TECHNICAL GUIDE. COOLING & HEAT PUMP MODELS: F2RP024 THRU Hz SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS

Similar documents
TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS DESCRIPTION FEATURES YTG-A-0806

STELLAR 2000 SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS DESCRIPTION FEATURES MODELS: AHR18 THRU 60* WARRANTY

TECHNICAL GUIDE SINGLE PIECE STANDARD ECM AIR HANDLERS. DESCRIPTION

DESCRIPTION FEATURES

TECHNICAL GUIDE SINGLE PIECE STANDARD ECM AIR HANDLERS. DESCRIPTION FEATURE

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS DESCRIPTION MODELS: AHP18 THRU 60 AND SHP48 THRU 60 FEATURES

SUBMITTAL DATA SHEET FEATURES. SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15, 20 & 25 TONS MODELS: J07 thru 25NC, 2-PIPE J10 thru 20ND, 4-PIPE

TECHNICAL GUIDE ADD - ON COILS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: GHD, GFD, GFA, GNA, GUA & GHA CFM 2-5 TON COILS

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS DESCRIPTION FEATURES MODELS: AHX SERIES YTG-A-0409

Modular Variable Speed Air Handlers

DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS

TECHNICAL GUIDE SINGLE PIECE VARIABLE SPEED AIR HANDLERS. DESCRIPTION FEATURE

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES EER 8.5 ARI RATINGS* K2ES120A25 10 NOMINAL TONS WITH TWO 5 TON CIRCUITS

Product Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES

TECHNICAL GUIDE MODELS: MA MODULAR AIR HANDLERS FOR USE WITH SPLIT SYSTEM COOLING & HEAT PUMP DESCRIPTION FEATURES

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

Product Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES

ARPF. Air Handler with Painted Cabinet. 1½ to 5 Tons Multi-Position,

TECHNICAL GUIDE ADD - ON COILS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS DESCRIPTION MODELS: MC, PC, FC, HD, UC CFM 1.


HMG Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Air Handler. 13 SEER Residential System 18,000-60,000 Btuh (Heat Pump & Air Conditioner)

N1VS VARIABLE SPEED AIR HANDLERS

Product Data FFMA BASE SERIES FAN COIL SIZES 018 TO 037 FEATURES

AIR HANDLERS RBHC- SERIES HEAT PUMP AIR HANDLERS AND FAN COIL UNIT

HMG*T TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Air Handler Residential System 18,000-60,000 Btuh (Heat Pump & Air Conditioner)

MB6(B,E,V)M Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Modular Indoor Blower 13+ SEER Residential System. Additional MB6EM Features:

DESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System

12 CB30M SERIES UNITS INCLUDING ECB29 ELECTRIC HEAT

AIR HANDLERS RBHK- SERIES HEAT PUMP AIR HANDLERS AND FAN COIL UNIT

B6BMMX Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Air Handler Residential System 18,000-60,000 Btuh (Heat Pump & Air Conditioner)

TECHNICAL GUIDE GENERAL HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AND WATER COOLED AIR CONDITIONERS

ELECTRIC HEAT AIR HANDLERS

APARTMENT FAN COILS AVAILABLE WITH FACTORY INSTALLED 5, 7, & 11 kw ELECTRIC HEAT, or NO HEAT R -22 SYSTEMS

DESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System

BCE5E PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER APPLICATION INSTALLATION CABINET COILS COMPONENTS WARRANTY

PACKAGE GAS ELECTRIC UNITS

AIR HANDLERS UBHN- SERIES AIR HANDLERS AND FAN COIL UNIT PRELIMINARY NOT FOR DISTRIBUTION

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS FEATURES DESCRIPTION. H5CE090 & H3CE AND 10 NOMINAL TONS (World 50HZ)

Rheem High Efficiency Air Handler

CFM (L/s) Min Max 450 (212) 600 (283) 750 (354) Dimensions H x W x D in. (mm) 675 (319) 36 1/2 x 20 1/2 x (425)

B6EMMX Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

FORM NO. HSC-543 AIR HANDLERS

PACKAGE HEAT PUMP UNITS

DCC Commercial. 3- to 6-Ton Packaged Air Conditioner. Cooling Capacity: 34,600 71,000 BTU/h

AIR HANDLERS AIR HANDLERS. RHPN- SERIES 18 SEER featuring Earth-Friendly R-410A Refrigerant. Features

Modular Variable Speed Air Handlers

TECHNICAL MANUAL *PG10

AIR HANDLERS AIR HANDLERS. UHKA- SERIES featuring R-22 Refrigerant UHKL- SERIES featuring Earth-Friendly R-410A Refrigerant.

