17-18 Technical Sales Guide # 040 YDFC 0 1 Page 2
Technical Sales Guide # 040 YDFC 0 1 Page 3
York China Fan Coil Unit Model Type ST - Standard DC - District Cooling Number of rows 3: 3 Rows 4: 4 Rows A: 3+1 Rows C: 4+1 Rows Filter type G2: 27mm Rail for Filter F2: 25mm Al filter media with rail Motor type A5: IP20 50 Hz A6: IP20 60 Hz B5: IP54 50 Hz B6: IP54 60 Hz YDFC 10 ST CB 3 X G2 X A5 L 1 2 3 4 5 6 7 8 9 10 Unit Size 08, 10, 12, 14 16, 18, 20 Installation Type CB : Ceiling Concealed with back plenum Drain pan type X: Galvanized Steel Standard Drain Pan E: Galvanized Steel Extended Drain Pan S: Stainless Steel Standard Drain Pan T: Stainless Steel Extended Drain Pan Electric Heater H : With electric heater X : Without electric heater Connection Side L: Left Hand R: Right Hand Technical Sales Guide # 040 YDFC 0 1 Page 4
PE Insulation Return Plenum Fixing Beam Galvanized Steel PE Insulation Technical Sales Guide # 040 YDFC 0714 Page 5
District Cooling MODEL [ CB ] 08 10 12 14 16 18 20 Performance Nominal Air Flow Nominal Total Capacity Water Flow Rate Water Pressure Drop m3/h kw m 3 /h kpa 1369 6.28 0.601 46.1 1777 8.15 0.780 53.9 2095 9.44 0.903 41.9 2471 10.12 0.968 26.8 2965 12.61 1.207 40.6 3124 13.64 1.305 47.1 3645 14.67 1.404 46.2 CFM Btuh G.P.M.(US) ft.wg. 805 21427 3 15.44 1045 27808 3 18.06 1232 32209 4 14.04 1454 34529 4 8.98 1744 43025 5 13.60 1838 46540 6 15.78 2144 50054 6 15.48 COIL Face Area sq.m 0.20 0.24 0.28 0.32 0.38 0.43 0.47 Face Velocity m/s 1.90 2.06 2.08 2.14 2.17 2.02 2.15 Header Material Copper MOTOR Type 3 - Speed Permanent Split Capacitor Motor No. of Motor # 1 1 1 1 1 1 1 Total Rating Input watt 266 293 385 473 616 660 777 Amp. (220V / 1 Ph. / 50-60 Hz.) A 1.21 1.33 1.75 2.15 2.80 3.00 3.53 FAN Type Centrifugal Fan (Forward Curve) No. of Fans # 2 2 2 2 2 2 2 WATER CONTENT 3 Rows Liters 1.8 2.1 2.5 2.8 3.3 3.6 4.0 4 Rows Liters 2.3 2.7 3.3 3.7 4.3 4.8 5.2 Standard Cooling MODEL [ CB ] 08 10 12 14 16 18 20 Performance Nominal Air Flow Nominal Total Capacity Water Flow Rate Water Pressure Drop m3/h kw m 3 /h kpa 1374 6.28 1.082 19.4 1806 8.31 1.430 35.8 2117 9.72 1.674 34.5 2486 11.35 1.954 30.5 2991 12.64 2.177 30.2 3200 14.31 2.464 40.0 3689 16.24 2.796 49.7 CFM Btuh G.P.M.(US) ft.wg. 808 21427 4.76 6.50 1062 28354 6.30 11.99 1245 33165 7.37 11.56 1462 38726 8.60 10.22 1759 43128 9.59 10.12 1882 48826 10.85 13.40 2170 55411 12.31 16.65 COIL Face Area sq.m 0.20 0.24 0.28 0.32 0.38 0.43 0.47 Face Velocity m/s 1.91 2.09 2.10 2.16 2.19 2.07 2.18 Header Material Copper MOTOR Type 3 - Speed Permanent Split Capacitor Motor No. of Motor # 1 1 1 1 1 1 1 Total Rating Input watt 259 294 379 482 594 655 795 Amp. (220V / 1 Ph. / 50-60 Hz.) A 1.18 1.34 1.72 2.19 2.70 2.98 3.61 FAN Type Centrifugal Fan (Forward Curve) No. of Fans # 2 2 2 2 2 2 2 WATER CONTENT 3 Rows Liters 1.7 2.0 2.5 2.8 3.3 3.6 4.0 4 Rows Liters 2.3 2.7 3.2 3.6 4.5 5.0 5.5 Cooling Capacity For 3 Row Coils at Entering Air Temperature = 24 C DB, 18 C WB For Standard Cooling Coil: Entering Chilled Water Temperature = 7 C, Leaving Chilled Water Temperature = 12 C For District Cooling Coil: Entering Water Temperature = 5.5 C, Leaving Water Temperature = 14.5 C Air Flow: Fan Speed =, 220v/1 Ph. / 50 Hz, 30 Pa External Static Pressure Technical Sales Guide # 040 YDFC 0714 Page 6
