30 Volt (CE).3.08 GP3/4 Mini Panels GP8-4 Standard-Size Panels provide power and dimming for up to 4 load circuits and control any light source, including full-conduction non-dim. Models available with: 30 V input power. 3 to 4 circuits. Different feed types and breakers. work with: GRAFIK Eye 4000 Control Units. GRAFIK 5000TM, GRAFIK 6000, and GRAFIK 7000TM Systems. P Dimming Panels. XP Softswitch Panels. DMX5 dimming systems via the INKTM option.
Specifications - 30 Volt (CE) 6.3.08 Standards Complies with CE. California Energy Commission isted Power Input power: 30 V, 50/60 Hz, phase-to-neutral. Branch Circuit Capacity: 0 A Number of Circuits: 3-4 Branch Circuit Breakers: IEC-rated thermal magnetic. AIC rating (other ratings available): 6000 A ightning strike protection: Meets ANSI/IEEE standard 6.4-980. Can withstand voltage surges of up to 6000 V and current surges of up to 3000 A. 0-year power failure memory: Automatically restores lighting to scene selected prior to power interruption. Sources/oad Types Operates these sources with a smooth continuous Square aw dimming curve or on a full conduction non-dim basis: Incandescent (Tungsten)/Halogen Magnetic ow Voltage Transformer Electronic ow Voltage Transformer utron Electronic Fluorescent Dimming Ballasts Magnetic Fluorescent amp Ballasts Optional modules allow for control of 0-0 V, DSI, and PWM load types. Operates HID sources on a full conduction non-dim basis. Internal: Prewired by utron. System communications: owvoltage Class (PEV) wiring connects Dimming Panels to other components. ine (mains) voltage:, load, and control circuit wiring only. No other wiring or assembly required. Filter Chokes oad current rise time is measured at a 90 degree conduction angle, with 0 V input power. 0-90% of load current waveform: - 350μSec rise time at 50% dimmer capacity. - 400μSec rise time at 00% dimmer capacity. 0-00% of load current waveform: - 55μSec rise time at 50% dimmer capacity. - 600μSec rise time at 00% dimmer capacity. At no point in the waveform can the rate of current change exceed 300 ma per μsec. Consult utron for higher rise time options. Dimming Cards Panel current ratings are listed for continuous operation. RTISS filter circuit technology compensates for incoming line voltage variations: No visible flicker with +/-% change in RMS voltage/cycle and +/-% Hz change in frequency/second. Arcless-relay air gap-off switches (one per load circuit) ensure open load circuits when off function selected. Eliminate arcing at mechanical contacts when loads are switched. Physical Design Enclosure: NEMA-Type (Type available upon request), IP-0 protection; #6 U.S. Gauge Steel. Indoors only. Weight: 30-75 pounds (4-80 kg). Mounting: Surface mount only. Allow space for ventilating. Environment/Heat Dissipation Patented, ribbed aluminum heat sink base cools Panel by convection. No fans. 3-04 F (0-40 C). Relative humidity less than 90% non-condensing. Reverse-phase control transformers require an EVI Power Interface. Check phase with transformer manufacturer.
9.3.08 Anatomy of a GP Model Number G P - 3 0 4 I S - 0 C E - C G P - _ Prefix Number of oad Circuits Voltage Type Panel Custom Panel Suffix Region Suffix Branch Circuit Breakers Prefix: GP for GP Dimming Panel Number of oad Circuits: Indicates number of load circuits in the panel Voltage: 30 for CE Type: for phase wire 4 for 3 phase 4 wire Panel : IS for Isolator Switch Branch Circuit Breakers: 0 for 0 A branch circuit breakers Region Suffix: CE for 30 V Custom Panel Suffix: Indicates panel with special options
5.3.08 GP3/4 Mini Models Only standard panels listed. Consult utron for further options. 30 V (CE) Power Number Of Circuits Type Maximum Panel / Branch Circuit Breakers GP3 Ø, W 3Ø, 4 W 30 A 0 A 0 A 0 A GP4 Through 0 A 0 A GP8-4 Standard-Size Models Only standard panels listed. Consult utron for further options. 30 V Power Number Of Circuits Type Panel Maximum Branch Circuit Breakers GP8 GP GP6 Ø, W 3Ø, 4 W 3Ø, 4 W 3Ø, 4 W Isolator Switch Isolator Switch Isolator Switch Isolator Switch 5 A 5 A 5 A 5 A 0 A 0 A 0 A 0 A GP0 3Ø, 4 W Isolator Switch 5 A 0 A GP4 3Ø, 4 W Isolator Switch 5 A 0 A 30 V (CE) Mains CE Panels are listed as appliances. A distribution panel must provide a main circuit breaker that does not exceed the rating of the panel. Breakers located in distribution panel supplied by others.
