zelsius Installation and operating manual All that counts. EnergyMetering

Similar documents
zelsius Installation and operating manual All that counts EnergyMetering

Compact Heat Meters. Features. -A Pulsed output. -B M-Bus output. Accessories. UK Sales Tel: International Tel:

Datasheet PDCSY-MW-CHM. Technical Overview. Features. Product warranty and total quality commitment. General Information.

Heat Meter Integrator

Datasheet PDCSY-MW-U. Technical Overview. Features. Product warranty and total quality commitment.

zelsius C5-ISF Installation and operating manual All that counts. EnergyMetering

Screw-type and measuring capsule heat meter with IrDA interface and an interface for retrofitting external modules or with integrated communication.

ULTRASONIC FLOW SENSOR QALCOSONIC FLOW 2

Hello, I am the new Zelsius C5 heat meter. The new generation of ultrasonic heat and cooling meters for precise energy consumption measurement.

RAY COMPACT ENERGY METER MECHANICAL

SensoStar C. Installation and Operating Instructions Heat Meter Calculator Heat/Cooling Meter Calculator Cooling Meter Calculator

IFX-M4-03 IFX-M4-03_D_E_2017_05_REV.0

RAY MECHANICAL COMPACT METER. 4 MID approved class 2 from DN 15mm qp 0,6m3/h up to DN 40mm qp 10m3/h

US-S/FFL. Ultrasonic energy meters. Function. Flexible design. Connection. Mounting. High reliability

WSTH/WPTH. Woltmann type combined energy meter. Measuring distance. Function. Connection. High reliability. Mounting.

ULTRASONIC FLOW SENSOR IFX-M4-01

Fluidic Oscillation Compact Heat Meter

Compact Static Heat Meter of High-Tech Composite

Measuring capsule heat meter G54 / G55

Supercal 539. Compact thermal energy meter

Electronic Water Meters

Heat / Chill Meter PolluCom M Installation and Operating Instructions. PolluCom M. Installation and Operating Instructions. M H 1210 INT, Page 1

Superstatic 749. Fluidic Oscillation Compact Heat Meter

SonoMeter 30 Energy Meters

Superstatic 440. Static Heat Meter, Static Cooling Meter. Application

Fluidic Oscillation Compact Heat Meter of High-Tech Composite

SonoSensor 30 Ultrasonic flow meter for heating and cooling applications

EW447-EW452 Series Mechanical Heat Meters FOR HEATING AND COOLING APPLICATIONS

SonoMeter 30 Energy Meters

Electronic Heat Meters

SHARKY 775 COMPACT ENERGY METER ULTRASONIC

Operating instructions Safety sensor BNS About this document. Content. 6 Disassembly and disposal 6.1 Disassembly Disposal...

Electronic Water Meters in measuring cell design

Superstatic 440. Static Heat- and Cooling Meter. Application

Operating Instruction for Electronic Pressure Switch. Model: PDD

Valve terminal VTUG-...-M/VTUG-...-V

ULTRASONIC METER FOR HEATING AND COOLING SKU-03

Metering systems 0578EN January 2014 Thermal energy meters, ultrasounds type for use in a boiler room GE552-1 series

WSTH/WPTH. Woltmann type combined energy meter. Woltmann flow meters for large nominal flows combined with calculator and temperature sensors.

Mounting and Operating Instructions EB 5894 EN. Electric control valves with jet pump. Flanged version of valve with jet pump

Heating / Cooling Meter PolluCom E Installation and Operation Instructions

Infocal 9 Energy calculator for heating and cooling applications

Declaration of Conformity as per Directive 97/23/EC

Ex m Solenoid Operator Type 0519

Solenoid Operator 0516 / 1216

Data sheet MULTICAL 6L2. Data loggers Info loggers Data backup in case of power failure MID-2004/22/EC EN 1434

Infocal 9 Energy calculator for heating and cooling applications

Installation and Connection: Installation and Operating Manual

EN Operating manual. Motorised zone valve. Three-way, 22 mm & 28 mm 3PV2, 3PV8 & VRMH3

Metering systems 0483EN October 2013 Metering units for sanitary or service water

Operating Instructions. Pneumatic Control Valve Low Temperature. Type Series GS3

Installation Instructions (Translation) Marking. Description. Danger, warning and note symbols. Technical data. ANTARES ExtSet.