UNIT DIMENSIONS - ST TYPE UNIT DIMENSIONS - DC TYPE UNIT DIMENSIONS - ST A & C TYPE Size Type A B B1 C D E F G H I J K L D1 M3R M4R N3+1 N4+1 O 08 830 1050 1210 860 768 800 380 184 289 225 190 775 27 25 162 151 101 90 84 10 990 1210 1340 1020 928 960 380 184 289 225 190 775 27 25 162 151 101 90 84 12 990 1210 1340 1020 928 960 380 235 340 275 240 775 27 25 162 151 101 90 109 14 ST 1120 1340 1480 1150 1058 1090 380 235 340 275 240 775 27 25 162 151 101 90 109 16 1120 1340 1480 1150 1058 1090 420 279 390 325 280 815 33 38.1 162 151 101 90 134 18 1260 1480 1610 1290 1198 1230 420 279 390 325 280 815 33 38.1 162 151 101 90 134 20 1390 1610 1710 1420 1328 1360 420 279 390 325 280 815 33 38.1 162 151 101 90 134 08 850 1050 1210 860 768 800 380 289 225 190 775 83 19.1 184 184 10 990 1210 1340 1020 928 960 380 289 225 190 775 83 19.1 184 184 12 990 1210 1340 1020 928 960 380 340 275 240 775 108 19.1 184 184 14 DC 1120 1340 1480 1150 1058 1090 380 340 275 240 775 108 19.1 184 184 16 1120 1340 1480 1150 1058 1090 420 390 325 280 815 134 19.1 184 184 18 1260 1480 1610 1290 1198 1230 420 390 325 280 815 134 19.1 184 184 20 1390 1610 1710 1420 1328 1360 420 390 325 280 815 134 19.1 184 184 B1. Extended Drain Pan * All dimensions are in mm Technical Sales Guide # 040 YDFC 0714 Page 7
UNIT DIMENSIONS AND WEIGHTS Model Length Width Weight Height Standard Drain Pan Extended Drain Pan 3 Rows 4 Rows 3+1 Rows 4+1 Rows mm mm mm mm kg kg kg kg 08 775 1050 1210 295 36 49 41 54 10 775 1210 1340 295 38 51 43 56 12 775 1210 1340 345 45 59 50 64 14 775 1340 1480 345 50 65 56 70 16 815 1340 1480 396 61 77 67 83 18 815 1480 1610 396 74 92 81 98 20 815 1610 1710 396 78 97 85 103 Technical Sales Guide # 040 YDFC 0714 Page 8
YDFC 08 ST CB 3 X G2 X A5 L YDFC 10 ST CB 3 X G2 X A5 L YDFC 12 ST CB 3 X G2 X A5 L YDFC 14 ST CB 3 X G2 X A5 L YDFC 16 ST CB 3 X G2 X A5 L YDFC 18 ST CB 3 X G2 X A5 L YDFC 20 ST CB 3 X G2 X A5 L Air Conditions(EDB/EWB) Cooling : 24 / 18 C Fin Material / Protection : Aluminum / None Water Conditions (EWT/LWT) Cooling: 7 / 12 C Delta T: 5 C Technical Sales Guide # 040 YDFC 0714 Page 9
YDFC 08 ST CB 4 X G2 X A5 L YDFC 10 ST CB 4 X G2 X A5 L YDFC 12 ST CB 4 X G2 X A5 L YDFC 14 ST CB 4 X G2 X A5 L YDFC 16 ST CB 4 X G2 X A5 L YDFC 18 ST CB 4 X G2 X A5 L YDFC 20 ST CB 4 X G2 X A5 L Air Conditions(EDB/EWB) Cooling : 24 / 18 C Water Conditions (EWT/LWT) Cooling: 7 / 12 C Fin Material / Protection : Aluminum / None Delta T: 5 C Technical Sales Guide # 040 YDFC 0714 Page 10
YDFC 08 DC CB 3 X G2 X A5 L YDFC 10 DC CB 3 X G2 X A5 L YDFC 12 DC CB 3 X G2 X A5 L YDFC 14 DC CB 3 X G2 X A5 L YDFC 16 DC CB 3 X G2 X A5 L YDFC 18 DC CB 3 X G2 X A5 L YDFC 20 DC CB 3 X G2 X A5 L Air Conditions(EDB/EWB) Cooling : 24 / 18 C Water Conditions (EWT/LWT) Cooling: 5.5 / 14.5 C Fin Material / Protection : Aluminum / None Delta T: 9 C Technical Sales Guide # 040 YDFC 0714 Page 11
YDFC 08 DC CB 4 X G2 X A5 L YDFC 10 DC CB 4 X G2 X A5 L YDFC 12 DC CB 4 X G2 X A5 L YDFC 14 DC CB 4 X G2 X A5 L YDFC 16 DC CB 4 X G2 X A5 L YDFC 18 DC CB 4 X G2 X A5 L YDFC 20 DC CB 4 X G2 X A5 L Air Conditions(EDB/EWB) Cooling : 24 / 18 C Water Conditions (EWT/LWT) Cooling: 5.5 / 14.5 C Fin Material / Protection : Aluminum / None Delta T: 9 C Technical Sales Guide # 040 YDFC 0714 Page 12
