SUBMITTAL Project Palm Beach Gardens Fire Station Date February 5, 2018 Fausto Frias Prepared For TLC Attention- Steve
Job Name Palm Beach Gardens Fire Station Mark for AHU-1 Date February 5, 2018 Unit Parameters Aero Indoor Air Handler 39MN Size 06W Insulation: R-13 Double Wall Sealed Panel Exterior Finish: Galvanized Exterior Panels Interior Finish: Galvanized Interior Panels Level I Thermal Break 6 inch tall Base Rail Flat Filter 2In. Flat Filter 2" Pleated MERV 8 Filter Qty (2) 20in. x 25in. Door Right Side Minihelic Differential Pressure Gage 0-2" w.c. Right Side Chilled Water Coil 304 Stainless Steel Drain Pan Right Side Chilled Water 5.9 sq.ft 6 Row 11 FPI Half Circuit Coil Connection Right Side 1/2 in. Tube Diameter AL fins Galv. Casing Steel Header No Coating Draw-Thru Supply Fan Bottom Inlet Fan Sled Forward Curve B FCA10_8A 1371 fanrpm Class I UpBlast Front Discharge Right Side Fan Motor Location Spring Fan Isolation Motor SUBJECT TO CHANGE WITHOUT NOTICE 6.6
Job Name Palm Beach Gardens Fire Station Mark for AHU-1 Date February 5, 2018 1.5 HP Premium Efficiency ODP 208-230/460 3Ph 60Hz 1800 RPM Manufacturer - Generic Frame Size - 145T Motor Shaft Diameter (in.) - 0.875 Voltage Selected - 460/3/60 Full Load Amps - 2.2 MCA - 2.8 MOCP - 3 Efficiency - 86.5% Belt Drive 1.2 Service Factor Fixed Pitch Drive 1 or more belts Door Right Side Configuration Notes Discharge duct(s) must be gasketed and screwed directly to the discharge panel of the unit. Weights and Dimensions (LxWxH in ft in) 4' 6" x 3' 10" x 6' 0" ** Operating 1307 LB ** Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are provided primarily for shipping purposes. Shipping skids are not included. All filter media efficiency ratings are for the filter media only. SUBJECT TO CHANGE WITHOUT NOTICE 6.6
Project: Tag: Palm Beach Gardens Fire Station AHU-1 Chilled Water Coil Performance Summary Cooling Application's Balance Criteria: Fluid Flow Coil Model Carrier 28MC Number of Coils 1 Row / FPI / Circ 6 / 11 / HF Fin Type Sine Wave Face Area Type Large Coil Face Area 5.90 sqft Face Velocity 340.5 fpm Fin-Casing Material Al-Galv. Tube Diameter 0.5 in Tube spacing: Stf x Str 1.25 x 0.781 in Tube Wall Thickness 0.016 in Actual Airflow 2010 CFM Site Altitude 0 ft Total Cooling Capacity 85.54 MBH Sensible Cooling Capacity 58.74 MBH Fluid Flow Rate 17.1 gpm Fluid Pressure Drop 6.5 ft wg Fluid Velocity 2.9 ft/s Entering Fluid Temperature 45.00 F Leaving Fluid Temperature 55.00 F Fluid Temperature Rise 10.0 F Entering Air Dry Bulb 80.00 F Entering Air Wet Bulb 67.00 F Entering Air Enthalpy 31.50 BTU/lb Leaving Air Dry Bulb 52.44 F Leaving Air Wet Bulb 52.34 F Leaving Air Enthalpy 21.6 BTU/lb Air Friction 0.46 in wg Brine FW Brine Concentration 0 % Fouling Factor 0.0 (hr-sqft-f)/btu NOTE: Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory (www.ahridirectory.org). v6.61 12/22/17 www.carrier.com
Project: Tag: Palm Beach Gardens Fire Station AHU-1 Unit Acoustics Summary Unit Acoustics Sound Power Level: Discharge Inlet Casing 63 Hz 87 76 78 125 Hz 76 66 67 250 Hz 76 58 60 500 Hz 72 53 56 1000 Hz 72 55 56 2000 Hz 69 52 53 4000 Hz 67 51 42 8000 Hz 60 41 35 Sound power levels for 39M units are rated in accordance with AHRI Standard 260. Unit Acoustics A-weighted Sound Power Level: Discharge Inlet Casing 63 Hz 61 50 52 125 Hz 60 50 51 250 Hz 67 49 51 500 Hz 69 50 53 1000 Hz 72 55 56 2000 Hz 70 53 54 4000 Hz 68 52 43 8000 Hz 59 40 34 Sound power levels for 39M units are rated in accordance with AHRI Standard 260. v6.61 12/22/17 www.carrier.com