FLENDER ZAPEX couplings. Type ZWT. Operating instructions BA 3505 EN 10/2011. FLENDER couplings

Mounting and Operating Instructions EB 8111/8112 EN. Series V2001 Valves Type 3321 Globe Valve

Technical Documentation

Type Operating Instructions. Bedienungsanleitung Manuel utilisateur

Supercal 539 Universal compact heat meter

M-bus impeller type heat and heat/refrigeration meters

SPARKSCAN1 HIGH VOLTAGE CLAMP OPERATING MANUAL

Octave Water Meter Installation Manual

Domestic water meters

Ultrasonic heat meter

DKG-114 MANUAL AND REMOTE START UNIT

SCOPELITE TIMING LIGHT OPERATING MANUAL

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

ENGLISH SAFETY INSTRUCTIONS. Recommendations for safe operation. Operator safety. General warnings

Level Measuring Sensor for Diesel Fuel Tanks

Globe Valve Type Fig. 1 Type 3241 Globe Valve. Mounting and Operating Instructions EB EN

PTB 14 ATEX 2023 X, IECEx PTB X. Operating Instructions. Solenoid coil Type AC10 Magnetspule Typ AC10 Bobine magnétique Type AC10

F 90 Heat Meter Warmly recommended to cool-headed economisers

CORONA ER ELECTRONIC METER MULTI-JET

ECONOMISER SERIES E2T USER MANUAL

Compact System NRGS 11-2 NRGS Original Installation Instructions English

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies

Electronic Limit Switch Type

Model TUR-200D Turbine Flowmeter

Electronic Water Meters

Pipe surface resistance thermometer, for clamping Model TR57-M, miniature design

Mounting and Operating Instructions EB 8097 EN. Type and Type Pneumatic Control Valves

COUNTIS E22 Three-phase energy meter Direct - 80 A

Installation & Maintenance Instructions MULTICAL 403. Supplied by. .com. Call us on +44 (0)

WESAN WPV E ELECTRONIC METER WOLTMAN

User Guide. Lubricus Lubrication System LUB-D1/LUB-D2/LUB-D3/LUB-D4 (24 VDC)

Inline Flow meter for compressed air and gases DN15 (1/2 ) - DN80 (3 )

Flow limiter SP/SMB3 Flow limiter SP/SMB6

Type 6213 EV, 6281 EV

- 1 Datasheet L5-X-X. Swiss power connector now available

WATERFLUX 3070 Quick Start

Mounting and Operating Instructions EB 8048 EN. Type and Type Pneumatic Control Valves Type 3249 Aseptic Angle Valve

Operating instructions Flow monitors SI6600 SI6700 SI /02 01/2011

Installation and Operating Instructions Magnetic Vibrator MR 1

Operating instructions Switching cushion with safety function SSG-SK. 1. About this document. Content

Temperature Sensors. Information Sheet

Series 7000 Torque Sensor for PTO-shafts

HYDRUS ULTRASONIC METER

Mounting and Operating Instructions EB 5868/5869 EN

SonoSelect and SonoSafe energy meters

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

Heating Cost Allocation Valve with local acquisition of the flow temperature

Quick Guide. brite Advanced Retail scale

Transcription:

EnergyMetering zelsius Installation and operating manual Electronic compact heat meter with single jet flow sensor M-Bus and 2 inputs/outputs optional qp 0.6/1.5/2.5 m³/h All that counts.

General information With zelsius you have acquired one of the most up-to-date, modern heat meters currently available on the market. Expressive symbols in the display and easy menu navigation make readout simple. It can be operated with one single button. The meter is equipped with a long-life battery made for operation during the initial verification validity period (5 years) including a reserve of at least another year. Initial verification zelsius is produced and tested in compliance with the new european measuring instruments directive (MID). According to this directive, devices do no longer carry an initial verification stamp, but rather the year of the device s declaration of conformity (recognizable on the front of the device, for example: M11). The MID controls the use of heat meters up to the moment they are placed on the market resp. their first putting into use. After this, the national regulations for devices subject to legal verification apply within the EU. The duration of initial verification validity in Germany remains 5 years for heat meters. After this period has expired, the measuring device may no longer be used for billing in commercial use. The regulations resp. validity period may vary in other countries of the EU. Electro-magnetic interference zelsius fulfils the national and international requirements for interference resistance. To avoid malfunctions due to other interferences, do not install fluorescent lamps, switch cabinets or electric devices such as motors or pumps in the immediate vicinity of the meter (minimum distance 1 m). Cables leaving the meter should not be laid parallel to live cables (230V, minimum distance 0.2 m). Care instructions Clean plastic surfaces with a damp cloth only. Do not use any scouring or aggressive cleaning agents! The device is maintenance-free during the service life. Repairs can only be made by the manufacturer. Declaration of Conformity ZENNER International Gmb & Co. KG declares that this product with the number of the EC typeexamination certificate DE-10-MI004-PTB005 complies with the requirements of the EC directives 2004/22/EC (Measuring instruments directive) and 89/336/ EEC (electro-magnetic compatibility). The most up-to-date information about this product can be found at www.zenner.com 2