7.3.08 Dimensions for GP3/4 Mini Panels Top View 5 /8 in. (30 mm) 3 5/8 in. (9 mm) 6 /4 in. (60 mm) 5/8 in. (4 mm) Class (PEV) eft Side View Front View 9 5/8 in. (44 mm) Right Side View 5 /4 in. (33 mm) 3/6 in. (30 mm) 8 in. 8" (457mm) 9 /" in. (495mm) /8" in. (537mm) /8 in. (9 mm) /8 in. (9 mm) 3/4 in. (70 mm) in. (79 mm) Keyhole accepts a maximum of /4 in. (6 mm) mounting bolt. #0 M6 recommended. 3/4 in. (70 mm) Bottom View oad Circuit 3/4 in. (70 mm) / in. (38 mm) 5 / in. (40 mm) / in. (38 mm)
Dimensions for GP8-4 Standard-Size Panels 8.3.08 Top View 8 in. (7 mm) Suggested feed wiring entry Suggested load wiring entry 4 in. (00 mm) eft Side in. (50 mm) Front View in. (50 mm) Removable top cover is shipped in the same box as the panel. Right Side 37 in. (940 mm) 33 in. (838 mm) 35 in. (889 mm) 3 (330 mm) Keyhole accepts a maximum of 5/6 in. (8 mm) mounting bolt (/4 in. (m8) recommended). Class /PEV entry knockout is 7/8 in. dia. ( mm) in. (304 mm) Bottom View in. (50 mm) Required control wiring entry in. (304 mm)
GP3/4 Mini Panel Mounting.3.08 Surface mount indoors. Panel generates heat. Mount only where ambient temperature will be 0-40 C (3-04 F). This equipment is air cooled. Do not block vents or warranty will be void. eave in. (3cm) clearances above, below, and in front of Panel. No clearance necessary on sides. Reinforce wall structure for weight and local codes. GP3/4 Front View Terminal Blocks for oad Circuits Class (PEV) GP3/4 Side View in. (3cm) minimum top and front Panel GP3/4 Maximum BTUs/Hour 685 Weight (without packaging) 30 lbs. (4kg) Branch Circuit Breakers Dimming Panels will hum slightly and internal relays will click while in operation. Mount where audible noise is acceptable. Mount Panels so line (mains) voltage wiring is at least 6 feet (.8m) from sound or electronic equipment and wiring. GP Panels must be mounted within 7 of true vertical. oad Circuit Raceway in. (3cm) minimum For maximum and Wire Sizes, consult Overview page. Warning! Water damages Panels. Install where they will not get wet.
GP8-4 Standard-Size Panel Mounting 3.3.08 Surface mount indoors. Panel generates heat. Mount only where ambient temperature will be 0-40 C (3-04 F). This equipment is air cooled. Do not block vents or warranty will be void. eave in. (3cm) clearances above, below, and in front of Panel. eave clearance on sides for Class (PEV) wiring. Reinforce wall structure for weight and local codes. Panel GP8 GP GP6 GP0 GP4 Maximum BTUs/Hour 365 045 75 3405 4085 Weight (without packaging) 5 lbs. (5 kg) 30 lbs. (59 kg) 45 lbs. (66 kg) 60 lbs. (73 kg) 75 lbs. (80 kg) Dimming Panels will hum slightly and internal relays will click while in operation. Mount where audible noise is acceptable. Mount Panels so line (mains) voltage wiring is at least 6 feet (.8m) from sound or electronic equipment and wiring. GP Panels must be mounted within 7 of true vertical. GP8-4 Front View Raceway Main ugs or Main Breaker. oad Circuit in. (3cm) minimum top and front Terminal Blocks for oad Circuits Class (PEV) GP8-4 Side View air flow in. (3cm) minimum For maximum and Wire Sizes, consult Overview page. Warning! Water damages Panels. Install where they will not get wet.
4.3.08 Mounting One Panel Above Another At least 8 ft. 8 in. (65 cm) between the floor and the suspended ceiling is required for this layout. GP8-4 Front View GP8-4 Side View Raceway oad Circuit in. (3cm) minimum Class (PEV) 8 ft. 8 in. (65cm) minimum to ceiling Class (PEV) Air flow in. (3cm) 3 ft. 4 5/8 in. (03cm) to mounting holes 6 ft. 6 in. (95cm) NEC Breaker Height imit 7 ft. 5 5/8 in. (8cm) to mounting holes 6 in. (6cm) minimum Air flow 6 in. (6 cm) approved for this layout only. Warning! Water damages Panels. Install where they will not get wet.
