OPERATOR ADAPTER A21ABA Installation Instructions for Allen Bradley Bulletin 1494F Disconnect Switches And Bulletin 1494D Circuit Breaker Operating Mechanisms (For parts list, see page 2) For floor mounted enclosures with disconnect on the right flange, see pages 3 7 For one through six door free standing enclosures with the disconnect on the right flange, see pages 8 12 For floor mounted enclosures with the disconnect on the centerpost, see pages 13 17 Rev. C 2018 Hoffman Enclosures Inc. PH 7634222211 nvent.com/hoffman P/N 99401943 87569084
WARNING The functions, fits, and clearances of the installation described hereon are calculated from information supplied by the manufactures of the equipment to be installed. Be certain to check the function, fits, and clearances of all equipment both before and after installation to assure that is operates properly and safely and meets all applicable codes, standards, and regulations. In the event the completed installation does not function properly or fails to meet any such codes, standards, or regulations, do not attempt to make alterations or operate the equipment. Report such facts immediately to: Hoffman Customer Service 2100 Hoffman Way Anoka, MN 55303 763 422 2211 http://hoffman.nvent.com/contact-us PARTS LIST Operator Adapter, Catalog Number A21ABA, for Allen Bradley Disconnects (Bulletin 1494F and 1494D) Item No...Part Name...Part No........ Quantity 1...Adapter Plate, A B...26248001... 1 2...Adapter Plate, A B 200 AMP...26249001...1 3...Gasket, Plate...26216011...1 4...Screw, 1/4 20x1/2 Pan Head...99401031...4 5...Door Catch...27201001...1 6...Screw, 10 32x3/8 Pan Head...99401007...2 7...Lockwasher 10 ext...99401329...2 8...Slide Arm...27204001...1 9...Threaded Rod 1/4 20x17.88....22155002...4 10...Nut 1/4 20 Hex...99401406...14 11...Lockwasher 1/4 Spring...99401318...10 12...Label (extra)...26147001...1 13...Sub Assy, Release Mechanism....26284001...1 14...Sub Assy, Release Mechanism (CPX)...26285001...1 15...Washer, Flat...22101003...2 16...Retaining Washer...27142001...1 17...Installation Instruction...99401943...1-2 - 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman 87569084
INTRODUCTION This installation instruction is for Allen Bradley Bulletin 1494F and 1494D mechanisms. These mechanisms are for disconnect switches (1494F) and circuit breakers (1494D) mounted in Hoffman two door, floor mounted, enclosures with the disconnect on the right flange. Master Door INSTALLATION STEPS Step 1 Drill and tap holes required in panel; see figure 1. Two holes are required for un fused switches; three holes for 30, 60 100 AMP fused switches, and four holes for 200 AMP fused switches. Two holes are required for operators for circuit breakers. Step 2 Install mounting plate (item 1) positioned as shown on figure 3, (item 2 for a 200 AMP switch) and plate gasket (item 3) on the inside of the enclosure behind the rectangular opening provided. Secure in place with four screws (item 4). Step 3 Install door catch (item 5) on tapped block provided on master door; see figure 3. Locate door catch vertically as shown, and secure in place with two screws (item 6) and lockwashers (item 7). Step 4 Remove and discard lock release mechanism from enclosure flange (see bottom of figure 3). Install lock release mechanism (item 13) as shown in figure 3 using the same spacer, nuts, and washers. Adjust lock release mechanism so top of door latch contacts latch stop when door is closed and door handle is fully latched. Step 5 Install Allen Bradley disconnect switch or operator for circuit breakers as follows: 1. Remove nuts and lockwashers from Allen Bradley flange plate. Discard the Allen Bradley flange plate. 2. Place operator handle into enclosure with the operating handle in the OFF position. Tilt the assembly under the flange and at the same time bring the handle through the slot provided in the mounting plate installed in step 2. 3. Secure operator handle to mounting plate with nuts and lockwashers. Fusible Disconnect Switches Only 1. Attach fuse clips provided with the fuse block adapter plate kit to the disconnect switch terminals. See Allen Bradley instructions. 