Project: Tag: Palm Beach Gardens Fire Station AHU-1 Supply Fan Performance Summary Fan Model 39M Unit Size 06 Fan Type FORWARD CURVED Fan Wheel Diameter 10 Fan Class I Fan Application Draw Thru Orientation Vertical Actual Airflow, CFM 2010 Site Altitude, ft 0 Upstream Ext. Static, in wg 0.00 Downstream Ext. Static, in wg 1.00 Cooling Coil Static, in wg 0.46 Heating Coil Static, in wg 0.00 Total Accessory Static, in wg 0.55 Total Static Pressure, in wg 2.06 Calculated Fan RPM / Motor RPM 1371 / 1800 Class I Max. RPM 1806 Static Efficiency (%) 54 Fan BHP 1.2 Accessories: (1) Flat pleated (2") MERV 8, Dirty [0.55] v6.61 12/22/17 www.carrier.com
Project: Unit Tag: Palm Beach Gardens Fire Station AHU-1 Air Filter Submittal Carrier Part Number... Kit Description... Unit Airflow, CFM... Filter Velocity, FPM... Filter Sizes and Quantities... 31K2B0000000220253 Filter Kit 2010 289 Qty (2) 20in. x 25in. Quality Pleat MERV 8 Pleated Filter The 100% synthetic graduated density media is continuously bonded to a 30 gauge galvanized, corrosion resistant, expanded metal support grid with an effective open area of 96%. The media is resistant to a wide range of chemicals, does not absorb moisture and will not support microbial growth. The controlled pleat spacing maximizes surface area and dust holding capacity and is bonded to the enclosure frame to prevent dust bypass. The enclosure frame is constructed of high wet strength moisture resistant beverage board. The diagonal support members of the frame are bonded to the entering and exiting apexes of each pleat to prevent pleat collapse and filter bowing. 0.4 Filter Pleated (2") MERV 8 Initial Resistance (in. w.g.) 0.3 0.2 0.1 0 200 250 300 350 400 450 500 550 600 650 700 Filter Face Velocity (feet per minute) v6.61 12/22/17
Job Name Palm Beach Gardens Fire Station Mark for AHU-2 Date February 5, 2018 Unit Parameters Aero Indoor Air Handler 39MN Size 03W Insulation: R-13 Double Wall Sealed Panel Exterior Finish: Galvanized Exterior Panels Interior Finish: Galvanized Interior Panels Level I Thermal Break 6 inch tall Base Rail Flat Filter 2In. Flat Filter 2" Pleated MERV 8 Filter Qty (1) 20in. x 25in. Door Right Side Minihelic Differential Pressure Gage 0-2" w.c. Right Side Chilled Water Coil 304 Stainless Steel Drain Pan Right Side Chilled Water 3.47 sq.ft 8 Row 11 FPI Half Circuit Coil Connection Right Side 1/2 in. Tube Diameter AL fins Galv. Casing Steel Header No Coating Draw-Thru Supply Fan Bottom Inlet Fan Sled Forward Curve B FCA9_4A 2013 fanrpm Class I UpBlast Front Discharge Right Side Fan Motor Location Spring Fan Isolation Motor SUBJECT TO CHANGE WITHOUT NOTICE 6.6
Job Name Palm Beach Gardens Fire Station Mark for AHU-2 Date February 5, 2018 2 HP Premium Efficiency ODP 208-230/460 3Ph 60Hz 1800 RPM Manufacturer - Generic Frame Size - 145T Motor Shaft Diameter (in.) - 0.875 Voltage Selected - 460/3/60 Full Load Amps - 2.9 MCA - 3.6 MOCP - 6 Efficiency - 86.5% Belt Drive 1.2 Service Factor Fixed Pitch Drive 1 or more belts Door Right Side Configuration Notes Discharge duct(s) must be gasketed and screwed directly to the discharge panel of the unit. Weights and Dimensions (LxWxH in ft in) 4' 6" x 2' 9" x 6' 0" ** Operating 1111 LB ** Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are provided primarily for shipping purposes. Shipping skids are not included. All filter media efficiency ratings are for the filter media only. SUBJECT TO CHANGE WITHOUT NOTICE 6.6
