DETAILED EQUIPMENT SPECIFICATION MDAS SERIES DEALKALIZERS

Similar documents
DETAILED EQUIPMENT SPECIFICATION MR SERIES WATER SOFTENERS

DETAILED EQUIPMENT SPECIFICATION MHC SERIES WATER SOFTENERS

INDUSTRIAL GRADE WATER SOFTENERS LWTS INDUSTRIAL SERIES

CAT231.1 PRESSURE GAUGE AND TEST TAP KIT SKID MOUNTING 220V, 50HZ, 1Ø OPERATING CONDITIONS 25 TO 100 PSI 100 F MAX IMUM TEMPERATURE SERIES METER

CAT231.1 SHUT OFF KIT (SOK) TO PREVENT BYPASS PRESSURE GAUGE AND TEST TAP KIT SKID MOUNTING 220V, 50HZ, 1Ø

PRESSURE GAGES AND TEST TAPS

INDUSTRIAL GRADE WATER SOFTENERS LWTSF INDUSTRIAL SERIES

DETAILED EQUIPMENT SPECIFICATION HIGH PURITY LABORATORY WATER SYSTEM

DETAILED EQUIPMENT SPECIFICATION MRO-4 SERIES REVERSE OSMOSIS SYSTEMS

Fleck Fiberglass Section 9 Chloride Dealkalizers

TNT SERIES WATER CONDITIONERS

Clean and soft water for business needs. Commercial softening equipment. COMMERCIAL WATER SOFTENERS

SECTION 1. Fleck Fiberglass Softeners. *Shown with factory SKID & Interconnecting Plumbing

Fleck Top Mount Section 1 Fiberglass Softeners

Fleck Epoxy Lined Section 2 Steel Softeners

INSTALLATION, OPERATING AND SERVICE MANUAL

Commercial Softeners

BNT 85 /185 Valve Operation Manual

AQT-56SE ELECTRONIC SERIES PROGRAMMING MANUAL CONTROL VALVES

CLEAVER-BROOKS. SAB/Q Heavy Duty Co-Current Commercial and Industrial Water Softeners

FreezeFree TM Nitro Anti-Icing System GENERAL SPECIFICATIONS

SECTION H3 TRAYMASTER SERIES DEAERATORS

65 Series. Valve Operation Manual

IWT 565 Series Valve Operation Manual

SECTION H4 BOILERMATE DEAERATORS

Signature Series. Duplex Softener Service Manual

Technical Manual. Models: Standard Softeners High Efficiency Softeners Combination Softeners S150 S250 S250 OD S350 S550 S650 S650 OD Q850 Q850 OD

WATER SOFTENER SEMI AUTOMATIC INSTALLATION & OPERATING INSTRUCTIONS. Serial No :

Duplex Commercial Pressurizer -DCP

SAMPLE SPECIFICATIONS

BLAKE WATER SOLUTIONS U.S. NORTHEAST REGION DISTRIBUTION CATALOG REV 09/09

Series 774 Automatic Skid Package

MASTER. Water Conditioning Corp. Installation and Operation Manual. MCA Combination Series Residential Units

Installation and Operations Manual

Water Specialist 1 Control Valve Series Model: WS1CS 1.25 Control Valve Series Model: WS1.25CS

TECHNICAL SPECIFICATIONS

AQT-275 SERIES SERVICE MANUAL CONTROL VALVES

DCS7 Water Softener - Product Manual

MGTE Series 1 1/2 Metered & Time Clock

Water Specialist CI Control Valve Programming and Cover Drawing Manual

or OWNER S MANUAL MODEL R

AMERICAN RECIRCULATING SAND FILTER SYSTEMS

AQT-56 POWERFLO SERIES SERVICE MANUAL CONTROL VALVES

OPERATION AND MAINTENANCE MANUAL PF-20 Series. Permanent Media Filters PUROFLUX FILTRATION AND CONTROL SYSTEMS

Plastic Valve Nest Epoxy Lined Section 7 Steel Filters - 18 thru 48

Rayne Guardian Water Conditioner This manual contains information on setting the controller and normal operating maintenance required by the owner

Installation and Operation Manual

ProFloSE. Downflow Brining Service Manual. IMPORTANT: Fill in pertinent information on page 2 for future reference.

