Pressure relief controller V22 D28

Similar documents
Pressure relief controller for oil V22D28 (PN 16, 25)

Mounting and Operating Instructions EB 5894 EN. Electric control valves with jet pump. Flanged version of valve with jet pump

Pressure Reducing Valve Type 2114/2415

Mounting and operating instructions EB EN. Differential Pressure and Temperature Regulator with Flow Limiter Type 2479/2430 K

Mounting and Operating Instructions EB 8053 EN. Series 250 Type and Type Pneumatic Control Valves

Mounting and Operating Instructions EB 5868/5869 EN

Series 250 Pneumatic Control Valves Type and

Mounting and Operating Instructions EB 8111/8112 EN. Series V2001 Valves Type 3321 Globe Valve

Mounting and Operating Instructions EB 8039 EN. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve

Mounting and Operating Instructions EB 8091 EN. Pneumatic Control Valve Type and Type Type with 120 cm 2 actuator

Mounting and Operating Instructions EB 8111/8112 EN. Valve Series V2001 Globe Valve Type 3321

Differential pressure relief controller (PN 16, 25, 40) AFPA / VFG 2(1)

Pressure relief controller AFA / VFG 2(1) (PN 16, 25, 40)

Valve Series V2001 Three-way Valve Type 3323

Mounting and operating instructions EB 8093 EN. Series 240 Pneumatic Control Valve for Cryogenic Temperatures. Type and

Globe Valve Type Fig. 1 Type 3241 Globe Valve. Mounting and Operating Instructions EB EN

Flow controller with integrated control valve (PN 16) AHQM return and flow mounting

Mounting and operating instructions EB Pneumatic Control Valve Type and Type Globe Valve Type 3522 ANSI Class 300

Series 42 Self-operated Regulators. Type RS Check Valve (backflow protection)

Mounting and Operating Instructions EB 5863 EN. Electric Control Valves. Pneumatic Control Valve

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil

Series 46 Self-operated Regulators Differential Pressure and Flow Limiters Type 46-5 Type 46-6

Typetested versions With Type 3213 Globe Valve, unbalanced. With Type 3214 Globe Valve, balanced

Mounting and Operating Instructions EB 8097 EN. Pneumatic Control Valves Type and Type

Differential pressure controller with flow limitation and with integrated control valve (PN 16) AHPBM-F flow mounting, fixed setting

k VS DN (mm) Connections ( C) (m 3 /h)

Differential pressure controller (PN 16, 25, 40) AFP(-9) / VFG 2(1) return and flow mounting, adjustable setting

Flow controller with integrated control valve (PN 16) AVQM - return and flow mounting

Data sheet Pressure independent control valve with integrated flow limiter AVQM (PN 16) - return and flow mounting

Mounting and Operating Instructions EB 8048 EN. Type and Type Pneumatic Control Valves Type 3249 Aseptic Angle Valve

Flow controller with integrated control valve (PN 16) AHQM - return and flow mounting

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

Mounting and Operating Instructions EB 8097 EN. Type and Type Pneumatic Control Valves

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

Self-operated Pressure Regulators Type Universal Excess Pressure Valve

Differential pressure controller AFP / VFG 2 (VFG 21)

Pressure relief valve

Pressure relief controller AVA (PN 25)

T R A N S L A T I O N Declaration of Conformity as per Directive 2014/68/EU

Pressure reduction controllers (PN 25) AVDS - for steam AVD - for water

back to main page Type: Butterfly valves Instructions and Operation Manual Warning! Warning! Danger for life! 1. Intended use Danger for life!

Differential pressure relief controller AFPA / VFG 2 (VFG 21)

Flow controller (PN 25) AVQ - return and flow mounting

Flow controller (PN 16, 25, 40) AFQ / VFQ 2(1) - return and flow mounting

Self-operated Pressure Regulators Type Universal Pressure Reducing Valve

Flow controller (PN 25) AVQ - return and flow mounting

Declaration of Conformity as per Directive 97/23/EC

Pressure independent control valve with integrated flow limiter AVQM (PN 16) - return and flow mounting

AVQMT. AVQT controller can be combined with AVT or STM thermostatic actuators.

