Motor parameters setting. Motor Control Parameters. These motor parameters below are needed to set:

Similar documents
TOSVERT VF-S11. V/F control functions

General Purpose Permanent Magnet Motor Drive without Speed and Position Sensor

DYNEO Synchronous motors with permanent magnets-drive Commissioning

Application Note CTAN #234

Permanent Magnet Synchronous Motor. High Efficiency Industrial Motors

Drive Fundamentals. Motor Control Bootcamp May 15-18, Copyright 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC CO900H

Application Note: SyMAX Permanent Magnet Motor Simple Startup Procedure

Overvoltage Suppression F7 Drive Software Technical Manual

Parker AC10 Frequency Inverter (to 22kW) Easy Start Guide

Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module.

Standard Drives A & D SD Application Note

Question Bank ( ODD)

Yaskawa AC Drive L1000A Supplement to the L1000A Technical Manual No. SIEP C , SIEP C , and SIEP C

List of Tables: Page # Table 1: Emerson Commander SK VFD parameter settings 2. Table 2: Allen Bradly Power Flex 4M VFD parameter settings 3

CHAPTER 4 MODELING OF PERMANENT MAGNET SYNCHRONOUS GENERATOR BASED WIND ENERGY CONVERSION SYSTEM

Technical Guide No. 7. Dimensioning of a Drive system

TUTORIAL Motor Control Design Suite

USER INSTRUCTION FOR PROGRAMMING INVERTER FUJI FRENIC LIFT

Three-Phase Induction Motor With Frequency Inverter

University of L Aquila. Permanent Magnet-assisted Synchronous Reluctance Motors for Electric Vehicle applications

Motor Protection Fundamentals. Motor Protection - Agenda

VFD E Series. Features

Effect of Permanent Magnet Rotor Design on PMSM Properties

CRANE FUNCTION MANUAL. FR-A (0.4K) to 04750(90K)-CRN FR-A (0.4K) to 06830(280K)-CRN FR-A (315K) to 12120(500K)-CRN

Planning and Commissioning Guideline for NORD IE4 Synchronous Motors with NORD Frequency Inverters

TRIPS AND FAULT FINDING

Quick Start Guide of CV50- ControlVIT Series

Low Speed Control Enhancement for 3-phase AC Induction Machine by Using Voltage/ Frequency Technique

COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1001 SPECIAL ELECTRICAL MACHINES

Modeling and Simulation of A Bldc Motor By Using Matlab/Simulation Tool

FREQUENCY CONVERTER DANFOSS FC101 NOVENCO CONFIGURATION USER GUIDE

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY MAMALLAPURAM, CHENNAI

GHD Global Help Desk. HOISTING commissioning with ATV71 03/2010

QUESTION BANK SPECIAL ELECTRICAL MACHINES

Introduction The aim of this application note is to outline how to configure an ACSM1 drive to run with an ABB BSM series AC servo motor.

EG DYNAMIC user manual

Planning and Commissioning Guideline for NORD IE4 Motors with NORD Frequency Inverters

DRIVE STARTUP MANUAL. Magnetek HPV900-S2 Drive. PM Motor Installation

Technical Information

Mechatronics and Electrical Drives

Aspects of Permanent Magnet Machine Design

HIDRA CRONO Controller VVVF Control Techniques Unidrive SP (Asynchronous motors)

Quick Start Guide TS 910 & TS 920

Technical Explanation for Inverters

Non-Compumotor Motors IN THIS APPENDIX

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Lectures on Mechanics. Lesson#1

Design of Sensorless Controlled IPMSM with Concentrated Winding for EV Drive at Low speed

SK-10. Features. Solar Charge Controller User Manual. Important Safety Information

Hardware Reference C H A P T E R ➆. ZX600 Electrical Specifications. ZX600 Motor/Drive Configuration. Input Power. Output Power

Service Guide VLT OneGearDrive

Tension Control Inverter

YASKAWA AC Drive A1000

Datasheet. Pitch Motor PMSM SP190F8

Piktronik d. o. o. Cesta k Tamu 17 SI 2000 Maribor, Slovenia Fax:

Small step, big impact: Energy efficiency and dynamic performance

RVS-AX Instruction Manual

EE 370L Controls Laboratory. Laboratory Exercise #E1 Motor Control

EC Gold Series Synchronous permanent magnet motor

Frame size R2, IP20 / NEMA 1

Quantum Series Size 17, 23, 34 and 56 Brushless Servo Motors Frameless and Housed Engineering Guide