WATER SOFTENER SERIES DAY TIMER INSTALLATION & OPERATING INSTRUCTIONS. Serial No :

ROGERS MACHINERY COMPANY, INC

HORIZONTAL BLADDER TANKS

FLOOD PROTECTION SHUT DOWN VALVE (3 and smaller)

P/N: (Rev. G 1/19/10)

GLYCOL FEED SYSTEMS OPERATION & MAINTENANCE MANUAL

VALVE. Water Treatment Controls ~~~~ SERVICEMANUAL ----

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

XFL70 FLOW RATE (LPM) Flow Rate (GPM)

September 22, 2016 To: All Contractors Re: Boiler Back-Up Fuel Tank System Renovation. Dear Sir:

Pump Specifications FL100 Series Submersible Effluent Pump

COMMERCIAL UST ADD WATER BULLETIN; ISSUE 1

Model 7000XTR. Service Manual. IMPORTANT: Fill in Pertinent Information on Page 3 for Future Reference

3200ET TIMER. Service Manual. IMPORTANT: Fill in pertinent information on page 2 for future reference.

Commercial Pressure Booster Systems

Pump Specifications FL50 Series 1/2 hp Submersible Effluent Pump

SPECIFICATIONS EFFLUENT/SUMP DUPLEX SYSTEM ZOELLER SUBMERSIBLE DEWATERING OR EFFLUENT PUMPS

Weld tabs are standard on all media tanks and screen filter housings.

6700XTR Upflow. Service Manual. IMPORTANT: Fill in Pertinent Information on Page 3 for Future Reference

General Operation. To set Time of Day. To set Time of Regeneration / Backwash

TECHNICAL SHEET AUTOTROL PERFORMA CV CONTROL VALVE - LOGIX SERIES WATER PURIFICATION VALVES - AUTOTROL

Automatic Self-Cleaning Strainer/Filter Systems

Parts List. Item # Part # # Reqd. Description

Water Specialist 1 Control Valve Series Model: WS1CI 1.25 Control Valve Series Model: WS1.25CI

SILVER COMPOSITE SERIES VALVE Manufactured After June, 2000

Automatic Self-Cleaning Strainer/Filter Systems

Logix Magnum IT and Cv Valves. Installation and Service Manual

Reverse Osmosis System

TECHNICAL DATA OBSOLETE

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY

AUTOTROL 742/762 CONTROL 255 & PERFORMA SERIES VALVES (263, 268, 268 FA)

SPECIFICATIONS EFFLUENT/SUMP SIMPLEX SYSTEM ZOELLER SUBMERSIBLE DEWATERING OR EFFLUENT PUMPS

SOLICITATION C INSTALLATION AND MAINTENANCE OF POTABLE WATER FILTRATION SYSTEMS THROUGHOUT THE STATE OF FLORIDA QUESTIONS AND ANSWER

XLE50 FLOW RATE (LPM) Flow Rate (GPM)

245 W. Roosevelt Road Building 12, Suite 83 West Chicago, IL

Commercial Water Treatment Catalog

SPECIFICATIONS SEWAGE/SUMP DUPLEX SYSTEM ZOELLER COMPANY SUBMERSIBLE SEWAGE OR DEWATERING PUMPS

Vertical Pre-Piped Bladder Tanks with Proportioner

wd-2

Pump Specifications FL60/FLH60 Series 6/10 hp Submersible Effluent Pump

Pump Specifications LE70-Series 3/4 HP Submersible Sewage Pump

SIMPLEX PREMIUM WATER SOFTENER INSTALLATION AND USER GUIDE

SECTION (15444) - DOMESTIC WATER PACKAGED BOOSTER PUMPS

NECO Pumping Systems

SOLAR HEATING SYSTEM

HYDRO ION Water softener Type: VAD CS

Pump Specifications LE70-Series 3/4 HP Submersible Sewage Pump

SECTION PUMPS GENERAL PUMPS PART RELATED DOCUMENTS

NOTE: LEH100-Series high-head pumps require a minimum application of 15' head. Do not use pump in this area use a smaller pump.