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

Storage, operating and maintenance instructions for AZ plug valves and Standard valves

Self-operated Pressure Regulators Universal Pressure Reducing Valve Type 41-23

INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE OF

Shut-off valves SVA-DH, SVA-DL

Self-operated Pressure Regulators Type Universal Excess Pressure Valve

Installation and Operating Instructions DDM-DS11 DDM-DS11-MS1 DDM-DS11-MS2

PRESSURE RELIEF VALVE CONTROL VALVE

Type Operating Instructions. Angle Seat Motor Valve Compact. BM24C, BM24C/I BM24C/IOS, BM230C/IOS with and without spring return

Globe Control Valve Series 1a

Mounting and Operating Instructions EB 8256 EN. Type 3286 Steam Conditioning Valve

Differential pressure controller AFP / VFG 2 (VFG 21)

Flow Control and Differential Pressure Controller AFPQ / VFQ 2(21) - Installation in return line AFPQ 4 / VFQ 2(21) - Installation in flow line

Flow-compensated temperature controller AVTQ DN 15

Starting up hydraulic systems

Differential pressure controller AFP / VFG 2 (VFG 21)

HERZ-Motorised flow controler

Company Standard Mounting Instructions for Type Valves with Type AT Actuator

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

Two-port seat valves with male thread, PN16

Instructions for installation, operation and maintenance of: GATE VALVE

Pneumatic Rotary Actuator Type 3278

ANSI version. The valve closes when the differential pressure rises

DYNAFLUID 2000 STEAM & WATER MIXING VALVE INSTALLATION & OPERATING MANUAL

Installation Operation Maintenance

Supplementary instructions. Mounting accessories, pressure measurement technology. Document ID: 43478

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

Operating Instructions

Keystone Series GR resilient seated butterfly valves GRW/GRL Installation and operation manual

ZONE CONTROLE / 2-WAY

Pressure reduction controller AFD / VFG 2, VFG 21, VFGS 2

Type overview. R B2 en-gb subject to changes 1

KEYSTONE OPTISEAL F14/16-15/17 AND BREWSEAL BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Combined Self-operated Regulators Regulators for Differential Pressure, Flow Rate and Temperature

BUTTERFLY VALVE WITH WELDED ENDS INSTALLATION AND MAINTENANCE MANUAL

Pressure reduction controller AFD / VFG 2, VFG 21, VFGS 2

Nominal sizes: DN 10, 15, 20, 25, 32, 40, 50, 65, 80, 100, 125, 150 Pressure rating: PN 16. Product No. Nominal size Body connection

Strainers with flanged connections Type 2 N Type 2 NI. Type 2 N/2 NI Strainers. Mounting and Operating Instructions EB 1015 EN

DIFFERENTIAL PRESSURE RELIEF REGULATOR TYPE A4AL Port Size 3/4"- 4" (20-100mm) For Ammonia, R-22, R134a, R404a, R507 and other common refrigerants.

HAYWARD FLOW CONTROL TBH SERIES TRUE UNION BALL VALVE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Mounting and Operating Instructions EB 8252 EN. Type 3281 Steam Conditioning Valve

Pneumatic Controller for Temperature. Type Pneumatic Controller for Temperature. Type Mounting and Operating Instructions EB 7065 EN

Standard Valves Series Globe Valves Series Angle Valves Series Way-Valves

Series 240 Type Gas and Type Gas Automatic Shut-off Valves for Gases (valve class D)

Mounting and Operating Instructions EB 8052 EN. Type 3251 Valve

A408 GB. Pneumatic oil and diesel pumps 1:1

VALFONTA PRESSURE REGULATOR WITHOUT AUXILIARY ENERGY EXCESS PRESSURE VALVE (PRESSURE RELIEF VALVE) MODEL S1 MAIN CHARACTERISTICS

Special Kv available. Classification according pressure equipment Directive, 2014/68/UE

T R A N S L A T I O N Declaration of Conformity as per Directive 2014/68/EU

EZH and EZHSO Series. Pressure Reducing Regulators. EZH and EZHSO Series. Introduction. Scope of the Manual. Product Description !