TECHNICAL GUIDE SINGLE PIECE FAN COIL/AIR HANDLER FOR USE WITH SPLIT SYSTEM COOLING ONLY ELECTRIC OR HYDRONIC HEAT AND HEAT PUMPS

TECHNICAL GUIDE LISTED TECHNICAL GUIDE SPLIT-SYSTEM AIR CONDITIONERS 13 SEER R-410A 3 PHASE MODELS: TCGD30 THRU 60 (2.5 THRU 5 NOMINAL TONS)

TECHNICAL GUIDE 80 AFUE DOWNFLOW GAS-FIRED FURNACES MODELS: G8T-DN DESCRIPTION WARRANTY FEATURES Rev. B (0303)

Product Data. FF1E Base Series Fan Coil Sizes 018 thru 036 FEATURES

CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) 1800Aǂ 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

1. Air Handler Features Page Physical data Page Available kits Page Model nomenclature Page 5

Rheem High Efficiency Air Handler

ELITE SERIES R-410A Ready - Multi-Position

Q5RD Series Single Packaged Heat Pump, Single Phase

CFM (L/s) Dimensions. Filter Size in. Ship Wt. H x W x D in. (mm) 1800A 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

Product Data. Convertible Air Handlers 1 1/2 5 Ton D-EN. September 2016

DSC Commercial. 3-5 Ton Packaged Air Conditioner 14 SEER / Up to 12.0 EER. Cooling Capacity: 35,000 58,000 BTU/h

UARDIAN TECHNICAL GUIDE MODELS: GCGD18 THRU 60

CFM (L/s) Dimensions. Filter Size Ship Wt. HxWxDin.(mm) 1800Aǂ 1-1/2 18, (212) 675 (319) 36-1/2 x 20-1/2 x (45) FMA4P (928 x 521 x 381)

GQ5RD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase 13 SEER, R-410A, WARRANTY

HEAT PUMP AIR HANDLERS AND FAN COIL UNIT

DSC Commercial. 3-5 Ton Packaged Air Conditioner 14 SEER / Up to 12.0 EER. Cooling Capacity: 35,000 58,000 BTU/h

DIRECT-DRIVE BLOWER FAN COIL AIR CONDITIONER ENGINEERING GUIDE

VHIA High-Static Ducted Indoor Units - 60HZ

TECHNICAL GUIDE. Echelon MODELS: FC8S GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE DESCRIPTION WARRANTY FEATURES

Product Data. CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) FMA4P1800AL 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

Ruud High Efficiency Air Handler

TECHNICAL GUIDE MODELS: G8T-UP 80 AFUE UPFLOW/HORIZONTAL GAS-FIRED FURNACES DESCRIPTION WARRANTY FEATURES Rev.

B6VMMX Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Air Handler with TXV 18,000-60,000 Btuh (Heat Pump & Air Conditioner)

TECHNICAL GUIDE AFFINITY MODELS: PS8 GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE DESCRIPTION WARRANTY FEATURES

DZ13SA. Split-System heat pump. Cooling Capacity: 17,400-55,000 BTU/h Heating Capacity: 15,200-59,000 BTU/h

TECHNICAL GUIDE DESCRIPTION MODELS: D4HH 024 THRU 180 HORIZONTAL FEATURES SINGLE PACKAGE AIR CONDITIONERS HORIZONTAL INDOOR & CONDENSER AIR FLOW

AIR HANDLERS RBHM- SERIES AIR HANDLERS AND FAN COIL UNIT

Rheem Air Handlers. RHLP- Standard Efficiency X-13 (ECM) Motor

ASZ13 13 SEER / R-410A. Heating Capacity: 18,000-59,000 BTU/h

APARTMENT FAN COILS AVAILABLE WITH FACTORY INSTALLED 5, 7, & 11 kw ELECTRIC HEAT, or NO HEAT R-410A and R-22 SYSTEMS

SUNLINE 2000 (WORLD 50 HZ)

