Liquid level control. Thermostatic liquid level regulators, type TEVA. High pressure float valve, type HFI

Similar documents
Modulating liquid level regulators, direct-controlled SV 1 and SV 3

High pressure float valve, type HFI REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Float valve Type HFI. Data sheet

Capacity regulators (hot gas bypass) PMC and CVC

Solenoid valves, type EVRA 3 40 and EVRAT REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Stop check valves type SCA Check valves type CHV Technical leaflet REFRIGERATION AND AIR CONDITIONING

Stop check valves type SCA , SCA-SS Check valves type CHV , CHV-SS Technical leaflet REFRIGERATION AND AIR CONDITIONING

Pressure control valve Type KDC

Pressure and temperature regulators, type PM, and pilot valves

Shut-off Check valves and regulating valves for for Industrial Refrigeration

Pilot operated main valves for regulating pressure and temperature, type PM

Solenoid valves EVRA and EVRAT

Pilot-operated servo valve Type ICS

Pilot-operated servo valve Type ICS

Check & stop valve, SCA-X Check valve, CHV-X

Pilot controlled servo valves Type ICS - Solenoid Valves Pressure Regulating Valves. Technical leaflet MAKING MODERN LIVING POSSIBLE

Pilot-operated servo valve Type ICS

Pilot Controlled Servo Valves ICS

Solenoid valves type EVRA 3 to 40 and EVRAT 10 to 20

Stop check valves, SCA-X Check valves, CHV-X

Shut-off Check valves and regulating valves for for Industrial Refrigeration

Pressure operated water valve Type WVFX and WVS

Shut-off valves in stainless steel SVA-S SS

Expansion valves - 2 of 2

Refrigeration and Air Conditioning Controls. Technical leaflet. Stop valves type SVA 6-10 REFRIGERATION AND AIR CONDITIONING

Pilot valves for servo opereated main valves REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Solenoid valve Types EVR 2 EVR 40 NC/NO

Solenoid valves. Solenoid valves, type PKVD Solenoid valves, type EVR NC / NO

Solenoid valves Type EVR 2 40 NC/ NO REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Thermostatic expansion valves PHT

Liquid level switch Type AKS 38

MAKING MODERN LIVING POSSIBLE. Solenoid valves Type EVU for fluorinated refrigerants REFRIGERATION AND AIR CONDITIONING.

Shut-off valves in stainless steel Types SVA-S SS and SVA-L SS

Electric expansion valves Types AKVA 10, 15 & 20

Pilot valves for servo operated main valves

Solenoid valves type EVR 2 40 NC / NO

Shut-off valves Types SVA-DL and SVA-DH

Filter type FIA (½ - 12 in.) type FIA-SS (½ - 2½ in.) REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Shut-off valves Types SVA-S and SVA-L

SVL product range with butt-weld connection F

Valve Station in stainless steel ICF SS 20 and ICF SS 25

Pilot valves for servo operated main valves

Solenoid valves Type EVU for fluorinated refrigerants

Solenoid valves Type EVU

Filter type FIA (½ - 12 in.) REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Float Switch AKS 38. Technical brochure MAKING MODERN LIVING POSSIBLE

Stop valves SVA-DL & SVA-DH

Solenoid valve for R410A and R744 Types EVR 2 - EVR 6 and EVRH 10 - EVRH 40

Hot gas bypass regulator type CPCE Liquid gas mixer type LG (accessory)

FA + solenoid valve Type ICF 15/20 EVRAT

Filter FIA and FIA-SS

Stop valves SVA-S and SVA-L

Pilot valves Types CVP, CVPP, CVC, CVE, EVM and CVH

Electrically Operated Expansion Valve Types AKV 10, AKV 15 and AKV 20

Injection valve, type TXI 2 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Stop valves SVA-S and SVA-L

Stainless steel - the strong solution

Technical leaflet Thermostatic expansion valves with fixed orifice

CCMT - Electrically operated valves for transcritical and subcritical CO2

Strainers in stainless steel Type FIA SS

Thermo. operated water valve Type WVTS

SVL parts program 65 bar (943 psi) series

Gauge valves Type SNV-ST and SNV-SS

Solenoid valves type EVSA 25 50

Thermostatic expansion valves Type TGE 10, TGE 20 and TGE 40

Stop Needle Valves SNV-ST and SNV-SS

Motor types SMV/SMVE for MEV/MRV motorised valves

DANFOSS. Thermostatic Expansion Valves. Nominal Capacity Ranges in TR for Range N -40 to 50 F R-12 R-22 R-410A R-134A R-404A/

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

Electronically operated expansion valve for CO 2 Type AKVH

HANDBOOK SOLENOID VALVES. Ed SOLENOID VALVES VS-ED 01/ ENG 1

Electric expansion valve for R744 (CO 2 ) Type AKVH

Thermostatic expansion valves type TGE 10, TGE 20 and TGE 40

HANDBOOK VALVES. Ed VALVES VR-ED 02/ ENG 1

Motor Valves type ICM Actuators type ICAD 600,900, 1200 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Temperature regulating valve Type ORV

Thermostatic expansion valves type TGE 10, TGE 20 and TGE 40

Injection valve Type TXI 2

List of Parts for Screw Compressor VMY 347 H and VMY 347 M Model 1994

ISO 9002 Hansen Technologies Corp. Burr Ridge, IL Cert. # Orlando, FL Cert. #

Electric operated valves Type CCM for R744 / CO2

List of Parts for Screw Compressor VMY 447 H and VMY 447 M Model 1994

HANDBOOK SOLENOID VALVES. Ed SOLENOID VALVES VS-ED 01/ ENG 1

Pressure Reducing Valve Type 2114/2415

Crankcase pressure regulator Type KVL

quality products for refrigeration and air conditioning products suitable for CFC, HCFC and HFC 2006 release PRODUCT HANDBOOK

Specifications, Applications, Service Instructions & Parts. HCK1, HCK1W PISTON-TYPE CHECK VALVE ¾" thru 6" (20 thru 150 mm)

High Flow Safety Valves

Crankcase pressure regulator Type KVL

Pressure reducing valve Pressure reducing valve in straightway form DN

Grey cast iron Fig. 600 Page 2. Forged steel High temperature steel Stainless steel Fig. 600/601 (Y) DN15-25 Page 4 DN40-50 Page 6

Grey cast iron Fig. 610 Page 2. Forged steel Stainless steel Fig. 610/612 (Y) Page 4

VTZ variable speed Reciprocating compressors

Excess pressure regulator Excess pressure regulator, straight through DN

ANSI version. The valve closes when the differential pressure rises

Flow-compensated temperature controller AVTQ DN 15

SIHI prime - Side Channel Pumps Self-priming, segmental type with very low NPSH

ARI-STEVI 450 / 451 (DN15-150) Control valve - 3-way-form (mixing/diverting valve) (optional with screwed seat ring)

Technical Information

Thermostatic Expansion Valve

Transcription:

Liquid level control Contents Page Thermostatic liquid level regulators, type TEVA Introduction... 7 Materials... 7 Technical data... 7 Ordering... 8 Identification... 8 Capacity... 9 Design/Function... 9 Dimensions and weights...10 High pressure float valve, type HFI Introduction... 11 Features... 11 Design... 12 Technical data... 12 The principle of high pressure control... 13 Computation and selection... 14 Capacity tables - SI units... 14 Capacity tables - US units... 15 High pressure control in refrigeration system with condenser/evaporator... 16 Material specification... 17 Connections... 18 Dimensions and weights...19 Volumes... 20 Ordering... 20 Modulating liquid level regulators, direct-controlled, type SV 1 and 3 Introduction... 21 Technical data... 21 Approvals... 21 Identification... 21 Dimensioning example for SV (L)... 21 Ordering... 22 Pipe dimensions... 22 Capacity... 23 Design/Function... 24 SV 1-3 used as a high pressure defrost drain float valve... 28 Dimensions and weight... 29 ã Danfoss A/S (RC-CM/hbs), 12-2002 RK0YQ102 3

Liquid level control Contents Page Modulating liquid level regulators, types SV 4, 5 and 6 Introduction... 31 Features... 31 Technical data... 31 Approvals... 31 Identification... 31 Materials... 32 Dimensioning example for SV... 32 Capacity... 33 Construction/Function... 34 Application... 37 Dimensions and weight... 38 Ordering... 39 Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Introduction... 41 Features... 41 Technical data... 41 Design/Function... 42 PMFL... 42 PMFH... 44 Sizing... 46 Capacity in kw... 47 R 717 (NH3)... 47 R 22... 48 Material specification... 49 Ordering... 51 Dimensions and weights... 54 Liquid level alarms, safety switches, liquid level regulators, RT 280A, RT 281A Introduction... 55 Materials... 55 Technical data... 55 Ordering... 56 Design/Function... 56 Dimensions and weight... 56 Liquid level glasses, type LLG 185-1550 Introduction... 57 Features... 57 Design... 58 Technical data... 58 Frostproof liquid level glasses... 59 Material specification... 61 Dimensions and weights... 62 Ordering... 63 4 RK0YQ102 ã Danfoss A/S (RC-CM/hbs), 12-2002

Liquid level control Contents Page Motorised valve, type MEV Introduction... 65 Features... 65 Design... 66 Technical data... 66 Function... 67 Application examples for MEV... 68 Ordering... 69 Nominal capacities... 70 R717 (NH 3 )... 70 R22... 71 Material specification... 72 Dimensions and weight... 74 Motor types SMV/SMVE for MEV/MRV motorised valves Introduction... 75 Features... 75 Design... 75 Technical data... 76 Function... 76 Applications... 77 SMV connection... 78 SMVE connection... 78 Dimensions... 79 Ordering... 80 Accessories... 80 ã Danfoss A/S (RC-CM/hbs), 12-2002 RK0YQ102 5

Thermostatic liquid level regulators type TEVA Introduction TEVA valves are designed for use as liquid level regulators for flooded evaporators, intermediate receivers, and liquid separators. Materials Valve housing made of GGG40.3 Gaskets are non asbestos Technical data Refrigerant R 717 (NH 3 ). Can also be used for R 22. Temperature of medium -50 +10 C Capillary tube length 5 m Connection for external pressure equalization 1 /4 in. (Æ 6.5 / Æ 10 mm) weld nipple or 8 mm cutting ring connection. Approvals DSRK Max. working pressure PB = 19 bar Max. test pressure p = 28.5 bar Voltage and consumption 24 V a.c. 10 W Length of electric cable 1.5 m ã Danfoss A/S (RC-CM/hbs), 09-2002 Technical leaflet - RD2AA202 7

Thermostatic liquid level regulators, type TEVA Ordering Separate thermostatic element with electric heater for TEVA 20 and 85, code no. 068G3255. Separate electric heater for TEVA 20 and 85, code no. 068G0037. Extra weld bush for bulb, including coupling nut, sealing plug and gasket, code no. 068G0026. Type and rated capacity in tons (TR) Rated capacity R 717 1 ) (NH 3 ) kw Inlet in. Connection weld flanges Outlet in. Ass. regulator with strainer 2 ) Code no. Ass. regulator without strainer 2 ) Separate orifice assembly TEVA 20 068G6040 TEVA 20-1 3.5 1/2 1/2 + 068G6040 068G2050 006-0042 068G6041 TEVA 20-2 7.0 1/2 1/2 + 068G6041 068G2051 006-0042 068G6042 TEVA 20-3 10.5 1 /2 1 /2 + 068G6042 068G2052 006-0042 068G6043 TEVA 20-5 17.5 1/2 1/2 + 068G6043 068G2053 006-0042 068G6044 TEVA 20-8 30.0 1/2 1/2 + 068G6044 068G2054 006-0042 068G6045 TEVA 20-12 42.0 1 /2 1 /2 + 068G6045 068G2055 006-0042 068G6046 TEVA 20-20 70.0 1/2 1/2 + 068G6046 068G2056 006-0042 TEVA 85 068G6047 TEVA 85-33 115 3/4 3/4 + 068G6047 068G2057 006-0048 068G6048 TEVA 85-55 195 3/4 3/4 + 068G6048 068G2058 006-0048 068G6049 TEVA 85-85 295 3 /4 3 /4 + 068G6049 068G2059 006-0048 1 ) The rated capacity is the regulator capacity at -15 C evaporating temperature and +32 C condensing temperature. The capacities are based on 4 C subcooling ahead of the regulator. 2 ) The strainer is supplied with gaskets, bolts and nuts. Note: Subcooling of the liquid in front of the valve is essential for the function of the valve. Lack of subcooling will lead to malfunction of the valve and increase wear on orifice. Identification The thermostatic element has a white label on the top. The colour refers to the refrigerant for which the valve is designed: R 717 (NH 3 ). The orifice assembly is market with the valve type (TEVA 20) rated capacity (8 TR = 28 kw), refrigerant (R 717 = NH 3 ), and date marking (394 = week 39, 1994). Element label Stamping on orifice assembly 8 Technical leaflet - RD2AA202 ã Danfoss A/S (RC-CM/hbs), 09-2002

Thermostatic liquid level regulators, type TEVA Capacity The capacities apply to the evaporating temperature range -50 +10 C. R 717 (NH 3 ) Type and rated capacity in tons Capacity in kw at pressure drop across regulator 1 ) Dp bar (TR) 2 4 6 8 10 12 14 16 TEVA 20 kw TEVA 20-1 1.7 2.4 2.9 3.2 3.5 3.7 3.8 4.0 TEVA 20-2 3.6 4.9 5.8 6.5 7.0 7.4 7.8 8.1 TEVA 20-3 5.5 7.4 8.6 9.7 10.5 10.9 11.5 12.0 TEVA 20-5 9.2 12.4 14.8 16.3 17.6 18.5 19.4 20.4 TEVA 20-8 14.5 19.8 22.7 25.6 27.9 29.0 30.8 32.0 TEVA 20-12 22.1 29.7 33.7 39.0 41.9 44.2 46.5 48.8 TEVA 20-20 36.6 50.0 58.0 64.5 70.4 74.4 77.9 81.4 TEVA 85 TEVA 85-33 60.5 82.0 96.0 107 116 122 130 135 TEVA 85-55 98.9 137 160 179 192 201 213 224 TEVA 85-85 150 207 243 276 298 312 329 340 1 ) Dp is generally the pressure difference between condensing and evaporating pressures. In the case of other substantial pressure drops, e.g. due to resistance in long liquid lines, across fittings or difference in height between evaporator and receiver, these pressure drops should be taken into account. Capacity tables for TEA and TEAT can also be used as the orifice assembly in the valves are the same. Design Function Thermostatic liquid level regulator type TEVA consists of a thermostatic expansion valve with a bulb containing a low voltage electric heating element. The purpose of the bulb is to transmit a "superheat signal", to the regulator independent of the temperature of the vapour drawn from the evaporator. A weld bush is supplied with the bulb for welding into the evaporator or receiver at the required liquid level height. The bulb is fitted in the weld bush. With the TEVA fitted and the heating element connected, heat is supplied to the bulb. If the liquid level is below the bulb, the heat will not dissipate and pressure across the valve diaphragm will rise. When the liquid level reaches the bulb, the heat in the bulb will dissipate through the refrigerant liquid and the regulator will throttle or shut off completely. Note: The TEVA valve is not able to close completely tight, so a solenoid valve is needed to shut off liquid supply when system stops. 1. Thermostatic element (diaphragm) 2. Orifice assembly 3. Valve body 4. Setting spindle 5. Ext. pressure equalizing connection TEVA 20 / TEVA 85 ã Danfoss A/S (RC-CM/hbs), 09-2002 Technical leaflet - RD2AA202 9

Thermostatic liquid level regulators, type TEVA Dimensions and weights Type H 1 mm H 2 mm H 3 mm H 4 mm Without strainer mm Weight TEVA 20 94 38 25 96 110 164 80 2.1 3.0 TEVA 85 104 37 35 106 125 199 95 3.0 4.5 L With strainer mm B mm Without strainer kg With strainer kg 10 Technical leaflet - RD2AA202 ã Danfoss A/S (RC-CM/hbs), 09-2002

High pressure float valve type HFI Introduction HFI is a high pressure float valve with internal liquid measuring device The float valve is designed for direct flange mounting or welding on to plate heat exchanger type condensers, as illustrated in fig 1 HFI is direct acting, therefore no differential pressure is required to activate the valve HFI is sturdy and reliable owing to its simple design The float valve is equipped with a purge valve for purging non condensable gases e g air from the top of the valve housing This facility is also useful if the valve has to be serviced Fig 1 Features Designed for direct flange mounting on to plate heat exchanger type condensers Can be mounted directly on vessels Temperature range: 50/+80 C ( 58/+176 F) Equipped with purge valve for purging non condensable gasses Maximum operating pressure is 25 bar g (363 psi g) Suitable for ammonia and other refrigerants with a density of 500 through 700 kg/m 3 (31 21-43 70 lb/ft 3 ) Housing i e shell and flange are made of special steel approved for low temperature application Classification: To get an updated list of certification on the products please contact your local Danfoss Sales Company ã Danfoss A/S (RC-CM / MWA), 09-2002 Technical leaflet - RD2BE202 11