YDFC 08 ST CB A X G2 X A5 L YDFC 10 ST CB A X G2 X A5 L YDFC 12 ST CB A X G2 X A5 L YDFC 14 ST CB A X G2 X A5 L YDFC 16 ST CB A X G2 X A5 L YDFC 18 ST CB A X G2 X A5 L YDFC 20 ST CB A X G2 X A5 L Air Conditions(EDB/EWB) Cooling : 24 / 18 C Water Conditions (EWT/LWT) Cooling: 7 / 12 C Delta: 5 C Heating: 20 C Heating: 50 / 40 C Delta T: 10 C Fin Material / Protection : Aluminum / None Technical Sales Guide # 040 YDFC 0714 Page 13
Model YDFC 20 ST CB C X G2 X A5 L YDFC 18 ST CB C X G2 X A5 L YDFC 16 ST CB C X G2 X A5 L YDFC 14 ST CB C X G2 X A5 L YDFC 12 ST CB C X G2 X A5 L YDFC 10 ST CB C X G2 X A5 L YDFC 08 ST CB C X G2 X A5 L Speed ESP Air Cooling Capacity Air Off FCU Water Water Power Heating Water Water LDBT Flow Total Sensible DB WB Flow Pressure Input Capacity Flow Pressure Pa m³/h kw kw C C m³/h kpa W kw C m³/h kpa 20 1350 7.32 5.07 12.9 12.2 1.260 16.4 268 3.06 26.70 0.263 4.2 50 1252 6.98 4.80 12.6 12.0 1.202 15.1 252 2.96 27.0 0.255 4.0 100 1000 5.93 4.02 12.1 11.6 1.021 11.3 214 2.70 28.0 0.232 3.4 20 1285 7.09 4.89 12.7 12.1 1.222 16.3 255 3.00 26.9 0.258 4.0 50 1176 6.70 4.58 12.4 11.9 1.153 14.7 239 2.88 27.3 0.248 3.8 100 940 5.68 3.83 11.9 11.5 0.978 11.0 202 2.63 28.3 0.227 3.2 20 720 5.02 3.24 10.6 10.3 0.864 6.7 124 2.37 29.8 0.204 2.7 50 611 4.36 2.78 10.5 10.1 0.774 5.6 108 2.22 30.8 0.191 2.4 100 312 2.31 1.42 10.5 9.8 0.466 2.4 79 1.51 34.3 0.130 1.3 20 1685 9.94 6.64 12.3 11.7 1.712 31.6 302 3.82 26.7 0.329 6.6 50 1546 9.44 6.25 12.0 11.4 1.625 28.8 281 3.68 27.1 0.317 6.2 100 1270 8.29 5.41 11.4 10.9 1.428 22.8 247 3.36 27.9 0.289 5.3 20 1570 9.35 6.24 12.2 11.6 1.609 28.1 283 3.70 27.0 0.319 6.2 50 1411 8.74 5.78 11.8 11.3 1.504 24.9 258 3.53 27.4 0.304 5.7 100 1115 7.47 4.85 11.1 10.7 1.287 18.8 218 3.18 28.5 0.274 4.8 20 1100 6.80 4.55 11.7 11.3 1.171 19.1 178 3.16 28.5 0.272 4.7 50 892 5.90 3.88 11.1 10.8 1.016 14.9 159 2.91 29.7 0.250 4.1 100 490 3.52 2.23 10.5 10.0 0.655 6.9 128 2.22 33.5 0.192 2.6 20 1975 11.49 7.73 12.4 11.8 1.979 29.9 391 4.65 27.0 0.400 11.2 50 1847 11.04 7.37 12.2 11.6 1.901 27.8 377 4.51 27.2 0.388 10.6 100 1600 10.05 6.63 11.7 11.2 1.731 23.5 349 4.24 27.9 0.365 9.5 20 1890 11.27 7.52 12.2 11.6 1.940 27.8 367 4.55 27.2 0.392 10.8 50 1774 10.84 7.20 12.0 11.4 1.867 26.0 351 4.43 27.4 0.381 10.3 100 1525 9.80 6.43 11.5 11.0 1.687 21.7 324 4.15 28.1 0.357 9.1 20 1180 7.20 4.87 11.8 11.4 1.240 11.6 150 3.70 29.3 0.318 7.4 50 1000 6.40 4.27 11.3 11.0 1.101 9.4 135 3.43 30.2 0.295 6.5 100 640 4.51 2.91 10.5 10.2 0.797 5.4 109 2.79 32.9 0.240 4.5 20 2540 13.54 9.37 13.0 12.3 2.332 34.8 569 5.77 26.7 0.497 17.4 50 2377 12.85 8.88 12.9 12.3 2.213 31.7 548 5.56 26.9 0.479 16.3 100 2120 11.83 8.12 12.6 12.0 2.036 27.3 519 5.23 27.3 0.450 14.6 20 2335 12.65 8.74 12.9 12.2 2.178 30.6 475 5.50 27.0 0.474 16.0 50 2222 12.20 8.40 12.8 12.2 2.100 28.7 462 5.36 27.2 0.461 15.2 100 1945 11.20 7.62 12.4 11.8 1.928 24.6 430 5.03 27.7 0.433 13.6 20 1290 8.34 5.52 11.3 11.0 1.436 14.9 203 4.22 29.7 0.363 9.9 50 1102 7.49 4.90 10.8 10.6 1.290 12.4 189 3.92 30.5 0.337 8.7 100 750 5.35 3.41 10.5 10.1 0.968 7.5 154 3.22 32.7 0.277 6.1 20 2985 14.19 10.33 13.7 13.0 2.443 26.3 638 6.44 26.4 0.554 