B Series Multi-Position & Hydronic Air Handlers Electric or Hot Water Heat, with available Variable-Speed High Efficiency ECM Motor

GSZ13. Energy-Efficient Split System Heat Pump 1½ to 5 Tons. Cooling Capacity: 17,400 to 57,000 BTU/h Heating Capacity: 17,000 to 58,000 BTU/h

DSZC16. Split System Heat Pump Up to 16 SEER & 9.5 HSPF. Cooling Capacity: 24,000-60,000 BTU/h Heating Capacity: 24,000-60,000 BTU/h

Product Data. Convertible Air Handlers 1 1/2 5Ton

DCH Commercial. 3- to 6-Ton, Three-Phase Packaged Heat Pumps. Cooling Capacity: 35,000 70,000 BTU/h Heating Capacity: 34,600 70,000 BTU/h

DESCRIPTION FEATURES

TECHNICAL GUIDE MODELS: MV MODULAR VARIABLE SPEED AIR HANDLERS FOR USE WITH SPLIT SYSTEM COOLING & HEAT PUMP DESCRIPTION FEATURES

MERIT Series R-410A - Upflow / Horizontal - Variable Speed

Product Data PF1MNC DIRECT EXPANSION FAN COIL SIZES 018 THRU 061 FEATURES/BENEFITS AVAILABLE SIZES: 18,000 to 61,000 BTU unit ELECTRICAL RANGE:

Product Data. Convertible Air Handlers 1 1/2 5 Ton B-EN. August 2015

TECHNICAL GUIDE MODELS: P4DN 80 AFUE DOWNFLOW GAS-FIRED FURNACES DESCRIPTION. WARRANTY 20-year limited warranty on the heat exchanger.

A I R H A N D L E R S CB26UH-R. MERIT Series R-22 - Upflow / Horizontal P R O D U C T S P E C I F I C AT I O N S

48CWA2-00 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 48,000 BTUH

GQ3RD Series. Single Packaged Heat Pump, Single Phase TECHNICAL SPECIFICATIONS

Advance Information SPLIT SYSTEM HEAT PUMP 10 SEER. ERA 018 thru thru 5 NOMINAL TONS DESCRIPTION FEATURES

TECHNICAL GUIDE LISTED SPLIT-SYSTEM HEAT PUMPS 13 SEER R-410A MODELS: THGD30 THRU 60 (2.5 THRU 5 NOMINAL TONS - 3 PHASE)

PA95 12 SEER FEATURES 2 THRU 4 TON SINGLE PACKAGE

Product Data. FF1E Base Series Fan Coil Sizes 018 thru 036 FEATURES

Product Data. Convertible Air Handlers 1 1/2 5Ton

Transcription:

036-21624-001 ev. A (1104) TECHNICAL GUIDE COOLING & HEAT PUMP S: F2P024 THU 060 50 Hz SINGLE PIECE AI HANDLES FO USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at www.york.com for the most up-to-date technical information. DESCIPTION This fan coil unit provides the flexibility for installation in any upflow or horizontal application. These versatile models may be used for split-system cooling or heat pump operation. Compact cabinets along with return air options in both the upflow and horizontal positions allow this unit to fit into tight spaces such as attics, crawl spaces, and closets. NOTE: For matching condensing units and performance data, refer to condenser technical guides. FEATUES CABINET -The compact and sturdy cabinet is protected with a durable, attractive finish to prevent rust. The cabinet is also insulated to prevent cabinet sweating. BLOWES - Blowers are sized to circulate air both quietly and efficiently. The direct-drive, 3-speed motors provide a selection of air volume to match any application. Motor speeds may be selected via quick connect terminal at the motor. Slide-out blower/motor assemblies provide for easy servicing. COILS - Using the latest in heat transfer technology, the rifled tube coil/aluminum fin coils produce high performance ratings and provide long lasting quality. The coils are capable of bottom return air in the upflow position, and right or left end return air in the horizontal position. ELECTIC HEATES - s providing up to 25kw of heat are available as field installed accessories. Electric heaters are available in both single and three phase. EASY INSTALLATION - These fan coil units are designed to provide the lowest total installation cost. Accessible color coded control wiring, top and side power wiring knockouts, easy to install drain connections and electric heaters all combine to minimize installed cost on every job. CONTOL BOAD - The control board is equipped with low voltage terminal strips for easy installation. The control board is also equipped with plug-in receptacles for the auxiliary heaters. FO DISTIBUTION USE ONLY - NOT TO BE USED AT POINT OF ETAIL SALE

