Operating Instructions. VEGASWING 61, 63 with oscillator SW E60N (EX)

Similar documents
Operating Instructions OPTISWITCH 5200 C, 5250 C with NAMUR output

Operating Instructions OPTISWITCH 5100 C, 5150 C with contactless electronic switch

Operating Instructions OPTISWITCH 5200 C, 5250 C with contactless electronic switch

Operating Instructions OPTISWITCH 5100 C, 5150 C with transistor output

Operating Instructions OPTISWITCH 5200 C, 5250 C with transistor output

OPTISWITCH 4000/5000. Vibration level switches for liquids

Operating Instructions OPTISWITCH 4000 C with transistor output

Operating Instructions April 2008 SITRANS LVL200E

Instruction Manual September 2010 SITRANS LVL200S

Operating Instructions 11/2015

Operating Instructions April 2008 SITRANS LVL100

Operating Instructions OPTISWITCH 5200 C, 5250 C

Level Measurement Point level measurement - Vibrating switches

Level instruments. Point level measurement - Vibrating switches SITRANS LVL100. 5/78 Siemens FI Horizontal mounting.

Operating Instructions 07/2013

SITRANS L Level instruments

Level detection in liquids. Vibration VEGASWING 51 VEGASWING 61 VEGASWING 63. Product Information

Level Limit Switch liquiphant FTL 365 / FTL 366

Assembly. 1 Compact version with valve plug 2 Short tube version with cable 3 Compact version with M12 plug 4 Short tube version with M12 plug

Level measurement Guided microwave Product Information VEGAFLEX ma/hart. Level Switching Pressure

Magnetic float switch For vertical installation Model FLS (models with Ex approval: 60, AL-ADF)

OPTISWITCH 5300 C. Handbook. Vibrating Level Switch. - transistor (NPN/PNP)

OPTISWITCH 5300 C. Handbook. Vibrating Level Switch. - transistor (NPN/PNP) With SIL qualification

Level Limit Switch liquiphant FTL 360 / FTL 361

Operating Instructions VEGASWING 66. Vibrating level switch for liquids under extreme process temperatures and pressures

Operating Instructions 07/2017

Vibrating Level Switch TF 511, TF 611, TF 633

Metal tube variable area flowmeter for gases, liquids and steam

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

Product information. Capacitive. Level measurement in bulk solids VEGACAL 62 VEGACAL 65 VEGACAL 66 VEGACAL 67. Document ID: 30139

Operating Instructions VEGASWING 63 - transistor (NPN/PNP)

Supplementary instructions. Air cooling - FIBERTRAC 31. Active air cooling system for radiation-based sensors. Document ID: 50339

Level Measurement. Point level measurement Capacitance switches. Pointek CLS200 Standard. 4/18 Siemens FI Overview.

Level Measurement. Point level measurement Capacitance switches. Pointek CLS200 Standard. icenta Controls Ltd

Level Measurement Point level measurement - RF Capacitance switches

Operating instructions

OPTISWITCH 6500 C Technical Datasheet

Solenoid Valves Type 3963

Operating Instructions VEGASWING 63. Vibrating level switch with tube extension for liquids. - transistor (NPN/PNP) Document ID: 29230

OPTIMASS 3000 Technical Datasheet

Metal tube flowmeters. Series SC250. Metal Tube Flow Meters. Series SC250. Variable area flowmeter for liquids, gases and steam

Level Limit Switch soliphant II FTM 30 (D/S), FTM 31 (D/S), FTM 32 (D/S)

Operating Instructions VEGASWING 51. Vibrating level switch for liquids. - contactless electronic switch. Document ID: 41045

Supplementary instructions. Air cooling - FIBERTRAC 31 with Conduit tube connection. Active air cooling system for radiation-based sensors

Operating Instructions VEGASWING 63. Vibrating level switch with tube extension for liquids. Contactless electronic switch. Document ID: 29228

Operating Instructions VEGASWING 63. Vibrating level switch with tube extension for liquids. - contactless electronic switch. Document ID: 29228

SITRANS P measuring instruments for pressure

Vibration Limit Switch liquiphant M FTL 51 C

INSTRUCTION MANUAL. Read before installing the recommendations and warnings on the last page of this manual. Vibra Switch S LEVEL SWITCH

Pressure measurement. Process pressure VEGABAR 14 VEGABAR 17. Product Information