9.1 50 2829 13.70 9.92 13.6 12.9 2.359 24.7 623 6.29 26.6 0.541 8.8 100 2535 12.76 9.14 13.3 12.7 2.197 21.9 590 5.99 27.0 0.516 8.1 20 2905 14.14 10.20 13.6 12.9 2.435 26.9 595 6.36 26.5 0.548 9.0 50 2727 13.57 9.72 13.4 12.8 2.336 25.1 582 6.18 26.7 0.532 8.5 100 2410 12.53 8.87 13.1 12.5 2.158 21.9 545 5.86 27.2 0.504 7.8 20 1655 9.72 6.65 12.1 11.7 1.674 13.8 256 4.95 28.9 0.426 5.8 50 1507 9.11 6.19 11.8 11.5 1.570 12.4 244 4.76 29.4 0.410 5.4 100 1300 8.23 5.52 11.4 11.1 1.418 10.5 220 4.48 30.2 0.386 4.9 20 3165 16.47 11.56 13.2 12.5 2.836 36.2 700 7.21 26.8 0.621 11.7 50 3002 15.92 11.12 13.0 12.4 2.742 34.1 684 7.03 27.0 0.605 11.2 100 2650 14.77 10.17 12.6 12.1 2.543 29.9 652 6.65 27.4 0.573 10.1 20 2995 15.54 10.96 13.1 12.5 2.676 35.3 642 7.02 27.0 0.605 11.2 50 2834 15.02 10.53 13.0 12.4 2.587 33.3 632 6.85 27.2 0.589 10.7 100 2560 14.10 9.77 12.7 12.1 2.428 29.8 602 6.56 27.6 0.564 9.9 20 1720 10.37 7.05 11.8 11.5 1.785 16.6 284 5.48 29.5 0.472 7.3 50 1553 9.63 6.50 11.6 11.3 1.658 14.6 275 5.24 30.0 0.451 6.7 100 1230 8.14 5.39 11.0 10.8 1.402 11.1 246 4.70 31.4 0.405 5.6 20 3550 18.16 12.83 13.3 12.6 3.128 47.2 837 8.19 26.8 0.705 15.3 50 3387 17.63 12.40 13.1 12.5 3.036 45.0 821 7.98 27.0 0.687 14.6 100 3092 16.65 11.60 12.9 12.3 2.867 41.0 778 7.61 27.3 0.656 13.4 20 3425 17.63 12.45 13.2 12.6 3.035 44.8 790 8.03 27.0 0.692 14.8 50 3264 17.10 12.01 13.1 12.4 2.944 42.6 775 7.83 27.1 0.674 14.1 100 2990 16.18 11.27 12.8 12.2 2.785 39.0 732 7.50 27.4 0.645 13.1 20 1875 11.73 7.87 11.5 11.2 2.020 21.9 345 6.13 29.7 0.528 9.2 50 1734 11.14 7.41 11.3 11.0 1.918 20.2 329 5.91 30.1 0.509 8.6 100 1515 10.18 6.69 10.9 10.6 1.753 17.6 302 5.54 30.9 0.477 7.7 C Air Conditions(EDB/EWB) Cooling : 24 / 18 C Water Conditions (EWT/LWT) Cooling: 7 / 12 C Delta: 5 C Heating: 20 C Heating: 50 / 40 C Delta T: 10 C Fin Material / Protection : Aluminum / None Technical Sales Guide # 040 YDFC Page 14
Follows JB standard JB/T 4330-1999 Technical Sales Guide # 040 YDFC Page 15
Follows JB standard JB/T 4330-1999 Model YDFC 08 YDFC 10 YDFC 12 YDFC 14 YDFC 16 YDFC 18 YDFC 20 Speed ESP Pa 20 63 31.0 125 44.0 250 46.8 500 47.1 1000 51.8 2000 47.8 4000 44.0 8000 38.4 db(a) 55.7 50 30.6 42.9 45.9 46.7 51.8 47.7 43.5 37.7 55.4 100 29.1 40.9 44.1 45.5 51.3 48.1 43.3 36.7 54.8 20 30.1 43.1 46.0 46.3 51.0 47.4 43.1 36.9 54.9 50 29.4 42.1 45.1 46.1 51.1 47.5 42.9 36.5 54.8 100 28.4 40.6 43.5 45.3 51.1 48.0 42.9 36.0 54.5 20 17.1 28.7 31.9 34.5 38.4 33.2 28.1 18.7 41.7 50 28.7 31.1 33.9 36.5 42.0 37.1 31.8 22.1 45.0 100 28.7 34.8 37.7 39.7 46.7 43.4 36.6 28.4 49.7 20 33.9 44.7 47.2 49.5 51.9 49.1 45.8 38.6 56.6 50 33.5 44.3 46.5 48.5 51.4 48.5 44.9 37.4 55.9 100 31.9 43.6 45.9 47.5 50.5 47.4 43.4 35.2 54.9 20 31.4 42.0 44.6 46.8 49.6 46.5 42.8 35.5 54.0 50 31.5 42.0 44.5 46.9 49.6 46.2 42.5 34.7 54.0 100 31.8 42.8 44.7 46.0 49.1 46.0 41.6 33.0 53.6 20 27.7 29.6 32.6 34.9 36.9 31.9 25.9 18.9 41.2 50 26.9 33.6 35.8 37.5 40.3 35.9 30.0 21.1 44.5 100 29.5 38.7 40.6 41.3 44.2 40.5 35.1 25.3 48.7 20 32.4 44.5 47.1 46.7 50.6 47.7 45.2 39.0 55.3 50 32.0 44.2 46.7 46.0 50.4 47.4 44.5 38.2 55.0 100 31.2 44.3 46.5 46.0 50.6 47.8 44.2 37.3 55.0 20 32.4 43.3 45.5 45.4 49.3 46.4 43.6 37.0 54.0 50 31.1 43.0 45.3 45.1 49.6 46.3 43.4 36.7 