Brushless dc motor (BLDC) BLDC motor control & drives

Unidrive M700 Class leading performance with onboard real-time Ethernet

Inverter control of low speed Linear Induction Motors

Development of High-Speed AC Servo Motor

1-3 RAMP AND TORQUE BOOST EXERCISE OBJECTIVE

Quick Start Guide TS 910

825-P Modular Protection System for motors Specification Guide

PAS Series AC Servo Motor. Datasheet

B.E-EEE(Marine) Batch 7. Subject Code EE1704 Subject Name Special Electrical Machines

VFD - Mitsubishi. VFD Manuals. Mitsubishi D700 VFD Installation. Mitsubishi FR-D700 VFD User Manual. Mitsubishi D700 Parallel Braking Resistors

EAOM-10.2 AUTOMATIC TRANSFER SWITCH & START UNIT FOR DIESEL GENERATORS

Switching Control for Smooth Mode Changes in Hybrid Electric Vehicles

Design of Brushless Permanent-Magnet Machines. J.R. Hendershot Jr. T.J.E. Miller

HIGH POWER SOLENOID DRIVER 1

Mitsubishi. VFD Manuals

ECE1750, Spring Motor Drives and Other

hofer powertrain GmbH

MEBS Utilities services M.Sc.(Eng) in building services Department of Electrical & Electronic Engineering University of Hong Kong

THREE PHASE RECHARGING SYSTEM DIAGNOSIS

Datasheet. Pitch Motor PMSM SP260B8

Datasheet. Pitch Motor PMSM SP190C8

ECE 325 Electric Energy System Components 6 Three Phase Induction Motors. Instructor: Kai Sun Fall 2016

Short Term Course On Hydropower Development Engineering (Electrical) for Teachers of Polytechnics in Uttarakhand L33-2

Elbtalwerk GmbH. Universität Karlsruhe Elektrotechnisches Institut. Switched Reluctance Motor. Compact High-torque Electric Motor. Current.

Power Factor Improvement

APPLICATION NOTE AN-ODP March 2009

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road QUESTION BANK (DESCRIPTIVE)

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages.

LECTURE 27 SERVO VALVES FREQUENTLY ASKED QUESTIONS

DeVi-Comfort B.V. Netherlands

Código de rotor bloqueado Rotor bloqueado, Letra de código. Rotor bloqueado, Letra de código

APPLICATION NOTE

YASKAWA AC Drive V1000. YASKAWA AC Drive V1000

Permanent Magnet Synchronous Frameless Torque Motors KSO/H Series

Design, Engineering, and Manufacturing of Motors for Electric Vehicle Applications

Dynamic Response Analysis of Small Wind Energy Conversion Systems (WECS) Operating With Torque Control versus Speed Control

G Prasad 1, Venkateswara Reddy M 2, Dr. P V N Prasad 3, Dr. G Tulasi Ram Das 4

Instruction Bulletin NF Panelboard Dual Sub-Feed Circuit Breaker Adapter Kit Installation onto an NF Panelboard Class 1670

APPLICATION GUIDE. Pure easiness for a wide range of applications ACS580 general purpose drives

Transcription:

Permanent Magnet Motor Control Law ([PM Control] (PM)) Drive may be set to control synchronous motor. When [PM control] is activated, motor parameters are set to new default value. You can access to additional settings to optimize the motor control. Motor parameters setting. These motor parameters below are needed to set: - Set (Pt) [Mot cont. mode sel.] to [PM Control] (6) see page 82. 2 - Set [Motor rated freq.] (ul), see page 74: Note: Motor rated freq.] (ul) = [Motor rated speed] (F47) / (6 / np) [Motor rated speed] (F47), see page 74, indicated on the motor nameplate or follow the procedure step 4 above. np = Number of pole pairs, indicated on the motor nameplate. 3 - Set the Motor rated power (unit is kw) by [Motor rated cap.] (F45), see page 82 Note: P = C x ω P = Power in W C = N.m, indicated on the motor nameplate. ω = rad s - ω = 2π x (FRS/np) FRS = [Motor rated freq.] (ul) see page 74, indicated on the motor nameplate. np = Number of pole pairs, indicated on the motor nameplate. 4 - Motor rated current (unit is A) is set by [Motor rated current] (F45), see page 74. 5 - Set [Motor rated speed] (F47), see page 74, without information: Set the motor rated speed by FRS x (6 / np) FRS = [Motor rated freq.] (ul) see page 74, indicated on the motor nameplate. np = Number of pole pairs, indicated on the motor nameplate. 6 - Configure [Auto-tuning drive] (F4) to [Tun Static 2] (5), see page 83. Make the TUN (Run order is needed to start the TUN.) - Motor s rated voltage is set by [Motor Rated Voltage] (ulu) a, see page 82. - Stator resistance is set by [Auto Torque Boost] (F42) a, see page 84. - Axis "q" stator inductance in mh is set by [Autotune L q-axis] (F92) a, see page 85. - Axis "d" stator inductance in mh is set by [Autotune L d-axis] (F93) a, see page 85. 7 - Check the value of [Saliency Level] (F936), see page 84. 8 - Set [PM mode selection] (F95) according to the [Saliency Level] (F936) value (see page 84). 9 - If (F936) is u.2, increase [Init. Pos. Current] (F92) see page 85. Configure [Auto-tuning drive] (F4) to [Tun Static 2] (5), see page 83. Make the TUN (Run order is needed to start the TUN.) - Start the motor, - if there is current limitation on starting, increase the [PM Align cur. Level] (F96) value (See page 85). - if its behavior is not optimal, reduce by 2% [Motor Rated Voltage] (ulu) value (see page 82). - After this procedure, if you need further assistance, contact your Schneider Electric Product Support. (a) Auto Torque Boost] (F42), [Autotune L q-axis] (F92), [Autotune L d-axis] (F93), and [Motor Rated Voltage] (ulu) may be defined automatically after activation of [Auto-tuning drive] (F4) = [Tun Dyn. 2] (3) or [Tun Static 2] (5) SA53838 /24 8

Code Name / Description Adjustment range Factory setting Pt [Mot cont. mode sel.] Motor control mode selection - If [Driving Scroll] (F324) page 6 is set to [yes] () the setting is replaced by [SVC] (3) 2 3 4 5 6 [Constant V/Hz]: Constant V/Hz [Variable Torque]: Variable torque [Cst V/Hz+Boost]: Constant V/Hz with automatic torque boost [SVC]: Sensorless vector control [Economy]: Energy saving [Do not use]: Reserved [PM Control]: Permanent Magnet Motor Control Law DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH If [Mot cont. mode sel.] (Pt) is set to (6) (Permanent Magnet Motor Control Law), output phase loss monitoring, while the motor is running, is disabled. Phase loss and, by implication, accidental disconnection of cables, are not detected. Verify that this behavior does not result in unsafe conditions and implement alternative monitoring function if required. Failure to follow these instructions will result in death or serious injury. ulu [Motor Rated Voltage] According to drive rating () According to drive rating () Set parameter ulu (vlv) to the motor s rated voltage as indicated on the motor nameplate. ATV22pppM3X: 5...33 V ATV22pppN4: 5...66 V Note: Drive output voltage cannot be set to exceed the input line voltage level. ulu (vlv) may be defined automatically after activation of F4 = [Tun Dyn. 2] (3) or [Tun Static. 2] (5) if [Mot cont. mode sel.] (Pt) = (6) ul [Motor rated freq.] 25. to 4 Hz 5. Hz Set parameter ul(vl) to the motor s rated frequency as indicated on the motor nameplate. Note: It is possible to set the drive s various motor control frequencies to 5 Hz by setting [Parameter reset] (typ) to, the 5 Hz reset. For more information, see page 66. F45 [Motor rated cap.] Motor rated capacity. to 75 kw According to drive rating () Set parameter F45 to the motor rated capacity in kilowatt. It permite to calculate automatically [Motor Rated Voltage] (ulu) after TUN F4 [Auto-tuning drive] F45 [Motor rated current]. to 2. A According to drive rating () Set parameter F45 to the motor rated current in amperes as indicated on the motor s nameplate. F47 [Motor rated speed] Motor rated speed. to 5 rpm According to drive rating () Set parameter F47 to the motor rated speed in rpm as indicated on the motor s nameplate. () See table page 99. 82 SA53838 /24