036-21624-001 ev. A (1104) SHIPPING BACKET* EMOVE PIO TO INSTALLATION (2 SCEWS) J 10-3/8 F ALL DIMENSIONS AE IN INCHES. THEY AE SUBJECT TO CHANGE WITHOUT NOTICE. CETIFIED DIMENSIONS WILL BE POVIDED UPON EQUEST. 3/4 F 4-1/8 DAIN CONNECTIONS FO HOIZONTAL APPLICATIONS K 10-3/8 7-1/2 TOP VIEW (ALL S) 4 A =DAIN PAN FOOTPINT VAPO OPENING LIQUID OPENING D 3/4 MAX. FILTE LENGTH (21 INCHES) MAX. FILTE WIDTH (B MINUS 1-1/2 INCHES) EA 3/4 2 DAIN CONNECTIONS FO UPFLOW APPLICATIONS B C FILTE ACCESS E 18-3/8 BOTTOM VIEW DIMENSIONS Dimensions Wiring K.O.s 1 efrigerant Connections Line Size A B C J K D E F Liquid Vapor Height Width Depth Power Control F2P024(N,H)93 40-3/4 18 14-7/8 16-1/2 7/8 (1/2) 5/8 12-1/8 F2P036(N,H)93 40-3/4 21-1/2 18-3/8 20 1-3/8 (1) 3/4 22 7/8 (1/2) 3/8 F2FP048(N,H)93 50-3/4 24 20-7/8 22-1/2 7/8 (1/2) 7/8 17-3/8 1-3/8 (1) F2FP060(N,H)93 50-3/4 24 20-7/8 27-1/2 1-23/32 (1-1/4) 7/8 1. Actual conduit size is shown in parenthesis. COIL DATA Application efrigeration STD. Face Fins Coil Deep Orifice Area Per Slabe Size Conn. Type ows Size (Sq. Ft.) Inch H W F2P024(N,H)93 A/C & HP 61 3.40 2 14 14 17.5 F2P036(N,H)93 A/C & H/P 75 3.40 3 12 14 17.5 Sweat F2FP048(N,H)93 A/C & H/P 84 5.35 3 12 22 17.5 F2FP060(N,H)93 A/C & H/P 90 5.83 3 12 24 17.5 Tube Geometry Tube Dia. Fin. Type Metering Device 1x.886 3/8 Enhanced Orifice 2 Unitary Products Group

036-21624-001 ev. A (1104) COOLING CAPACITY BLOWE ATED CFM F2P024(N,H)93 830/1411 F2P036(N,H)93 1250/2124 F2P048(N,H)93 1600/2720 1850/3145 ENTEING AI F (Dry/Wet Bulb) ENTEING AI C (Dry/Wet Bulb) UPFLOW / HOIZONTAL POSITIONS ONLY MBH @ Evaporator Temperature and Corresponding Pressure C / PA ( F / PSIG) 1.7/427 4.4/476 7.2/528 10.0/584 35/61.5 40/68.5 45/76.0 50/84.0 85/72 29/22 36.3 33.0 29.5 25.6 80/67 27/19 33.4 30.2 26.7 23.1 75/62 24/17 27.4 24.3 21.0 17.7 70/57 21/14 22.2 19.3 16.2 12.6 85/72 29/22 53.4 48.6 43.4 38.3 80/67 27/19 42.8 37.8 33.1 28.2 75/62 24/17 33.4 28.1 30.6 22.8 70/57 21/14 28.7 26.5 24.5 22.8 85/72 29/22 100.5 86.4 72.0 56.8 80/67 27/19 80.4 67.5 55.0 42.1 75/62 24/17 62.7 49.9 40.7 34.0 70/57 21/14 53.9 47.2 40.7 34.0 85/72 29/22 119.9 101.0 82.0 62.2 80/67 27/19 96.0 79.2 62.6 45.8 75/62 24/17 74.8 58.6 46.2 37.0 70/57 21/14 64.3 55.4 46.2 37.0 ACCESSOIES efer to Price Manual for specific model numbers. VETICAL SUSPENSION KIT - The suspension kit is designed to be used with all sizes of blowers whenever the application requires vertical suspension of the unit. ELECTIC HEATES - s shown under Electrical Data include sequencers and temperature dual limit switches for safe, efficient operation. Circuit breakers are provided where shown. BOLT-ON THEMAL EXPANSION VALVE - TXV kits are available for enhanced efficiency. HOIZONTAL DAIN PAN - The drain pan kit is designed for field conversion to Horizontal left or right applications. Also available as factory installed option (horizontal right only). LIMITATIONS These units must be wired and installed in accordance with all national and local safety codes. Voltage limits are as follows: Normal Operating voltage ange 1 198-250 1. Utilization range A in accordance with AI Std. 110. Air flow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units: Entering Air Temperature Limits Wet Bulb Temp. C/ºF Dry Bulb Temp. C/ºF Min. Max. Min. Max. 14/57 22/72 18/65 35/95 Unitary Products Group 3