High pressure float valve, type HFI Design Available connections Flange: Inlet: Flange DN 100 or DN 150 (DIN-2635/ DIN 2512-F) Outlet: Welding connection DN 50 (DIN 2448) Butt-weld, DIN: Inlet: DN 100 or DN 150 (DIN 2448) Outlet: Welding connection DN 50 (DIN 2448) Butt-weld, ANSI: Inlet: DN 100 (4 in ) or DN 150 (6 in ) (ANSI B 36 10) Outlet: Welding connection DN 50 (2 in ) (ANSI 36 10) Housing Housing i e shell and flange is made of special steel approved for low temperature operation Installation Refer to installation instruction for HFI Identification: Pressure Equipment Directive (PED) The HFI-valves are approved in accordance with the European standard specified in the Pressure Equipment Directive and are CE marked For further details / restrictions - see Installation Instruction Nominal bore Classified for Category HFI valves DN 100 and 150 mm. (4 in. and 6 in.) Fluid group I III Technical data Refrigerants HFI as standard can be used for R 717 (ammonia) and other refrigerants with a density of 500 through 700 kg/m 3 (31 21-43 70 lb/ft 3 ) If the density of the refrigerant in question is outside this range, please contact your local Danfoss Sales Company Flammable hydrocarbons are not recommended For further information please contact your local Danfoss Sales Company Temperature range 50/+80 C ( 58/+176 F) Pressure The float valve is designed for: Maximum operating pressure: 25 bar g (363 psi g) Strength test without float ball: 50 bar g (725 psi g) Leakage test: 25 bar g (363 psi g) Valves for higher pressure are available on request 12 Technical leaflet - RD2BE202 ã Danfoss A/S (RC-CM / MWA), 09-2002

High pressure float valve, type HFI The principle of high pressure control Introduction In installations with one application high pressure control is an effective and cost saving way of expanding liquid from the condenser to the low pressure side High pressure refrigerant entering the condenser will start to condense, consequently condensate will accumulate at the bottom of the condenser and in the float valve When capacity demands increase, the liquid level in the float valve will rise, which will cause the valve to open and the refrigerant to expand into the separator at the low pressure side Fig 2 shows how the HFI works In pos (a) the valve is closed When the liquid in the float valve rises to the level of pos (b) the slide will have moved approx half of its total travel, however, the valve has only reached approx 25 % of its maximum capacity Pos (c) illustrates the fully opened valve The curve shows how the capacity increase will be relatively larger as the slide moves, due to the nozzle design This ensures perfect regulation throughout the whole capacity area from part load to full load When the valve is closed, there will still be a small by-pass over the seat, so any remaining liquid will equalize slowly to the low pressure side, for instance during an off cycle Therefore the system will equalize automatically and the compressor can start up without excessive back pressure The size of the bypass is predetermined and set in the adjustment of the float assembly However, the bypass can, if required, be set to a minimum by readjusting the position of the slide position (d) (see installation instruction for HFI) It follows from the above, that almost all the refrigerant will be accumulated on the low pressure side under normal conditions Therefore under normal conditions no high pressure receiver is necessary when using the HFI for high pressure control Fig 2, function of the HFI Computation and selection In R 717 plants (ammonia) On the following pages you will find tables with capacities of the float valve at various operating conditions Select a valve using the specific operating conditions The chosen valve must have a capacity higher than the required capacity during nominal operation, as well as during plant start up In plants using other refrigerants than ammonia The capacity of the float valve can be calculated by using the values and the equation to the right However, the density of the refrigerant must be in the range: 500 to 700 kg/m 3 For densities outside this range please contact your local Danfoss Sales Company Valve type Nominal capacity [kw] Valve (R 717, 10/+35 C) constant [K] HFI 040 FD 400 16 79 HFI 050 FD 800 33 58 HFI 060 FD 1200 50 36 Mass flow G = K p ρ [ kg/h] Dp = differential pressure [bar] r = density of liquid [kg/m 3 ] K = valve constant (from the above table) ã Danfoss A/S (RC-CM / MWA), 09-2002 Technical leaflet - RD2BE202 13

High pressure float valve, type HFI Computation and selection capacity tables - SI units HFI 040 - R 717, evaporating capacity [kw] Condensing Evaporating temperature ( C) temp ( C) 40 35 30 25 20 15 10 5 0 5 10 15 20 50 475 480 480 475 475 475 470 460 455 445 430 415 395 45 460 460 460 460 455 455 445 440 430 420 405 385 360 40 440 440 440 440 435 430 425 415 405 390 375 350 325 35 420 420 420 415 415 405 400 390 375 360 340 315 280 30 400 400 400 395 390 385 375 360 345 325 300 270 230 25 380 380 375 370 365 360 345 330 315 290 260 220 160 20 360 355 355 350 340 330 315 300 280 250 210 155 15 340 335 330 325 315 300 285 265 240 200 150 10 315 310 305 295 285 270 250 225 195 140 5 290 285 280 270 255 240 215 185 135 0 270 260 255 240 225 205 175 125 5 245 235 225 210 190 165 120 10 220 210 200 180 155 115 HFI 050 - R 717, evaporating capacity [kw] Condensing Evaporating temperature ( C) temp ( C) 40 35 30 25 20 15 10 5 0 5 10 15 20 50 955 955 955 955 950 945 935 925 910 890 865 830 790 45 920 920 920 915 910 905 895 880 860 835 805 770 725 40 880 880 880 875 870 860 850 830 810 780 745 700 645 35 845 845 840 835 825 815 800 780 755 720 680 625 560 30 805 800 800 790 780 765 750 725 695 655 605 540 455 25 765 760 755 745 730 715 695 665 630 580 520 440 320 20 720 715 705 695 680 660 635 600 555 500 420 310 15 675 670 660 645 630 605 570 530 480 405 295 10 630 625 610 595 570 545 505 455 385 285 5 585 575 560 540 515 480 430 365 270 0 540 525 505 485 450 405 345 255 5 490 475 455 425 385 325 240 10 440 420 395 360 305 230 HFI 060 - R 717, evaporating capacity [kw] Condensing Evaporating temperature ( C) temp ( C) 40 35 30 25 20 15 10 5 0 5 10 15 20 50 1430 1435 1435 1430 1425 1420 1405 1385 1365 1335 1295 1245 1190 45 1380 1380 1380 1375 1370 1360 1340 1320 1290 1255 1210 1155 1085 40 1325 1325 1320 1315 1305 1290 1270 1245 1215 1170 1120 1055 970 35 1265 1265 1260 1250 1240 1220 1200 1170 1130 1080 1020 940 840 30 1205 1205 1195 1185 1170 1150 1120 1085 1040 980 905 810 685 25 1145 1140 1130 1115 1100 1075 1040 995 940 870 780 660 485 20 1080 1070 1060 1045 1020 990 950 900 835 750 635 465 15 1015 1005 990 970 940 905 860 795 715 605 445 10 945 935 915 890 860 815 755 680 580 425 5 875 860 840 810 770 720 645 550 405 0 805 785 760 725 675 610 520 380 5 735 710 680 635 575 490 360 10 660 635 595 540 460 340 14 Technical leaflet - RD2BE202 ã Danfoss A/S (RC-CM / MWA), 09-2002

High pressure float valve, type HFI Computation and selection capacity tables - US units HFI 040 - R 717, evaporating capacity [TR] Condensing Evaporating temperature ( F) temp ( F) 40 30 20 10 0 10 20 30 40 50 60 70 80 120 134 135 135 134 134 132 131 128 125 121 116 109 101 110 129 129 129 128 127 126 123 121 117 112 106 98 87 100 123 123 122 122 120 118 116 112 108 102 94 84 71 90 117 117 116 115 113 111 107 103 98 91 81 69 50 80 110 110 109 107 105 102 99 94 87 78 66 49 70 103 103 102 100 97 94 89 83 75 63 47 60 97 96 94 92 89 84 79 71 60 44 50 90 88 86 83 80 74 67 57 42 40 82 81 78 75 70 63 54 40 30 75 73 70 65 59 51 38 20 67 65 61 55 47 35 10 59 56 51 44 33 HFI 050 - R 717, evaporating capacity [TR] Condensing Evaporating temperature ( F) temp ( F) 40 30 20 10 0 10 20 30 40 50 60 70 80 120 268 269 269 269 267 265 261 256 250 242 231 218 201 110 258 258 257 256 254 251 247 241 233 224 211 195 175 100 246 246 245 243 241 237 232 224 215 204 189 169 143 90 234 233 232 229 226 221 215 207 196 181 163 138 101 80 221 220 218 215 211 205 197 187 174 156 132 97 70 207 206 203 200 194 187 178 166 149 127 93 60 193 191 188 184 177 169 157 142 121 89 50 179 176 172 167 159 149 134 114 84 40 165 161 156 149 140 127 108 80 30 150 145 139 130 118 102 75 20 135 129 121 110 95 70 10 119 112 102 88 65 HFI 060 - R 717, evaporating capacity [TR] Condensing Evaporating temperature ( F) temp ( F) 40 30 20 10 0 10 20 30 40 50 60 70 80 120 403 404 404 403 401 397 392 385 375 363 347 327 302 110 386 387 386 384 381 377 370 362 350 335 317 293 262 100 369 368 367 365 361 355 347 337 323 305 283 253 214 90 350 350 348 344 339 332 322 310 293 272 244 207 151 80 331 329 327 322 316 307 296 281 261 234 199 146 70 310 309 305 299 292 281 267 249 224 190 140 60 290 287 282 275 266 253 236 213 181 133 50 269 265 259 250 239 223 202 172 126 40 247 242 234 224 209 190 162 120 30 225 218 209 196 178 152 113 20 202 194 182 165 142 106 10 178 168 153 132 98 ã Danfoss A/S (RC-CM / MWA), 09-2002 Technical leaflet - RD2BE202 15

High pressure float valve, type HFI High pressure control in refrigeration system with condenser/evaporator Example 1 shows a water chiller with plate heat exchanger as both condenser and evaporator HFI is flanged directly on to the condenser Example 1 Compressor Vapor Liquid High pressure Float Valve - HFI High pressure condenser Water chiller (evaporator) 16 Technical leaflet - RD2BE202 ã Danfoss A/S (RC-CM / MWA), 09-2002

High pressure float valve, type HFI Material specification Fig 3 No Part Material DIN/EN ISO ASTM 1 Housing: a Shell Steel TTSt 35 N, 17173 TW6, 2604/3 Grade 1, A333, A334 b Flange (shell) Steel P275 NL1, EN 10 028-3 c Flange (inlet) Steel P275 NL1, EN 10 028-3 d Branch (discharge) Steel TTSt 35 N/V, 17173 TW6, 2604/3 Grade 1, A333, A334 3 End cover with cylinder Steel P275 NL1, EN 10 028-3 4 Set screw Stainless steel A2-70 A2-70 5 Tube Steel 6 Gasket Aluminium 7 Purge valve, SNV 8 1 ) 8 Gasket Non asbestos 9 Float Ball Steel 1 ) for further information please see the datasheet for SNV stop valves ã Danfoss A/S (RC-CM / MWA), 09-2002 Technical leaflet - RD2BE202 17

High pressure float valve, type HFI Connections DIN - Outlet Butt welding DIN (2448) Size mm Size in. OD mm T mm Outlet OD in. T in. For use with valve type 100 4 60.3 2.9 150 6 60.3 2.9 2.37 0.11 2.37 0.11 HFI 40 HFI 50 HFI 60 HFI 50 HFI 60 ANSI - Outlet Butt welding ANSI B 36 10 Size mm Size in. OD mm T mm Outlet OD in. T in. For use with valve type 100 4 60.3 2.9 150 6 60.3 2.9 2.37 0.11 2.37 0.11 HFI 40 HFI 50 HFI 60 HFI 50 HFI 60 DIN - Inlet Butt welding DIN (2448) Size mm Size in. OD mm T mm Inlet OD in. T in. For use with valve type 100 4 114.3 3.6 4.50 0.14 150 6 168.3 4.5 6.63 0.18 HFI 40 HFI 50 HFI 60 HFI 50 HFI 60 ANSI - Inlet Butt welding ANSI B 36 10 Size mm Size in. OD mm T mm Inlet OD in. T in. For use with valve type 100 4 114.3 6.0 4.50 0.24 150 6 168.3 7.1 6.63 0.28 HFI 40 HFI 50 HFI 60 HFI 50 HFI 60 Inlet flange 40 bar / DIN 2635 / DIN 2512-F* D b k d 42 d 43 F d 2 Z Size 100 (4 in.) Size 100 (4 in.) mm 235 24 190 129 149 4.5 22 in. 9.3 0.94 7.48 5.08 5.87 0.18 0.97 mm 300 28 250 183 203 4.5 26 in. 11.8 1.1 9.84 7.2 7.99 0.18 1.02 8 pcs. 8 pcs. *Inlet flange and DIN outlet 18 Technical leaflet - RD2BE202 ã Danfoss A/S (RC-CM / MWA), 09-2002

High pressure float valve, type HFI Dimensions and weights Fig 4 High pressure float valve without flange (Fig. 4) Valve size A 1 A 2 A 3 B C ØD F min. Weight HFI 100 HFI 150 mm mm 192 167 113 113 25 276 276 435 435 219 219 200 200 37 kg 37 kg in. in. 7.56 6.57 4.45 4.45 0.98 10.87 10.87 17.13 17.13 8.62 8.62 7.87 7.87 81.5 lb 81.5 lb Specified weights are approximate values only Fig 5 High pressure float valve with flange (Fig. 5) Valve size A 1 A 2 A 3 B C ØD F min. Weight HFI 100 HFI 150 mm mm 192 167 180 189 25 317 309 511 502 219 219 200 200 41 kg 41 kg in. in. 7.56 6.57 7.09 7.44 0.98 12.48 12.17 20.12 19.76 8.62 8.62 7.87 7.87 90.4 lb 90.4 lb Specified weights are approximate values only ã Danfoss A/S (RC-CM / MWA), 09-2002 Technical leaflet - RD2BE202 19

High pressure float valve, type HFI Volumes max min Fig 6 Internal volume (gross): 8 2 10 3 m 3 (2 17 USgal) Internal volume with float ball: 6 4 10 3 m 3 (1 69 USgal) Liquid volume at max level: 4 6 10 3 m 3 (1 22 USgal) Liquid volume at min level: 1 6 10 3 m 3 (0 42 USgal) Ordering FD = inlet flange DIN D = Butt welding DIN A = Butt welding ANSI The table below is used to identify the valve required Example: HFI 100 D 040 = 148G3092 Type Inlet connection size Nozzle size Code numbers HFI 100 FD 040 40 148G3102 HFI 100 FD 050 100 DIN Flange 50 148G3103 HFI 100 FD 060 60 148G3104 HFI 150 FD 050 50 148G3105 150 DIN Flange HFI 150 FD 060 60 148G3106 HFI 100 D 040 40 148G3092 HFI 100 D 050 100 DIN BW 50 148G3093 HFI 100 D 060 60 148G3094 HFI 150 D 050 50 148G3095 150 DIN BW HFI 150 D 060 60 148G3096 HFI 100 A 040 40 148G3097 HFI 100 A 050 100 ANSI BW 50 148G3098 HFI 100 A 060 60 148G3099 HFI 150 A 050 50 148G3100 150 ANSI BW HFI 150 A 060 60 148G3101 20 Technical leaflet - RD2BE202 ã Danfoss A/S (RC-CM / MWA), 09-2002

Modulating liquid level regulators, direct-controlled type SV 1 and 3 Introduction The SV 1 and 3 can be used separately as a modulating liquid level regulator in refrigerating, freezing and air conditioning systems for ammonia or fluorinated refrigerants. However, in most cases, the SV is used as a float pilot valve for the main expansion valve type PMFL or PMFH. Technical data Refrigerant R 717, R 22, 134a, 404A and other fluorinated refrigerants P band 35 mm Temperature of medium -50 +65 C Max. working pressure PB = 28 bar Max. test pressure p' = 36 bar k v value for float orifice SV 1 = 0.06 m 3 /h SV 3 = 0.14 m 3 /h The highest k v value for the built-in throttle valve is 0.18 m 3 /h. The throttle valve can be used both in parallel and in series with the float orifice. Approvals Pressure Equipment Directive (PED) SV1 and 3 are approved in accordance with the European standard specified in the Pressure Equipment Directive and are CE marked. For further details / restrictions - see Installation Instruction Classified for Category SV1 and 3 Fluid group I I Identification Dimensioning example for SV (L) Refrigerant R 717 (NH 3 ) Evaporating capacity Q e = 27 kw Evaporating temperature t e = -10 C (~ p e = 2.9 bar abs.) Condensing temperature t c = +30 C (~ p c = 11.7 bar abs.) Liquid temperature for SV t l = +20 C Subcooling Dt sub = t c - t l = 30 C - 20 C = 10 K Pressure drop in SV Dp = p c - p e = 11.7-2.9 = 8.8 bar Correction factor k for 10 K subcooling 0.98 Corrected capacity 27 0.98 = 26.4 kw At t e = -10 C and Dp = 8 bar SV 1 yields 27 kw and can therefore be used. If SV 3 is used for this capacity, it will mean a small offset. ã Danfoss A/S (RC-CM / MWA), 06-2002 Technical leaflet - RD2BB302 21