2. Attach the fuse block adapter plate to the disconnect switch mounting bracket. See Allen Bradley instructions. Step 6 Attach disconnect platform and fuse block adapter plate to panel with threaded rods, lockwashers, and nuts. See figure 2. Cut threaded rods (item 9) to length required. See P dimension in table 1. Install threaded rods as shown in figure 2. Adjust threaded rods and nuts so disconnect platform is level. The ends of threaded rods should not extend above nuts on front of disconnect platform. Step 7 Install slide arm (item 8). Unhook spring from the tab on the A B locking lever. Place end of slide arm (item 8) and retaining washer (item 16) over tab, and re attach spring. Attach the bottom of slide arm (item 8) to lock release mechanism (item 13) using flat washer (item 15), lockwasher (item 11), and nut (item 10) as shown in figure 1. See step 8 for adjustment. Step 8 Adjust slide arm (item 8) and door catch (item 5) as follows: 3. Close master door. Attempt to turn ON the Allen Bradley handle. The slide arm should release the Allen Bradley operating handle just before the enclosure master door is fully latched. Adjust slide arm up or down, if required. 4. Leave the Allen Bradley handle in the ON position. Attempt to open master door. Door catch should hook on the Allen Bradley interlock to prevent the door from opening. Adjust up or down if required. 87569084 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman - 3 -
For Two Door, Floor Mounted Enclosures With Disconnect on Right Flange Figure 3-4 - 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman 87569084
For Two Door, Floor Mounted Enclosures With Disconnect on Right Flange Figure 1 87569084 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman - 5 -
For Two Door, Floor Mounted Enclosures With Disconnect on Right Flange Figure 2-6 - 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman 87569084
For Two Door, Floor Mounted Enclosure With Disconnect on Right Flange TABLE 1 Sub panel Drilling TYPE SIZE E F M For 60.12 High G For 72.12 High G For 12.12 Deep P * For 18.12 Deep P * For 24.12 Deep P 1494F 30 AMP 3.31 5.31 1.50 2.75 8.75 5.63 11.63 17.63 1494F 60 AMP 3.31 5.31 1.50 2.75 8.75 5.63 11.63 17.63 1494F 100 AMP 3.69 7.19 1.50 1494F 200 AMP 5.75 9.63.25 DO NOT INSTALL DO NOT INSTALL 6.34 3.63 9.63 15.63 5.06 3.56 9.56 15.56 1494D N4/N40 3.31 7.19 1.50 2.75 8.75 5.59 11.59 17.59 1494D N5/N55 2.88 10.88 1.39 2.06 8.06 3.59 9.59 15.59 1494D N5/N50 2.88 10.88 1.39 2.06 8.06 3.59 9.59 15.59 1494D N5/N60 2.88 10.88 1.39 DO NOT INSTALL 8.06 3.59 9.59 15.59 * The P dimensions for 24.12 inch deep enclosures are the same as for 18.12 inch deep when using the 6 inch platform. Platform can be omitted if longer threaded rods are used. TABLE 2 Extra Holes for Fusible Switches Only SWITCH SIZE FUSE CLIP Q / R 30 AMP 30A/600V H 2.81 60A/600V H 3.31 30A/600V H 3.38 100A/250V H 3.88 60 AMP 60A/600V H 3.88 100A/600V H 5.88 100A/600V J 2.69 100A/250V H 3.50 200A/250V H 4.38 100 AMP 100A/600V H 5.50 200A/600V H 6.88 100A/600V J 2.31 200A/600V J 3.06 200A/250V H 3.50 400A/250V H 5.00 200 AMP 200A/600V H 6.00 400A/600V H 8.00 200A/600V J 2.19 400A/600V J 3.50 87569084 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman - 7 -
INTRODUCTION This installation instruction is for Allen Bradley Bulletin 1494F and 1494D mechanisms. These mechanisms are for disconnect switches (1494F) and circuit breakers (1494D) mounted in Hoffman one through six door, free standing enclosures with the disconnect on the right flange. Master Door INSTALLATION STEPS Step 1 Drill and tap holes required in panel; see figure 1. Two holes are required for un fused switches; three holes for 30, 60 100 AMP fused switches, and four holes for 200 AMP fused switches. Two holes are required for operators for circuit breakers. Step 2 Install mounting plate (item 1) positioned as shown on figure 3, (item 2 for a 200 AMP switch) and plate gasket (item 3) on the inside of the enclosure behind the rectangular opening provided. Secure in place with four screws (item 4). Step 3 Install door catch (item 5) on tapped block provided on master door; see figure 3. Locate door catch vertically as shown, and secure in place with two screws (item 6) and lockwashers (item 7). Step 4 Remove and discard lock release mechanism from enclosure flange (see bottom of figure 3). Install lock release mechanism (item 13) as shown in figure 3 using the same spacer, nuts, and washers. Adjust lock release mechanism so top of door latch contacts latch stop when door is closed and door handle is fully latched. Step 5 Install Allen Bradley disconnect switch or operator for circuit breakers as follows: 1. Remove nuts and lockwashers from Allen Bradley flange plate. Discard the Allen Bradley flange plate. 