036-21624-001 ev. A (1104) EXTENDED AI FLOW DATA 1 F2P024(N,H)93 F2P036(N,H)93 F2P048(N,H)93 BLOWE MOTO SPEED 240 Volts - 50 Hz CFM or M 3 /H @ External Static Pressure - IWG or Pa 0.10 25 0.20 50 0.30 75 0.40 100 0.50 1.25 CFM M 3 /H CFM M 3 /H CFM M 3 /H CFM M 3 /H CFM M 3 /H High 950 1615 910 1547 865 1471 835 1420 775 1318 Med 845 1437 815 1386 785 1335 745 1267 705 1199 Low 650 1105 630 1071 605 1029 575 978 540 918 High - - 1310 2227 1250 2125 1175 1998 1120 1904 Med 1200 2040 1150 1955 1100 1870 1040 1768 985 1675 Low 1060 1802 1015 1726 970 1649 925 1573 860 1462 High 1855 3154 1795 3052 1730 2941 1670 2839 1605 2729 Med 1685 2865 1630 2771 1575 2675 1520 2584 1470 2499 Low 1465 2491 1435 2440 1405 2389 1370 2329 1335 2270 High 2285 3885 2195 3732 2105 3579 2015 3426 1920 3264 Med 2125 3613 2020 3434 1910 3247 1805 3069 1705 2899 Low 1655 2814 1605 2729 1550 2635 1500 2550 1450 2465 1. Includes eturn Air Filter and Largest Electric Heater. EXTENDED AI FLOW DATA 1 F2P024(N,H)93 F2P036(N,H)93 F2P048(N,H)93 BLOWE MOTO SPEED 220 Volts - 50 Hz CFM or M 3 /H @ External Static Pressure - IWG or Pa 0.10 25 0.20 50 0.30 75 0.40 100 0.50 1.25 CFM M 3 /H CFM M 3 /H CFM M 3 /H CFM M 3 /H CFM M 3 /H High 855 1454 819 1392 779 1324 752 1278 698 1187 Med 760 1292 733 1246 706 1200 670 1139 634 1078 Low 585 994.5 567 937 545 927 518 881 486 826 High 1235 2100 1179 2004 1125 1913 1058 1799 1008 1714 Med 1080 1836 1035 1760 990 1683 936 1591 887 1508 Low 954 1622 914 1554 873 1484 833 1416 774 1319 High 1670 2839 1616 2 747 1557 2647 1503 2555 1445 2457 Med 1517 2579 1467 2494 1418 2411 1368 2326 1323 2250 Low 1319 2242 1292 2196 1265 2151 1233 2096 1202 2043 High 2057 3497 1976 3359 1895 3222 1814 3184 1728 2938 Med 1913 3252 1818 3091 1719 2922 1625 2763 1535 2610 Low 1490 2533 1445 2457 1395 2372 1350 2295 1305 2219 1. Includes eturn Air Filter and Largest Electric Heater. APPLICATION FACTOS-ATED CFM VS. ACTUAL CFM % Of ated Airflow 80% 90% ATED CFM 110% 120% CAPACITY FACTO 0.96 0.98 1.00 1.02 1.03 4 Unitary Products Group