OPTISWITCH 6500 C Technical Datasheet

Operating Instructions VEGASWING 51 - transistor (PNP)

Type 2511/12. Type Type 2030 Cable plug. ASI cable plug. Dosing control. General technical data Orifice Type 6518

Limit level measurement of bulk solids. Vibration VEGAVIB VEGAWAVE Product Information

PHOENIX CONTACT - 01/2008

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

Type 3761 Pneumatic or Electropneumatic Positioner for Rotary Actuators. Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

Level limit switch Series RF 3000 Selection list

NIVOSWITCH R-400/R-500

Mobrey MLT100. Displacer Level Transmitter. Product Data Sheet February 2015 IP119, Rev CA. Level, contents or interface measurement transmitter

Operating Instructions VEGASWING 51. Vibrating level switch for liquids. - transistor (PNP) With extended status indication. Document ID: 40552

Supplementary instructions. Centering. for VEGAFLEX series 80. Document ID: 44967

Point level measurement Capacitance switches

Rosemount 2110 Compact Vibrating Fork Liquid Level Switch 2110 FEATURES:

Compact System NRGS 11-2 NRGS Original Installation Instructions English

Mounting and Operating Instructions EB 5868/5869 EN

Solenoid Valve Island Type 3965

Supplementary instructions Flanges according to DIN - EN - ASME - JIS - GOST Technical data. Document ID: 31088

Supplementary instructions. Connection cable IP 66/IP 68 (1 bar) Retrofitting set/accessory for instruments of the plics family. Document ID: 34107

Operating Instructions VEGASWING 66. Vibrating level switch for liquids under extreme process temperatures and pressures. - transistor (NPN/PNP)

Soliphant T FTM260. Technical Information. Level limit switch Cost-effective vibration limit switch for fine-grained solids

JUMO dtrans p20. Process pressure transmitter. Type Brief description. Key features. Block diagram

Flap-Type Flow Meter Prall

SITRANS T measuring instruments for temperature

TORRIX Magnetostrictive level sensor

Supplementary instructions. Mounting accessories, pressure measurement technology. Document ID: 43478

Level instruments. Continuous level measurement - Capacitance transmitters SITRANS LC300. 5/262 Siemens FI Overview.

SITRANS F flowmeters SITRANS F C

Supplementary instructions. Water cooling - MINITRAC 31. Active water cooling system for radiationbased. Document ID: 48522

Level Probes multicap T DC 12 TE multicap T DC 11/16/21/26 TEN/TES

Product information. Differential pressure. Mechanical and electronic differential pressure measurement

RHM 80 - Coriolis Mass Flowmeter for large flow applications optional heavy duty version

Pneumatic or Electropneumatic Positioner for Rotary Actuators Type Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

SITRANS F flowmeters SITRANS F C SITRANS F C MC2 4/169. Overview

Continuous level sensor NSK

RHM The world s largest Coriolis Mass Flowmeter for flow rates up to kg/min

Globe Valve Type Fig. 1 Type 3241 Globe Valve. Mounting and Operating Instructions EB EN

+ = Angle-seat Valve System for continuous control. Type 8802/2300 electro-pneumatically operated angle-seat valve

RHM Coriolis Mass Flowmeter for high Flow Applications

BFS-10-O G1/4: BFS-10-O G1/2: BFS-10-O G1: Contact rating: BFS-10-O G1/4

Safety instructions VEGAVIB VB6*.GI**C/R/T/Z/N*** IECEx BVS Ex ta, ta/tb, tb IIIC T Da, Da/Db, Db IP66

Continuous level sensor NSK

Soliphant II FTM30(D/S)/31(D/S)/32(D/S)

Level switches (two-term level controllers) ERH-xx-04,-06,-07,-16,-16.1 Description

Rod probe 11375Z. Technical Information. Conductive level limit detection Partially insulated rod probe for use in conductive liquids

Vortex Flowmeters VFM 3100 F-T VFM 3100 W-T

Rosemount 2110 Compact Vibrating Fork Liquid Level Switch 2110 FEATURES:

Compact Pressure Transmitter DAN-HH

OPTIMASS 2000 Technical Datasheet

Transcription:

Operating Instructions VEGASWING 61, 63 with oscillator SW E60N (EX)