2. Place operator handle into enclosure with the operating handle in the OFF position. Tilt the assembly under the flange and at the same time bring the handle through the slot provided in the mounting plate installed in step 2. 3. Secure operator handle to mounting plate with nuts and lockwashers. Fusible Disconnect Switches Only 1. Attach fuse clips provided with the fuse block adapter plate kit to the disconnect switch terminals. See Allen Bradley instructions. 2. Attach the fuse block adapter plate to the disconnect switch mounting bracket. See Allen Bradley instructions. Step 6 Attach disconnect platform and fuse block adapter plate to panel with threaded rods, lockwashers, and nuts. See figure 2. Cut threaded rods (item 9) to length required. See P dimension in table 1. Install threaded rods as shown in figure 2. Adjust threaded rods and nuts so disconnect platform is level. The ends of threaded rods should not extend above nuts on front of disconnect platform. Step 7 Install slide arm (item 8). Unhook spring from the tab on the A B locking lever. Place end of slide arm (item 8) and retaining washer (item 16) over tab, and re attach spring. Attach the bottom of slide arm (item 8) to lock release mechanism (item 13) using flat washer (item 15), lockwasher (item 11), and nut (item 10) as shown in figure 1. See step 8 for adjustment. Step 8 Adjust slide arm (item 8) and door catch (item 5) as follows: 1. Close master door. Attempt to turn ON the Allen Bradley handle. The slide arm should release the Allen Bradley operating handle just before the enclosure master door is fully latched. Adjust slide arm up or down, if required. 2. Leave the Allen Bradley handle in the ON position. Attempt to open master door. Door catch should hook on the Allen Bradley interlock to prevent the door from opening. Adjust up or down if required. - 8-2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman 87569084
For One Through Six Door, Free Standing Enclosures With Disconnect on Right Flange Figure 3 87569084 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman - 9 -
For One Through Six Door Free Standing Enclosures With Disconnect on Right Flange Figure 1-10 - 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman 87569084
For One Through Six Door Free Standing Enclosures With Disconnect on Right Flange Figure 2 87569084 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman - 11 -
For One Through Six Door, Free Standing Enclosure With Disconnect on Right Flange TYPE SIZE E F M TABLE 1 Sub Panel Drilling A 28 1 & 2 DOOR * P A 28 3,4,5,6 DOOR A 34 1 & 2 DOOR * P 72.12 High Enclosures G 84.12 High Enclosures G 90.12 High Enclosures G 1494F 30 AMP 3.31 5.31 1.50 11.63 10.63 4.75 10.75 13.75 1494F 60 AMP 3.31 5.31 1.50 11.63 10.63 4.75 10.75 13.75 1494F 100 AMP 3.69 7.19 1.50 9.63 8.63 2.34 8.34 11.34 1494F 200 AMP 5.75 9.63.25 9.56 8.56 1.06 7.06 10.06 1494D N4 150 AMP CB 3.31 7.19 1.39 11.63 10.63 4.75 10.75 13.75 1494D N5 225 400A CB 2.88 10.88 1.39 8.63 8.63 4.06 10.06 13.06 * The P dimensions shown are for 18.12 inch deep enclosures or 24.12 inch deep enclosures with a 6 inch platform. Platform could be omitted if 6 inch longer threaded rods are used. The P dimensions for 20.12 inch deep enclosures are 2 inches more the P dimensions shown. TABLE 2 Extra Holes for Fusible Switches Only SWITCH SIZE FUSE CLIP Q / R 30 AMP 30A/600V H 2.81 60A/600V H 3.31 30A/600V H 3.38 100A/250V H 3.88 60 AMP 60A/600V H 3.88 100A/600V H 5.88 100A/600V J 2.69 100A/250V H 3.50 200A/250V H 4.38 100 AMP 100A/600V H 5.50 200A/600V H 6.88 100A/600V J 2.31 200A/600V J 3.06 200A/250V H 3.50 400A/250V H 5.00 200 AMP 200A/600V H 6.00 400A/600V H 8.00 200A/600V J 2.19 400A/600V J 3.50-12 - 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman 87569084
INTRODUCTION This installation instruction is for Allen Bradley Bulletin 1494F and 1494D mechanisms. These mechanisms are for disconnect switches (1494F) and circuit breakers (1494D) mounted in Hoffman two door, floor mounted enclosures with the disconnect on the centerpost. Master Door INSTALLATION STEPS Step 1 Drill and tap holes required in panel; see figure 1. Two holes are required for un fused switches; three holes for 30, 60 100 AMP fused switches, and four holes for 200 AMP fused switches. Two holes are required for operators for circuit breakers. Step 2 Remove and save locknut; remove and discard parts shown at the bottom of figure 3. Step 3 Install mounting plate (item 1) positioned as shown on figure 3, (item 2 for a 200 AMP switch) and plate gasket (item 3) on the inside of the enclosure behind the rectangular opening provided. Secure in place with four screws (item 4). Step 4 Install door catch (item 5) on tapped block provided on master door; see figure 3. Locate door catch vertically as shown, and secure in place with two screws (item 6) and lockwashers (item 7). Step 5 Replace parts removed in step 2 with release mechanism (item 14); secure in place with locknut. See figure 3. Step 6 Install Allen Bradley disconnect switch or operator for circuit breakers as follows: 1. Remove nuts and lockwashers from Allen Bradley flange plate. Discard the Allen Bradley flange plate. 