Physical and Electrical Data 036-21624-001 ev. A (1104) F2P024(N,H)93 F2P036(N,H)93 F2P048(N,H)93 Blower - Diameter x Width, MM (IN.) 254 x 152 (10 x 6) 254 x 2036 (10 x 8) 279 x 254 (11 x 10) 279 x 254 (11 x 10) Motor Voltage AMPS kw (HP) 0.19 (1/4) 0.37 (1/2) 0.37 (1/2) 0.56 (3/4) Nominal PM 1075 1350 1350 1065 220/240 (198 Min. - 250 Max.) Full Load 2.1 2.3 2.4 5.7 Locked otor 5.4 5.4 4.9 7.7 Filter 1 Type Disposable/Permanent Size 16x20x1 20x21x1 22x21x1 22x21x1 Shipping/Operating Weight Kg. (lbs.) 42/44 (93/98) 49/52 (109/115) 64/67 (142/148) 68/70 (149/155) 1. Field Supplied. ELECTICAL DATA - Cooling Only with No Heat Power Kit (1 & 3 φ) Total Motor Amps Maximum Minimum Wire 220V 240V O.C.P.D. Size A.W.G. F2P024(N,H)93 2.9 2.6 15 14 F2P036(N,H)93 3.1 2.9 15 14 F2P048(N,H)93 3.3 3.0 15 14 7.8 7.1 15 14 ELECTICAL DATA - 1φ - 220/240-1-50 F2P024(N,H)93 F2P036(N,H)93 F2P048(N,H)93 Heater 1 1. 0 or 1 as follows: 0 = No Breaker, 1 = Breaker. 2. See Conversion Table below: MAX. Total Heat 2 kw Staging STATIC & MIN. CFM kw MBH W1 Only W2 Only W1 + W2 Static Tap 220V 240V 220V 240V 220V 240V 220V 240V 220V 240V 2HK*6500506B 0.5 LO 4.2 5.0 14.3 17.1 4.2 5.0 4.2 5.0 4.2 5.0 2HK*6500806B 0.5 LO 6.3 7.5 21.5 25.6 4.2 5.0 6.3 7.5 6.3 7.5 2HK*6501006B 0.5 LO 8.4 10.0 28.7 34.1 4.2 5.0 8.4 10.0 8.4 10.0 2HK*6500506B 0.5 LO 4.2 5.0 14.3 17.1 4.2 5.0 4.2 5.0 5.0 5.0 2HK*6500806B 0.5 LO 6.3 7.5 21.5 25.6 4.2 5.0 6.3 7.5 6.3 7.5 2HK*6501006B 0.5 LO 8.4 10.0 28.7 34.1 4.2 5.0 8.4 10.0 8.4 10.0 2HK16501506B 0.5 MED 12.6 15.0 43.0 51.2 4.2 5.0 8.4 10.0 12.6 15.0 2HK16501906B 0.5 HI 14.8 17.6 50.5 60.1 3.2 3.8 11.6 13.8 14.8 17.6 2HK*6500506B 0.5 LO 4.2 5.0 14.3 17.1 4.2 5.0 4.2 5.0 4.2 5.0 2HK*6500806B 0.5 LO 6.3 7.5 21.5 25.6 4.2 5.0 6.3 7.5 6.3 7.5 2HK*6501006B 0.5 LO 8.4 10.0 28.7 34.1 4.2 5.0 8.4 10.0 8.4 10.0 2HK16501506B 0.5 LO 12.6 15.0 43.0 51.2 4.2 5.0 8.4 10.0 12.6 15.0 2HK16502006B 0.5 LO 16.8 20.0 57.3 68.3 4.2 5.0 8.4 10.0 16.8 20.0 2HK16502506B 0.5 LO 21.0 25.0 71.7 85.3 4.2 5.0 12.6 15.0 21.0 25.0 2HK*6500506B 0.5 LO 4.2 5.0 14.3 17.1 4.2 5.0 4.2 5.0 4.2 5.0 2HK*6500806B 0.5 LO 6.3 7.5 21.5 25.6 4.2 5.0 6.3 7.5 6.3 7.5 2HK*6501006B 0.5 LO 8.4 10.0 28.7 34.1 4.2 5.0 8.4 10.0 8.4 10.0 2HK16501506B 0.5 LO 12.6 15.0 43.0 51.2 4.2 5.0 8.4 10.0 12.6 15.0 2HK16502006B 0.5 LO 16.8 20.0 57.3 68.3 4.2 5.0 8.4 10.0 16.8 20.0 2HK16502506B 0.5 LO 21.0 25.0 71.7 85.3 4.2 5.0 12.6 15.0 21.0 25.0 KW & MBH CONVESIONS - FO TOTAL POWE INPUT EQUIEMENT FO 208V 240V.751 OPEATION MULTIPLY TABULATED KW & MBH BY 230V 240V.918 Unitary Products Group 5