Modulating liquid level regulators, direct-controlled, type SV 1 and 3 Ordering Regulator The code nos. stated apply to liquid level regulators type SV 1 and SV 3 incl. Æ 6.5 / Æ 10 mm weld connection 1 ) for the pilot line. Balance tube connection (liquid/vapour): 1 in. weld / 1 1 /8 in. solder. The rated capacity refers to the valve capacity at evaporating temperature t e = +5 C, condensing temp. t c = +32 C and liquid temperature t l = +28 C. Valve type Code no. Rated capacity in kw R 717 R 22 R 134a R 404A R 12 R 502 SV 1 027B2021 25 4.7 3.9 3.7 3.1 3.4 SV 3 027B2023 64 13 10.0 9.7 7.9 8.8 SV 1 027B2021CE* 25 4.7 3.9 3.7 3.1 3.4 SV 3 027B2023CE* 64 13 10.0 9.7 7.9 8.8 1 ) 3/8 in. flare connection can be supplied under code no. 027B2033. *CE-marked Spare parts and accessories See spare parts catalogue. Pipe dimensions Liquid line The following suggested dimensions for the liquid line, which is connected to the nipple pos. C, see "Design / Function", are based on a maximum velocity in a line with subcooled ammonia of approx. 1 m/s and a maximum velocity in a line with subcooled fluorinated refrigerant of approx. 0.5 m/s. 1. R 717 (ammonia) Dimensions Type 0.8 bar < Dp sv < 4 bar 4 bar < Dp sv < 16 bar Steel tube Steel tube SV 1 3/8 in. 3/8 in. SV 3 3/8 in. 1/2 in. 2. R 22, R 134a, R 404A Dimensions Type 0.8 bar < Dp sv < 4 bar 4 bar < Dp sv < 16 bar Steel tube Copper tube Steel tube Copper tube SV 1 3/8 in. 3/8 in. 3/8 in. 1/2 in. SV 3 3/8 in. 5/8 in. 1/2 in. 3/4 in. Upper balance pipe (connect to pos. D on SV (L) Type SV (L) 1 SV (L) 3 Dimensions 1 in. 1 1 /2 in. 22 Technical leaflet - RD2BB302 ã Danfoss A/S (RC-CM / MWA), 06-2002

Modulating liquid level regulators, direct-controlled, type SV 1 and 3 Capacity The values in the capacity tables are based on a subcooling of 4 K just ahead of the SV valve. If the subcooling is more or less than 4 K, refer to the following correction factors. Type Evaporating temperature t e Capacity in kw at pressure drop across valve Dp bar C 0.8 1.2 1.6 2 4 8 12 16 R 717 (NH 3 ) SV 1 +10 9.5 11 13 15 20 27 30 0 9.9 12 14 15 20 27 31 33-10 10 12 14 15 21 27 31 33-20 11 12 14 15 21 27 30 33-30 11 12 14 15 20 26 30 33-40 11 13 14 15 20 26 29 32-50 11 12 13 15 20 26 29 32 SV 3 +10 25 31 35 39 52 71 77 0 26 32 36 40 52 69 78 83-10 26 32 36 40 52 68 77 83-20 26 31 35 39 52 67 76 82-30 25 30 34 38 50 66 75 82-40 24 29 33 36 49 65 73 80-50 23 27 31 35 47 64 71 79 Type Evaporating temperature t e Capacity in kw at pressure drop across valve Dp bar C 0.8 1.2 1.6 2 4 8 12 16 R 22 SV 1 +10 2.2 2.6 3.0 3.2 4.2 4.8 5.7 5.7 0 2.3 2.7 3.1 3.4 4.4 4.9 5.8 5.8-10 2.4 2.8 3.2 3.5 4.5 5.0 5.8 5.9-20 2.4 2.9 3.3 3.6 4.6 5.0 5.8 5.8-30 2.5 2.9 3.3 3.6 4.5 5.0 5.7 5.7-40 2.5 2.9 3.3 3.6 4.4 4.9 5.6 5.6-50 2.6 2.9 3.3 3.5 4.3 4.8 5.4 5.4 SV 3 +10 5.6 6.8 7.7 8.5 11 13 15 15 0 5.8 7.0 8.0 8.8 11 13 15 15-10 6.0 7.3 8.2 9.0 12 13 15 15-20 6.1 7.3 8.3 8.9 11 13 14 15-30 6.2 7.3 8.1 8.8 11 12 14 14-40 6.1 7.1 7.9 8.5 11 12 14 14-50 5.9 6.9 7.6 8.2 11 12 13 14 Correction factors When dimensioning, multiply the evaporator capacity by a correction factor k dependent on the subcooling Dt sub just ahead of the valve. The corrected capacity can then be found in the capacity table. R717 (NH 3 ) Dt K 2 4 10 15 20 25 30 35 40 45 50 k 1.01 1.00 0.98 0.96 0.94 0.92 0.91 0.89 0.87 0.86 0.85 R22 Dt K 2 4 10 15 20 25 30 35 40 45 50 k 1.01 1.00 0.96 0.93 0.90 0.87 0.85 0.83 0.80 0.78 0.77 ã Danfoss A/S (RC-CM / MWA), 06-2002 Technical leaflet - RD2BB302 23

Modulating liquid level regulators, direct-controlled, type SV 1 and 3 Design Function SV with low-pressure function C. Nipple D. Connection for balance pipe P. Parallel connection of pos. C (screw 25 in pos. A) S. Series connection of pos. C (screw 25 in pos. B) No. Part Material DIN / EN 1 Float Housing Stainless steel Low temperature, steel X5CrNi18-10, DIN 17440 P285QH, EN 10222_4 2 Float Stainless steel 3 Split pin Steel 4 Float arm Stainless steel 5 Link Steel 6 Pin Stainless steel 7 Valve housing Steel 8 O-ring Cloroprene (Neoprene) 9 Float orifice Plastic 10 Manual regulation unit. Steel Throttle valve 11 Gasket Non asbestos 12 Plug Steel 13 O-ring Cloroprene (Neoprene) 14 Pilot connection Steel (spare part) 15 Orifice needle Plastic 16 O-ring Cloroprene (Neoprene) 17 Screw Steel 18 Gasket Non asbestos 19 Pin Steel 20 Cover Low temperature, cast iron (spherical) EN-GJS-400-18-LT EN 1563 21 Screw Stainless steel A2-70 22 Gasket Non asbestos 23 Label cardboard 25 Screw Steel 26 Spring washer Steel 28 Sign Aluminium 24 Technical leaflet - RD2BB302 ã Danfoss A/S (RC-CM / MWA), 06-2002

Modulating liquid level regulators, direct-controlled, type SV 1 and 3 Design Function (continued) SV (L), low-pressure function SV (L) is used for small, flooded evaporators, where only slight variations in the liquid level can be accepted. When the liquid level falls, the float pos. (2) moves downwards. This draws the needle pos. (15) away from the orifice and the amount of liquid injected is increased. The liquid inlet line, which is mounted on the nipple pos. (C), should be dimensioned in such a way that acceptable liquid velocities and pressure drops are obtained. This is particularly important when the liquid is only slightly subcooled, since valve capacity is reduced considerably if flashgas occurs in the liquid ahead of the orifice and wear is strongly increased. See the suggested dimensions for the liquid line in "Pipe dimensions". The flashgas quantity which occurs on expansion is removed through the balance pipe from pos. (D). On refrigeration plant using fluorinated refrigerants, slight subcooling and a large pressure drop can give a flashgas quantity of approx. 50% of the injected liquid quantity. Therefore the pressure drop in this balance pipe must be kept at a minimum, since there will otherwise be a risk that - the liquid level in the evaporator will vary to an unacceptable degree as a function of evaporator load - the absolute difference between the liquid level of the evaporator and the SV valve will be too large. See the suggested dimensions for the balance pipe in "Pipe dimensions". ã Danfoss A/S (RC-CM / MWA), 06-2002 Technical leaflet - RD2BB302 25

Modulating liquid level regulators, direct-controlled, type SV 1 and 3 Design Function (continued) SV with high-pressure function C. Nipple D. Connection for balance pipe P. Parallel connection of pos. C (screw 25 in pos. A) S. Series connection of pos. C (screw 25 in pos. B) No. Part Material DIN / EN 1 Float Housing Stainless steel Low temperature, steel X5CrNi18-10, DIN 17440 P285QH, EN 10222_4 2 Float Stainless steel 3 Split pin Steel 4 Float arm Stainless steel 5 Link Steel 6 Pin Stainless steel 7 Valve housing Steel 8 O-ring Cloroprene (Neoprene) 9 Float orifice Plastic 10 Manual regulation unit. Steel Throttle valve 11 Gasket Non asbestos 12 Plug Steel 13 O-ring Cloroprene (Neoprene) 14 Pilot connection Steel (spare part) 15 Orifice needle Plastic 16 O-ring Cloroprene (Neoprene) 17 Screw Steel 18 Gasket Non asbestos 19 Pin Steel 20 Cover Low temperature, cast iron (spherical) EN-GJS-400-18-LT EN 1563 21 Screw Stainless steel A2-70 22 Gasket Non asbestos 23 Label cardboard 25 Screw Steel 26 Spring washer Steel 28 Sign Aluminium 26 Technical leaflet - RD2BB302 ã Danfoss A/S (RC-CM / MWA), 06-2002

Modulating liquid level regulators, direct-controlled, type SV 1 and 3 Design Function (continued) SV (H), high-pressure function SV (H) is used as a liquid level regulator for small condensers or receivers. When the liquid level rises, the float pos. (2) moves upwards. This draws the needle pos. (15) away from the orifice and the excess liquid is drawn away. On refrigeration plant using fluorinated refrigerants slight subcooling and a large pressure drop can, as already mentioned, cause the formation of a large amount of flashgas. This mixture of liquid and vapour has to pass through the nipple pos. (C) and out into the liquidline. If the dimensions of the line are too small, a pressure drop will occur which can reduce the capacity of the SV (H) valve considerably. This will mean a risk of inadvertent liquid accumulation in the condenser or receiver. See the suggested dimensions for the liquid line in "Pipe dimensions". The connection nipple (C) can be mounted either in P or in S. P-connection P-connection (= parallel) With P-connection an SV with closed float orifice will have a capacity which corresponds to the degree of opening of the adjustable throttle valve 10. S-connection S-connection (= series) With S-connection the throttle valve 10 will function as a pre-orifice on SV (L) and as a post orifice on SV (H). ã Danfoss A/S (RC-CM / MWA), 06-2002 Technical leaflet - RD2BB302 27

Modulating liquid level regulators, direct-controlled, type SV 1 and 3 SV 1-3 used as a high pressure defrost drain float valve SV 1-3 can be used as a defrost drain float valve, when one balance pipe is sealed off and the liquid level regulator is mounted with a special kit (code no. 027B2054) consisting of: Special orifice and orifice needle with a larger k v -value of 0.28 m 3 /h. Gas drain pipe SV 1-3 fitted with the special kit Liquid out to wet suction Condensed liquid in from evaporator Application example Wet suction line PMLX Liquid line Hotgas line SV 1-3 with special kit mounted as defrost drain float valve on a flooded evaporator with hotgas defrost. 28 Technical leaflet - RD2BB302 ã Danfoss A/S (RC-CM / MWA), 06-2002

Modulating liquid level regulators, direct-controlled, type SV 1 and 3 Dimensions and weight SV 1 and SV 3 Weight 5.7 kg ã Danfoss A/S (RC-CM / MWA), 06-2002 Technical leaflet - RD2BB302 29

Modulating liquid level regulators, direct operated, for low pressure side, types SV 4, 5 and 6 Introduction SV 4-6 are for use on the low pressure side as modulating liquid level regulators in refrigeration, freezing and air conditioning systems with ammonia and other common types of refrigerants. Features Reliable function Stable regulation, even during momentary load change Liquid injection into the float housing or directly into the evaporator through external pipe connection Orifice assembly and filter can be replaced without evacuating the float housing Can be supplied without float housing for direct installation in the system (special order only) Can be used as pilot float for PMLF if mounted with special orifice (diameter Æ2.5 mm) Technical data Refrigerants Can be used for all normal, non-flammable refrigerants, including R 717, and non-corrosive gases/liquids - assuming seals of the correct material are used. Use with flammable hydrocarbons cannot be recommended; please contact Danfoss. P band Approx. 35 mm Max. working pressure MWP = 28 bar Max. Dp SV 4 = 23 bar SV 5 = 21 bar SV 6 = 19 bar Media temperature 50 C to 120 C Max. test pressure MTP = 42 bar k v value and diameter for orifice SV 4: k v = 0.23 m 3 /h D = 3.0 mm SV 5: k v = 0.31 m 3 /h D = 3.5 mm SV 6: k v = 0.43 m 3 /h D = 4.0 mm Approvals Pressure Equipment Directive (PED) SV 4, 5 and 6 are approved in accordance with the European standard specified in the Pressure Equipment Directive and are CE marked. Classified for Category SV 4, 5 and 6 Fluid group I II For further details / restrictions - see Installation Instruction Identification ã Danfoss A/S (RC-CM/hbs), 09-2002 Technical leaflet - RD2BC302 31

Modulating liquid level regulators, direct operated, for low pressure side, types SV 4, 5 and 6 Materials Dimensioning example for SV Gaskets are non asbestos Valve housing made of lowtemperature cast iron, spherical (EN-GJS-400-18-LT) Refrigerant R 717 (NH 3 ) Evaporating capacity Q e = 145 kw Evaporating temperature t e = -10 C (~ p e = 2.9 bar abs.) Condensing temperature t c = +30 C (~ p c = 11.7 bar abs.) Liquid temperature ahead of SV t l = +20 C Float housing: ST 35.8 DIN 17175 W. no. 1.0305 Subcooling Dt sub = t c - t l = 30 C - 20 C = 10ÿK Pressure drop in SV Dp = p c - p e = 11.7-2.9 = 8.8 bar Correction factor k for 10ÿK subcooling = 0.98 Corrected capacity 145 0.98 = 142 kw At t e = -10 C and Dp = 8 bar SV 5 yields 147 kw and can therefore be used. 32 Technical leaflet - RD2BC302 ã Danfoss A/S (RC-CM/hbs), 09-2002

Modulating liquid level regulators, direct operated, for low pressure side, types SV 4, 5 and 6 Capacity The values in the capacity tables are based on a subcooling of 4ÿK just ahead of the SV valve. If the subcooling is more or less than 4ÿK, refer to the following correction factors. Type Evaporating temperature t e C Capacity in kw at pressure drop across valve Dp bar 0.8 1.2 1.6 2 4 8 12 16 R 717 (NH 3 ) SV 4 +10 37 45 52 58 79 105 122 134 0 39 47 54 59 81 107 124 136-10 40 48 55 61 82 108 125 137-20 41 49 56 62 83 109 125 137-30 42 50 57 63 84 109 125 136-40 42 51 58 63 84 108 124 135-50 43 51 58 63 83 107 122 133 SV 5 +10 51 62 71 78 107 143 166 183 0 53 64 73 81 110 145 168 185-10 54 66 75 83 112 147 170 186-20 56 67 76 84 113 148 170 186-30 57 68 78 85 114 148 170 185-40 58 69 78 86 114 147 168 184-50 58 69 78 86 113 146 167 182 SV 6 +10 68 83 95 105 144 191 222 245 0 71 86 98 108 147 195 226 248-10 73 88 101 111 150 197 227 250-20 75 90 103 113 152 198 228 250-30 76 92 104 115 153 198 227 248-40 77 93 105 115 153 197 226 246-50 78 93 105 115 152 196 223 243 Type Evaporating temperature t e C Capacity in kw at pressure drop across valve Dp bar 0.8 1.2 1.6 2 4 8 12 16 R 22 SV 4 +10 8.5 10.3 11.7 12.9 17.2 21.8 24.1 25.1 0 8.9 10.7 12.2 13.5 17.8 22.4 24.6 25.7-10 9.3 11.2 12.7 14.0 18.3 22.8 25.0 25.9-20 9.7 11.6 13.1 14.4 18.7 23.1 25.1 25.9-30 9.9 11.8 13.4 14.6 18.9 23.1 25.0 25.7-40 10.1 12.1 13.6 14.8 18.9 22.9 24.7 25.3-50 10.3 12.1 13.6 14.8 18.8 22.6 24.2 24.8 SV 5 +10 11.6 14.0 15.9 17.6 23.4 29.6 32.7 34.2 0 12.1 14.6 16.7 18.4 24.3 30.5 33.5 34.9-10 12.7 15.2 17.3 19.0 24.9 31.1 34.0 35.3-20 13.1 15.7 17.8 19.6 25.4 31.4 34.1 35.3-30 13.5 16.1 18.2 19.9 25.7 31.4 34.0 35.0-40 13.8 16.4 18.4 20.1 25.7 31.2 33.6 34.5-50 14.0 16.5 18.5 20.2 25.6 30.7 33.0 33.7 SV 6 +10 15.5 18.7 21.3 23.6 31.4 39.7 43.9 45.8 0 16.3 19.6 22.3 24.6 32.6 40.9 45.0 46.8-10 17.0 20.4 23.2 25.5 33.5 41.7 45.6 47.3-20 17.6 21.1 23.9 26.2 34.1 42.1 45.8 47.3-30 18.1 21.6 24.4 26.7 34.5 42.1 45.6 47.0-40 18.5 22.0 24.7 27.0 34.5 41.8 45.0 46.2-50 18.7 22.2 24.8 27.1 34.3 41.2 44.2 45.2 Correction factors When dimensioning, multiply the evaporating capacity by the correction factor k, dependent on the subcooling Dt sub just ahead of the valve. The corrected capacity can then be found in the capacity table. R717 (NH 3 ) R22 Dt K 2 4 10 15 20 25 30 35 40 45 50 k 1.01 1.00 0.98 0.96 0.94 0.92 0.91 0.89 0.87 0.86 0.85 Dt K 2 4 10 15 20 25 30 35 40 45 50 k 1.01 1.00 0.96 0.93 0.90 0.87 0.85 0.83 0.80 0.78 0.77 ã Danfoss A/S (RC-CM/hbs), 09-2002 Technical leaflet - RD2BC302 33