Contents Contents Safety information... 2 Note Ex area... 2 1 Product description... 3 2 Function and application... 4 2.1 Principle of operation... 4 2.2 Measuring system... 4 3 Types and versions... 5 3.1 Overview... 5 3.2 Technical data... 6 3.3 Dimensions... 10 4 Mounting... 12 4.1 VEGASWING... 12 5 Electrical connection... 16 5.1 VEGASWING 61 and 63... 16 6 Set-up... 17 6.1 VEGASWING 61 and 63... 17 6.2 Function chart... 19 Safety information Please read this manual carefully, and also take note of country-specific installation standards (e.g. the VEGA regulations in Germany) as well as all prevailing safety regulations and accident prevention rules. For safety and warranty reasons, only qualified VEGA personnel must carry out any internal work on the instruments, apart from that involved in normal installation and electrical connection. Note Ex area Please note the attached safety instructions, containing important information on installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex approved instruments. 2 VEGASWING 61, 63 - N

Product description 1 Product description VEGASWING 61 and 63 VEGASWING 61/63 vibrating level switches are used for level detection of liquids. Typical applications are overfill and dry run protection. Using a tuning fork with a length of only 40 mm, VEGASWING 61 opens up new areas of application, e.g. in pipelines from DN 25. Power supply and output signal correspond to the Namur interface acc. to IEC 60947-5-6 (EN 50227). VEGASWING series 60 vibrating level switches detect levels of liquids with a viscosity of 0.1 10.000 mpa s and a density of 0.5 g/cm 3. Modular construction enables their use in vessels, tanks and pipelines. Thanks to its simple and rugged measuring system, VEGASWING is virtually unaffected by the chemical and physical properties of the liquid. It does its job even under unfavourable conditions such as turbulences, air bubbles, foam generation, buildup, strong external vibration or constantly changing products. Tuning fork with only 40 mm length. Thread from ¾ and flanges from DN 25 (ANSI 1"). Process temperature -50 C... +250 C without shock limitation. Insensitive to external vibration. Process pressure up to 64 bar. Also ECTFE or PFA coated or enamelled. Viscosity 0.1... 10000 mpa s. Density range 0.5 g/cm 3 2.5 g/cm 3. NAMUR output. Ex-Zone 0/1 ATEX II 1G or 1/2G EEx ia IIC T6 ATEX II 1/2G or 2G EEx d IIC T6 Overfill protection acc. to WHG. Integrated fault monitoring. Fixed, exactly reproducible switching point. Switching point visible with closed instrument (LED). Set-up without adjustment. Installation in any position. Min. or max. mode. VEGASWING 61, 63 - N 3

Function and application 2 Function and application 2.1 Principle of operation VEGASWING vibrating level switches detect levels in almost all liquids. Viscosity: 0.1... 10.000 mpa s Density: 0.5... 2.5 g/cm 3 VEGASWING measuring principle The tuning fork is piezoelectrically energised and vibrates at its mechanical resonance frequency of approx. 1200 Hz. The piezoelectric elements are fastened mechanically and are therefore not subject to temperature shock limitations. When the tuning fork is submerged in the product, the frequency changes. This change is detected by the integrated oscillator and converted into a switching command. Compact instrument with NAMUR output The oscillator delivers as output signal a current jump acc. to IEC 60947-5-6. The switching signal is further processed via complementary NAMUR processing systems, e.g. PLC input card or remote I/O. 2.2 Measuring system Level detection of liquids with NAMUR compact instrument The integrated fault monitoring detects: - interruption of the connection cable to the piezoelectric elements - extreme wear on the tuning fork - break of the tuning fork - absence of vibration. In case of failure, a defined current ( 1.0 ma) is impressed on the cable to the NAMUR amplifier. Measuring system with VEGASWING as NAMUR compact instrument A measuring system consists of: - a VEGASWING vibrating level switch with integrated oscillator SW E60N - a NAMUR amplifier acc. to IEC 60947-5-6 (EN 50 227 / DIN 19 234). 4 VEGASWING 61, 63 - N

