes a high accuracy sensor for measuring pressure. The flow-through, noninvasive digital sensor allows for maintenance-free pressure measurement. The PTX outputs a 0-10 VDC signal proportional to any of the five (5) selectable pressure ranges. Status Indication Light Differential Pressure Ports Pluggable 24 VAC Power Terminal 0-10 VDC Pressure Signal Output 8 VENTURI FX - Manual pricecriticalcontrols.com

INSTALLATION AND MOUNTING INSTRUCTIONS Wiring Diagram DIAGRAM pricecriticalcontrols.com VENTURI FX - Manual 9

DISPLAY NAVIGATION Start Up and Operation Before start up operation, familiarize yourself with the unit, options, accessories and controls so you understand proper system operation. All personnel should have a good working knowledge of general start-up procedures and have the appropriate start-up and balancing guides available for consultation. Air System Balancing All duct-work must be complete and connected, and all grilles, filters, access doors and panels must be properly installed to establish actual system operating conditions BEFORE beginning air balancing operations. Each individual unit and attached duct-work is a unique system with its own operating characteristics. For this reason, air balancing is normally done by balance specialists who are familiar with all procedures required to properly establish air distribution and fan system operating conditions. These procedures should not be attempted by unqualified personnel. After the proper system operation is established, the actual unit air delivery should be recorded in a convenient place for future reference. The manufacturer assumes no responsibility for undesirable system operation due to improper design, equipment or component selection, and/or installation of ductwork, grilles, and other field supplied components. Troubleshooting Symptom Noise Actuator Does Not Operate (Where Available) No Feedback Signal Actual airflow does not match airflow feedback Possible Cause 1. Foreign material in valve 2. Vibrating duct work 1. Confirm that power is being delivered to the unit 2. Verify control signal 3. Verify that the disconnect switch (where available) is not open 4. Verify that the fuse (where available) is not blown 5. Verify that actuator control signal is connected to the correct analog output as per the submittals 1. Confirm that power is being delivered to the unit 2. Verify tubing has not been kinked or damaged from installation 1. Confirm that there is no blockage inside the duct or valve 2. Confirm that there is no damage to any tamper proof paint 3. Verify that there are no ductwork leaks before or after the valve 4. Verify that the valve is installed in the correct orientation 5. Verify the tubing has not been kinked or damaged Replacement Parts Replacement parts are available. Please contact a Price Critical Controls Application Specialist. Please see page 1 of this document for contact information. 10 VENTURI FX - Manual pricecriticalcontrols.com

NOTES pricecriticalcontrols.com VENTURI FX - Manual 11

NOTES 12 VENTURI FX - Manual pricecriticalcontrols.com

NOTES pricecriticalcontrols.com VENTURI FX - Manual 13

This document contains the most current product information as of this printing. For the most up-to-date product information, please go to pricecriticalcontrols.com 11/22/16 Price Industries Limited. All rights reserved.