53.9 100 31.3 43.7 45.5 45.2 49.9 46.8 43.2 36.3 54.2 20 24.8 30.3 32.3 33.9 36.5 33.0 27.1 19.2 41.0 50 28.3 32.4 33.9 35.7 38.9 35.2 29.2 20.8 43.1 100 30.2 38.2 40.2 39.8 44.2 40.3 34.3 24.2 48.3 20 35.6 48.3 52.1 49.6 54.4 51.9 49.1 43.6 59.3 50 35.5 47.9 51.6 49.0 54.0 51.1 48.6 43.0 58.8 100 35.3 47.5 50.8 48.3 53.4 50.5 47.6 41.8 58.1 20 35.3 47.5 50.7 48.6 53.4 50.6 48.0 42.3 58.2 50 34.9 47.3 50.4 48.2 53.0 50.2 47.3 41.6 57.8 100 34.8 46.8 49.7 47.6 52.7 49.6 46.7 40.7 57.3 20 30.3 32.4 33.5 34.2 37.3 33.5 28.0 18.7 42.0 50 38.4 34.3 32.2 34.6 35.5 36.0 31.3 32.4 43.9 100 32.2 39.6 41.2 39.3 44.8 39.5 34.2 23.7 48.7 20 35.9 45.9 46.9 49.4 51.8 49.4 46.9 39.8 56.8 50 35.5 47.0 48.2 48.4 52.1 49.4 46.9 39.6 56.9 100 35.3 47.0 49.0 48.4 52.9 49.3 47.0 38.8 57.3 20 35.2 45.7 47.8 48.3 52.0 48.8 46.3 38.7 56.6 50 35.8 46.4 48.2 47.9 51.5 48.8 46.0 38.5 56.4 100 35.6 46.2 47.7 48.3 51.7 48.8 45.8 37.5 56.4 20 28.1 33.5 35.8 37.3 40.9 35.8 31.5 28.0 44.8 50 30.7 35.3 37.2 38.9 42.5 37.3 32.5 26.1 46.4 100 33.8 40.0 41.2 41.9 46.0 40.8 36.4 26.5 49.9 20 34.1 46.3 46.5 48.0 50.1 48.9 46.4 39.3 55.8 50 35.8 46.3 46.4 47.5 50.2 48.7 46.1 38.9 55.7 100 34.9 46.5 47.1 47.8 50.6 49.1 45.9 38.3 56.0 20 34.5 45.3 45.8 47.7 49.5 47.8 45.6 38.7 55.2 50 34.6 45.1 45.7 47.0 49.7 47.8 45.1 37.8 55.0 100 33.9 45.6 46.1 47.2 50.1 48.3 44.8 36.9 55.3 20 30.0 32.7 34.3 36.7 38.7 35.0 29.3 20.2 43.4 50 30.7 34.5 34.9 38.4 40.6 36.8 30.5 21.2 45.0 100 31.8 39.5 40.0 42.4 44.1 41.8 35.0 25.1 49.1 20 36.2 48.3 50.1 49.3 52.0 52.1 49.5 43.5 58.4 50 35.8 48.1 49.7 48.9 51.9 51.7 49.0 43.0 58.1 100 36.1 47.9 49.3 48.4 51.8 51.3 48.3 42.0 57.7 20 35.3 47.1 48.4 47.9 50.8 50.9 48.2 42.0 57.1 50 35.3 47.2 48.3 47.8 51.2 51.0 48.0 41.9 57.2 100 35.2 47.1 48.2 47.9 51.2 50.6 47.6 41.2 57.0 20 30.0 33.7 34.7 37.2 38.1 36.7 31.3 23.4 43.9 50 29.2 35.1 35.9 39.0 39.8 38.1 32.4 24.0 45.3 100 30.2 38.8 38.8 41.3 42.8 40.9 35.3 26.3 48.1 Technical Sales Guide # 040 YDFC Page 16
2 OR 4 PIPE SYSTEM - YDFC08 2 OR 4 PIPE SYSTEM - YDFC10-20 Technical Sales Guide # 040 YDFC Page 17
2 PIPE SYSTEM WITH ELECTRICAL HEATING AND SPECIAL TERMINAL BOX WITH RELAYS AND FUSE 1 Heater Element and 1 Temp Cutout upto size 12 2. Heater Element and 2 Temp Cutout for size 14 Three Speed Switch 2 Pipe System Two Port & Three Port Water Valves for Cooling 4 Pipe System Hot Water Heating Unit motor is a single-phase, permanent split capacitor type with three speeds tappings / /, wired to the terminal block with colour coded wires. Cooling is controlled by either modulating of switching On and Off the chilled water supply by means of an electrically operated valve. (Refer Fig.1 & 2) 3+1 (A) and 4+1(C) configurations can be used for hot water heating. A separate hot water valve is required to be installed on the 1 row eating coil. Mode of switching from cooling to heating can be automatic or manual 2 Pipe System with Electric Heating Special Terminal Box YDFC can be provided with one stage electrical heater of following capacities: Size 08 to 12-1500 Watts Size 14-2000 Watts Size 16 to 20-3000 Watts These heaters are provided as an option at extra cost. It is important that electrical heaters are interlocked to ensure that the heating elements receive no power supply when the fan is not selected to operate. Heater are provided with high temperature cut out at standard and are terminated in a terminal box for field wiring (Refer. Fig.3) The electric heater input power based on the condition: -speed&0pa, accuracy: ±10% A special terminal box equipped with relays and fuse can eb provided at extra cost. This allows the power for the electrical heaters to be supplied separately. Technical Sales Guide # 040 YDFC 0714 Page 18