F4 [Auto-tuning drive] - DANGER HAZARD OF ELECTRIC SHOCK OR ARC FLASH During auto-tuning, the motor operates at rated current. Do not service the motor during auto-tuning. Failure to follow these instructions will result in death or serious injury. WARNING LOSS OF CONTROL It is essential that the following parameters ulu, ul, F45 and F47 are correctly configured before starting autotuning. When one or more of these parameters have been changed after auto-tuning has been performed, F4 will return and the procedure will have to be repeated. Failure to follow these instructions can result in death or serious injury. NOTICE RISK OF DAMAGE TO THE MOTOR Conduct auto-tuning only after the motor has been connected and operation completely stopped. If auto-tuning is conducted immediately after operation stops, the presence of a residual voltage may result in abnormal tuning. Failure to follow these instructions can result in equipment damage. 2 3 4 5 Auto tuning enable [Disabled] [Initialize constant]: Factory setting of [Auto Torque Boost] (F42) for asynchronous motor. Factory setting of [Auto Torque Boost] (F42), [Autotune L q-axis] (F92), and [Autotune L d-axis] (F93), and [Motor Rated Voltage] (vlv) for synchronous motor. [Tun Dyn. ]:Tune Dynamic, with driving run after the tuning. Application settings of [Auto Torque Boost] (F42) for asynchronous motor. Application settings of [Auto Torque Boost] (F42), [Autotune L q-axis] (F92), and [Autotune L d-axis] (F93) for synchronous motor. [Tun Dyn. 2]: Complete tune Dynamic, with driving run after the tuning. Application settings of [Auto Torque Boost] (F42), [Autotune L q-axis] (F92), [Autotune L d-axis] (F93), and [Motor Rated Voltage] (vlv) for synchronous motor. [Tun Static ]: Tune Static, without driving run after the tuning. Application settings of [Auto Torque Boost] (F42) for asynchronous motor. Application settings of [Auto Torque Boost] (F42), [Autotune L q-axis] (F92), and [Autotune L d-axis] (F93) for synchronous motor. [Tun Static 2]: Complete tune Static, without driving run after the tuning. Application settings of [Auto Torque Boost] (F42), [Autotune L q-axis] (F92), and [Autotune L d-axis] (F93), and [Motor Rated Voltage] (vlv) for synchronous motor. Parameter F4 is reset to after the auto tuning is performed. F458 [Current loop gain] Current loop gain... Hz Hz Parameter F458 is set to the response gain of current loop. If [Mot cont. mode sel.] (Pt) page 82 is set to [PM control] (6) the setting is replaced by 25 Hz. Note: Contact Schneider electric product support to confirm the modification of this parameter. () See table page 99. SA53838 /24 83

F48 [Frequency loop gain] to 5 4 Parameters F48 and [Freq. loop stability] (F49) reduce the speed of the drive s response to a change in speed command. The factory setting of these two parameters assumes that the inertia of the load is three times as large as that of the motor shaft. Adjust these two parameters if the factory setting is not appropriate for the application. Note: It is possible for the drive s output frequency to exceed its upper limit (parameter [Max frequency] (FH)) if the acceleration parameter (ACC or F57) is set to its minimum value. Increasing the setting of parameter F48 reduces the drive s response time to changes in the speed reference. F49 [Freq. loop stability] Frequency loop stability to 2 Increasing the setting of parameter F49 further reduces the drive s response to changes in the speed reference. F495 [Motor voltage coef.] Maximum voltage adjustment coefficient 9 to 2% 4% Use parameter F495 to limit the drive s maximum output voltage. Increasing this setting increases torque when the motor is operated above its rated frequency, but may also cause motor vibration. Do not increase the value of F495 if motor vibrations occur. F936 [Saliency Level] Saliency coefficient for PM motor to 2.55 PM type [PM mode selection] (F95) is selected by the saliency level [Saliency Level] (F936) F936 u.2 = high saliency F936 <.2 = low saliency. Note: This parameter is automatically computed with the setting of [Autotune L q-axis] (F92) and [Autotune L d-axis] (F93) F95 [PM mode selection] PM control mode selection - 3 2 3 4 [Basic Ctrl]: basic control [Ctrl Type]: control type (for IPM, interior-buried Permanent Magnet motor) [Ctrl Type2]: control type 2 (for IPM, interior-buried Permanent Magnet motor) [Ctrl Type3]: control type 3 (for IPM / SPM, interior-buried Permanent Magnet motor / Surface-mounted Permanent Magnet motor) [Ctrl Type4]: control type 4 (for IPM / SPM, interior-buried Permanent Magnet motor / Surface-mounted Permanent Magnet motor) Refer to the following tables to select the setting of the parameter F95, F95 is selected by the saliency level F936 - big starting torque is needed. - for constant torque application.() - big starting torque is not needed. - for variable torque application (2) - big starting torque is not needed - for variable torque application - motor electrical magnetic noise is forbidden (3) The saliency level is high (F936 u.2) The saliency level is low (F936 <.2) F95 = 4 or 2 F95 = or 3 F95 = F95 =3 () There is some motor electrical magnetic noise at start and low speed area. (2) There is some motor electrical magnetic noise at start. It can not be started in case of high start-up torque. (3) It goes opposite direction at start sometimes. It cannot be started in case rotor saliency is high. Code Name / Description Adjustment range Factory setting F42 [Auto Torque Boost]. to 3.% According to drive rating Use parameter F42 to adjust the amount of automatic torque boost that is applied. Motor rated voltage Output Voltage (%) : Automatically adjusts the amount of torque boost. Motor Rated Frequency Output Frequency (Hz) 84 SA53838 /24