Types and versions 3 Types and versions 3.1 Overview Version 61 63 61 63 ExD ExD Standard (fixed installation length) Tube version Approvals (SW E60N) Ex-Zone 0 acc. to ATEX 100a II 1G or 1/2G EEx ia IIC T6 Ex-Zone 0 acc. to ATEX 100a II 1/2G or 2G EEx d IIC T6 Overfill protection acc. to WHG Mechanical connection G¾A ¾ NPT G 1 A 1 NPT Flange from DN 25, ANSI 1" Tri-Clamp 1" Tri-Clamp 1½" Bolting DN 40 Tuchenhagen Varivent Tuning fork material 1.4435 (316 L) 2.4610 (Hastelloy C4) Material, mechanical connection 1.4435 (316 L) 2.4610 (Hastelloy C4) Coating ECTFE (Halar) PFA Enamel Oscillator Two-wire output (SW E60N) NAMUR acc. to IEC 60947-5-6 Adapters Temperature adapter 1.4435 (316 L) up to 250 C Gastight leadthrough VEGASWING 61, 63 - N 5

Types and versions 3.2 Technical data VEGASWING 61 and 63 Housing Housing material PBT (Polyester), Aluminium (plastic coated) Protection IP 66 and IP 67 (meets both requirements) Cable entry 2 x M20 x 1.5 or 2 x ½ NPT Terminals max. 1 x 1.5 mm 2 Adapters Gastight leadthrough (option) - material 1.4435 (316 L) / glass - leakage rate < 10-6 mbar l/sec - pressure resistance PN 64 Temperature adapter (option) - material 1.4435 (316 L) Process fitting Thread G¾A, ¾ NPT, G 1 A or 1" NPT PN 64 - material 1.4435 (316 L) or 2.4610 (Hastelloy C4) Flanges DIN from DN 25 and ANSI ab 1" - material 1.4435 (316 L), 1.4435 (316 L) with Hastelloy C4 coating, enamelled steel, 1.4435 (316 L) ECTFE or PFA coated Hygienic fittings - material 1.4435 (316 L) - bolting DN 40 PN 40 - Tri-Clamp 1", 1½ " PN 10 - conus DN 25 PN 40 - Tuchenhagen Varivent DN 50 PN 10 Supplied process seal Klingersil Extension tube (VEGASWING 63) Material Length - 1.4435 (316 L), 2.4610 (Hastelloy C4) 80 mm 6000 mm - Hastelloy C4 enamelled 80 mm 1500 mm - 1.4435 (316 L) ECTFE coated 80 mm 3000 mm - 1.4435 (316 L) PFA coated 80 mm 3000 mm 1.4435 (316 L), 2.4610 (Hastelloy C4), Hastelloy C4 enamelled 1.4435 (316 L) with ECTFE or PFA coating 6 VEGASWING 61, 63 - N

Types and versions Tuning fork Material 1.4435 (316 L), 2.4610 (Hastelloy C4), 2.4610 Hastelloy C4 enamelled, 1.4435 (316 L) with ECTFE or PFA coating Coating thicknesses - ECTFE approx. 0.5 0.8 mm - PFA approx. 0.3 0.5 mm - enamel approx. 0.8 mm High voltage test (enamel) max. 5 KV Surface quality (option) - standard Ra 3.2 µm - hygienic version (3A) Ra 0.8 µm Weight Basic weight - with Aluminium housing approx. 980 g - with plastic housing approx. 480 g Tube extension (VEGASWING 63A) approx. 0.11 kg/m Product Viscosity - dynamic 0.1 10.000 mpa s (requirement: with density 1) Density 0.7 2.5 g/cm 3 (0.5 0.7 g/cm 3 by switching over) Ambient conditions Ambient temperature on the housing -40 C 70 C Storage and transport temperature -40 C 80 C Process temperature -50 C 150 C Process temperature with temperature adapter (option) - uncoated -50 C 250 C - enamelled -50 C 200 C Temperature shock without limitation Permissible ambient temperature 70 C 40 C With temperature adapter -50 C 0 C 0 C 50 C 100 C Process temperature 150 C 200 C 250 C -40 C Process pressure Process pressure max. 64 bar depending on the mechanical connection VEGASWING 61, 63 - N 7