POWER SUPPLY 220 VOLT / 1 PHASE / 50 HZ POWER SUPPLY 220 VOLT / 1 PHASE / 60 HZ Technical Sales Guide # 040 YDFC Page 19
GENERAL Furnish and install Fan Coil Units as indicated and scheduled in the plans. Units shall be factory assembled with coils that are pressure tested individually to 400 psi (2.8 MPa). The fans must be factory run and manufacturer must have a facility to test the capacity of cooling coils at specified entering air conditions and specified chilled water temperature, to assure correct capacity. In addition the test facility shall be suitable to test air capacity at specified external pressure drop at indicated speed setting. BASIC UNIT The basic unit shall be fabricated out of 1mm galvanized steel to JIS G 3302 to Z18 or above. The coil top panel and return plenum shall be insulated with PE foam. The fan motor shall be easily removable for serviceability. A terminal box with terminal strip shall be provided for terminating the wiring. The filter shall be easily removable from either side or the back. Units with powder coating finish shall be available as an option. COILS Coils shall be made out of 3/8 inch or 9.52 mm OD copper tubes. Aluminum fins shall be 0.110 mm thick and the coil shall have maximum spacing of 2.3 mm between the fins. The coil shall be pressure tested under water to 2.8 MPa (For a working pressure of 1600 kpa) and dehydrated before assembly. Coil shall be provided with a drain plug in the bottom and a manual air vent on the top. The coil assembly shall be protected on the side on which piping is to be fitted with a cover made of GI sheet. The metal sheet below the coil shall be powder coated to avoid corrosion. Gold Epoxy and Blue Hydrophilic coated fins shall be available as options. There shall also be the availability of copper fins for higher hazardous and/or humid environments. option. Total enclosed motors shall be available on request (option). Motors shall be protected by an internal overload that is UL Certified component. FANS Fans shall be centrifugal direct-drive, double inlet double width, forward curved type. Fan wheels shall be statically and dynamically balanced. TERMINAL BOX All units shall be provided with factory installed terminal box with the fan motor wired to the box. DRAIN PAN Drain Pan shall be die-formed steel, sloped to the piping connection, which will be threaded for easy connection. Internal surface shall be painted with anti-corrosive paint. The drain pan shall be insulated from below the closed cell formed insulation that complies with BS476 part 6 to class 1 requirements. TESTING Manufacturer shall have a test facility to verify the air flow rate at specified external static pressure on all three speeds. It shall also be possible to verify the cooling capacity with water