Mounting and Operating Instructions EB 8227 EN. Pneumatic Control Valve Type 3331/BR 31a Special version Type 3331/3278. Type 3331 Butterfly Valve

Transcription:

Pressure relief controller V22 D28 For heavy oil and high-viscosity media Instructions for Mounting, Start-up and Maintenance SIBC VI.CB.I1.02

Contents 1. General data Page 1.1 Correct application 1 1.2 Incorrect operation 1 1.3 Storage, transport and packing 1 1.4 Warranty 1 1.5 Nameplate 1 1.6 Design 2 1.7 Technical data 2 2. Mounting 2.1 Safety notes 3 2.2 Safety precautions on the site 3 2.3 Mounting 3 2.4 Application examples 3 2.5 Mounting dimensions 4 3 Start-up procedure 3.1 Principle of operation 5 3.2 Special notes 5 3.3 Start-up 5 4. Maintenance and repairs 4.1 Troubleshooting 6 4.2 Repair instructions 6 4.3 Maintenance notes 6 4.4 Solutions 6 4.5 Spare parts list 6

General Data Pressure relief controller is designed for modulating control of the pressure in technical devices operating with heavy oil and other high-viscosity media with temperature of up to 140 C. 1.1 Correct application Pressure relief controller may only operate in the required mounting position and with the medium stated above. Operation in conditions which differ from the technical requirements is not allowed. Ensure that the ranges stated in Technical data are strictly observed. 1.2 Incorrect application Check if the shipment is complete. In case the goods are damaged during transport, immediately inform transport agent and manufacturer. If the goods are transhipped during the transport, the original packing must be used. Storage location must be clean and dry. Storage and transport temperature: 1.3 Storage, transport and packing Warranty is applied according to the delivery conditions valid in the time of delivery. Warranty becomes void if mounting and start-up is not performed according to Instructions for Mounting, start-up and Maintenance. Mounting, start-up and maintenance may only be performed by authorized personnel. 1.4 Warranty Valve Actuator 1.5 Nameplate Typ S.-Nr. kvs tmax p m 3 /h C bar pensatoren Reglerund Kom 0 0 0 0 0 0 0 0 0 0 Typ A cm 2 PN T MAX I.Nr.: W Medium: S.Nr.: bar W erkstof f GehŠuse: Membrane: Auftr.Nr.: Fig. 1: Nameplate 1

Design 1.6 Design V22 Valve 1 Valve body 2 Seat 3 Valve cone 4 Plug stem D28 Control element 13 12 11 5 Coupling nut 6 Actuator stem 7 Diaphragm plate 8 Diaphragm 9 Larger Diaphragm plate 10 Diaphragm housing 11 Set-up spring 12 Pressure element with spheres 13 Set point adjustment 8 10 9 7 6 5 4 3 2 1 1.7 Technical data Table 1: Technical data valve V22 Nominal size DN 15 20 25 32 40 50 65 kvs (m 3 /h) 3,6 6,6 9,3 13,5 23,5 35 55 Differential pressure p max (bar) 16 16 16 16 16 16 16 Nominal flow (m 3 /h) 1,5 3 4,5 7 11 18 27 Weight (kg) 5,5 6 9 12 15 19 30 Max. operating temperature Body material Max. operating pressure Table 2: Technical data actuator D28 140 o C GGG-40.3 Nominal pressure PN 16 (DIN 2401), do not exceed p max Control element D28 Size (cm 2 ) 32 80 Set point acc. to the spring colour silver (bar) 3-11 1-5 yellow (bar) - 0,5-2,5 black (bar) 10-16 - Weight approx. (kg) 8,0 7,5 Nominal pressure 25 Material body Steel, mat. No. 1.0338, chromated diaphragm FKM 2