Modulating liquid level regulators, direct operated, for low pressure side, types SV 4, 5 and 6 Construction Function No. Part M aterial DIN / EN 1 Bottom flange for float valve Steel P275NL1 EN10028-3 2 Tube for valve body Steel TTST35N DIN 17173 3 Connection for float house Steel P275NL1 EN10028-3 4 Top cover for float valve Steel P275NL1 EN10028-3 5 Valve Housing Low temperature, cast iron (spherical) EN-GJS-400-18-LT EN 1563 6 Spindle Stainless steel 7 Spring Steel 8 Sealing ring Nylon (PA 6) 9 O-ring Cloroprene (Neoprene) 10 Distance ring Nylon (PA6) 11 Packing ring Nylon (PA 6) 12 Packing box Steel 13 Cap Steel 14 Float Stainless steel 15 Adjusting ring Steel 16 Pin Steel 17 Fork for spindle Steel 18 Screw Steel 19 Locking ring Steel 20 Pin Steel 34 Technical leaflet - RD2BC302 ã Danfoss A/S (RC-CM/hbs), 09-2002

Modulating liquid level regulators, direct operated, for low pressure side, types SV 4, 5 and 6 Construction Function (cont.) No. Part M aterial DIN / EN 21 Pin Steel 22 Cover w ith guide Steel 23 Screw Steel 24 Plug Steel 25 Gasket Non asbestos 26 Gasket Aluminium 27 Valve cone (guide) w ith pin Steel / Nylon (PA6) 28 Valve cone Teflon (PTFE) 29 O-ring Cloroprene (Neoprene) 30 Nozzle Teflon (PTFE) 31 Gasket Non asbestos 32 Filter Steel / Stainless steel 33 Spring Steel 34 Cover for filter Steel 35 Gasket Aluminium 36 Nipple Steel 37 Union nut Steel 38 Gasket Aluminium 39 Welding Nipple Steel 40 Locking ring Steel 41 Ring Nylon (PA6) 42 Pin Steel 43 Screw Stainless steel A2-70 44 Screw Stainless steel A2-70 45 Washer Steel 46 Screw Stainless steel A2-70 ã Danfoss A/S (RC-CM/hbs), 09-2002 Technical leaflet - RD2BC302 35

Modulating liquid level regulators, direct operated, for low pressure side, types SV 4, 5 and 6 Construction Function (cont.) SV 4-6 float valves are for low pressure operation only. They are used for flooded evaporators, where only slight variations in the liquid level can be accepted. When the liquid level decreases, the float moves downwards. This opens the orifice (pos. 7) and the amount of liquid injected is increased. The liquid inlet line should be dimensioned in such a way that acceptable liquid velocities and pressure drops are obtained. This is particularly important when the liquid is only slightly subcooled, since valve capacity is reduced considerably if flashgas occurs in the liquid ahead of the orifice. The flashgas quantity which occurs on expansion is removed through the balance pipe. On refrigeration plant using fluorinated refrigerants, slight subcooling and a large pressure drop can result in a flashgas quantity of approx. 50% of the injected liquid quantity. Therefore the pressure drop in this balance pipe must be kept at a minimum, otherwise there is a risk that: - the liquid level in the evaporator will vary to an unacceptable degree as a function of evaporator load - the absolute difference between the liquid level of the evaporator and the SV valve will be too large. If too large amounts of flash gas are created it is recommended to use the external injection connection or let the liquid expand directly into the surge drum. See application drawings 3 and 4. See instruction for SV 4-6 for: Cleaning of strainer Change of orifice Change of valve plate 36 Technical leaflet - RD2BC302 ã Danfoss A/S (RC-CM/hbs), 09-2002

Modulating liquid level regulators, direct operated, for low pressure side, types SV 4, 5 and 6 Application The liquid expands into the float housing The liquid expands into the float housing 1) 2) Direct liquid injection into the float housing 4 pcs. M6 screws (pos. 23) are removed, and pos. 24 remains blanked off. This leaves four holes through which liquid expands directly. Note: If the capacity is too high, only remove two or three screws. Pos. 23 and 24, see Construction & Function. 4 pcs. M6 screws (pos. 23) are removed, and pos. 24 remains blanked off. This leaves four holes through which liquid expands directly. Note: If the capacity is too high, only remove two or three screws. Pos. 23 and 24, see Construction & Function. The liquid expands into the evaporator 3) 4) The liquid expands directly into the surge drum Used in large evaporators with long pipe lines. - pos. 24 is removed and weld connection is mounted - pos. 23 remains screwed Pos. 23 and 24, see Construction & Function. 4 pcs. M6 screws (pos. 23) are removed, and pos. 24 remains blanked off. This leaves four holes through which liquid expands directly. Note: If the capacity is too high, only remove two or three screws. Pos. 23 and 24, see Construction & Function. ã Danfoss A/S (RC-CM/hbs), 09-2002 Technical leaflet - RD2BC302 37

Modulating liquid level regulators, direct operated, for low pressure side, types SV 4, 5 and 6 Dimensions and weight Weight: 19.6 kg Weight: 9.7 kg Weight: 3.1 kg 38 Technical leaflet - RD2BC302 ã Danfoss A/S (RC-CM/hbs), 09-2002

Modulating liquid level regulators, direct operated, for low pressure side, types SV 4, 5 and 6 Ordering Regulator The code nos. stated apply to liquid level regulators type SV 4, 5 and 6 with two 1" weld connections for balance tubes and two ½" weld joints for liquid and evaporator connections respectively. Valve type Orifice Code no. Code no. Rated capacity in kw 1) diameter without housing 2) R 717 R 22 R 134a R 404A SV 4 Æ 3.0 mm 027B2024 027B2014 102 21.0 16.4 15.4 SV 5 Æ 3.5 mm 027B2025 027B2015 138 28.6 22.3 21.0 SV 6 Æ 4.0 mm 027B2026 027B2016 186 38.3 29.9 28.1 1) The rated capacity refers to the valve capacity at evaporating temperature t e = +5 C, condensing temp. t c = +32 C and liquid temperature t l = +28 C. 2) Flange for mounting without housing Code no. 027B2027. Spare parts and accessories Smaller orifices for the SV 4-6 are available as spare parts and can be mounted in the SV 4-6 if smaller capacities are required. - Seal kit: 027B2070 - Other spare parts: See spare parts catalogue RK0XG. Special orifice code no. and rated capacities for SV 4-6 Orifice diameter k v Capacities at 10 C evaporating temperature at pressure Code no. 1) drop across valve DP bar R717 4 7 10 4 7 10 Æ 1.0 mm 0.026 9 12 13.5 1.6 2.2 2.4 027B2080 Æ 1.5 mm 0.06 21 27 29 3.8 4.9 5.2 027B2081 Æ 2.0 mm 0.10 35 46 50 6.3 8.3 9 027B2082 Æ 2.5 mm 0.16 56 70 81 10 13 15 027B2083 Æ 2.8 mm 0.20 70 87.5 101 12 16 18 027B2084 1) The code no. includes orifice and all necessary gaskets R22 Note: The SV 4-6 mounted with special orifice diameter Æ2.5 mm is recommended as pilot float valve for the servo-operated level regulators type PMFL for higher capacities. ã Danfoss A/S (RC-CM/hbs), 09-2002 Technical leaflet - RD2BC302 39

Modulating liquid level regulators, servo-controlled type PMFL / PMFH and SV Introduction For modulating liquid level control in refrigeration, freezing and air conditioning plant, a system comprising a modulating servo-controlled main expansion valve type PMFL or PMFH, controlled by a pilot float valve type SV, is used. PMFL and SV systems are used on the evaporator side. PMFH and SV systems are used on the condenser side. The system is suitable for use with ammonia or fluorinated refrigerants. The PMFL and PMFH can be used in liquid lines to or from - evaporators - separators - intermediate coolers - condensers - receivers Modulating liquid level regulation provides liquid injection that is proportional to the actual capacity. This gives a constant amount of flashgas, thus ensuring stable regulation and economic operation because variations in pressure and temperature are held to a minimum. Features Applicable to all common, non-flammable refrigerants, including R 717, and non-corrosive gases/liquids - dependent on sealing material compatability PMFL/PMFH are based on PM valve family housings Same flange programme as for PM valve series Valve housing in low temperature cast iron (spherical) - EN GJS 400-18-LT Manual operation possible Position indicator available Pressure gauge connection to monitor inlet pressure Simple installation Main valve top cover can be located in any position without affecting the function Pressure Equipment Directive (PED) The PMFL / PMFH valves are approved and CE marked in accordance with Pressure Equipment Directive - 97/23/EC. For further details / restrictions - see Installation Instruction. Nominal bore DN 25 (1 in.) PMFL/FMFH valves* DN32-125 mm (1 1/4-5 in.) DN 150 mm (6 in.) Classified for Fluid group I Category Article 3, paragraph 3 II III *CE is only applicable to the EN GJS 400-18-LT Technical data Refrigerants R 717, R 22, R 134a, R 404A and other fluorinated refrigerants. Max. working pressure PMFL / H: MWP = 28 bar SV: MWP = 28 bar Max. test pressure PMFL / H: Max. test pressure = 42 bar SV: Max. test pressure = 42 bar Temperature of media: 60 C to +120 C. Note: Max. working pressure is limited to MWP = 21 bar when media temperatures are: below 20 C for valves made of GGG-40.3 and below 10 C for valves made of GG-25. ã Danfoss A/S (RC-CM/hbs), 12-2002 Technical leaflet - RD2CB402 41

Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Design/Function PMFL To SV float 6. Seal plug 10. Valve spindle 12. Valve seat 19. Valve body 19a. Channel in valve body 20. Bottom cover 23. Main spring 24. Servo piston 24a. Channel in servo piston 30. Top cover 30a.b.c. Channels in top cover 31. Valve cone 43. Supplementary spring 44. Manometer connection 53. Spindle cap 60. Setting spindle 73. Pilot connection PMFL When the liquid level inside the float drops, the float orifice opens. This relieves the higher pressure, ps, acting on the servo piston to the low pressure side causing the PMFL to open. Variations in liquid level will result in variations in pressure over the piston and variation in the amount of liquid injected. It is important to choose the correct spring set when designing the plant. The spring set should be selected from the table below: Subcooling Pressure difference over main valve bar psi bar psi K F 4-15 58-218 1.2-4.0 17-58 0-8 0-14 Normal spring set Weak spring set 8-40 14-72 Strong spring set The setting spindle, pos. 60, has not been set from factory. It is imperative that the setting spindle is adjusted before the valve is put into operation. The outer spring, pos. 23, is preset and the inner spring, pos. 43, is adjusted when turning the spindle. The following tables shows the adjustment of the inner spring in number of turns of the spindle as a function of valve size, spring type and pressure difference: PMFL C/w normal (factory mounted) spring set, subcooling 0-8 K ~ 0-14 F Pressure difference ( p) over PFML in bar or psi < 5 bar 5-8 bar 8-10 bar 10-12 bar > 12 bar < 72 psi 72-116 psi 116-145 psi 145-174 psi > 174 psi 80 No tension 2-3 3-4.5 4.5-6 appr. 7 125 No tension 3-5 5-7 7-9 appr. 10 200 No tension 3-5 5-7 7-9 appr. 10 300 No tension 4-6 6-9 9-12 appr. 14 PMFL C/w strong spring set, subcooling 8-40 K ~ 14-72 F Pressure difference ( p) over PFML in bar or psi 6-9 bar > 9 bar 87-131 psi > 131 psi 80 4 Max. tension 125 6 Max. tension PMFL 200 300 C/w strong spring set, subcooling 8-40 K ~ 14-72 F Pressure difference ( p) over PFML in bar or psi 6-16 bar 87-232 psi Spring must always be set to max. tension PMFL C/w weak spring set, low pressure plants Pressure difference ( p) over PFML in bar or psi 1.2-1.8 bar 1.8-2.5 bar 2.5-3 bar 3-4 bar 17-26 psi 26-36 psi 36-43 psi 43-58 psi 80 No tension 3-4 4-6 Max. tension 125 No tension 4-6 6-8 Max. tension 200 No tension 4-6 6-8 Max. tension 300 No tension 5-7 5-7 Max. tension 42 Technical leaflet - RD2CB402 ã Danfoss A/S (RC-CM/hbs), 12-2002

Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Design/Function (continued) The values for spindle turns are an indication for an initial setting only. If a position indicator is used, a more precise modulation can be achieved when fine tuning the valve setting. If the PMFL is not opening fully, the spring tension must be reduced. If the PMFL is operating in a ON/OFF function, the spring tension should be increased. The condenser pressure will have an effect on the fine tuning and large variations in condensing pressure might call for readjustment. The subcooling is measured just before the PMFL and the pressure difference is for the valve only excluding piping and armatures. PMFL function example The PMFL can be used together with either SV 1-3 or SV 4-6 as the pilot valve. The orifices determines the k v (C v ) value of the pilot and the following table can be used as an initial selection guide: PMFL SV 1-3 SV 4-6 SV 1 SV 3 Ø 2.5 Ø 3 (SV 4) 80 X X 125 X X 200 X X 300 X X The final choice of orifice may vary depending on refrigerant and pressure levels. Smaller pressure levels needs a bigger orifice. Pressure difference levels below 3 bar (43 psi) need SV 3 or SV 4-6 with Ø3 mm orifice. From compressor To compressor From evaporator Condenser Alarm Alarm float switch Overflow valve Liquid level Through type receiver Filter Oil drain valve Low pressure float system (for explanatory purposes only) To evaporator SV floats for PMFL Both the SV 1-3 and SV 4-6 can be used for PMFL low pressure control system. If SV 4-6 is used as shown above, the float must be connected as shown. If SV 1-3 float is used, this has 2 different pilot connections: S-port (series connection with the PMFL) or P-port (parallel connection with the PMFL). P-port: When using the P-port, it is possible to force open the PMFL valve to a fully open position. This is practical for service purposes or to confirm if the float has sufficient capacity for the PMFL and the operating conditions. However, when P-port connection is used it is possible to overfill a system due to constant bleeding or unauthorised tampering. In this case, its advisable to introduce a shut off when the liquid level reaches a preset point. Shut off can be done via an electrical switch if an EVM valve is mounted in the SII port in the top of the PMFL. It is only advisable to use the P-port connection at low subcooling, < 8 K (< 14 F). In general: If the float system is unstable, set a larger bleed. If the PMFL stays open when the float is closed, set a smaller bleed. S-port: The S-port offers the advantage of a preorifice which divides the pressure drop and any wear possibility due to cavitation. S-port connection must be used if the subcooling is higher than 8 K (14 F). The spindle should be opened 4 turns initially before adjustment. Adjustment should be done in steps of ¼ turn until the PMFL has a modulating function. The k v (C v ) value of the SV is higher using S-port than using P-port. A higher P-band can thus be obtained. ã Danfoss A/S (RC-CM/hbs), 12-2002 Technical leaflet - RD2CB402 43

Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Design/Function (continued) PMFH 3. Manometer connection 6. Seal plug 10. Valve spindle 19. Valve body 19a. Channel in valve body 20. Bottom cover 21a. Channel in servo piston 23. Main spring 24. Servo piston 30. Top cover 30a.b.c. Channels in top cover 31. Valve cone 53. Spindle cap 60. Manual opening 73. Pilot connection PMFH If the liquid level inside the SV float rises, the float orifice opens and relieves pressure through the pilot line to the top of the PMFH, increasing the pressure, ps, moving the pushrod downwards and opening the PMFH. The pilot line is connected in the topcover at SI. Override of the pilot signal can be made by using an EVM valve at SII. It is important to choose the correct spring set when designing the plant. The spring set should be selected from the table below: The PMFH can be used together with either SV 1 or 3 whith the SV mounted with the bleed valve downwards, refer to the drawing below. This reverses the opening so that rising float opens the orifice. Pressure difference over main valve bar psi bar psi 0-4.5 0-65 > 4.5 > 65 Weak spring set Normal spring set PMFH function example From low stage compressor(s) To high stage compressor(s) From high stage compressor(s) Alarm float switch Alarm Condenser Liquid trap receiver To low stage separator Intermediate pressure vessel To compressor cooling Filter High pressure float system (for explanatory purposes only) 44 Technical leaflet - RD2CB402 ã Danfoss A/S (RC-CM/hbs), 12-2002

Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Design/Function (continued) SV 1-3 SV 1-3 float has 2 different pilot connections: S-port (series connection with PMFH) or P-port (parallel connection with the PMFH). P-port: When using the P-port, it is possible to force open the PMFH valve to a fully open position. This is practical for service purposes or to confirm if the float has sufficient capacity for the PMFH and the operating conditions. However, when P-port connection is used it is possible to overfill a system due to constant bleeding or unautorised tampering. In this case, it is advisable to introduce a shut off when the liquid level reaches a preset point. Shut off can be done via an electrical switch if an EVM valve is mounted in the SII port in the top of the PMFH. It is only advisable to use the P-port at low pressure difference. S-port: The S-port offers the advantage of a preorifice which divides the pressure drop and any wear possibility due to cavitation. S-port connection must be used at high pressure differences, dp > 10 bar (145 psi). The k v (C v ) value of the SV is higher using S-port than using P-port. A higher P-band can thus be obtained. ã Danfoss A/S (RC-CM/hbs), 12-2002 Technical leaflet - RD2CB402 45

Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Sizing Sizing example for PMFL Refrigerant R 717 (NH 3 ) Evaporator capacity Q e = 600 kw Evaporating temperature t e = -10 C (~ p e = 2.9 bar abs.) Condensing temperature t c = +30 C (~ p c = 11.9 bar abs.) Liquid temperature ahead of valve t l = +20 C at max. capacity Subcooling Dt sub = t c - t l = 30 C - 20 C = 10 K Calculations do not take into account pressure loss in pipelines. Pressure drop across valve Dp = p c - p e = 11.9 bar - 2.9 bar = 9 bar Correction factor for 10 K subcooling 0.98 Corrected capacity 600 kw 0.98 = 588 kw The corrected capacity can be found in the capacity table. It will be seen from the table that valve type PMFL 80-4 should be chosen. Refering to "ordering table", code number 027F0053 can be found. For details of flanges, accessories and pilot valve, see the ordering table. Since Dp = 9 bar and Dt sub = 10 K, it will be seen from the "C/w strong spring set" for PMFL that a "STRONG" spring set must be used. The pilot line is connected to SV at connection S. In the ordering table the code number for the spring set can be found: 027F0118. Sizing example for PMFH Refrigerant R 717 (NH 3 ) Evaporator capacity Q e = 2200 kw Evaporating temperature t e = -10 C (~ p e = 2.9 bar abs.) Condensing temperature t c = +30 C (~ 11.9 bar abs.) Liquid temperature ahead of valve t l = +20 C Subcooling Dt sub = t c - t l = 30 C - 20 C = 10 K Calculations do not take into account pressure loss in pipelines. Pressure drop across valve Dp = p c - p e = 11.9 bar - 2.9 bar = 9 bar Correction factor for 10 K subcooling 0.98 Corrected capacity 2200 kw 0.98 = 2156 kw The corrected capacity can be found in the capacity table. It will be seen from the table that valve type PMFH 80-7 should be chosen. In the ordering table the code number for the valve can be found: 027F3060 for CE-approved valve. For details of flanges, accessories and pilot valve, see the ordering table. Correction factors When dimensioning, multiply the evaporator capacity by a correction factor k dependent on the subcooling Dt sub just ahead of the valve. The corrected capacity can then be found in the capacity table. R717 (NH 3 ) Dt K 2 4 10 15 20 25 30 35 40 45 50 k 1.01 1.00 0.98 0.96 0.94 0.92 0.91 0.89 0.87 0.86 0.85 R22 Dt K 2 4 10 15 20 25 30 35 40 45 50 k 1.01 1.00 0.96 0.93 0.90 0.87 0.85 0.83 0.80 0.78 0.77 46 Technical leaflet - RD2CB402 ã Danfoss A/S (RC-CM/hbs), 12-2002

Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Capacity in kw Type Evaporating temperature t e Rated capacity in kw at pressure drop across valve Dp bar C 0.8 1.2 1.6 2.0 Evaporating temperature t e R 717 (NH 3 ) R 717 (NH 3 ) PMFL 80-1 +10 50 60 69 76 PMFL 80-1 +10 104 140 161 0-10 -20-30 -40-50 51 53 54 55 56 56 62 64 65 66 67 67 71 73 74 75 79 75 79 81 82 83 86 82 0-10 -20-30 -40-50 107 110 111 111 111 109 142 143 143 143 142 140 165 166 166 165 162 160 176 178 179 179 177 175 PMFL 80-2 +10 80 97 111 123 PMFL 80-2 +10 167 224 257 0-10 -20-30 -40-50 83 85 86 88 89 90 101 103 105 106 107 106 115 118 119 120 120 119 127 130 132 133 132 131 PMFH 80-2 0-10 -20-30 -40-50 172 176 177 177 175 173 227 228 238 227 225 222 264 265 264 262 258 253 281 284 285 284 281 277 PMFL 80-3 +10 127 154 176 194 PMFL 80-3 +10 264 353 404 0-10 -20-30 -40-50 131 134 137 139 140 139 159 163 164 167 166 164 182 186 188 188 187 184 201 205 207 207 205 201 PMFH 80-3 0-10 -20-30 -40-50 271 276 278 276 272 267 356 357 356 353 349 343 414 416 413 407 400 393 440 444 445 443 438 431 PMFL 80-4 +10 206 250 286 316 PMFL 80-4 +10 427 571 651 0-10 -20-30 -40-50 214 219 222 224 223 219 259 264 267 267 263 257 295 301 303 301 295 288 327 333 334 330 323 315 PMFH 80-4 0-10 -20-30 -40-50 438 444 445 439 429 420 573 572 568 561 552 543 664 665 657 647 635 624 704 709 709 704 696 685 PMFL 80-5 +10 325 394 449 496 PMFL 80-5 +10 667 887 1010 0-10 -20-30 -40-50 336 344 347 345 338 327 406 413 414 407 396 383 463 470 468 458 444 429 511 518 514 502 486 470 PMFH 80-5 0-10 -20-30 -40-50 679 685 680 666 649 632 883 874 864 852 837 823 1020 1020 1000 984 966 948 1080 1080 1080 1070 1060 1040 PMFL 80-6 +10 565 682 773 851 P MFL 80-6 +10 1130 1490 1670 0-10 -20-30 -40-50 584 591 587 571 546 520 700 705 692 666 636 608 792 795 777 746 712 684 869 871 850 816 781 751 PMFH 80-6 0-10 -20-30 -40-50 1130 1130 1110 1080 1050 1020 1460 1430 1410 1380 1360 1340 1690 1670 1640 1610 1570 1540 1780 1780 1770 1760 1730 1710 PMFL 80-7 +10 881 1060 1190 1300 PMFL 80-7 +10 1690 2220 2480 0-10 -20-30 -40-50 909 910 887 844 794 750 1080 1070 1030 975 921 875 1210 1190 1150 1090 1030 984 1310 1300 1250 1190 1130 1080 PMFH 80-7 0-10 -20-30 -40-50 1670 1660 1630 1580 1530 1490 2150 2090 2050 2010 1970 1940 2500 2470 2410 2350 2300 2250 2610 2610 2610 2590 2550 2510 PMFL 125 +10 1400 1690 1910 2100 PMFL 125 +10 2770 3650 4100 0-10 -20-30 -40-50 1450 1460 1450 1400 1330 1260 1730 1740 1700 1630 1550 1480 1950 1950 1930 1820 1730 1660 2140 2140 2080 1990 1900 1830 PMFH 125 0-10 -20-30 -40-50 2770 2770 2720 2650 2570 2490 3570 3500 3430 3370 3320 3260 4140 4090 4010 3920 3840 3770 4350 4350 4340 4300 4240 4180 PMFL 200 +10 2250 2710 3060 3360 PMFL 200 +10 4410 5810 6530 0-10 -20-30 -40-50 2320 2340 2310 2220 2110 2000 2770 2780 2710 2590 2480 2340 3120 3120 3030 2890 2750 2630 3420 3410 3310 3160 3020 2900 PMFH 200 0-10 -20-30 -40-50 4420 4400 4330 4210 4080 3960 5680 5550 5450 5360 5260 5170 6590 6510 6370 6240 6110 5990 6920 6920 6900 6830 6740 6640 PMFL 300 +10 3420 4110 4650 4990 PMFL 300 +10 6690 8810 9880 0-10 -20-30 -40-50 3530 3560 3500 3370 3190 3030 4210 4210 4100 3910 3710 3540 4740 4730 4590 4370 4160 3980 5180 5170 5010 4780 4560 4380 PMFH 300 PMFH 500 0-10 -20-30 -40-50 +10 0-10 -20-30 -40-50 6690 6660 6550 6360 6170 5990 10700 10700 10600 10400 10100 9830 9540 8600 8400 8240 8100 7960 7820 14100 13700 13400 13100 12900 12700 12400 9980 9850 9650 9430 9240 9050 15800 15900 15700 15400 15000 14700 14400 10500 10500 10400 10300 10200 10000 16700 16700 16700 16500 16300 16000 ã Danfoss A/S (RC-CM/hbs), 12-2002 Technical leaflet - RD2CB402 47 Type Rated capacity in kw at pressure drop across valve Dp bar C 4.0 8.0 12.0 16.0

Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Capacity in kw (continued) Type Evaporating temperature t e Rated capacity in kw at pressure drop across valve Dp bar C 0.8 1.2 1.6 2.0 Type Evaporating temperature t e Rated capacity in kw at pressure drop across valve Dp bar C 4.0 8.0 12.0 16.0 R 22 R 22 PMFL 80-1 +10 11 13 15 17 PMFL 80-1 +10 22 28 31 32 0 12 14 16 18 0 23 29 32 33-10 12 15 17 18-10 24 30 32 34-20 12 15 17 19-20 25 30 32 34-30 13 15 17 19-30 25 30 32 33-40 13 16 18 19-40 25 30 32 32-50 13 16 18 19-50 24 29 31 32 PMFL 80-2 10 18 22 25 27 PMFL 80-2 +10 36 46 51 52 0 19 23 26 29 PMFH 80-2 0 38 47 52 53-10 20 24 27 30-10 39 48 52 54-20 20 24 28 30-20 40 48 52 54-30 21 25 28 31-30 40 48 52 53-40 21 25 28 31-40 40 48 51 52-50 21 25 28 31-50 39 47 49 51 PMFL 80-3 10 29 35 39 43 PMFL 80-3 +10 57 72 80 82 0 30 36 41 46 PMFH 80-3 0 60 74 82 84-10 31 37 43 47-10 62 76 82 85-20 32 39 44 48-20 63 76 82 85-30 33 39 44 48-30 63 76 81 83-40 34 40 45 49-40 62 75 79 81-50 34 40 44 48-50 61 73 77 79 PMFL 80-4 10 47 57 64 71 PMFL 80-4 +10 94 118 130 133 0 49 59 67 74 PMFH 80-4 0 98 121 133 136-10 51 61 70 77-10 101 123 133 138-20 52 63 71 78-20 102 123 132 137-30 54 64 72 78-30 101 122 130 134-40 54 64 72 78-40 99 120 127 131-50 55 64 71 77-50 97 117 124 127 PMFL 80-5 10 74 89 102 112 PMFL 80-5 +10 147 184 202 206 0 78 94 107 117 PMFH 80-5 0 153 188 205 211-10 80 96 110 121-10 157 190 205 212-20 83 99 112 122-20 157 189 203 210-30 84 99 112 122-30 156 187 199 206-40 84 99 110 120-40 152 184 195 200-50 84 97 108 117-50 148 179 189 194 PMFL 80-6 10 129 156 177 194 PMFL 80-6 +10 251 310 341 345 0 135 162 184 202 PMFH 80-6 0 260 314 343 352-10 140 167 188 206-10 263 315 341 353-20 142 168 189 205-20 262 313 335 348-30 143 167 186 202-30 257 308 328 340-40 141 163 181 196-40 249 302 320 331-50 137 158 175 189-50 241 294 312 321 PMFL 80-7 10 202 242 273 299 PMFL 80-7 +10 381 466 510 515 0 211 251 283 308 PMFH 80-7 0 390 467 510 524-10 216 256 286 311-10 393 465 504 523-20 218 255 283 307-20 389 461 495 516-30 215 249 275 298-30 378 454 483 503-40 209 240 265 286-40 366 444 471 489-50 200 230 254 275-50 353 433 458 473 PMFL 125 10 321 386 437 479 PMFL 125 +10 620 763 837 847 0 336 402 455 498 PMFH 125 0 639 770 842 864-10 346 412 464 507-10 647 771 835 865-20 352 415 464 505-20 643 767 821 853-30 352 410 455 494-30 628 755 804 834-40 346 399 442 478-40 609 739 784 810-50 335 386 426 461-50 589 720 762 785 PMFL 200 10 515 618 700 767 PMFL 200 +10 990 1220 1330 1350 0 538 645 728 796 PMFH 200 0 1020 1230 1340 1380-10 555 660 742 810-10 1030 1230 1330 1380-20 563 663 740 805-20 1020 1220 1310 1360-30 561 653 725 786-30 1000 1200 1280 1330-40 550 635 702 760-40 969 1170 1250 1290-50 532 612 677 732-50 937 1150 1210 1250 PMFL 300 10 782 940 1060 1170 PMFL 300 +10 1500 1850 2020 2050 0 819 980 1110 1210 PMFH 300 0 1550 1860 2030 2080-10 843 1000 1130 1230-10 1560 1860 2010 2090-20 855 1010 1120 1220-20 1550 1850 1980 2060-30 851 990 1100 1190-30 1510 1820 1930 2010-40 833 961 1060 1150-40 1470 1780 1890 1950-50 804 925 1020 1110-50 1420 1730 1830 1890 PMFH 500 +10 2410 2950 3240 3270 0 2480 2970 3250 3330-10 2500 2970 3210 3330-20 2480 2950 3160 3290-30 2420 2900 3090 3210-40 2340 2840 3010 3120-50 2260 2770 2930 3020 48 Technical leaflet - RD2CB402 ã Danfoss A/S (RC-CM/hbs), 12-2002

Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Material specification PMFL PMFH Material specification for PMFL/PMFH valves (GG-25 code nos.) No. Part Material DIN/EN ISO ASTM 2 Gasket between body and Non-metal flange Non-asbestos 3 Bolts for flange Stainless steel A2-70 A2-70 Type 308 4 Flange PM 5-65 Steel RSt. 37-2, 10025 Fe360 B, 630 Grade C, A 283 6 Plug Steel 9SMn28 Type 2 1213 1651 R683/9 SAE J 403 10 Valve spindle Steel 9SMn28 Type 2 1213 1651 R683/9 SAE J 403 12 Valve seat Teflon [PTFE] 19 Valve body Cast iron GG-25 Grade 250 Class 40B DIN 1691 185 A48 20 Bottom cover Cast iron GG-25 Grade 250 Class 40B 23 Spring Steel 24 Servo piston Cast iron GG-25 Grade 250 Class 40B 30 Cover Cast iron GG-25 Grade 250 Class 40B DIN 1691 185 A48 31 Trottle cone Steel 9SMn28 Type 2 1213 1651 R683/9 SAE J 403 32 Gasket between body and Non-metal bottom cover Non-asbestos 34 Bolts for top and bottom cover Stainless steel A2-70 A2-70 Type 308 41 Gasket Non-metal Non-asbestos 43 Spring Steel ã Danfoss A/S (RC-CM/hbs), 12-2002 Technical leaflet - RD2CB402 49

Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Material specification PMFL PMFH Material specification for PM FL/PMFH valves (GG-25 code nos.) - continued No. Part Material DIN/EN ISO ASTM 53 Spindle cap Steel 9SMn28 Type 2 1213 1651 R683/9 SAE J 403 60 Setting / manual operating Steel 9SMn28 Type 2 1213 spindle 1651 R683/9 SAE J 403 73 Pilot connection Steel 9SMn28 Type 2 1213 1651 R683/9 SAE J 403 Material specification for PMFL/PMFH valves (EN-GJS-400-18-LT code nos.) No. Part Material DIN/EN ISO ASTM 3 Bolts for flange Stainless steel A2-70 A2-70 TYPE 308 19 Valve body Low temperature, EN-GJS-400-18-LT cast iron (spherical) EN 1563 20 Bottom cover Low temperature, EN-GJS-400-18-LT cast iron (spherical) EN 1563 30 Cover Low temperature, EN-GJS-400-18-LT cast iron (spherical) EN 1563 34 Bolts for top and bottom cover Stainless steel A2-70 A2-70 TYPE 308 50 Technical leaflet - RD2CB402 ã Danfoss A/S (RC-CM/hbs), 12-2002

Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Ordering Rated capacity in kw (1 kw = 0.284 TR) Valve type R 717 R 22 R 134a R 404A R 12 R 502 PMFL/H 80-1 139 27.8 22.1 33 17.4 30 PMFL/H 80-2 209 41.8 35.3 49.7 27.8 45.2 PMFL/H 80-3 348 70 53.1 82.7 41.8 75.2 PMFL/H 80-4 558 105 88.9 124 70 113 PMFL/H 80-5 835 174 133 207 105 188 PMFL/H 80-6 1395 278 221 330 174 300 PMFL/H 80-7 2080 435 353 569 278 470 PMFL/H 125 3480 700 552 831 435 755 PMFL/H 200 5580 1050 889 1243 700 1130 PMFL/H 300 8350 1740 1333 2068 1050 1880 PMFL/H 500 13900 2780 2210 3300 1740 3000 The rated capacity is given at evaporating temperature t e = +5 C, condensing temperature t c = +32 C and liquid temperature t l = +28 C. Main valves Valve type Code no GG 25 EN GJS 400-18-LT PMFL 80-1 027F0050 027F3054 PMFL 80-2 027F0051 027F3055 PMFL 80-3 027F0052 027F3056 PMFL 80-4 027F0053 027F3057 PMFL 80-5 027F0054 027F3058 PMFL 80-6 027F0055 027F3059 PMFL 80-7 027F0056 027F3060 PMFL 125 027F0057 027F3061 PMFL 200 027F0058 027F3062 PMFL 300 027F0059 027F3063 The code nos. stated apply to main valves type PMFL or PMFH incl. flange gaskets, flange bolts, blanking plug and pilot connection with Æ 6.5 / Æ 10 mm weld nipple ( 3 /8 in. flare connection can be supplied, code no. 027F0115). Valve type Code no GG 25 EN GJS 400-18-LT PMFH 80-2 027F0061 027F3065 PMFH 80-3 027F0062 027F3066 PMFH 80-4 027F0063 027F3067 PMFH 80-5 027F0064 027F3068 PMFH 80-6 027F0065 027F3069 PMFH 80-7 027F0066 027F3070 PMFH 125 027F0067 027F3071 PMFH 200 027F0068 027F3072 PMFH 300 027F0069 027F3073 PMFH 500 027F0070 027F3074 Spring set Special spring set for PMFL Pressure drop Dp in PMFL Subcooling Dt sub 4 15 bar 1.2 4 bar K Spring set Pilot connection on SV 0-8 "STANDARD" "WEAK" P 8-40 "STRONG" S Pos. 23 + 43 Type PMFL 80-1 80-7 125 200 300 "WEAK" 027F0123 027F0124 027F0125 027F0126 Code no. "STRONG" 027F0118 027F0119 027F0120 027F0121 Weak/Strong Special spring set for PMFH Pressure drop in PMFH Dp bar 1 4 Type PMFH 80.1 7 PMFH 125 PMFH 200 PMFH 300 PMFH 500 "WEAK" Code no. 027F2190 027F2191 027F2192 027F2193 027F2194 ã Danfoss A/S (RC-CM/hbs), 12-2002 Technical leaflet - RD2CB402 51

Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Ordering (continued) Flanges 1 ) Valve type Flange type Weld flanges in. Code no. 2 ) in. Code no. 2 ) mm 1 ) Dimension sketch see spare part catalogue. 2 ) Code no. applies to one flange set consisting of one inlet and one outlet flange. Solder flanges Code no. 2 ) PMFL 80 / 12 3 /4 027N1220 7 /8 027L1223 22 027L1222 PMFH 80 1 027N1225 1 1 /8 027L1229 28 027L1228 1 1 /4 027N1230 PMFL 125 / 23 1 1 /4 027N2332 1 3 /8 027L2335 35 027L2335 PMFH 125 1 1 /2 027N2340 PMFL 200 / 24 1 1 /2 027N2440 1 5 /8 027L2441 42 027L2442 PMFH 200 2 027N2450 PMFL 300 / 25 2 027N2550 2 1 /8 027L2554 54 027L2554 PMFH 300 2 1 /2 027N2565 PMFH 500 26 2 1 /2 027N2665 2 5 /8 027L2666 76 027L2676 3 027N2680 Stainless steel: flanges, bolts for flanges and top and bottom covers, see spare parts catalogue. Pilot valves SV 1-3 Type Connection Code no. Float pilot valve type SV Balance tube liquid / vapour 1 in. weld Pilot line SV 1: 027B2021 027B2021CE Æ 6.5 / Æ 10 mm 2 weld 1 ) SV 3: 027B2023 027B2023CE 2 1 ) 3 /8 in. flare connection can be supplied under code no. 027B2033. 2 ) Approved and CE-marked in accordance with Pressure Equipment Directive - 97/23/EC. Pilot valves SV 4 Orifice Code no. Valve type Code no. diameter w ithout housing 1) SV 4 Ø 3.0 mm 027B2024 2) 027B2014 2) 1 ) Flange for mounting without housing Code no. 027B2027. 2 ) Approved and CE-marked in accordance with Pressure Equipment Directive - 97/23/EC. The code nos. stated apply to liquid level regulators type SV 4, 5 and 6 with two 1" weld connections for balance tubes and two ½" weld joints for liquid and evaporator connections respectively. Spare parts and accessories Smaller orifices for the SV 4 are available as spare parts. - Seal kit: 027B2070 Special orifice code no. for SV 4 Orifice diameter k v Code no. 1) Ø 1.0 mm 0.026 027B2080 Ø 1.5 mm 0.06 027B2081 Ø 2.0 mm 0.10 027B2082 Ø 2.5 mm 0.16 027B2083 Ø 2.8 mm 0.20 027B2084 1) The code no. includes orifice and all necessary gaskets Pilot valve kits (EVM and coil) Can be screwed on to the PMFL or PMFH instead of the blanking plug. a.c.: d.c.: 027B1122xx 027B1124yy Coils, 10 W a.c. where xx can be where yy can be 24 V, 50 Hz 16 02 (24 V) 110 V, 60 Hz 21 09 (220 V) 115 V, 50 Hz 22 220 V, 50 Hz 31 220 V, 50/60 Hz 32 240 V, 50 Hz 33 52 Technical leaflet - RD2CB402 ã Danfoss A/S (RC-CM/hbs), 12-2002

Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Ordering (continued) Optional accessories Description Pressure gauge connection Æ 6.5 / Æ 10 mm weld / solder Code no. 027B2035 Pressure gauge connection 1 /4 in. flare (self-closing) 027B2041 (Must not be used in ammonia plant) Pressure gauge connection Cutting ring connection 6 mm 027B2063 10 mm 027B2064 Pressure gauge connection 1/4 NPT 027B2062 Damping cylinder for PMFH 80 500 027F2195 Function indicator Description Function indicator Can be fitted in place of the main valve bottom plug. When the protective cap of the indicator is removed, the degree of opening of the PMFL-regulator can be observed in relation to the degree of opening of the SV pilot valve. Note: The function indicator must be considered as a very important tool for the accurate adjustment of the spring pressure. Manual operating unit for PMFL. Can be fitted in place of the regulator bottom plug 3 / 8 in. flare pilot connection for PMFL and PMFH 3 / 8 in. flare pilot connection for SV Code no. 027F0085 027F0128 027F0115 027B2033 Electronic position indicator, type AKS 45 Electronic position indicator Code no. Type AKS 45-26 084H4045 AKS 45 is an electronic transmitter that provides a standard 4-20 ma output signal in accordance with the opening degree of a PMFL/PMFH valve, and digital signals for fully open/closed valve. AKS 45 is designed on the induction/eddy current principle. This means that the measuring circuit is not in physical contact with mineral oils and diverse refrigerants. Calibration/LED a/flats 32 AKS 45-26 Accessories L L 1 L 2 H H 1 B B 1 Electronic position indicator, type AKS 45 AKS 45-26 mm 28 45 48 12 78 in. 1.10 1.77 1.89 0.47 3.07 AF 32 M 24 1.5 ã Danfoss A/S (RC-CM/hbs), 12-2002 Technical leaflet - RD2CB402 53

Modulating liquid level regulators, servo-controlled, type PMFL / PMFH and SV Dimensions and weights PMFL/PMFH L 5 max. Weight excl. Type H 1 H 2 H 3 H 4 H 5 L L 1 B 10 W 20 W 1 B 2 B 3 solenoid valve mm mm mm mm mm mm mm mm mm mm mm mm kg PMFL 80 66 162 79 113 176 177 106 130 140 75 87 7.0 PMFH 125 72 178 96 128 193 240 170 130 140 84 82 94 11.3 200 79 187 105 138 202 254 170 130 140 94 89 102 14.2 300 95 205 123 155 220 288 200 130 140 104 106 113 19.8 PMFH 500 109 227 146 176 242 342 250 130 140 127 113 135 28.3 54 Technical leaflet - RD2CB402 ã Danfoss A/S (RC-CM/hbs), 12-2002

Liquid level alarms, safety switches, liquid level regulators, type RT 280A, RT 281A Introduction RT 280A and 281A are primarily used as liquid level alarms and safety switches to prevent too high a liquid level in liquid separators. Secondarily, RT 280A and 281A can be used as liquid level regulators where a liquid level differential of up to ±40 mm can be permitted. RT 280A and 281A used as safety switches ensure that the max. permissible refrigerant level in flooded evaporators, pump tanks or liquid separators is not exceeded. As liquid level regulators, RT 280A and 281A maintain a constant average refrigerant level in flooded evaporators, pump tanks or liquid separators. Materials Gaskets are non-asbestos. Technical data 1. General Refrigerants R 717 (NH 3 ), R 22 and R 502 Other refrigerants Ask Danfoss Operating ranges for RT 280A R 12: -50 +10 C R 22 og R 717 (NH 3 ): -50 0 C R 502: -65-5 C Operating ranges for RT 281A R 22 and R 717 (NH 3 ): -30 +20 C Liquid level differential With a steady liquid level and a liquid level variation rate of max. 15 mm / min, the differential will be approx. 10 mm on a rise in level and approx. 20 mm on a fall in level. In unfavourable operating conditions, differentials of approx. 20 mm on a rise in level and approx. 60 mm on a fall in level must be expected. Ambient temperature -50 +70 C Switch Single pole changeover switch (SPDT), code no. 017-4030 Approvals CE-approved according to EN 60947-4, -1 EN 60947-5, -1 Meet the requirements of VDE 0660 (VDE: Verband Deutscher Elektrotechniker) Contact load Alternating current AC1: 10 A, 400 V AC3: 4 A, 400 V AC15: 3 A, 400 V Max. short-time AC 3 current: 28 A Direct current DC13: 12 W, 220 V Weight 2.0 kg Enclosure IP 66 to IEC 529. 2. Pressure element Pressure connection G 3/8 A with Æ 6.5 / Æ 10 mm weld nipple Max. working pressure PB = 22 bar Max. test pressure p = 25 bar 3. Thermostatic element Adsorption charge 3 m capillary tube Max. permissible bulb temperature: +80 C 4. Bulb with electric heater 10 W heater for 24 V d.c. or a.c. The heater must be constantly energized whilst the system is in operation. 1.5 m connection cable. ã Danfoss A/S, 09-1999 Technical leaflet - RD2DA202 55

Liquid level alarms, safety switches, liquid level regulators, type RT 280A, RT 281A Ordering RT 280A code no. 017D0040 RT 281A code no. 017D0046 Design Function 3. Pressure connection 4. Bellows element 5. Setting disc 9. Scale 10. Loop terminal 11. Pg 13.5 screwed cable entry 12. Spring 14. Terminals 15. Spindle 16. Switch (17-4030) 17. Upper guide bush 18. Contact arm 20. Lower guide bush 38. Earth terminal RT 280A / 281A units are based on RT 260A. The lower element is thermal and has an electrically heated bulb. As stated, the units are primarily for use as liquid level alarms and safety switches. In designing the units, emphasis was placed on failsafe function. In the event of a defect in the thermal element, the compressor is stopped and liquid injection cut off. Restart is only possible after the defect has been rectified. This also applies in the case of loss of charge, for example if the capillary tube or heating element in the bulb is damaged, or if current to the heating element falls. The element heating or cooling signal is compared with the reference pressure and then converted to an electric on/off impulse. The regulating principle is based on the heat conduction difference between the liquid and vapour phases of the refrigerant. Note: If the evaporating temperature, and with it the reference pressure, is higher than the max. regulation range temperature, the unit will react as though the liquid level in the liquid container was too high. Dimensions and weight Weight 2.0 kg 56 Technical leaflet - RD2DA202 ã Danfoss A/S, 09-1999

Liquid level glasses type LLG 185-1550 Introduction LLG are liquid level glasses in ductile steel which meets the strictest requirements on industrial and marine refrigeration installations. The liquid level glasses are offered in 3 different versions: - with welding nipples (LLG) - with stop valves equipped with caps (LLG S) - with stop valves and sight adapter in acrylic glass ready for insulation on site (LLG SF). The range of liquid level glasses is based on 3 basic liquid level glasses: LLG 185, LLG 335 and LLG 740. The other standard lengths are combined by using variations of basic glass lengths. LLG produce sufficient flow areas to secure the highest possible degree of synchronous operation, and have a specially hardened reflection glass for quick reading. The front and the base frame are mounted together from the front with countersunk allen screws. This ensures easy insulation on site as well as easy inspection and service, if any. The liquid level glasses are equipped as standard with a built-in safety system (non return device). If a glass is damaged, the pressure of the refrigerant will activate the safety system and refrigerant loss will be limited to an absolute minimum. Features Refrigerants Applicable to all common non flammable refrigerants including R 717 and non corrosive gases/liquids dependent on sealing material compatibility Temperature range 10/+100 C ( 14/+212 F) or 50/+30 C ( 58/+86 F) Maximum operating pressure: 25 bar g (363 psi g) Equipped with boron silicate glass, hardened by an accurately controlled heat treatment process Classification: To get an updated list of certification on the products please contact your local Danfoss Sales Company. ã Danfoss A/S (RC-CM/hbs), 08-2002 Technical leaflet - RD6DB302 57

Liquid level glasses, type LLG 185-1550 Design Glass LLG's are equipped with a boronsilicate glass, hardened by an accurately controlled heat treatment process. All glasses are according to DIN 7081. Gaskets The glasses are equipped with a special nonasbestos carbon compound gasket which provides superior mechanical characteristics and a long time guarantee against service leakage. Connectors LLG 590, LLG 995, LLG 1145 and LLG 1550 are joined together by 2 basic LLG s by means of a connector. The connector holds the two basic glasses together by means of screws and guiding pins, which ensures a rigid construction. Stop Valves/Nipples The glasses are connected to the refrigeration system by means of welding nipples or stop valves. Which ever system is used, the nipples or stop valves are screwed into a flange, which is located in the correct position and subsequently tightened with a seal gasket and 4 screws. Installation Install the glasses on a bracket using the 4 screws supplied with the glass. Use the threaded holes on the back of the frame to mount the glass on a bracket (not of Danfoss supply). Always connect the piping after mounting on the bracket. Please note the importance of a minimum of stress in the liquid level glasses from the connected pipes. Please also make sure that there is sufficient space behind the the liquid level glasses to ensure proper insulation, service and inspection, etc. For installations below 10 C (+14 F) it is recommended to add the sight adapter to enable reading after insulation has been applied. For installations below 10 C (+14 F) in R 717 plants it is recommended to use an oil column as described in the following pages. There will be no formation of bubbles or ice build-up in oilfilled liquid level glasses, which may be the case in the refrigerant-filled glasses. The liquid sight glasses are designed to withstand high internal pressures. However, the piping system in general should be designed to avoid liquid traps and reduce the risk of hydraulic pressure caused by thermal expansion. Note: The LLG liquid level glass can only be placed in CE approved applications with the stop valves in front. Technical data Refrigerants The liquid level glasses are applicable to all common non flammable refrigerants including R 717 and non corrosive gases/ liquids dependent on sealing material compatibility. For further information please see installation instruction for LLG. Flammable hydrocarbons are not recommended. For further information please contact your local Danfoss Sales Company. Temperature range The liquid level glasses are applicable to the above mentioned refrigerants within the temperature range of: 10/+100 C (+14/+212 F) for the LLG types with safety system with welding nipples and the LLG S types with safety system with stop valves. 50/+30 C ( 58/+86 F) for the LLG SF type with safety system with stop valves and acrylic glass. Pressure range All LLG types are designed for: Max. operating pressure 25 bar g(363 psi g) Strength test: 50 bar g (725 psi g) Leakage test: at 25 bar g (363 psi g). 58 Technical leaflet - RD6DB302 ã Danfoss A/S (RC-CM/hbs), 08-2002