flow rates and temperature shown in the product guide. Verification of Airflow and Capacities shall be an option available at a declared cost. The manufacturing process should have a certified ISO 9000 quality plan. FILTER As an option, 25mm aluminum media filters shall be available. MOTORS Motors shall be 3 speed, permanent split capacitor type with Thermal overload protection. Motors shall have permanently lubricated ball bearings. The motors shall have a class F insulation. Standard motor shall be IP20, IP54 shall be available on as an Engineering Guide # 040 YDFC 0714 Page 20
2008 Certificate of Registration This is to certify that the quality management system of York Guangzhou Air Conditioning and Refrigeration Equipment Co., Ltd. Xuetian, Longshan Town, Fogang County, Qingyuan, Guangdong Province, P. R. China has been assessed and registered by Intertek as conforming to the requirements of ISO 9001: 2008 The quality management system is applicable to: Design and manufacture of room air conditioner, air cooled ducted split air conditioner, air cooled (heat pump) water chiller, air cooled split (heat pumper) water chiller, air cooling heat pump water heater, digital scroll multi-connected air conditioner, YORK VRF (variable refrigerant flow), water cooled floor mounted package air conditioner, air handling unit, fan coil, variable air volume terminals and spare parts. Certificate Number: 111312022 Certificate Issue Date: 21 February 2014 Certificate Expiry Date: 20 February 2017 Authorised Signature: Calin Moldovean President, Business Assurance Intertek Certification Limited, 10A Victory Park, Victory Road, Derby DE24 8ZF, United Kingdom Intertek Certification Limited is a UKAS accredited body under schedule of accreditation no. 014. In the issuance of this certificate, Intertek assumes no liability to any party other than to the client, and then only in accordance with the agreed upon Certification Agreement. This certificate s validity is subject to the organization maintaining their system in accordance with Intertek s requirements for systems certification. Validity may be confirmed via email at certificate.validation@intertek.com or by scanning the code to the right with a smartphone. The annual validity of the certificate can also be checked through the website http://www.cnca.gov.cn of CNCA in China. The certificate remains the property of Intertek, to whom it must be returned upon request. Technical Sales Guide # 040 YDFC 0714 Page 21
Certificate of Registration This is to certify that the environmental management system of York Guangzhou Air Conditioning and Refrigeration Equipment Co., Ltd. Xuetian, Longshan Town, Fogang County, Qingyuan, Guangdong Province, P. R. China has been assessed and registered by Intertek as conforming to the requirements of ISO 14001: 2004 The environmental management system is applicable to the management of the environmental aspects related to: Design and manufacture of room air conditioner, air cooled ducted split air conditioner, air cooled (heat pump) water chiller, air cooled split (heat pumper) water chiller, air cooling heat pump water heater, digital scroll multi-connected air conditioner, YORK VRF (variable refrigerant flow), water cooled floor