036-21624-001 ev. A (1104) ELECTICAL DATA - 1φ (SINGLE SOUCE POWE SUPPLY) - COPPE WIE Heater Field Wiring Heater 1 Amps Min. Circuit Ampacity Max. O.C.P. 2 Amps/Type 75 C Wire Size - AWG 240V 220V 240V 220V 240V 220V 240V 2HK*6500506B 20.8 26.7 28.7 30 30 10 10 F2P024(N,H)93 2HK*6500806B 31.3 38.7 41.7 40 45 8 8 2HK*6501006B 41.7 50.6 54.7 60 60 6 6 2HK*6500506B 20.8 27.0 28.9 30 30 10 10 2HK*6500806B 31.3 31.3 41.9 40 45 8 8 F2P036(N,H)93 2HK*6501006B 41.7 50.9 55.0 60 60 6 6 2HK16501506B 62.5 74.7 81.0 80 90 4 3 2HK16501906B 73.3 87.2 94.5 90 100 3 3 2HK*6500506B 20.8 27.1 29.0 30 30 10 10 2HK*6500806B 31.3 39.0 42.1 40 45 8 8 F2P048(N,H)93 2HK*6501006B 41.7 51.0 55.1 60 60 6 6 2HK16501506B 62.5 74.8 81.1 80 90 4 3 2HK16502006B 83.3 98.7 107.2 100 110 3 2 2HK16502506B 104.2 122.6 133.2 125 150 1 1/0 2HK*6500506B 20.8 31.6 33.2 35 35 8 8 2HK*6500806B 31.3 43.5 46.2 45 50 8 8 2HK*6501006B 41.7 55.5 59.2 60 60 6 6 2HK16501506B 62.5 79.3 85.3 80 90 4 3 2HK16502006B 83.3 103.2 111.3 110 215 2 1 2HK16502506B 104.2 127.1 137.3 150 150 1/0 1/0 1. 0 or 1 as follows: 0 = No Breaker, 1 = Breaker 2. OCP = Over current protection, HAC type circuit breaker or time delay fuse. ELECTICAL DATA - 1 φ (MULTI-SOUCE POWE SUPPLY) - COPPE WIE Min. Circuit Ampacity Max. Time Delay Fuse 75 C Wire Size - AWG Heater 220/240V 220/240V 220/240V 220/240V 220/240V 220/240V 220/240V 220/240V 220/240V Circuit Circuit Circuit 1st 2nd 3rd 1st 2nd 3rd 1st 2nd 3rd F2P036(N,H)93 F2P048(N,H)93 2HK16501506B 27.0/28.9 47.7/52.1-30/30 50/60-10/10 8/6-2HK16501906B 38.9/41.9 48.3/52.6-40/45 50/60-8/8 8/6-2HK16501506B 27.1/29.0 47.7/52.1-30/35 50/60-10/10 8/6-2HK16502006B 51.0/55.1 47.7/52.1-60/60 50/60-6/6 8/6-2HK16502506B 27.1/29.0 47.7/52.1 47.7/52.1 30/30 50/60 50/60 10/10 8/6 8/6 2HK16501506B 31.6/33.2 47.7/52.1-35/35 50/60-8/8 8/6-2HK16502006B 55.5/59.2 47.7/52.1-60/60 50/60-6/6 8/6-2HK16502506B 31.6/33.2 47.7/52.1 47.7/52.1 35/35 50/60 50/60 8/8 8/6 8/6 ELECTICAL DATA - 3 φ - 220/240-3-50 Total Heat 1 Total Heat 1 KW Staging 2 Heater kw kw MBH W1 Only W2 Only W1 + W2 220V 240V 220V 240V 220V 240V 220V 240V 220V 240V 220V 240V F2P024(N,H)93 2HK06501025B 0.5 LO 8.4 10.0 28.7 34.1 4.2 5.0 8.4 10.0 8.4 10.0 F2P036(N,H)93 F2P048(N,H)93 2HK06501025B 0.5 LO 8.4 10.0 28.7 34.1 4.2 5.0 8.4 10.0 8.4 10.0 2HK06501525B 0.5 MED 12.6 15.0 43.0 51.2 4.2 5.0 8.4 10.0 12.6 15.0 2HK06501025B 0.5 LO 8.4 10.0 28.7 34.1 4.2 5.0 8.4 10.0 8.4 10.0 2HK06501525B 0.5 LO 12.6 15.0 43.0 51.2 4.2 5.0 8.4 10.0 12.6 15.0 2HK06501025B 0.5 LO 8.4 10.0 28.7 34.1 4.2 5.0 8.4 10.0 8.4 10.0 2HK06501525B 0.5 LO 12.6 15.0 43.0 51.2 4.2 5.0 8.4 10.0 12.6 15.0 1. See Conversion Table page 6. 2. If first stage heat or 66 is connected to W 1, otherwise refer to Table at bottom of page11. 6 Unitary Products Group