Project: Tag: Palm Beach Gardens Fire Station AHU-2 Chilled Water Coil Performance Summary Cooling Application's Balance Criteria: Fluid Flow Coil Model Carrier 28MC Number of Coils 1 Row / FPI / Circ 8 / 11 / HF Fin Type Sine Wave Face Area Type Large Coil Face Area 3.47 sqft Face Velocity 453.6 fpm Fin-Casing Material Al-Galv. Tube Diameter 0.5 in Tube spacing: Stf x Str 1.25 x 0.781 in Tube Wall Thickness 0.016 in Actual Airflow 1575 CFM Site Altitude 0 ft Total Cooling Capacity 94.07 MBH Sensible Cooling Capacity 50.79 MBH Fluid Flow Rate 18.8 gpm Fluid Pressure Drop 7.2 ft wg Fluid Velocity 3.2 ft/s Entering Fluid Temperature 45.00 F Leaving Fluid Temperature 55.00 F Fluid Temperature Rise 10.0 F Entering Air Dry Bulb 83.00 F Entering Air Wet Bulb 72.00 F Entering Air Enthalpy 35.71 BTU/lb Leaving Air Dry Bulb 52.37 F Leaving Air Wet Bulb 52.37 F Leaving Air Enthalpy 21.6 BTU/lb Air Friction 0.96 in wg Brine FW Brine Concentration 0 % Fouling Factor 0.0 (hr-sqft-f)/btu NOTE: Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory (www.ahridirectory.org). v6.61 12/22/17 www.carrier.com
Project: Tag: Palm Beach Gardens Fire Station AHU-2 Unit Acoustics Summary Unit Acoustics Sound Power Level: Discharge Inlet Casing 63 Hz 87 81 80 125 Hz 87 81 79 250 Hz 84 75 72 500 Hz 83 74 73 1000 Hz 83 74 71 2000 Hz 84 76 73 4000 Hz 81 73 70 8000 Hz 78 70 68 Sound power levels for 39M units are rated in accordance with AHRI Standard 260. Unit Acoustics A-weighted Sound Power Level: Discharge Inlet Casing 63 Hz 61 55 54 125 Hz 71 65 63 250 Hz 76 67 64 500 Hz 80 71 70 1000 Hz 83 74 71 2000 Hz 86 78 75 4000 Hz 82 74 71 8000 Hz 77 69 67 Sound power levels for 39M units are rated in accordance with AHRI Standard 260. v6.61 12/22/17 www.carrier.com
Project: Tag: Palm Beach Gardens Fire Station AHU-2 Supply Fan Performance Summary Fan Model 39M Unit Size 03 Fan Type FORWARD CURVED Fan Wheel Diameter 9 Fan Class I Fan Application Draw Thru Orientation Vertical Actual Airflow, CFM 1575 Site Altitude, ft 0 Upstream Ext. Static, in wg 0.00 Downstream Ext. Static, in wg 1.00 Cooling Coil Static, in wg 0.96 Heating Coil Static, in wg 0.00 Total Accessory Static, in wg 0.58 Total Static Pressure, in wg 2.64 Calculated Fan RPM / Motor RPM 2013 / 1800 Class I Max. RPM 2132 Static Efficiency (%) 38 Fan BHP 1.7 Accessories: (1) Flat pleated (2") MERV 8, Dirty [0.58] v6.61 12/22/17 www.carrier.com
Project: Unit Tag: Palm Beach Gardens Fire Station AHU-2 Air Filter Submittal Carrier Part Number... Kit Description... Unit Airflow, CFM... Filter Velocity, FPM... Filter Sizes and Quantities... 31K2B0000000120253 Filter Kit 1575 454 Qty (1) 20in. x 25in. Quality Pleat MERV 8 Pleated Filter The 100% synthetic graduated density media is continuously bonded to a 30 gauge galvanized, corrosion resistant, expanded metal support grid with an effective open area of 96%. The media is resistant to a wide range of chemicals, does not absorb moisture and will not support microbial growth. The controlled pleat spacing maximizes surface area and dust holding capacity and is bonded to the enclosure frame to prevent dust bypass. The enclosure frame is constructed of high wet strength moisture resistant beverage board. The diagonal support members of the frame are bonded to the entering and exiting apexes of each pleat to prevent pleat collapse and filter bowing. 0.4 Filter Pleated (2") MERV 8 Initial Resistance (in. w.g.) 0.3 0.2 0.1 0 200 250 300 350 400 450 500 550 600 650 700 Filter Face Velocity (feet per minute) v6.61 12/22/17