Types and versions Function Modes min. rising characteristics (High current with submersion) max. falling characteristics (Low current with submersion) NAMUR output switchable to falling or rising characteristics Integration time approx. 500 ms Frequency approx. 1200 Hz Hysteresis approx. 2 mm with vertical installation Control lamp - SW E60N single colour LED red 2.2 ma = High current dark 1.0 ma = Low current red flashing 1.0 ma = failure CE conformity VEGASWING 61 and 63 vibrating level switches meet the protective regulations of EMC (89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following standards: EMC Emission EN 61 326/A1: 1998 (class B) Susceptibility EN 61 326/A1: 1998 NSR EN 61 010-1: 1993 Oscillators Two-wire NAMUR output (SW E60N) Power supply (standard characteristics) for connection to amplifier acc. to NAMUR IEC 60947-5-6, approx. 8.2 V - open circuit voltage U O ~ 8.2 V - short-circuit current I U ~ 8.2 ma Output two-wire NAMUR output Required processing system NAMUR processing system acc. to IEC 60947-5-6 (EN 50 227 / DIN 19 234) Current consumption - falling characteristics 2.2 ma uncovered/ 1 ma covered - rising characteristics 1 ma uncovered/ 2.2 ma covered - fault signal 1 ma Protection class Overvoltage category Modes II III falling or rising characteristics selectable on the oscillator 8 VEGASWING 61, 63 - N

Types and versions Approvals VEGASWING 61 and 63 Water Resources Law (WHG) Approval as part of an overfill protection system acc. to the Water Resources Law (WHG) Ambient temperature on the housing -40 C 70 C Process temperature -50 C 150 C - test report VEGASWING 61 EX and 63 EX with oscillator SW E60N EX and suitable signal conditioning instrument - with temperature adapter up to 250 C Process pressure max. 64 bar Explosion protection VEGASWING 61 EX0, 63 EX0 Certificate EC type approval certificate acc. to ATEX 100 a Flame proofing ATEX II 1/2G EEx d IIC T6 ATEX II 1G or 1/2G or 2G EEx d IIC T6 Permissible application range Ex Zone 0 Ambient temperature depending on temperature class and Ex-Zone: see safety instructions Electrical safety-relevant characteristics: see safety instructions VEGASWING 61, 63 - N 9

Types and versions 3.3 Dimensions VEGASWING 61 Plastic housing Stainless steel housing Aluminium housing ~ 69 ø 77 ~ 69 ø 77 ~ 116 ø 84 20x1,5 ø 34 156 SW32 21,3 26 112 (*123) 112 (*123) 112 (*123) ½ NPT ½ M20x1,5 ½ NPT 13 Gastight leadthrough of 1.4435 (316 L) (option), length with thread 37 mm Temperature adapter of 1.4435 (316 L) (option) in conjunction with thread L = 180 mm Thread G¾A or ¾ NPT Tri-Clamp 1½" 55 58 53 50 53 37 Conus DN 25 Bolting DN 40 Flange DN 25 PN 40 66 16 40 53 36 Switching point 1) * with display 1) Also in version with switching point extension to VEGASWING 81A. 10 VEGASWING 61, 63 - N

Types and versions VEGASWING 63 Plastic housing Stainless steel housing Aluminium housing ~ 69 ø 77 ~ 69 ø 77 ~ 116 ø 84 20x1,5 112 (*123) 112 (*12 112 (*123) ½ ½ NPT M20x1 ½ NPT 13 Gastight leadthrough of 1.4435 (316 L) (option), length with thread 37 mm ø 34 156 Temperature adapter of 1.4435 (316 L) (option) in conjunction with thread and flange enamelled L = 180 mm Thread G¾A or ¾ NPT Tri-Clamp 1½" Conus DN 25 Bolting DN 40 Flange DN 25 PN 40 16 SW32 36 58 50 37 L (min. 150, max. 3000) ø 21,3 40 Switching point 26 * with display VEGASWING 61, 63 - N 11

Mounting 4 Mounting 4.1 VEGASWING In principle, VEGASWING can be mounted in any position. The instrument must be mounted such that the tuning fork is at the height of the required switching point. Note the following installation instructions. Transport Do not hold VEGASWING on the tuning fork. Especially with flange and tube versions, the tuning fork can be damaged simply by the weight of the instrument. Transport enamelled and ECTFE coated instruments very carefully and avoid touching the tuning fork. Vertical installation from top, from bottom Switching point approx. 13 mm Switching point with lower density Switching point with higher density Switching 27 point mm Fig. 2.1 Switching point The tuning fork is provided with lateral markings (notches), marking the switching point with vertical installation. The switching point refers to the medium water at the basic setting of the density switch 0.7 g/cm 3. Make sure when mounting VEGASWING that this marking is at the height of the requested level. Note that the switching point of the instrument shifts when the medium has a density other than that of water (water = 1.0 g/cm 3 ). For products < 0.7 g/cm 3 the density switch has to be set to 0.5 g/cm 3. Horizontal installation Switching point recommended installation position for adhesive products: Switching point Marking on top Direct exchange of a VEGASWING 81A or 71A (with thread G1A) Fig. 2.2 If VEGASWING 61 with a sensor length the same as VEGASWING 81A or 71A is mounted into an existing mounting boss G1A, it is ensured that VEGASWING 61 will seal correctly. 12 VEGASWING 61, 63 - N