Pump Specifications FL150 Series Submersible Effluent Pump

Superior Water And Air OWNER S MANUAL Model 32-CL770 & 48-CL770

Installation and Operation Instruction Manual INSMAN-201. Industrial Multi Media Single Tank

Transcription:

5356 Hillside Avenue Indianapolis, IN 46220 P: +1 888-56-Water (569-2837) F: +1 317-255-4727 info@nancrede.com www.nancrede.com DETAILED EQUIPMENT SPECIFICATION MDAS SERIES DEALKALIZERS 1.0 SCOPE 1.1 Provide as indicated a factory assembled vertical pressure type chloride cycle dealkalizer system shipped with manifold piping attached to the resin tank for ease of installation and start up. The system shall be of an approved design as fabricated by a manufacturer regularly engaged in the production of water treatment equipment. All equipment and material shall be supplied in compliance with the specifications as intended for a complete and operational system. 1.2 Qualified manufacturers of water treatment equipment of the type specified are Marlo, Inc. or engineer s approval equal. 2.0 GENERAL DESCRIPTION 2.1 The system, in compliance with equipment specifications, is described as an automatic (single) (parallel twin) (alternating twin) (parallel triple) (alternating triple) water dealkalizer system meeting the performance and design data requirements as hereinafter specified. 2.2 The system specifications are based on Marlo Model MDAS-. 3.0 PERFORMANCE & DESIGN DATA 3.1 INFLUENT WATER ANALYSIS Total Hardness grain/gal (ppm) as CaCO 3 (soft water feed required) Total Alkalinity grain/gal (ppm) as CaCO 3 Total Sulfate grain/gal (ppm) as CaCO 3 Total Nitrate grain/gal (ppm) as CaCO 3 Total Chloride grain/gal (ppm) as CaCO 3 Total Dissolved Solids (TDS) grain/gal (ppm) as CaCO 3 ph 3.2 EFFLUENT WATER QUALITY 90% Alkalinity Reduction 3.3 DESIGN PARAMETERS Continuous System Flow & Pressure Drop GPM @ psi Peak System Flow & Pressure Drop GPM @ psi Daily Water Usage Gallons/Day Daily Hours of Water Demand Hours/Day Operating Temperature Range F Maximum Operating Pressure Range (System) PSIG Electrical Requirements V Hz 1

3.3 EQUIPMENT SCHEDULE Resin Tanks Qty. Dia. in. SideShell in. Service Valves Size in. Type. Exchange Resin Qty. cu. ft. Brine Maker Qty. Dia. in. Height in. Salt Storage lbs. Regeneration Type (Time clock) (Metered) Water Meter (s) Qty Size in. Type. 4.0 EQUIPMENT 4.1 Tank Dealkalizer tank(s) shall be of welded construction of tank-quality carbon steel. The tank(s) shall have threaded openings for pipe connections and an 11 x 15 manhole in the top head (for tanks 30 diameter and smaller; two 4 x 6 handholes shall be provided in the top head and lower side shell). The tank(s) shall be rated for 100 psig working pressure and 150 psig test pressure. Support legs shall be the strap-type permanently welded to the lower tank head. The tank(s) shall be provided with a cold-set epoxy internal lining with a minimum of 10 12 mils DFT and a rust resistant prime coat external coating 2 3 mils DFT.. A minimum freeboard of 50% shall be provided for backwash expansion above the normal ion exchange resin bed level. 4.2 Tank Option Provide pressure vessel in accordance with ASME Section VIII. Working pressure to be 100, 125 or 150 pounds, hydrotested to 1.3 times the working pressure, and stamped and certified. 4.3 Tank Option Provide safety blue epoxy finish paint 6 8 mils DFT over exterior tank and valve surfaces. 4.4 Upper Distributor The upper distribution system shall be a single point baffle constructed of Schedule-40 galvanized steel pipe and fittings. 4.5 Lower Distributor The lower distributor system shall be of the hub and radial type design, constructed of PVC with slotted full flow non-clogging replaceable ABS strainers and covered with a subfill of 1/8 x 1/16 washed gravel. 4.6 Main Operating Valves The main operating valves shall be a nest of individual diaphragm valves. The valves shall have cast iron bodies, Buna-N diaphragm and stainless steel and brass internal parts. The valves shall be slow opening and closing, and free of water hammer. There shall be no contact of dissimilar metals within the valves and no special tools shall be required to services the valves. Valves can be operated either hydraulically or pneumatically. 4.7 Flow Control An automatic backwash control shall be provided to maintain a proper backwash and fast flush flows over wide variations of operating pressure. Controller shall contain no moving parts, and require no filed adjustment. 4.8 Piping and Fittings The main operating valves and manifold piping shall be factory assembled and shipped attached to the resin tank for ease of installation and start-up. Piping shall be Scheduled 40 galvanized steel. Galvanized fittings shall be standard Class 150 threaded malleable cast iron. 4.9 Exchange Resin The ion exchange resin shall be virgin high capacity strongly basic, anion type stable over the entire ph range with high regeneration efficiency and low susceptibility to organic fouling. 2