Status display / Error codes The symbols in the table below show the meter s operational status. The status messages only appear in the main display (energy)! The temporary display of the warning triangle can be caused by special operating states and does not always mean that the device is malfunctioning. owever, should the symbol be displayed over a longer period of time you should contact the service company. Symbol Status Event Flow existent - Attention! Check system / device for errors Data transmission - Emergency operation Exchange device Error codes show faults detected by zelsius. If more than one error appears, the sum of the error codes is displayed: Error 1005 = error 1000 and error 5. Code Error Event 1 2 3 4 5 6 100 1000 2000 8001-5 ardware error Exchange device Interruption supply sensor " Interruption return sensor " ardware error " Short-circuit supply sensor " Short-circuit return sensor " Emergency operation " Battery life time exceeded " Initial verification expired " Memory error " 3

Technical data Temperature range calculator C 1 130 Temperature range flow sensor C 10 90 Temperature difference range Kelvin 3 100 Temperature sensor type PT500 Temperature range sensor C 0 105 (130) Diameter sensors mm 5,0/DS acc. to EN 1434 Cable length sensor m 1,5 (optional 3/5) Nominal flow qp m³/h 0,6 1,5 2,5 Maximum flow q s m³/h 1,2 3,0 5,0 Minimum flow q i (horizontal) I/h 12*/24 30/60 50/100 Minimum flow q i (vertical) I/h 12*/24 30/60 50/100 Starting flow horizontal approx. I/h 6 6 12 Operation pressure bar 16 Pressure loss at qp bar < 0,25 Minimum pressure (avoidance of a cavitation) bar 0,3 Display range LCD 8-digit Battery V 3,0 Lithium Battery life years > 6 Protection class IP 54 Ambient temperature range C 5...55 Mechanical/electro-magnetic class M1/E1 Measurement accuracy class 3 *Values for symmetrical temperature sensors installation. Only the values stated on the type plate apply. 4

Pulse inputs and outputs (optional) The pulse value can be called up in the display (see the display overview, Level 1) for devices with 2 pulse inputs. The pulse value of the outputs is permanently set and corresponds with the last position of the associated display value. Example: Output 1 = energy output Energy display = XXXXX.XX MWh Last position = 0.01 MWh = 10 kwh Output pulse = 10 KWh Technical data I/O Load max. 30V DC/20 ma I/0 1, 2 Open Drain, n-channel FET Cable D=4.9mm, 6-core Pulse-duty factor 1:1 (out); 1:5 (in) Cable length Input frequency 1.5 m max.1 z Input Output A firmly attached cable is included: external wiring must be done by qualified personnel. 5

M-Bus (optional) The optional M-Bus interface complies with the norm EN 1434-3 and operates with 2400 baud fixed. Both of the cable cores can be connected to the M-Bus network in any order. Colour Connection Meaning yellow (1) NC not connected pink (2) M-Bus 1 M-Bus line 1 grey (3) M-Bus 2 M-Bus line 2 green (4) I/O 1 I/O 1 white (5) GND common ground for I/O 1 and I/O 2 brown (6) I/O 2 I/O 2 ZENNER International Gmb & Co. KG Römerstadt 4 D-66121 Saarbrücken Telephone +49 681 99 676-30 Telefax +49 681 99 676-3100 E-Mail info@zenner.com Internet www.zenner.com Subject to modifications and errors excepted. Any liability for misprints excluded. SAP127806_111118_EN ZENNER is a registered trademark of ZENNER International Gmb & Co. KG. 6