Mounting Adhesive products In case of horizontal mounting in adhesive and viscous products, the surfaces of the tuning fork should be vertical in order to reduce buildup on the tuning fork (see fig. 2.2). The orientation of the tuning fork is marked by a notch on the hexagon of VEGA- SWING. With this you can check the orientation of the tuning fork when screwing it in. When the hexagon touches the seal, the thread can still be turned by approx. half a turn. This is sufficient to reach the recommended installation position. This applies mainly to applications in Ex areas category 1G or WHG. Make sure that the tube is not subjected to bending forces. In case of adhesive and viscous products, the tuning fork should protrude into the vessel to avoid buildup. Sockets for flanges and mounting bosses should therefore not exceed a certain length. The tuning fork should protrude into the vessel/pipeline. Stirrers Fig. 2.3 Pressure When there is gauge pressure or underpressure in the vessel, the mounting boss must be sealed on the thread. Cover the thread with teflon tape, hemp or similar material or use a sufficiently resistant seal ring. Vibrations Extreme vibrations and shocks, e.g. caused by stirrers and turbulence in the vessel, can cause the extension tube of VEGASWING 63 to vibrate. This will cause increased stress on the upper weld joint. Through the action of stirrers or similar devices, the level switches can be subjected to strong lateral forces. For this reason, do not use an overlong extension tube for VEGA- SWING 63, but check if it is possible to mount a VEGASWING 61 level switch on the side of the vessel in horizontal position. Cable entries Use a cable with round wire cross-section and tighten the cable entry firmly. The cable entry is suitable fro cable diameters from 5 mm to 9 mm. To counteract this, provide a support or straining directly above the tuning fork to firmly hold the extension tube (see fig. 2.3). VEGASWING 61, 63 - N 13

Mounting Moisture Turn the cable entries of horizontally mounted instruments downwards to avoid moisture ingress. For this purpose the plastic housing can be rotated by approx. 330. For vertically installed instruments, loop the cable connected to the instrument housing downwards so that rain and condensation water can drain off. This applies mainly when mounting outdoors, in humid areas (e.g. by cleaning processes) or on cooled or heated vessels (see fig. 2.4). Fig. 2.5 Chemical resistance When applied in Ex areas zone 0, VEGASWING must be used only in combustible liquids against which the materials of the tuning fork system are sufficiently chemically resistant. Lateral load Fig. 2.4 VEGASWING with enamel Treat instruments with enamel coating very carefully and avoid shocks. Unpack VEGASWING directly before installation. Insert VEGASWING carefully into the vessel opening and avoid touching any sharp vessel parts. Make sure that the vibrating element is not subjected to lateral forces. To assure this, mount the instrument at a location in the vessel where no adverse conditions, e.g. caused by stirrers, filling openings etc. can occur. This applies mainly to instrument types with extension tube (see fig. 2.5). The surfaces of the tuning fork should be parallel to the product movement. Flow (e.g. in tubes) When mounting in pipelines or in vessels having a certain flow direction, VEGASWING should be installed such that the surfaces of the tuning fork are aligned with that direction. 14 VEGASWING 61, 63 - N

Mounting Mounting boss VEGASWING s thread starting point is defined. This means that every VEGASWING is in the same position after being screwed in. Remove therefore the supplied seal from the thread of VEGASWING. This seal is not required when using a welded socket. Screw VEGASWING into the welded socket. You can determine the subsequent position of VEGASWING before welding (see fig. 2.2). Mark the appropriate position of the welded socket. Before welding, unscrew VEGA- SWING and remove the rubber ring from the socket. The welded socket has a marking (notch). Weld the socket with the notch facing upwards, or in the case of pipelines, aligned with the direction of flow (see fig. 2.6). Marking Fig. 2.6 VEGASWING 61, 63 - N 15