7.3.08 GP3 Mini Panel Overview 30 Volt (CE) Wire Sizes Power : 8 AWG (.0 mm ) to 4 AWG (5.0 mm ) Neutral : 4 AWG (.0 mm ) to 6 AWG (0.0 mm ) Dimmed Hot/ive: 4 AWG (.0 mm ) to 0 AWG (4.0 mm ) oad Neutral: 4 AWG (.0 mm ) to 6 AWG (0.0 mm ) Control Typical oad Circuit Bypass Jumpers - Do Not Remove D S D S D 3 S 3 3 Branch Circuit Breakers oad Terminal Block Dimmed Hot/ive oad Neutral Ground Tips Wire the GP3 similar to wiring a lighting Distribution Panel: Run feed and load wiring. No other wiring or assembly required. Common Neutrals are not permitted. Run separate Neutrals for each load circuit. The GP3 can provide temporary lighting: Wire all loads. Do not remove the bypass jumpers that protect the Dimming Modules. Use Branch Circuit Breakers to switch lights on and off. Neutral Power (Hot/ive)
30.3.08 GP4 Mini Panel Overview 30 Volt (CE) Wire Sizes Power : 4 AWG (.0 mm ) to 0 AWG (4.0 mm ) Neutral : 4 AWG (.0 mm ) to 0 AWG (4.0 mm ) Dimmed Hot/ive: 4 AWG (.0 mm ) to 0 AWG (4.0 mm ) oad Neutral: 4 AWG (.0 mm ) to 0 AWG (4.0 mm ) Typical Dimming eg Bypass Jumpers - Do Not Remove D S N N D S N N Dimmed Hot/ive oad Tips Wire the GP4 similar to wiring a lighting Distribution Panel: Run feed and load wiring. No other wiring or assembly required. Common Neutrals are not permitted. Run separate Neutrals for each load circuit. The GP4 can provide temporary lighting: Wire all loads. Do not remove the bypass jumpers that protect the Dimming Modules. oad Neutral Terminal Block Power (Hot/ive) Ground Neutral
33.3.08 GP8-4 Standard-Size Panel Overview 30 Volt (CE) Wire Sizes Power : 4 AWG (.0 mm ) to 4 AWG (5.0 mm ) Neutral : 4 AWG (.0 mm ) to 4 AWG (5.0 mm ) Dimmed Hot/ive: 4 AWG (.0 mm ) to 6 AWG (0.0 mm ) oad Neutral: 4 AWG (.0 mm ) to 0 AWG (4.0 mm ) Typical oad Circuit Dimmed ive oad Neutral oad Power (Hot/ive) Neutral D S N D S N Bypass Jumpers - Do Not Remove Terminal Block Tips Wire the GP8-4 similar to wiring a lighting Distribution Panel: Run feed and load wiring. No other wiring or assembly required. Common Neutrals are not permitted. Run separate Neutrals for each load circuit. The GP8-4 can provide temporary lighting: Wire all loads. Do not remove the bypass jumpers that protect the Dimming Modules. Use Branch Circuit Breakers to switch lights on and off. Branch Circuit Breakers Class (PEV)
30 V (CE) oad Circuits (GP3-4) 37.3.08 All oad Types except Fluorescent Dimming Ballasts GP Dimming Panel Dimmed ive Neutral oad Use the Dimmed ive (D) for all Non-Dim oad Types. All oad Circuit 4 AWG (.0 mm ) to 0 AWG (4.0 mm ) D S N Bypass Jumpers - Do Not Remove Consult Overview page for appropriate Neutral location. oad Terminals
GRAFIK Systems GP w/ GRX-TVM Overview for 0-0 V, DSI, and DAI oad Types - 30 Volt (CE) Panels 39.3.08 D = Dimmed ive = ive N = Neutral D N D N N oad + + +
45.3.08 Option Custom Main Breaker Delta Power Branch Circuit Protection utron Ten Volt Module (TVM) ocking Cover inktm Description Panel features a custom main breaker size. Panel accepts Delta power feed (phase to phase). Available for 40 V only. imited to 0 A, -pole circuits. Branch Circuit Breakers with higher AIC ratings or special breaker types such as: EB (Earth eakage Breaker - 30 V CE/40 V non-ce Only). RCD (Residual Current Device - 30 V CE/40 V non-ce Only). Allows panel to operate fluorescent ballasts that meet IEC 99 standards for 0-0 V control including: utron s TVE ballasts 0-0 V neon PWM fluorescent Tridonic DSI (Digital Serial Interface). The TVM can sink or source 5O ma (typically 5-50 ballasts) on each circuit. Prevents accidental switching of circuit breakers. Adds an additional.5 in. (57. mm) to the front of panel. Available for GP8-GP4 only Allows a DMX5 theatrical console to operate the load circuits in the dimming panel. Allows a GRAFIK Eye 4000 System to handle 8 zones (two links of 64 zones). Allows two GRAFIK Eye 4000 Systems to share the same dimming panel. Application Jobs with special load requirements. Areas with Delta power. Jobs with fluorescent ballasts that require 0-0 V, PWM, or DSI control. Service corridors and public areas. Control of architectural lighting from a DMX5 theatrical console is required. A mix of architectural and theatrical lighting exists on the job. Multiple systems where space for panels is limited. Tridonic is a registered trademark of Zumtobel AG.