Installation instructions General Information The installation has to be done by qualified professional personnel. The current laws and regulations have to be observed, especially EN 1434 part 1+6, (in Germany also AGFW directive FW202 and FW510 and the initial verification directive). At devices with M-Bus the respective regulations for electrical installations have to be followed. Make sure no heating water escapes during installation this can cause burns! For heating systems with a lack of temperature mixing resp. with temperature stratification a straight pipeline of min. 10xDN has to be provided upstream of the meter. The optionally integrated temperature sensor mounting must be provided with a user seal. It is important to ensure adequate system pressure to avoid cavitation. Notes flow sensor Mount ball valves up- and downstream of the flow sensor. Consider the correct installation point (supply or return). Normally this is the return pipe (cooler pipe at heating systems). Consider the correct flow direction. This is indicated by an arrow on the side of the flow sensor. Install horizontally or vertically only, not tilted, inclined or overhead. Installation into horizontal or upstreaming or downstreaming pipelines. Do not install at highest point of piping to avoidair inside the flow sensor. Consider the dimensions of the heat meter. Keep about 1 meter distance between zelsius and electromagnetic sources of interference like switch cabinets, motors or pumps. Keep about 0.2 m distance to power cables. Keep min. 3 cm free mounting space around the device. 7

Notes ball valves Mount ball valves up- and downstream of the meter. Mount a ball valve with bore M10x1 for directsensors in the supply. This is required for the installation of the supply sensor For symmetrical temperature sensor installation, mount an identical ball valve in the return. This one is used for mounting the return sensor. Installation of flow sensor Close valves upstream and downstream of the installation point and release pressure. Dismount the existing flow sensor or meter blank Use only new and flawless sealing material and check the seal face for damage. Install the new flow sensor according to the correct flow direction and installation position. The connecting cables may not be buckled, extended or shortened. Remove locking screw and seal at the ball valve completely, if existing. Attach the O-ring to the installation aid (the 2nd O-ring is only a spare O-ring). Using the installation aid, insert the O-ring into the installation point according to DIN EN 1434 with a slight circular motion. Using the other end of the installation aid bring the O-ring into the correct position. Insert the 2 halves of the plastic connector into the sensor s three notches (crimps) and press them together. Use the installation aid as positioning aid. Insert the temperature sensor into the installation point and screw it in tightly until the dead stop of the seal on the 12-point is reached (mounting torque 3-5 Nm). Installing the temperature sensors Close valves and release pressure. The installation of the temperature sensors should be preferably symmetrical and direct installation. Do not remove the return sensor if it comes already mounted in the flow sensor. This also applies for security seals which are attached to the device in the factory Sensors are colour-coded (red = supply, blue = return). Installation DF-adapter 8

Secure the sensor after installation against unauthorised removal with appropriate sealing (available as a sealing set)! Putting into use Open vales carefully Bleed and flush the system, avoid pressure hammers. Check installation for leakage. While the system is operating, check whether the volume display proceeds and the temperatures displayed correspond with the actual temperatures (see the display overview). Wait for the temperature display to be updated (1-2 sec). Supply Load Return Asymmetric sensor installation for zelsius with the return sensor integrated in the flow sensor Supply Load Return Symmetric sensor installation for zelsius 9

Dimensions eight compact version: max = 47,5 mm E max = 21 mm eight combiversion: max = 73 mm E max = 21 mm Width heat computer: Length heat computer: 72 mm 100 mm Connection sizes Nominal flow qp m³/h 0,6 1,5 2,5 Nominal diameter DN mm 15 15 20 Overall length L mm 110 110 130 Minimum required mounting height = 30 mm 10

Ebene 1 Ebene 2 You can switch levels at any point in the menu. Energy (main display) eat on S.R.D. Cooling (optional) Date of S.R.D. Volume S.R.D. value external meter 1 L Volume external meter 1 Pulse value meter 1 S.R.D. value external meter 2 Monthly consumption L L L Volume external meter 2 Pulse value meter 2 Current monthly consumption Date Month 1 Energy consumption Segment test Serial number Date Month 2 Energy consumption S Supply temperature Customer number (optional) S Return temperature Temperature difference Flow rate inweis Depending on your meter's model its displays can differ in number and order from those shown here. Instantaneous power S You can download a complete and detailed product description in our product area at www.zenner.com. 11

Ebene 3 Legend Sensor type and installation point Model number S Press the button briefly (S) to switch through the display from top to bottom. When you have reached the last menu item the device automatically jumps back to the menu item at the top (loop). n n tion S 1st monthly value heat energy Initial verification validity (in Germany) M-bus address Time Date L Press the button for about 2 seconds (L), wait for the door symbol to appear (upper right corner of the display) and then release the button. The menu is then updated resp. switches to the submenu. Error status Software version old down the button () until the device switches to another level or switches back from the sub-menu. S 12