Electrical connection 5 Electrical connection 5.1 VEGASWING 61 and 63 Note Switch off the power supply before starting connection work. Connect supply voltage according to the following wiring diagrams. As a rule, connect VEGASWING to vessel ground (PA) or, in plastic vessels, to the nearest ground potential. For this purpose, a grounding terminal is provided between the cable entries on the side of the housing. This connection serves to drain off electrostatic charges. In Ex applications, it is also necessary to note the installation regulations for hazardous areas. Two-wire NAMUR output (SW E60N) For connection to isolation amplifiers acc. to NAMUR (IEC 60947-5-6, EN 50227) (for further information see 3.2 Technical data) + - 1 2 + - Switching amplifier acc. to NAMUR (IEC 60947-5-6) 16 VEGASWING 61, 63 - N

Set-up 6 Set-up 6.1 VEGASWING 61 and 63 The numbers in brackets relate to the following illustration. Display and adjustment elements The switching status of the electronics can be checked when the housing is closed (LED display). In basic adjustment, products with a density > 0.7 g/cm 3 can be detected. For products with lower density, the switch must be set to > 0.5 g/cm 3. The following display and adjustment elements are located on the oscillator: - LED display (1) - DIL switch for adaptation of the switching point (3) and characteristics reversal (2) - test key (4) Note: When testing, always immerse the tuning fork of VEGASWING into a liquid. Do not test the functionality of VEGASWING by touching it. This can damage the sensor. Characteristics reversal (2) Characteristics reversal is possible with the DIL switch. You can choose between falling characteristics (switch position max.) and rising characteristics (switch position min.). The requested current can thus be outputted. min. rising characteristics (High current max. when immersed) falling characteristics (Low current when immersed) NAMUR output switchable to falling or rising characteristics (see also 6.2 Function chart). In applications acc. to WHG, the DIL switch must be set to position max. Switching point adaptation (3) With this DIL switch (3) you can set the switching point for liquids with a density between 0.5 and 0.7 g/cm³. In the basic setting, liquids with a density > 0.7 g/cm³ can be detected. For products with lower density, you have to set the switch to > 0.5 g/cm³. The information on the position of the switch point relates to water as the medium (density value 1.0 g/cm³). In products with a different density the switching point shifts, depending on density and type of installation, either in the direction of the housing or the tuning fork end. See also 4 Mounting - Switching point. Fault monitoring The oscillator of VEGASWING monitors the instrument continuously. The following criteria will be checked: - corrosion or damage to the tuning fork - failure of the tuning fork - line break to the actuation. LED display (1) red = High current 2.2 ma off = Low current 1 ma flashing = failure 1 ma VEGASWING 61, 63 - N 17

1 2 3 Set-up Simulation key (4) The simulation key is lowered in the upper side of the oscillator. Press the simulation key with a suitable object (screwdriver, ball pen, etc.) When the key is pressed, a line break between sensor and processing unit is simulated. The LED on the sensor extinguishes. When the key is pressed, the system must signal failure and switch to a safe condition. Make sure that all connected devices are activated when the key is pressed. By doing this, you can check the proper function of the measuring system. SW E60N Ex 4 NAMUR (IEC 60947-5-6) Simul. + Simul. max. 0,5 g / cm 3 min. 0,7 g / cm 3 1 2 1 2 1 LED display 2 DIL switch - characteristics reversal 3 DIL switch - switching point adaptation 4 Simulation key 18 VEGASWING 61, 63 - N

Set-up 6.2 Function chart The following chart provides an overview of the switching conditions depending on the adjusted mode and level. Level Signal Control current lamp VEGA- (red) SWING Falling characteristics max. 2.2 ma 1.0 ma Rising characteristics min. 2.2 ma 1.0 ma Failure any 1.0 ma flashing Note: The mode setting on the NAMUR switching amplifier must allow the switching output to assume safe status in case of failure (I 1.0 ma). VEGASWING 61, 63 - N 19

VEGA Grieshaber KG Am Hohenstein 113 D-77761 Schiltach Phone (07836) 50-0 Fax (07836) 50-201 E-Mail info@de.vega.com www.vega.com ISO 9001 All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the latest information at the time of printing. Technical data subject to alterations