2. Place operator handle into enclosure with the operating handle in the OFF position. Tilt the assembly under the flange and at the same time bring the handle through the slot provided in the mounting plate installed in step 2. 3. Secure operator handle to mounting plate with nuts and lockwashers. Fusible Disconnect Switches Only 1. Attach fuse clips provided with the fuse block adapter plate kit to the disconnect switch terminals. See Allen Bradley instructions. 2. Attach the fuse block adapter plate to the disconnect switch mounting bracket. See Allen Bradley instructions. Step 7 Attach disconnect platform and fuse block adapter plate to panel with threaded rods, lockwashers, and nuts. See figure 2. Cut threaded rods (item 9) to length required. See P dimension in table 1. Install threaded rods as shown in figure 2. Adjust threaded rods and nuts so disconnect platform is level. The ends of threaded rods should not extend above nuts on front of disconnect platform. Step 8 Install slide arm (item 8). Unhook spring from the tab on the A B locking lever. Place end of slide arm (item 8) and retaining washer (item 16) over tab, and re attach spring. Attach the bottom of slide arm (item 8) to lock release mechanism (item 14) using flat washer (item 15), lockwasher (item 11), and nut (item 10) as shown in figure 1. See step 8 for adjustment. Step 9 Adjust slide arm (item 8) and door catch (item 5) as follows: 1. Close master door. Attempt to turn ON the Allen Bradley handle. The slide arm should release the Allen Bradley operating handle just before the enclosure master door is fully latched. Adjust slide arm up or down, if required. 2. Leave the Allen Bradley handle in the ON position. Attempt to open master door. Door catch should hook on the Allen Bradley interlock to prevent the door from opening. Adjust up or down if required. 87569084 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman - 13 -
For Two Door, Floor Mounted Enclosures With Disconnect on Centerpost Figure 3-14 - 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman 87569084
For Two Door, Floor Mounted Enclosures With Disconnect on Centerpost Figure 1 87569084 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman - 15 -
For Two Door, Floor Mounted Enclosures With Disconnect on Centerpost Figure 2-16 - 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman 87569084
For Two Door, Floor Mounted Enclosure With Disconnect on Centerpost TABLE 1 Sub panel Drilling TYPE SIZE E F M For 60.12 High G For 72.12 High G For 12.12 Deep P * For 18.12 Deep P * For 24.12 Deep P 1494F 30 AMP 4.50 5.31 1.50 2.75 8.75 5.63 11.63 17.63 1494F 60 AMP 4.50 5.31 1.50 2.75 8.75 5.63 11.63 17.63 1494F 100 AMP 4.88 7.19 1.50 1494F 200 AMP 6.94 9.63.25 DO NOT INSTALL DO NOT INSTALL 6.34 3.63 9.63 15.63 5.06 3.56 9.56 15.56 1494D N4/N40 4.50 7.19 1.50 2.75 8.75 5.59 11.59 17.59 1494D N5/N55 4.06 10.88 1.39 2.06 8.06 3.59 9.59 15.59 1494D N5/N50 4.06 10.88 1.39 2.06 8.06 3.59 9.59 15.59 1494D N5/N60 4.06 10.88 1.39 DO NOT INSTALL 8.06 3.59 9.59 15.59 * The P dimensions for 24.12 inch deep is the same as 18.12 inch deep when using the 6 inch platform. Platform can be omitted for if longer threaded rods are used. TABLE 2 Extra Holes for Fusible Switches Only SWITCH SIZE FUSE CLIP Q / R 30 AMP 30A/600V H 2.81 60A/600V H 3.31 30A/600V H 3.38 100A/250V H 3.88 60 AMP 60A/600V H 3.88 100A/600V H 5.88 100A/600V J 2.69 100A/250V H 3.50 200A/250V H 4.38 100 AMP 100A/600V H 5.50 200A/600V H 6.88 100A/600V J 2.31 200A/600V J 3.06 200A/250V H 3.50 400A/250V H 5.00 200 AMP 200A/600V H 6.00 400A/600V H 8.00 200A/600V J 2.19 400A/600V J 3.50 87569084 2018 Hoffman Enclosures Inc. PH 763 422 2211 nvent.com/hoffman - 17 -
Rev. C 2018 Hoffman Enclosures Inc. PH 7634222211 nvent.com/hoffman P/N 99401943 87569084
Rev. C 2018 Hoffman Enclosures Inc. PH 7634222211 nvent.com/hoffman P/N 99401943 87569084
Rev. C 2018 Hoffman Enclosures Inc. PH 7634222211 nvent.com/hoffman P/N 99401943 87569084