Liquid level glasses, type LLG 185-1550 Frostproof liquid level glasses Example 1 Refrigerant: R 717 (ammonia). Temperature: Recommended for temperatures below 10 C (+14 F). The principle shown in fig. 1 can be used in connection with low temperature liquid separators or intermediate coolers when the refrigerant is R 717 (ammonia). As the liquid level in the R 717 separator varies the oil level will change simultaneously. Oil Charging The system is charged with synthetic oil type SHC 226 with a specific weight, differing from that of R 717, and (h) must be multiplied by approximately 1.35 (the ratio of density oil to density R 717) to calculate H. Charge the oil vessel (volume approximate 10 litres) to a level just below the lower balancing pipe (A) through the oil charging valve. Close the oil charging valve. The oil will show in the liquid level glass at a level equal to the level in the oil vessel. When R 717 is filled into the separator or intermediate cooler it will enter the oil vessel and press down the oil surface. The R 717 will also rise into the upper balance pipe (B) to a level equal to the level in the separator or intermediate cooler. As the oil surface in the oil vessel is pressed down, the oil will rise into the liquid level glass. Note: It is important to use an oil which is not likely to mix with R 717. The oil must have a high viscosity index to ensure easy flowing at low temperatures. Mobil SHC 226 of the synthetic polyalphaolefin type has proven suitable for this purpose. Seperator/ Intermediate cooler Purge valve Oil charging valve Oil vessel Fig. 1 ã Danfoss A/S (RC-CM/hbs), 08-2002 Technical leaflet - RD6DB302 59

Liquid level glasses, type LLG 185-1550 Frostproof liquid level glasses Example 2 Refrigerant: R 717 (ammonia). Temperature: Recommended for temperatures below 10 C (+14 F). Fig. 2 shows a frostproof liquid level glass for an R 717 liquid separator which is placed above ground level. The arrangement is called a Hampsonmeter. Due to the evaporation taking place in the uninsulated balance pipe (ND 80/3 in.) the pressure in this pipe will be equal to P 1 = P 0 + H r g. P 0 Separator pressure...n/m 2 H R 717 liquid level (see fig. 2)... m r R 717 density... kg/m 3 g Acceleration due to gravity 9.81... m/s 2 Oil Charging The pressure will act on the oil surface in the oil vessel and cause the oil to rise in the liquid level glasses which are installed in a length of e.g. 2 in. pipe, the top of which is connected to the top of the separator which is at pressure P 0. The oil will rise to a level h and H can then be calculated by multiplying h by 1.35 (the ratio of density oil to density R 717). Charge the oil vessel through the oil charging valve to a level of approximately 3 /4 of full level. The level will show in the lower liquid level glass. Take care that the volume of the oil vessel is sufficient to allow the oil to rise into the liquid level glasses. When the system is operating keep the bypass valve closed. Note: It is important to use an oil not likely to mix with R 717, and having a high viscosity index to ensure easy oil movements at low temperatures. Mobil SHC 226 of the synthetic polyalphaolefin type has proven suitable for this purpose. Separator pressure P 0 uninsulated Bypass Oil charging valve Purge valve Fig. 2 Oil vessel 60 Technical leaflet - RD6DB302 ã Danfoss A/S (RC-CM/hbs), 08-2002

Liquid level glasses, type LLG 185-1550 Material specification LLG LLG S and LLG SF No. Part Material DIN ISO ASTM 1 Front frame Steel RSt. 37.2, 17 100 Fe 360 B, 630 Grade C, A 283 2 Back frame Steel RSt. 37.2, 17 100 Fe 360 B, 630 Grade C, A 283 3 Sight glass Glass 4 Gasket Non-asbestos 5 Protective Non-asbestos coating for sight glass 6 Sight adapter PMMA-acrylic 8 Connecting piece Steel RSt. 37.2, 17 100 Fe 360 B, 630 Grade C, A 283 10 O-ring Cloroprene (Neoprene) 14 Flange Steel RSt. 37.2, 17 100 Fe 360 B, 630 Grade C, A 283 15 Balls Stainless steel 18 Welding nipple Steel RSt. 37.2, 17 100 Fe 360 B, 630 Grade C, A 283 19 Stop valve (* SVA 6 T 123) Steel * See technical data for SVA stop valves. ã Danfoss A/S (RC-CM/hbs), 08-2002 Technical leaflet - RD6DB302 61

Liquid level glasses, type LLG 185-1550 Dimensions and weights LLG LLG S and LLG SF * Only for LLG SF with sight adapter. Type A B C D Weight LLG 185-1550 LLG 185 LLG 335 LLG 590 LLG 740 LLG 995 LLG 1145 LLG 1550 1 ) Type LLG 2 ) Type LLG S and LLG SF mm 185 255 69 48 4.2 kg 1 ) in. 7 1 / 4 10 2 3 / 4 2 5.8 kg 2 ) mm 335 405 63 42 7.5 kg 1 ) in. 13 1 / 4 16 2 1 / 2 1 3 / 4 9.2 kg 2 ) mm 590 660 69 + 63 48 + 42 13.2 kg 1 ) in. 23 1 / 4 26 2 3 / 4 + 2 1 / 2 2 + 1 3 / 4 15.1 kg 2 ) mm 740 810 63 42 16.5 kg 1 ) in. 29 1 / 4 32 2 1 / 2 1 3 / 4 18.5 kg 2 ) mm 995 1065 69 + 63 48 + 42 22.5 kg 1 ) in. 39 1 / 4 42 2 3 / 4 + 2 1 / 2 2 + 1 3 / 4 24.7 kg 2 ) mm 1145 1215 63 42 + 42 25.7 kg 1 ) in. 45 47 3 / 4 2 1 / 2 1 3 / 4 + 1 3 / 4 28.0 kg 2 ) mm 1550 1620 63 42 33.5 kg 1 ) in. 61 63 3 / 4 2 1 / 2 1 3 / 4 36.1 kg 2 ) Specified weights are approximate values only. 62 Technical leaflet - RD6DB302 ã Danfoss A/S (RC-CM/hbs), 08-2002

Liquid level glasses, type LLG 185-1550 Ordering How to order The table below is used to identify liquid level glasses required. Example for type codes Please note that the type codes only serve to identify the liquid level glasses, some of which may not form part of the standard product range. For further information please contact your local Danfoss Sales Company. Type codes LLG 740 SF Valve type LLG Liquid Level Glass Nominal size in mm Combined by: 185 DN 185 335 DN 335 590 DN 590 LLG 185 + LLG 335 740 DN 740 995 DN 995 LLG 185 + LLG 740 1145 DN 1145 LLG 335 + LLG 740 1550 DN 1550 LLG 740 + LLG 740 Equipment - Safety system with welding nipples S Safety system with stop valves (SVA 6 T 123) SF Safety system with stop valves and acrylic glass Liquid level glasses - LLG With safety system and welding nipples Length Type Code No. mm in. 185 7 1/4 LLG 185 2512+049 335 13 1/4 LLG 335 2512+050 590 23 1/4 LLG 590 2512+051 740 29 1/4 LLG 740 2512+052 995 39 1/4 LLG 995 2512+053 1145 45 LLG 1145 2512+054 1550 61 LLG 1550 2512+055 Liquid level glasses for insulating - LLG F With safety system and sight adaptor Length Type Code No. mm in. 185 7 1/4 LLG 185 F 2512+078 335 13 1/4 LLG 335 F 2512+079 590 23 1/4 LLG 590 F 2512+080 740 29 1/4 LLG 740 F 2512+081 995 39 1/4 LLG 995 F 2512+082 1145 45 LLG 1145 F 2512+083 1550 61 LLG 1550 F 2512+084 Liquid level glasses - LLG S With safety system and stop valves (SVA 6 T 123) Length Type Code No. mm in. 185 7 1/4 LLG 185 S 2512+056 335 13 1/4 LLG 335 S 2512+057 590 23 1/4 LLG 590 S 2512+058 740 29 1/4 LLG 740 S 2512+059 995 39 1/4 LLG 995 S 2512+060 1145 45 LLG 1145 S 2512+061 1550 61 LLG 1550 S 2512+062 Liquid level glasses for insulating - LLG SF With safety system, stop valves (SVA 6 T 123) and sight adaptor Length Type Code No. mm in. 185 7 1/4 LLG 185 SF 2512+066 335 13 1/4 LLG 335 SF 2512+067 590 23 1/4 LLG 590 SF 2512+068 740 29 1/4 LLG 740 SF 2512+069 995 39 1/4 LLG 995 SF 2512+070 1145 45 LLG 1145 SF 2512+071 1550 61 LLG 1550 SF 2512+072 Important! Where products need to be certified according to specific certification societies or where higher pressures are required, the relevant information should be included at the time of order. ã Danfoss A/S (RC-CM/hbs), 08-2002 Technical leaflet - RD6DB302 63

Motorised valve type MEV Introduction MEV motorised valve, complete with SMV/SMVE motor, EVM and spindle heater Motor Expansion Valves (MEV) are direct operated motorised valves for expansion, servo operated by SMV/SMVE motors MEV valves are designed to modulate an expansion process in liquid lines with phase change MEV valves are designed so that opening and closing forces are balanced, therefore, only one size of SMV or SMVE motor can be used for the complete range of MEV s (from size 80-2 to 500) Consequently, MEV valves in combination with SMV/SMVE motors are compact motorised units of comparatively small dimensions MEV + SMV/SMVE are supplied as standard with spring return (i e the valve closes automatically when no voltage is applied to the motor, e g in the event of power failure) This function is incorporated in the SMV/ SMVE motor, but can be disconnected if it is not required The MEV valve is based on a PM valve body and has the same dimensions, connections and flanges The SMV motor controls the MEV valve by an ordinary three-point control (open-neutralclose) while the SMVE motor uses a signal (for instance 4-20 ma) Features Built on the PM housing Same flange program as for the PM Valve housing in EN-GJS-400-18-LT Balanced valve forces V-port and cavitation resistant valve seat Same motor program type, SMV/SMVE, for valve type MEV One motor handles all valve sizes Motor actuator control: standard control signals 4-20 ma or 3-point (close, neutral, open) Very compact design Manual operation possible Spring return (can be deactivated) Position indicator (accessory) Spindle heating element (accessory) Optional: EVM solution to optimise closing abilities ã Danfoss A/S (RC-CM/hbs), 08-2002 Technical leaflet - RD4AJ202 65

Motorised valve, type MEV Design MEV is designed as a balanced valve, which keeps closed by a built-in spring With counter-flow, the valve is capable of closing with the force of the return spring against a differential pressure Depending on the control signal requirement, an SMV or SMVE motor is fitted to open the valve by acting on the valve spindle push pin Valve body incl covers Material: EN-GJS-400-18-LT Pressure Equipment Directive (PED) MEV valves are approved according to the European standard specified in the Pressure Equipment Directive and are CE marked Valve cone A V-port regulating cone provides optimum regulation accuracy Push pin seal assembly Replaceable seal assembly in stainless steel with double sealing system Valve sizes MEV is available in sizes from: MEV 80-2 (k v : 0 6 m 3 /h) to MEV 500 (k v : 23 0 m 3 /h) Installation MEV + SMV/SMVE can be installed in vertical or horizontal pipelines when respect to the mounting direction is taken For further details / restrictions - see Installation Instruction MEV valves Nominal bore DN 25 (1 in.) DN32-65 mm (1¼ - 2½ in.) Classified for Category Fluid group I Article 3, paragraph 3 II Technical data Refrigerants Applicable to all common non flammable refrigerants including R717 and non corrosive gases/liquids dependent on sealing material compatibility Flammable hydrocarbons are not recommended For further information please contact your local Danfoss sales company Pressure Max permissible working pressure: PB = 28 bar (406 psi) Max permissible test pressure: P = 42 bar (609 psi) Temperature range: Media: 50/+120 C (a spindle heater must be used for temperatures below 0 C) Ambient: 20/+60 C Valve size k v -value C v -value Max Dp Max Dp Min opening/closing Lifting Closing times height 1 ) time 2 ) m 3 /h USgal/min bar psi 50 Hz 60 Hz mm s MEV 80-2 0 6 0 7 28 406 33 s 26 s 10 0 8 MEV 80-3 1 0 1 2 28 406 33 s 26 s 10 0 8 MEV 80-4 1 5 1 7 28 406 33 s 26 s 10 0 8 MEV 80-5 2 1 2 4 28 406 33 s 26 s 10 0 8 MEV 80-6 3 3 3 8 28 406 33 s 26 s 10 0 8 MEV 80-7 5 0 5 8 28 406 33 s 26 s 10 0 8 MEV 125 7 0 8 1 20 290 40 s 32 s 12 3 10 MEV 200 10 0 11 6 18 261 50 s 40 s 15 5 13 MEV 300 15 5 18 0 18 261 62 s 51 s 19 5 16 MEV 500 23 0 26 7 18 261 66 s 53 s 20 5 17 1) In a closed condition there will be a clearance of 0 6 mm - 1 0 mm between the SMV/SMVE motor spindle and the MEV valve push pin (27) 2) Closing time with spring return When an MEV is closed solely by the spring return system (because of power failure) the stated closing times can vary slightly, due to various conditions including the viscosity of the medium SMV/SMVE motor spindle speed Spindle speed at 50 Hz Spindle speed at 60 Hz 3 s/mm 2 4 s/mm 66 Technical leaflet - RD4AJ202 ã Danfoss A/S (RC-CM / hbs), 08-2002

Motorised valve, type MEV Function Only MEV 500 10 Drain plug screw 13 Nipple 18 Cylinder liner 21 Regulating cone 26 Bottom plug 27 Push pin 30 Heating element housing 33 Blanking plug 35 Balancing piston 36 Piston seal 39 Spring 46 Blanking plug MEV incorporates a balancing piston (35) that ensures the valve operates with low opening and closing forces Therefore, the differential pressure across the valve has minimal effect on the valve operation Inlet pressure P 1 acting on the underside of the regulating cone (21) is led via the internal channel (A) in the valve body to the top of the balancing piston Since P 3 =P 1 the pressure on the underside of the regulating cone is thus equalized In the same way, outlet pressure P 2, which acts on the top of the regulating cone, is led via an internal channel to the underside of the balancing piston The valve is thus totally balanced and the spring force will always keep the valve closed also against backpressure The balancing piston operates in a cylinder liner (18) and is fitted with a piston seal (36) for tight sealing MEV is fitted with a spring (39) that closes the valve when the push pin (27) is not activated The SMV/SMVE motor is fitted with a return spring that forces the motor spindle closed when no voltage is being applied to the motor This means that the MEV valve closes automatically when, for example, the power fails (This is a function of the SMV/SMVE motor, but can be disconnected, by using the angle bracket accessory) An AKS 45 electronic position indicator can be fitted instead of the MEV bottom plug (26) An output signal (4-20 ma) of the exact position of the valve cone can be obtained during operation, together with digital on/off signals for fully open and fully closed valve A heating element (30) can be fitted on the MEV nipple (13) to keep the pressure pin free of ice (for use with media temperatures below 0 C) An EVM solenoid valve (NC) can optionally be inserted in the port (at 46) This will close the connection between inlet pressure and the balancing piston (35) Since the drain plug (10) is removed, the pressure P 3 will equalize with P 2 through B making P 3 =P 2 P 1 will contribute to the spring force and the total closing force will increase depending on the pressure difference between P 1 and P 2 By putting the valve balancing out of order, the pressure P 1 will help keeping the valve closed against the backpressure In this status the valve will be forced open for backflow if P 2 >P 1 +spring pressure The EVM is available through a kit Danfoss recommendation is to use EVM if a higher closing pressure than the spring force should be applied and P 1 is always higher than P 2 MEV has a pressure gauge connection (at 33) for registering valve top pressure P 3 The pressure gauge will show P 2 when an optional EVM is closed or P 1 when open ã Danfoss A/S (RC-CM / hbs), 08-2002 Technical leaflet - RD4AJ202 67

Motorised valve, type MEV Application examples for MEV Conduite de liquide avec changement de phase A B Liquid line (expansion) Liquid line (pump operation) A+B Can all be calculated with DIRcalc version 1 1 or later A Tables with capacities on the later pages 68 Technical leaflet - RD4AJ202 ã Danfoss A/S (RC-CM / hbs), 08-2002

Motorised valve, type MEV Ordering Motorised valve Valve size k v value Code no MEV 80-2 0 6 027F3165 MEV 80-3 1 0 027F3166 MEV 80-4 1 5 027F3167 MEV 80-5 2 1 027F3168 MEV 80-6 3 3 027F3169 MEV 80-7 5 0 027F3170 MEV 125 7 0 027F3171 MEV 200 10 0 027F3172 MEV 300 15 5 027F3173 MEV 500 23 0 027F3174 Motor Code numbers include: MEV motorised valve, flange gaskets and flange bolts SMV/SMVE motor, flanges and spindle heater are ordered seperately Spindle heater A heating element can be fitted around the MEV push pin seal assembly to keep the push pin free of ice The element is described in more detail in the technical leaflet for the SMV/SMVE motors Type Description Code no SMV 24 24 V a c three-point control 082H3030 SMV 230 230 V a c three-point control 082H3031 SMVE 24 24 V a.c. modulating input 082H3032 Flange set 1) Code no applies to flange set consisting of one inlet and one outlet flange 2) Dimensioned sketch, see spare parts catalogue Valve size Flange type Weld flange Solder flange in Code no in Code no mm Code no 3 / 4 027N1220 7 / 8 027L1223 22 027L1222 MEV 80 3 1 027N1225 1 1 / 8 027L1229 28 027L1228 1 1 / 4 027N1230 MEV 125 10 MEV 200 11 MEV 300 12 MEV 500 13 1 1 / 4 027N2332 1 1 / 2 027N2340 1 1 / 2 027N2440 2 027N2450 2 027N2550 2 1 / 2 027N2565 2 1 / 2 027N2665 3 027N2680 1 3 / 8 027L2335 35 027L2335 1 5 / 8 027L2441 42 027L2442 2 1 / 8 027L2554 54 027L2554 2 5 / 8 027L2666 76 027L2676 Stainless steel: flanges, flange bolts, and bolts for top and bottom covers, see spare parts list for ordering Accessories Description Code no Pressure gauge connection, Ø 6 5/Ø 10 mm weld/solder 027B2035 Pressure gauge connection, ¼ in flare (self-sealing) Must not be used in systems with ammonia 027B2041 Pressure gauge connection, self-cutting connection 6 mm 027B2063 10 mm 027B2064 Pressure gauge connection 1 / 4 NPT 027B2062 Electronic position indicator, AKS 45 EVM kit for SMV motor EVM kit for SMVE motor Spindle heater 24 V a c Spindle heater 230 V a c 084H4045 027F1972 027F1971 027F3180 027F3181 ã Danfoss A/S (RC-CM / hbs), 08-2002 Technical leaflet - RD4AJ202 69