Each cubic foot of resin shall be capable of removing 10,000 grains of total exchangeable anions as calcium carbonate when regenerated with 5 lbs. of salt and 0.33 lbs. of caustic. 4.10 Control System A NEMA 12 rated, factory mounted and wired electrical enclosure with all timing and sequencing controls for each dealkalizer shall be manufactured and provided by the same vendor providing the water treatment hardware. The controls shall include an automatic regeneration timer having the capability of providing site adjustable regeneration steps of backwash, brine injection, brine displacement, flush and return to service. Indicator lights on the panel door shall display the current status of the system. A multi-ported pilot control stager shall be factory wired and pre-tubed to automatically pressure activate the main operating valves through the steps of regeneration. An indicator on the stager indicates the cycle of operation at all times. Complete function and control of all regeneration steps can be performed manually in the event of a power failure. 5.0 REGENERATION SYSTEM 5.1 Provide a complete regeneration system including all control valves, injector assemblies, combination brine measuring and salt storage tank, caustic feed system and controls as hereinafter specified for operation with the dealkalizer equipment. 5.2 Provide a single brine measuring and dry salt storage tank with salt platform. Size tank for at least four (4) regenerations at full salting. Brine dosage shall be adjusted in the field without piping revision. Brine tank with cover, shall be rotationally molded of polyethylene, be free of seams and have a wall thickness of 3/8. The brine tank shall be equipped with a float operated, plastic fitted, field serviceable brine valve for automatic control of brine withdrawal and fresh water refill. The brine valve shall provide positive shut-off to prevent air from entering the system. High purity evaporated pellet type or solar salt is recommended. 5.3 Provide an automatic chemical feed system to inject a small amount of caustic into the diluted brine solution during the brine draw period. Caustic assisted regeneration will remove carbon dioxide from the water and maximize capacity. The system shall consist of a caustic pump, portable pump stand, foot valve, suction and discharge tubing and controls. The caustic pump shall be a positive displacement diaphragm metering pump that is infinitely adjustable from 0 to 100% of the capacity range. Ball check valves on the suction and discharge will insure metering accuracy. The pump motor shall operate on 120 volt, 60 Hz, single phase electrical power. 6.0 REGENERATION INITIATION OPTIONS (Choose One) 6.1 Time Clock The 12-Day electrical time clock controller shall be fully adjustable to initiate regeneration at any hour of the day and any day of the week. 6.2 MF-ET Automatic Reset Meter (Single Tank) The dealkalizer shall be equipped with a single, impeller type water meter in the outlet piping. When the user specified volume is reached, the meter register will send a 120 volt signal to the control system that will direct the dealkalizer to begin regeneration immediately or delayed to a user set time. Meter register shall be mounted in a NEMA-3R environmental enclosure and have digital display of continuous flow rate and volume totalization. 3