F92 [Autotune L q-axis] q-axis self-inductance. to 65 mh Axis "q" stator inductance in mh The setting is replaced by the result of the auto-tuning operation, if it has been performed. Measured between the neutral and the phase, its value could be differente than the datasheet of the motor. [Autotune L q-axis] (F92) is defined automatically after activation of [Auto-tuning drive] (F4) = [Tun Dyn. 2] (3) F93 [Autotune L d-axis] d-axis self-inductance. to 65 mh Axis "d" stator inductance in mh The setting is replaced by the result of the auto-tuning operation, if it has been performed. Measured between the neutral and the phase, its value could be differente than the datasheet of the motor. [Autotune L q-axis] (F93) is defined automatically after activation of [Auto-tuning drive] (F4) = [Tun Dyn. 2] (3) F96 [PM Align cur. Level] Stabilization at the starting and low speed(for PM) to % 25 % It might be able to stabilize the motor rotation behavior by the current in D axis at no load when starting or low-speed If you have a torque jolt, when starting / stopping or low-speed, it is recommended to increased the setting of 96. If E-2 [Excess torque boost flt] trip occurs at the start, it is recommended to increased the setting of 96. In the case of F95=,, 2, 3 Current Level (%) F96 to 25 % Stabilization current in D axis K*Fn (K*vL) Rotor speed In the case of F95=4 Current Level (%) Stabilization current in D axis F96 to 25 % K*Fn (K*vL) Rotor speed Starting current F96 is set 25% as the default setting, Limit it to the value of about 75% in the maximum with consideration of copper loss and iron loss of the motor. If the loss of motor at no load is made decreased, please decrease the value of F96 confirming the stability when starting. F92 [Init. Pos. Current] Current for initial position estimation to 5 % % In case of position detection 3, the current level can be set by this parameter, during the auto-tuning for d axis / q axis inductance, the maximum current level can be adjusted by this parameter setting. F42 [Torque Boost Coef] Compensation coefficient of torque boost to 2% 9 % If synchronous or asynchronous motor is used, F42 [Torque Boost Coef] is set to 9%. If you have a torque jolt, when starting / stopping or low-speed, increase the value of F42 Note: If E-2 [Excess torque boost flt] trip occurs at the start, it is recommended to be decreased the setting of F42 SA53838 /24 85

Parameters described in this page can be accessed by the extended menu Code Name / Description Adjustment range Factory setting F94 [N-S direction] Method of detection - N-S Method of detection. If F94 =, the N-S direction of rotor position is judged by the method of DC offset for position detection. If F94 =, the N-S direction of rotor position is judged by the method of AC offset for position detection. Note : N-S method of detection is available if [PM mode selection] (F95) is set to [Ctrl Type] () or [Ctrl Type2] (2) F97 [PM Max torq. Ctrl] Max torque control activation (for IPM) - [] : Deactivation [] : Activation F98 [Cur. phase adjt] - 45. to 45. It is possible to aim the higher efficiency in the case of IPM (Interior Permanent Magnet), by activation of [PM Max torq. Ctrl] (F97) which makes required current the minimum, the loss of m otor and driver may be reduced and the efficiency may be attained higher level. F92 [Position Adjust] - 5 % = Auto In case of heavy load, the estimated position can be adjusted by setting this parameter. Adjustment for position estimation, available if [PM mode selection] (F95) is set to [Ctrl Type2] (2) or Ctrl Type4] (4). 86 SA53838 /24