Motorised valve, type MEV Nominal capacities Capacity in kw Type Evaporating temperature t e Rated capacity in kw at pressure drop across valve Dp bar C 1.0 2.0 4.0 8.0 12.0 16.0 R717 (NH 3 ) MEV 80-2 10 89 123 167 224 257 0 92 127 172 227 264 281 DN 25-10 94 130 176 228 265 284-20 95 132 177 238 264 285-30 97 133 177 227 262 284-40 98 132 175 225 258 281-50 98 131 173 222 253 277 MEV 80-3 10 141 194 264 353 404 0 145 201 271 356 414 440 DN 25-10 149 205 276 357 416 444-20 151 207 278 356 413 445-30 153 207 276 353 407 443-40 153 205 272 349 400 438-50 152 201 267 343 393 431 MEV 80-4 10 228 316 427 571 651 0 237 327 438 573 664 704 DN 25-10 242 333 444 572 665 709-20 245 334 445 568 657 709-30 246 330 439 561 647 704-40 243 323 429 552 635 696-50 238 315 420 543 624 685 MEV 80-5 10 360 496 667 887 1010 0 371 511 679 883 1020 1080 DN 25-10 379 518 685 874 1020 1080-20 381 514 680 864 1000 1080-30 376 502 666 852 984 1070-40 367 486 649 837 966 1060-50 355 470 632 823 948 1040 MEV 80-6 10 624 851 1130 1490 1670 0 642 869 1130 1460 1690 1780 DN 25-10 648 871 1130 1430 1670 1780-20 640 850 1110 1410 1640 1770-30 619 816 1080 1380 1610 1760-40 591 781 1050 1360 1570 1730-50 564 751 1020 1340 1540 1710 MEV 80-7 10 971 1300 1690 2220 2480 0 995 1310 1670 2150 2500 2610 DN 25-10 990 1300 1660 2090 2470 2610-20 959 1250 1630 2050 2410 2610-30 910 1190 1580 2010 2350 2590-40 858 1130 1530 1970 2300 2550-50 813 1080 1490 1940 2250 2510 MEV 100 10 1545 2100 2770 3650 4100 0 1590 2140 2770 3570 4190 4350 DN 32-10 1600 2140 2770 3500 4090 4350-20 1575 2080 2720 3430 4010 4340-30 1515 1990 2650 3370 3920 4300-40 1440 1900 2570 3320 3840 4240-50 1370 1830 2490 3260 3770 4180 MEV 200 10 2480 3360 4410 5810 6530 0 2545 3420 4420 5680 6590 6920 DN 40-10 2560 3410 4400 5550 6510 6920-20 2510 3310 4330 5450 6370 6900-30 2405 3160 4210 5360 6240 6830-40 2295 3020 4080 5260 6110 6740-50 2170 2900 3960 5170 5990 6640 MEV 300 10 3765 4990 6690 8810 9880 0 3870 5180 6690 8600 9980 10500 DN 50-10 3885 5170 6660 8400 9850 10500-20 3800 5010 6550 8240 9650 10400-30 3640 4780 6360 8100 9430 10300-40 3450 4560 6170 7960 9240 10200-50 3285 4380 5990 7820 9050 10000 MEV 500 10 7030 8360 10700 14100 15800 0 8290 9090 10700 13700 15900 16700 DN 65-10 8650 9260 10600 13400 15700 16700-20 8470 9090 10400 13100 15400 16700-30 7480 8410 10100 12900 15000 16500-40 6820 7920 9830 12700 14700 16300-50 6550 7640 9540 12400 14400 16000 Correction factors When dimensioning, multiply the evaporator capacity by a correction factor k dependent on the subcooling Dt sub just ahead of the valve. The corrected capacity* can then be found in the capacity table. Dt sub K k 2 1 01 4 1 00 10 0 98 15 0 96 20 0 94 25 0 92 30 0 91 35 0 89 40 0 87 45 0 86 50 0 85 * (The capacity table is based on nominal conditions of subcooling just ahead of the valve of 4 K) Calculation example: An application has the following operating conditions: Refrigerant R717 T e = 10 C T c = +30 C Q 0 = 1500 kw Dt sub = 20 K Correction factor for subcooling: 0 94 Pressure drop across the valve: 11 7 bar - 2 9 bar = 8 8 bar Corrected capacity: 1500 x 0 94 = 1410 kw From the R717 capacity table MEV 80-6 is selected with Q nom capacity 1430 kw at 8 bar 70 Technical leaflet - RD4AJ202 ã Danfoss A/S (RC-CM / hbs), 08-2002

Motorised valve, type MEV Nominal capacities (cont ) Capacity in kw Type Evaporating temperature t e Rated capacity in kw at pressure drop across valve Dp bar C 1.0 2.0 4.0 8.0 12.0 16.0 R22 MEV 80-2 10 20 27 36 46 51 52 0 21 29 38 47 52 53 DN 25-10 22 30 39 48 52 54-20 22 30 40 48 52 54-30 23 31 40 48 52 53-40 23 31 40 48 51 52-50 23 31 39 47 49 51 MEV 80-3 10 32 43 57 72 80 82 0 33 46 60 74 82 84 DN 25-10 34 47 62 76 82 85-20 36 48 63 76 82 85-30 36 48 63 76 81 83-40 37 49 62 75 79 81-50 37 48 61 73 77 79 MEV 80-4 10 52 71 94 118 130 133 0 54 74 98 121 133 136 DN 25-10 56 77 101 123 133 138-20 58 78 102 123 132 137-30 59 78 101 122 130 134-40 59 78 99 120 127 131-50 60 77 97 117 124 127 MEV 80-5 10 82 112 147 184 202 206 0 86 117 153 188 205 211 DN 25-10 88 121 157 190 205 212-20 91 122 157 189 203 210-30 92 122 156 187 199 206-40 92 120 152 184 195 200-50 91 117 148 179 189 194 MEV 80-6 10 143 194 251 310 341 345 0 149 202 260 314 343 352 DN 25-10 154 206 263 315 341 353-20 155 205 262 313 335 348-30 155 202 257 308 328 340-40 152 196 249 302 320 331-50 148 189 241 294 312 321 MEV 80-7 10 222 299 381 466 510 515 0 231 308 390 467 510 524 DN 25-10 236 311 393 465 504 523-20 237 307 389 461 495 516-30 232 298 378 454 483 503-40 225 286 366 444 471 489-50 215 275 353 433 458 473 MEV 100 10 354 479 620 763 837 847 0 369 498 639 770 842 864 DN 32-10 379 507 647 771 835 865-20 384 505 643 767 821 853-30 381 494 628 755 804 834-40 373 478 609 739 784 810-50 361 461 589 720 762 785 MEV 200 10 567 767 990 1220 1330 1350 0 592 796 1020 1230 1340 1380 DN 40-10 608 810 1030 1230 1330 1380-20 613 805 1020 1220 1310 1360-30 607 786 1000 1200 1280 1330-40 593 760 969 1170 1250 1290-50 572 732 937 1150 1210 1250 MEV 300 10 861 1170 1500 1850 2020 2050 0 900 1210 1550 1860 2030 2080 DN 50-10 922 1230 1560 1860 2010 2090-20 933 1220 1550 1850 1980 2060-30 921 1190 1510 1820 1930 2010-40 897 1150 1470 1780 1890 1950-50 865 1110 1420 1730 1830 1890 MEV 500 10 1847 2049 2410 2950 3240 3270 0 1969 2153 2480 2970 3250 3330 DN 65-10 1930 2144 2500 2970 3210 3330-20 1849 2091 2480 2950 3160 3290-30 1737 2002 2420 2900 3090 3210-40 1586 1882 2340 2840 3010 3120-50 1479 1786 2260 2770 2930 3020 Correction factors When dimensioning, multiply the evaporator capacity by a correction factor k dependent on the subcooling Dt sub just ahead of the valve. The corrected capacity* can then be found in the capacity table. Dt sub K k 2 1 01 4 1 00 10 0 96 15 0 93 20 0 90 25 0 87 30 0 85 35 0 83 40 0 80 45 0 78 50 0 77 * (The capacity table is based on nominal conditions of subcooling just ahead of the valve of 4 K) Calculation example: An application has the following operating conditions: Refrigerant R22 T e = 20 C T c = +40 C Q 0 = 1200 kw Dt sub = 10 K Correction factor for subcooling: 0 96 Pressure drop across the valve: 15 3 bar - 2 4 bar = 12 9 bar Corrected capacity: 1200 x 0 96 = 1152 kw From the R22 capacity table MEV 200 is selected with Q nom capacity 1310 kw at 12 bar ã Danfoss A/S (RC-CM / hbs), 08-2002 Technical leaflet - RD4AJ202 71

Motorised valve, type MEV Material specification Push pin seal assembly Only MEV 500 No Part Material DIN/EN ISO ASTM 1 Nut Stainless steel X8CrNiS 18-9 14440 683/13 type 17 AISI 303 EN 10088 W no 1 4305 2 Dirt seal PTFE (Teflon) 3 Bush Stainless steel X8CrNiS 18-9 14440 683/13 type 17 AISI 303 EN 10088 W no 1 4305 4 Seal PTFE (Teflon) 5 O-ring Cloroprene (Neoprene) 6 O-ring Cloroprene (Neoprene) 7 Insert Stainless steel X8CrNiS 18-9 14440 683/13 type 17 AISI 303 EN 10088 W no 1 4305 10 Drain plug screw Steel 12 Locking screw Steel X5CrNi 18-9 W no 1 4301 683/13 AISI 316 13 Nipple Stainless steel X8CrNiS 18-9 14440 683/13 type 17 AISI 303 EN 10088 W no 1 4305 14 Gasket Aluminium 15 Top cover Low temperature, EN-GJS-400-18-LT cast iron (spherical) EN 1563 16 Gasket Asbestos-free 17 O-ring Cloroprene (Neoprene) 18 Cylinder liner Cast iron GG-20 1691 1085, class 200 W no 0 6020 19 Spindle Steel 9S Mn Pb 28, 1651 Type 2, R 683/9 1213, SAE J 403 W no 1 0716 20 Valve body Low temperature, EN-GJS-400-18-LT cast iron (spherical) EN 1563 21 Regulating cone Steel 9S Mn Pb 28, 1651 Type 2, R 683/9 1213, SAE J 403 W no 1 0716 22 Gasket Asbestos-free 23 Bottom cover Low temperature, EN-GJS-400-18-LT cast iron (spherical) EN 1563 72 Technical leaflet - RD4AJ202 ã Danfoss A/S (RC-CM / hbs), 08-2002

Motorised valve, type MEV Material specification (continued) Push pin seal assembly Only MEV 500 No Part Material DIN/EN ISO ASTM 24 Bolt Stainless steel A2-70 A2-70 Type 308 25 Gasket Asbestos-free 26 Bottom plug Steel 9S Mn Pb 28, 1651 Type 2, R 683/9 1213, SAE J 403 W no 1 0716 27 Push pin Stainless steel X8CrNiS 18-9 14440 683/13 type 17 AISI 303 EN 10088 W no 1 4305 28 Distance piece Stainless steel X8CrNiS 18-9 14440 683/13 type 17 AISI 303 (MEV 80 only) EN 10088 W no 1 4305 29 Adjusting screw Stainless steel X8CrNiS 18-9 14440 683/13 type 17 AISI 303 EN 10088 W no 1 4305 30 Heating element housing Aluminium 1725 W no 3 3206 31 Locking screw Steel X5CrNi 18-9 W no 1 4301 683/13 AISI 316 32 Gasket Aluminium 33 Blanking plug Steel 9S Mn Pb 28, 1651 Type 2, R 683/9 1213, SAE J 403 W no 1 0716 34 Nut Steel 35 Balancing piston Cast iron GG-20 1691 185, class 20 W no 0 6020 36 Piston seal PTFE (Teflon) 37 O-ring Cloroprene (Neoprene) 38 O-ring Cloroprene (Neoprene) 39 Spring Steel 40 Valve seat Stainless steel X8CrNiS 18-9 14440 683/13 type 17 AISI 303 EN 10088 W no 1 4305 41 Sealing disc PTFE (Teflon) 42 Valve plate Steel 9S Mn Pb 28, 1651 Type 2, R 683/9 1213, SAE J 403 W no 1 0716 43 Nut Steel 45 Nipple Stainless steel X8CrNiS 18-9 14440 683/13 type 17 AISI 303 (MEV 500 only) EN 10088 W no 1 4305 46 Blanking plug Steel 9S Mn Pb 28, 1651 Type 2, R 683/9 1213, SAE J 403 W. no. 1.0716 ã Danfoss A/S (RC-CM / hbs), 08-2002 Technical leaflet - RD4AJ202 73

Motorised valve, type MEV Dimensions and weight Dimensions Valve size H 1 H 2 H 3 H 4 L L 1 B 1 B 2 B 3 MEV 80 (1 in ) MEV 125 (1 1 /4 in ) MEV 200 (1 1 /2 in ) MEV 300 (2 in ) MEV 500 (2 1 /2 in ) mm 66 105 79 266 177 106 75 Oval 87 in 2 60 4 13 3 11 10 47 6 97 4 17 2 95 flange 3 43 mm 72 121 96 282 240 170 84 82 94 in 2 83 4 76 3 78 11 10 9 45 6 69 3 31 3 23 3 70 mm 79 128 105 289 254 170 94 89 102 in 3 11 5 04 4 13 11 38 10 00 6 69 3 70 3 50 4 02 mm 95 151 123 312 288 200 104 106 113 in 3 74 5 94 4 84 12 28 11 34 7 87 4 09 4 17 4 45 mm 109 167 146 352 342 250 127 113 135 in 4 29 6 57 5 75 13 86 13 46 9 84 5 00 4 45 5 31 Weight Valve size Valve Motor Flange set without motor and flanges MEV 80 (1 in ) 5 8 kg (12 8 lb) 2 0 kg (4 4 lb) 1 1 kg (2 4 lb) MEV 125 (1 1 / 4 in ) 10 kg (22 0 lb) 2 0 kg (4 4 lb) 1 5 kg (3 3 lb) MEV 200 (1 1 / 2 in ) 12 kg (26 5 lb) 2 0 kg (4 4 lb) 1 9 kg (4 2 lb) MEV 300 (2 in ) 17 kg (37 5 lb) 2 0 kg (4 4 lb) 2 8 kg (6 2 lb) MEV 500 (2 1 / 2 in ) 25 kg (55 1 lb) 2 0 kg (4 4 lb) 3 3 kg (7 3 lb) Specified weights are approximately values only 74 Technical leaflet - RD4AJ202 ã Danfoss A/S (RC-CM / hbs), 08-2002

Motor types SMV/SMVE for MEV/MRV motorised valves Introduction Motor types SMV/SMVE are dedicated for use with MEV/MRV motorised valves. Using the same motor size, they cover the complete MEV/MRV product series and its whole capacity range. The SMV motor operates the MEV/MRV valve via an ordinary three-point control (open - neutral - closed) while the SMVE motor operates the MEV/MRV valve with a modulating signal (e.g. 4-20 ma). Features Very compact motor Specially designed for industrial refrigeration installations Built-in heating element in motor housing Motor with spring return system; returns the valve to closed position in the event of power failure Degree of protection: IP 54 Voltage supply: 24 V ac and 220 V ac, 50/60 Hz Feedback signal facility SMVE has an automatic calibration function The motors can be configured for direct or inverse operation Configurable input signal for SMVE Torque protection throughout the operating range of the motor gives protection against overload Design Types SMV: Three-point control SMVE: Modulating signal Coupling to MEV/MRV 32 mm A/F (M30 1.5). Tightening torque max. 25 Nm. Manual operation The motors can be operated manually with a 5 mm hexagon key. Cable connection 2-off Æ17 mm holes for PG 11 cable entries. Materials Cover: ABS plastic Housing: Pressure die cast aluminium. ã Danfoss A/S (RC-CM / MWA), 12-2001 Technical leaflet - RD4MA202 75