Verteiler Mounting Please read carefully and observe the Instructions for Mounting Start-up and Maintenance prior to starting any work on the device. Also observe the Operating Conditions and Guidelines of the Proffesional Association Süddeutsche Edelund Unedelmetallberufsgenoschenschaft, Stuttgart, Hausmanstrasse 6, as well as valid DIN guidelines. 2.1 Safety notes Make sure that the pipes which are connected to the device are depressurized and enough time is allowed for the pipes to cool down. Shut-off valves in the relevant section of the pipeline must be secured against accidental opening. Before starting welding procedures, necessary fire-preventing measures must be taken. 2.2 Safety precautions on the site Flush the pipe system before mounting the flow regulator. Pressure test must be performed before mounting takes place or test pressure must not exceed max. differential pressure across the flow regulator. Controller must be installed in horizontal pipeline with the actuator in pointing upwards. This mounting position enables the transfer of media temperature to the actuator. The medium must flow through the valve in the direction indicated by the arrow on the valve body. Installation of strainer is strongly recommended as well as the installation of shut-off valves and pressure gauges upstream and downstream of the pressure relief controller. Avoid mechanical stress of the valve body during installation of pipes. The operation of pressure relief controller does not require any control lines. In case valve and actuator are delivered separately, both parts must be joined. Firstly put the actuator on valve neck and then screw (clockwise) the actuator stem into the valve stem until it stops. Unscrew the joint for one turn (counter clockwise) to prevent any additional tension between actuator and valve. Fasten the actuator onto the valve neck with the R 1 1 4 coupling nut. 2.3 Mechanical mounting Recommended layout Shut-off valve Strainer Shut-off valve 2.4 Application examples Fig. 3: Recommended layout Pressure reduction in heavy-oil igniting devices Fig 4: Application example 3

H Mounting 2.5 Dimensions Table 3: Dimensions of valve V22 Nominal size DN 15 20 25 32 40 50 65 L (mm) 130 150 160 180 200 230 290 B (mm) 100 105 115 125 135 140 150 Table 4: Dimensions of actuator D28 Control element D28 Size (cm 2 ) 32 80 A (mm) 172 172 H (mm) 480 485 Fig. 5: Dimensions L B A 4 4

Start-up procedure After opening shut-off valves the medium flows through the valve and acts with its pressure on the control diaphragm of the actuator through the internal channels. After the system or end user is filled-up and the pressure reaches the pre-set value, the cross-section of flow in the valve changes proportional to the difference of the set point. The required equilibrium between pressure in the diaphragm chamber and setting force holds the valve stem and thus the valve cone in the position which gives the required flow. 3.1 Principle of operation Make sure that the operating values for temperature and pressure, stated in technical data are not exceeded. Pipeline system must be equipped with elements which compensate excessive stretch- or torsion forces. Avoid sudden pressure drops, which means that quick shut-off valves can be used as an emergency valves only. 3.2 Special notes Caution! Sealing of the upper and lower valve parts is performed when the valve is installed on the actuator. Therefore system must be depressurized before dismounting the actuator from the valve. Pressurize the system by turning on the circulation pump while shut-off valve in front of the regulator remains closed. Slowly open the shut-off valves and check the pressure relief controller connection for leaking. Adjust the required pressure by turning the set-up nut while watching the pressure gauge at the same time (Fig. 2, pos. 13). Turn the nut counter clockwise to increase the pressure and clockwise to reduce the pressure. The adjustment range can be obtained from the nameplate. After short operating time check all connections and ventilating plugs for leaking. 3.3 Start-up 5

Maintenance 4.1 Maintenance Pressure relief controller V22 D28 is maintenance free under normal operating conditions. 4.2 Repair instructions Prior to working on the regulator depressurizre and cool down the device. Perform repairs according to section 2.3. Follow the instructions in section 3.3 to perform start-up procedure. 4.3 Troubleshooting The pressure exceeds or does not reach the set point. Possible reasons: - valve does not close - actuator is out of order 4.4 Solution Replace the valve In case the valve leaks, the possible cause may be impurities in the valve or valve cone and seat being warn out. Replace or repair the valve. Replace the actuator In case actuator is not working the diaphragm chamber may be blocked by the deposits or the diaphragm is defective. Replace the actuator. 4.5 Spare parts Should you order spare pars please submit the data about control valve type, nominal size, actuator size and set point range. Please send your order to the address stated in 4.7 or to the manufacturer. Spare part - Valve V22 DN... PN 16 - Actuator D28, operating surface... set point... 6