036-21624-001 ev. A (1104) ELECTICAL DATA - 3 φ - (SINGLE SOUCE POWESUPPLY) - COPPE WIE Field Wiring Heater s Min. Circuit Ampacity Max. O.C.P. 1 Amps/Type 75 C Wire Size - AWG 220V 240V 220V 240V 220V 240V F2P024(N,H)93 2HK06501025B 43.8 47.4 45 50 8 8 F2P036(N,H)93 2HK06501025B 44.1 47.6 45 50 8 8 2HK06501525B 44.1 47.6 45 50 8 8 F2P048(N,H)93 2HK06501025B 44.2 47.7 45 50 8 8 2HK06501525B 44.2 47.7 45 50 8 8 2HK06501025B 48.2 51.4 50 60 8 6 2HK06501525B 48.2 51.4 50 60 8 6 1. OCP = Over current protection, HAC type circuit breaker or time delay fuse. FIELD WIING CONNECTION - COOLING ONLY FIELD WIING CONNECTION - WITH HEATE KIT THEMOSTAT OUTDOO THEMOSTAT OUTDOO Y Y G G W W * FAN COIL Y G W2 W1 O C FAN COIL Y G W2 W1 O C *NOTEQUIEDON2O5KW FO KW & MBH CONVESIONS - FO TOTAL POWE INPUT EQUIEMENT 208V 240V.751 OPEATION, MULTIPLY TABULATED KW & MBH BY 230V 240V.918 **ALTENATE ELECTIC HEAT STAGING FO AUXILIAY HEAT DUING DEFOST Adjust values in Table above when used. Defrost Output (66) Heater Size (208 / 240 V) Connected To 7.5 KW 10-20KW 25KW W1 3.8 3.8/5 3.8/5 W2 5.6 7.5 7.5/10 11.3/15 FIELD WIING CONNECTIONS - HEAT PUMP WITH HEATE KIT - F(2,3)P/F(2,3)FP FIELD INSTALLED JUMPE THEMOSTAT O LorX CorB Y G W ** T ** E OUTDOO O X B Y W 66 **TEMINALNOTAVAILABLE ONALLTHEMOSTATS FAN COIL Y G W2 W1 O C Unitary Products Group 7

TYPICAL INSTALLATION POWEWIING TOMAIN POWESOUCE SUPPLY AI POWEWIING CONTOL WIING EFIGEANT LINES THEMOSTAT TO CONDENSATE DAIN FILTE ACCESS LOUVEED ELECTICHOTWATEHEATE (Must complywithwaterheaterinstallationinstructions) TYPICAL APPLICATIONS UPFLOW HOIZONTAL IGHTHANDAPPLICATION LEFTHANDAPPLICATION Subject to change without notice. Printed in U.S.A. 036-21624-001 ev. A (1104) Copyright by York International Corp. 2004. All rights reserved. Supersedes: 535.02-TG4YI (0600) Unitary 5005 Norman Products York OK Group Drive 73069