mounted package air conditioner, air handling unit, fan coil, variable air volume terminals and spare parts. Certificate Number: 121312002 Certificate Issue Date: 21 February 2014 Certificate Expiry Date: 20 February 2017 Authorised Signature: Calin Moldovean President, Business Assurance Intertek Certification Limited, 10A Victory Park, Victory Road, Derby DE24 8ZF, United Kingdom Intertek Certification Limited is a UKAS accredited body under schedule of accreditation no. 014. In the issuance of this certificate, Intertek assumes no liability to any party other than to the client, and then only in accordance with the agreed upon Certification Agreement. This certificate s validity is subject to the organization maintaining their system in accordance with Intertek s requirements for systems certification. Validity may be confirmed via email at certificate.validation@intertek.com or by scanning the code to the right with a smartphone. The annual validity of the certificate can also be checked through the website http://www.cnca.gov.cn of CNCA in China. The certificate remains the property of Intertek, to whom it must be returned upon request. Technical Sales Guide # 040 YDFC 0714 Page 22
Certificate of Registration This is to certify that the occupationa l health & safety management system of York Guangzhou Air Conditioning and Refrigeration Equipment Co., Ltd. Xuetian, Longshan Town, Fogang County, Qi ngyuan, Guangdong Province, P. R. China has been assessed and registered by Intertek as conforming to the requirements of OHSAS 18001: 2007 The occupational health & safety management system is applicable to the management of occupational health and safety risks associated with: Design and manufacture of room air condition er, air cooled ducted split air conditioner, air cooled (heat pump) water chiller, air cooled split (heat pumper) water chiller, air cooling heat pump water heater, digita l scroll multi-connected air conditioner, YORK VRF (variable refrigerant flow), wa ter cooled floor mounted package air conditioner, air handling unit, fan coil, variab le air volume terminals and spare parts. Certificate Number: 05131312002 Certificate Issue Date: 21 February 2014 Certificate Expiry Date: 20 February 2017 Authorised Signature: Calin Moldovean President, Business Assurance Intertek Certif ication Limited, 10A Victory Park, Vict ory Road, Derby DE24 8ZF, United Kingdom Intertek Certification Limited is a UKAS accredited body under schedule of accreditation no. 014. In the issuance of this certificate, Inte rtek assumes no liability to any party other than to the client, and then only in acco rdance with the agreed upon Certification Agreement. This certificate s validity is subject to the organization maintaining their syst em in accordance with Intertek s requireme nts for systems certification. Validit y may be confirmed via email at certificate.validation@intertek.com or by scanning the code to the right with a smartphone. The annual validity of the ce rtificate can also be checked through the website http://www.cnca.gov.cn of CNCA in China. The certificate remains the property of Intertek, to whom it must be returned upon request. Technical Sales Guide # 040 YDFC 0714 Page 23
040 YDFC 0 1 040 YDFC 0