6.3 MF-ET Automatic Reset Meter (Twin Alternating) The twin dealkalizer shall be equipped with a single, impeller type water meter in the common outlet header. When the user specified volume is reached, the meter register will send a 120 volt signal to an alternator stager that will direct the dealkalizer presently on-line to begin regeneration immediately while placing the stand-by dealkalizer into service mode. System shall produce a continuous supply of soft water. Meter register shall be mounted in a NEMA-3R environmental enclosure and have digital display of continuous flow rate and volume totalization. 6.4 MX Electronic Programmable Controller The system shall consist of (two) or (three) media tanks each having a dedicated paddle wheel type flow sensor in the dealkalizer outlet piping and operate in either of these user selected modes: Alternating One (1) tank will be in standby or regeneration and one (1) or two (2) media tanks will be on-line. At a user-specified volume the standby tank will go on-line and the exhausted tank will go into regeneration. After regeneration this tank will go into standby until its rotation to go back on-line. Parallel-All tanks are on-line simultaneously. As each media tank s user specified volume is reached it shall immediately be taken off-line, regenerated and placed immediately back on-line. Additive Flow-One (1) tank, designated as the primary, will remain on-line at all times. Variation of treated water flow demand shall automatically cause one additional media tank (up to two additional media tanks) to change status from standby to on-line and back to standby as needed. When the primary media tank regenerates, the next media tank in sequence shall become the primary. As each tank user set volume is reached, it will immediately be taken off-line, regenerated and placed immediately back on-line or standby depending on treated water flow demand. The controller shall be capable of continuously determining the exhaustion rate of each media tank thus automatically avoiding the possibility of a simultaneous regeneration attempt. Simultaneous regenerations are not possible. The exchange capacity of each dealkalizer can be the same or different. Flow rate or peak flow rate indication shall be continuously displayed for each unit. The continuous flow range is 0 999 flow units per minute (gallons, cu-ft., liters, cu-m, etc.). Cumulative volume totalization to eight (8) digits shall be continuously displayed for each unit. 7.0 SKID MOUNT, PREPIPE AND PREWIRE OPTION The dealkalizer tanks shall be skid mounted on a structural carbon steel skid. The skid shall be crossbraced with channel or angle iron. All steel surfaces shall be finish coated to match exterior of dealkalizer tanks. All interconnecting piping shall be the same material as the valve nest manifold piping and shall be assembled by the manufacturer. This shall included inlet and outlet bronze isolation valves for each tank and a bronze system bypass valve. Inlet, outlet and drain headers shall be provided and terminated at the skid edge. All piping shall be suitable supported by channel supports anchored to the skid. Electric wiring, where applicable, shall be complete between all inter unit controls and require only a single power source connection. The inter unit wiring shall be contained in waterproof conduit. All inter-tank hydraulic or pneumatic tubing shall be installed as part of the skid package. The dealkalizer tanks are to be bolted to the skid. Permanent attachment, or welding, will not be acceptable. The entire skid mounted system shall be leak and electrically tested as a unit by the manufacturer before shipment. 8.0 ACCESSORIES 4

8.1 Water test kits for hardness. 8.2 Water test kits for alkalinity. 8.3 Pressure Gauges for raw water inlet and treated water outlet 8.4 Sampling Cocks for raw water inlet and treated water outlet. 9.0 INSTRUCTIONS A complete set of installation, operating and maintenance shall be provided. 10.0 FIELD SERVICE The services of a factory authorized service representative shall be made available to supervise, inspect and provide operator training as required for initial start-up and system operation. 11.0 GUARANTEES Attrition loss of mineral is guaranteed not to exceed 3% per year for a period of three (3) years. All mechanical and electrical equipment is guaranteed for one (1) year against any defects in workmanship or materials. Any part proving defective shall be replaced or repaired within this period at manufacturer s option. The manufacturer guarantees that under actual operating conditions the resin shall not be washed out of the system during the service run or backwashing period; and that the turbidity and color of the effluent, by reason of passing through the dealkalizer system, shall not be greater than the incoming water; and that the underdrain system, gravel and minerals shall not become fouled, either with turbidity or by dirt, rust or scale from the dealkalizer system while operating as noted in manufacturer s instructions. 5